GMP80PX/ - א.ב גנרטורים בע · 2017-11-13 · Designed to operate in ambient conditions...
Transcript of GMP80PX/ - א.ב גנרטורים בע · 2017-11-13 · Designed to operate in ambient conditions...
Features:
• PowerLink engine• PowerLink Alternator, Class H• Genset Canopy N/A protection, Control panelIP56 protection• Control module PLC-920• Breaker:• Speed governor: Electronic governor• Excitation system: Brushless• A.V.R model: SX460• 50℃ radiator• Big daily fuel tank(Below 800KVA)• Fire extinguisher• Oil pump on the engine• ATS receptacle• Lockable battery isolator switch• Vibration isolators between the engine/Alternatorand base frame• Integrated wiring design• High water temperature protection
Output Ratings
Generator Set
Model
Prime Power Standby Power
kVA kW kVA kW
GMP80PX 80 64 103 82
Ratings at 0.8 power factor
Dimensions and Weights
Model L × W × H-mmDry Weight-
kg
GMP80PX 2156× 881× 1495 1196
Ratings and Performance Data
Engine Brand PowerLink
Engine Model 4DTA4.8ECG2
Alternator Brand PowerLink
Alternator Model PL2DS
Control System PLC-920
Circuit Breaker Type
Frequency / Phase 50Hz/3Phase
Engine Speed((RPM)) 1500
Fuel Tank Capacity((L)) 206
Fuel Consumption((L/h))(100%load)
19.8
Model Type Open Type
Standard Package
Noise Level@7m((dBA)) N/A
Generator set Manufacture PowerLink
Oil Consumption((L/h)) 1.53
Volatage((V)) 380/400/415/440
Silencer Noise
Reduction((dBA))10-12
Notes:*Prime Power Continuous duty operation, under variable load 24/24h-10%over load permissible 1 hour/12 hours; **Standby Power Standby duty, operation under variable load, without overload; Standard Reference Conditions Note: Standard reference conditions25°C (77°F) Air Inlet Temp, 100m(328 ft) A.S.L. 30% relative humidity.
GMP80PX/ 100002493980kVA, Open Type, 4DTA4.8ECG2, PL2DS, 3phase, AutoGen
www.powerlinkworld.com | [email protected] 1/7
Engine Model:4DTA4.8ECG2
Engine Technical Data
Engine Model 4DTA4.8ECG2
Engine Brand PowerLink
Number of Cylinders 4
Cylinders Arrangement Inline
Bore/Stroke((mm)) 110/125
Speed((RPM)) 1500
Displacement((L)) 4.75
Compression Ratio 17
Air Intake systemTurbocharge
aftercooler
Cooling Method Water cooled
Coolant Capacity((L)) 6
Prime Power((kWm)) 82
Standby Power((kWm)) 90
Governing Type Electronic
Back Pressure((mmhg)) 6
Battery((V)) 12
Exhaust and silencer System
Exhaust Air Flow((m³/hr)) 1040.4
Exhaust Air Temp.((°C)) N/A
Maximum Allowable Back
Pressure((mmhg))6
NOx((mg/Nm³)) N/A
Silencer Quantity 1
Silencer Type Industrial silencer
Cooling System
Radiator 50
Coolant Capacity((L)) 6
Coolant Change Time((Year/h)) 2/10000
Coolant Intake Temp.((°C)) 76
Coolant Output Temp.((°C)) 99
Designed to operate in ambient conditions up to 50°C (122°F).Contactyour local PowerLink Dealer for power ratings at specific site conditions
Fuel System
Fuel Tank steel
Fuel Tank Capacity((L)) 206
Fuel tank type Single-layer
Recommended Fuel Type 0# or ASTM2
Injection System Direct injection
Fuel Consumption:
GMP80PX 100%Load
75%Load
50%Load
25%Load
L/h 19.8 15.6 10.8 6.4
(Based on diesel fuel with a specific gravity of 0.85 and conforming toBS2869,Class A2)
Air Intake system
