GMP80PX/ - א.ב גנרטורים בע · 2017-11-13 · Designed to operate in ambient conditions...

7
Features: • PowerLink engine • PowerLink Alternator, Class H • Genset Canopy N/A protection, Control panel IP56 protection • Control module PLC-920 • Breaker: • Speed governor: Electronic governor • Excitation system: Brushless • A.V.R model: SX460 • 50radiator • Big daily fuel tankBelow 800KVA• Fire extinguisher • Oil pump on the engine • ATS receptacle • Lockable battery isolator switch • Vibration isolators between the engine/Alternator and base frame • Integrated wiring design • High water temperature protection Output Ratings Generator Set Model Prime Power Standby Power kVA kW kVA kW GMP80PX 80 64 103 82 Ratings at 0.8 power factor Dimensions and Weights Model L × W × H-mm Dry Weight- kg GMP80PX 2156× 881× 1495 1196 Ratings and Performance Data Engine Brand PowerLink Engine Model 4DTA4.8ECG2 Alternator Brand PowerLink Alternator Model PL2DS Control System PLC-920 Circuit Breaker Type Frequency / Phase 50Hz/3Phase Engine SpeedRPM1500 Fuel Tank CapacityL206 Fuel ConsumptionL/h(100%load) 19.8 Model Type Open Type Standard Package Noise Level@7mdBAN/A Generator set Manufacture PowerLink Oil ConsumptionL/h1.53 VolatageV380/400/415/440 Silencer Noise ReductiondBA10-12 Notes: *Prime Power Continuous duty operation, under variable load 24/24h-10% over load permissible 1 hour/12 hours; **Standby Power Standby duty, operation under variable load, without over load; Standard Reference Conditions Note: Standard reference conditions 25°C (77°F) Air Inlet Temp, 100m(328 ft) A.S.L. 30% relative humidity. GMP80PX/ 1000024939 80kVA, Open Type, 4DTA4.8ECG2, PL2DS, 3phase, AutoGen www.powerlinkworld.com | [email protected] 1/7

Transcript of GMP80PX/ - א.ב גנרטורים בע · 2017-11-13 · Designed to operate in ambient conditions...

Page 1: GMP80PX/ - א.ב גנרטורים בע · 2017-11-13 · Designed to operate in ambient conditions up to 50°C (122°F).Contact your local PowerLink Dealer for power ratings at specific

Features:

• PowerLink engine• PowerLink Alternator, Class H• Genset Canopy N/A protection, Control panelIP56 protection• Control module PLC-920• Breaker:• Speed governor: Electronic governor• Excitation system: Brushless• A.V.R model: SX460• 50℃ radiator• Big daily fuel tank(Below 800KVA)• Fire extinguisher• Oil pump on the engine• ATS receptacle• Lockable battery isolator switch• Vibration isolators between the engine/Alternatorand base frame• Integrated wiring design• High water temperature protection

Output Ratings

Generator Set

Model

Prime Power Standby Power

kVA kW kVA kW

GMP80PX 80 64 103 82

Ratings at 0.8 power factor

Dimensions and Weights

Model L × W × H-mmDry Weight-

kg

GMP80PX 2156× 881× 1495 1196

Ratings and Performance Data

Engine Brand PowerLink

Engine Model 4DTA4.8ECG2

Alternator Brand PowerLink

Alternator Model PL2DS

Control System PLC-920

Circuit Breaker Type

Frequency / Phase 50Hz/3Phase

Engine Speed((RPM)) 1500

Fuel Tank Capacity((L)) 206

Fuel Consumption((L/h))(100%load)

19.8

Model Type Open Type

Standard Package

Noise Level@7m((dBA)) N/A

Generator set Manufacture PowerLink

Oil Consumption((L/h)) 1.53

Volatage((V)) 380/400/415/440

Silencer Noise

Reduction((dBA))10-12

Notes:*Prime Power Continuous duty operation, under variable load 24/24h-10%over load permissible 1 hour/12 hours; **Standby Power Standby duty, operation under variable load, without overload; Standard Reference Conditions Note: Standard reference conditions25°C (77°F) Air Inlet Temp, 100m(328 ft) A.S.L. 30% relative humidity.

GMP80PX/ 100002493980kVA, Open Type, 4DTA4.8ECG2, PL2DS, 3phase, AutoGen

www.powerlinkworld.com | [email protected] 1/7

Page 2: GMP80PX/ - א.ב גנרטורים בע · 2017-11-13 · Designed to operate in ambient conditions up to 50°C (122°F).Contact your local PowerLink Dealer for power ratings at specific

Engine Model:4DTA4.8ECG2

Engine Technical Data

Engine Model 4DTA4.8ECG2

Engine Brand PowerLink

Number of Cylinders 4

Cylinders Arrangement Inline

Bore/Stroke((mm)) 110/125

Speed((RPM)) 1500

Displacement((L)) 4.75

Compression Ratio 17

Air Intake systemTurbocharge

aftercooler

Cooling Method Water cooled

Coolant Capacity((L)) 6

Prime Power((kWm)) 82

Standby Power((kWm)) 90

Governing Type Electronic

Back Pressure((mmhg)) 6

Battery((V)) 12

Exhaust and silencer System

Exhaust Air Flow((m³/hr)) 1040.4

Exhaust Air Temp.((°C)) N/A

Maximum Allowable Back

Pressure((mmhg))6

NOx((mg/Nm³)) N/A

Silencer Quantity 1

Silencer Type Industrial silencer

Cooling System

Radiator 50

Coolant Capacity((L)) 6

Coolant Change Time((Year/h)) 2/10000

Coolant Intake Temp.((°C)) 76

Coolant Output Temp.((°C)) 99

Designed to operate in ambient conditions up to 50°C (122°F).Contactyour local PowerLink Dealer for power ratings at specific site conditions

Fuel System

Fuel Tank steel

Fuel Tank Capacity((L)) 206

Fuel tank type Single-layer

Recommended Fuel Type 0# or ASTM2

Injection System Direct injection

Fuel Consumption:

GMP80PX 100%Load

75%Load

50%Load

25%Load

L/h 19.8 15.6 10.8 6.4

(Based on diesel fuel with a specific gravity of 0.85 and conforming toBS2869,Class A2)

Air Intake system

Air Filter Type Dry type

Intake Air Flow((m³/h)) 399.6

Intake SystemTurbocharge

aftercooler

Intake Air Temp.((°C)) 25

Lubrication System

Lube oil label

Maximum Oil Temp.((°C)) ≤100

Oil capacity((L)) 14

Conditions

Altitude((m))

Ambient Temp.((°C)) -5℃-50℃Barometric Pressure((kpa)) 100

Relative Humidity <80%

GMP80PX/ 100002493980kVA, Open Type, 4DTA4.8ECG2, PL2DS, 3phase, AutoGen

www.powerlinkworld.com | [email protected] 2/7

Page 3: GMP80PX/ - א.ב גנרטורים בע · 2017-11-13 · Designed to operate in ambient conditions up to 50°C (122°F).Contact your local PowerLink Dealer for power ratings at specific

Alternator Model:PL2DS

Alternator Physical Data

AVR Model SX460

Alternator Brand PowerLink

Alternator Model PL2DS

Excitation System Brushless

Housing Protection IP23

Power Factor 0.8

Rated Stator Temp. rise((℃)) 125

Rotor Insulation Class H

Voltage Fluctuation(no load to

full load)±0.5%

Winding Pitch 2/3

Wiring Connection Series Star

Alternator Operating Data

Overspeed((rpm)) 2250

Voltage Reguation(Steady state) ± 1.0 %

THF(BS EN60034-1) <50

TIF(NEMA MG 1-22) <2%

Air Flow((m³/s))-Alternator

50Hz/60Hz0.514

Altitude-Alternator((m)) 1000

Performance Data

Time constants/400V((Ms))

T’d 0.042 s

T’’d 0.012 s

T’do 1.1 s

Ta 0.012 s

Short-circuit current (3 IN / 10 s) 300 % (3 IN) : 10s

SHORT CIRCUIT RATIO 1/Xd

Reactances((Per Unit))

Xd

X'd

X"d

Voltage Technical Data

VoltagePrime Standby

kVA kW kVA kW

380V@50Hz 80 64 88.0 70.4

400V@50Hz 80 64 88.0 70.4

415V@50Hz 80 64 88.0 70.4

415V@60Hz 98 78.4 107 86.24

440V@60Hz 98 78.4 107 86.24

480V@60Hz 98 78.4 107 86.24

GMP80PX/ 100002493980kVA, Open Type, 4DTA4.8ECG2, PL2DS, 3phase, AutoGen

www.powerlinkworld.com | [email protected] 3/7

Page 4: GMP80PX/ - א.ב גנרטורים בע · 2017-11-13 · Designed to operate in ambient conditions up to 50°C (122°F).Contact your local PowerLink Dealer for power ratings at specific

Overall Dimensions

GMP80PX/ 100002493980kVA, Open Type, 4DTA4.8ECG2, PL2DS, 3phase, AutoGen

www.powerlinkworld.com | [email protected] 4/7

Page 5: GMP80PX/ - א.ב גנרטורים בע · 2017-11-13 · Designed to operate in ambient conditions up to 50°C (122°F).Contact your local PowerLink Dealer for power ratings at specific

Control System

GMP80PX/ 100002493980kVA, Open Type, 4DTA4.8ECG2, PL2DS, 3phase, AutoGen

www.powerlinkworld.com | [email protected] 5/7

Page 6: GMP80PX/ - א.ב גנרטורים בע · 2017-11-13 · Designed to operate in ambient conditions up to 50°C (122°F).Contact your local PowerLink Dealer for power ratings at specific

Product Standard Configuration

Alternator

AlternatorA.V.R

Control System

PLC-920 Control SystemAir BreakerExternal CableConnectionCable Line Slot

Fuel System

Base Fuel TankWater Separator FuelPrefilterFuel Tank DrainFuel Level Control PanelDisplayOil Pan

Lubrication System

Lube Oil Drain Pump

Cooling System

50℃ RadiatorExternal Water InletProtection Mesh for Fanand Revolving Parts

Air intake system

Air FilterIntake Air Filter ScreenIntake Air Silencer

Exhaust system

Industrial SilencerHeat InsulationProtective SleeveExhaust Outlet withFlexibleHeat Hand Protection

Shipment and Installation

Forklift Lifting PointsLifting LugDragging HoleSide Collision AvoidanceDesignBase Mounting Hole

Safety protection devices

Earth ProtectionOil PressureWarning/DowntimeOil LevelWarning/DowntimeWater TemperatureWarning/DowntimeWater LevelWarning/DowntimeSpeedWarning/DowntimeExternal Emergency Stop

Technical documents

Genset OperationManualEngine Operation ManualAlternator OperationManualGenset Test ReportGanset Circuit DiagramGenset InstallationDrawingsMaintenance ManualMaintenance Records

Engine

Water-Cooled EngineBatteryBattery SwitchDraining Oil PumpStandard Air FilterRadiator Core GuardAir Filter withReplaceable CartridgeBattery Charger

Machine Body

Baseplate with RetentionTank

- - -

GMP80PX/ 100002493980kVA, Open Type, 4DTA4.8ECG2, PL2DS, 3phase, AutoGen

www.powerlinkworld.com | [email protected] 6/7

Page 7: GMP80PX/ - א.ב גנרטורים בע · 2017-11-13 · Designed to operate in ambient conditions up to 50°C (122°F).Contact your local PowerLink Dealer for power ratings at specific

Specification may change without prior notice. For more info,please contact PowerLink or your local distributors.

RP Series / 2017-11-01

Optional Configuration

Alternator

PMGAnti-condensationHeaterWinding TemperatureMeasurement

Control System

PLC-7420 ControlSystemPLC-8610 ControlSystemLeak Protection Device

Fuel System

External Fuel FillingDeviceFuel Level GaugeFuel Three-Way ValueAuto Refilling DieselSystem

Lubrication System

Auto Refilling Oil SystemLube Oil PreheaterLube Oil TemperatureSensor

Cooling System

45℃ Radiator40℃ RadiatorSupplied with Coolant

Air intake system

Forced Air Inlet SystemIntake Air PreheatingSystem

Exhaust system

Residential Silencer

Voltage

415/240V400/230V380/220V220-240V-SINGLEPHASE220/127V480/277V440/254V

Wheel Braking System

Trailer-Roadside TypeTrailer-Off-Road TypeTrailer SuspensionSystem

Safety protection devices

RCD ProtectionImbalanced Three-phaseWarning/DowntimeSpark-extinguishingDeviceAnti-lightning InstallationSecure TransportationOpen the Door ShutdownProtectionExtinguisherExplosion-proof LampNo-skid FloorRest Area

High-tech configuration

Remote ControlRemote Communicationand DiagnosisRemote MonitorAuto Start-Stop SystemAlert MessageNotificationMaintenance CycleNotification

Optional configuration

Three-way CatalyticConverterEngine Triple PaintedGenset ParallelInstallationExternal Fuel TankSECC Base FrameStainless Steel ExhaustSystem4 Poles Circuit BreakerATSQuick ConnectorFuel Leaking Protection

Technical documents

Genset Parts ManualEngine Parts ManualGenset Tools Package

Engine

Jacket Water Heater220/240VOil HeaterBlock HeaterHeavy Duty Air Filter

-

GMP80PX/ 100002493980kVA, Open Type, 4DTA4.8ECG2, PL2DS, 3phase, AutoGen