Air Filter Type Dry type
Intake Air Flow((m³/h)) 399.6
Intake SystemTurbocharge
aftercooler
Intake Air Temp.((°C)) 25
Lubrication System
Lube oil label
Maximum Oil Temp.((°C)) ≤100
Oil capacity((L)) 14
Conditions
Altitude((m))
Ambient Temp.((°C)) -5℃-50℃Barometric Pressure((kpa)) 100
Relative Humidity <80%
GMP80PX/ 100002493980kVA, Open Type, 4DTA4.8ECG2, PL2DS, 3phase, AutoGen
www.powerlinkworld.com | [email protected] 2/7
Alternator Model:PL2DS
Alternator Physical Data
AVR Model SX460
Alternator Brand PowerLink
Alternator Model PL2DS
Excitation System Brushless
Housing Protection IP23
Power Factor 0.8
Rated Stator Temp. rise((℃)) 125
Rotor Insulation Class H
Voltage Fluctuation(no load to
full load)±0.5%
Winding Pitch 2/3
Wiring Connection Series Star
Alternator Operating Data
Overspeed((rpm)) 2250
Voltage Reguation(Steady state) ± 1.0 %
THF(BS EN60034-1) <50
TIF(NEMA MG 1-22) <2%
Air Flow((m³/s))-Alternator
50Hz/60Hz0.514
Altitude-Alternator((m)) 1000
Performance Data
Time constants/400V((Ms))
T’d 0.042 s
T’’d 0.012 s
T’do 1.1 s
Ta 0.012 s
Short-circuit current (3 IN / 10 s) 300 % (3 IN) : 10s
SHORT CIRCUIT RATIO 1/Xd
Reactances((Per Unit))
Xd
X'd
X"d
Voltage Technical Data
VoltagePrime Standby
kVA kW kVA kW
380V@50Hz 80 64 88.0 70.4
400V@50Hz 80 64 88.0 70.4
415V@50Hz 80 64 88.0 70.4
415V@60Hz 98 78.4 107 86.24
440V@60Hz 98 78.4 107 86.24
480V@60Hz 98 78.4 107 86.24
GMP80PX/ 100002493980kVA, Open Type, 4DTA4.8ECG2, PL2DS, 3phase, AutoGen
www.powerlinkworld.com | [email protected] 3/7
Overall Dimensions
GMP80PX/ 100002493980kVA, Open Type, 4DTA4.8ECG2, PL2DS, 3phase, AutoGen
www.powerlinkworld.com | [email protected] 4/7
Control System
GMP80PX/ 100002493980kVA, Open Type, 4DTA4.8ECG2, PL2DS, 3phase, AutoGen
www.powerlinkworld.com | [email protected] 5/7
Product Standard Configuration
Alternator
AlternatorA.V.R
Control System
PLC-920 Control SystemAir BreakerExternal CableConnectionCable Line Slot
Fuel System
Base Fuel TankWater Separator FuelPrefilterFuel Tank DrainFuel Level Control PanelDisplayOil Pan
Lubrication System
Lube Oil Drain Pump
Cooling System
50℃ RadiatorExternal Water InletProtection Mesh for Fanand Revolving Parts
Air intake system
Air FilterIntake Air Filter ScreenIntake Air Silencer
Exhaust system
Industrial SilencerHeat InsulationProtective SleeveExhaust Outlet withFlexibleHeat Hand Protection
Shipment and Installation
Forklift Lifting PointsLifting LugDragging HoleSide Collision AvoidanceDesignBase Mounting Hole
Safety protection devices
Earth ProtectionOil PressureWarning/DowntimeOil LevelWarning/DowntimeWater TemperatureWarning/DowntimeWater LevelWarning/DowntimeSpeedWarning/DowntimeExternal Emergency Stop
Technical documents
Genset OperationManualEngine Operation ManualAlternator OperationManualGenset Test ReportGanset Circuit DiagramGenset InstallationDrawingsMaintenance ManualMaintenance Records
Engine
Water-Cooled EngineBatteryBattery SwitchDraining Oil PumpStandard Air FilterRadiator Core GuardAir Filter withReplaceable CartridgeBattery Charger
Machine Body
Baseplate with RetentionTank
- - -
GMP80PX/ 100002493980kVA, Open Type, 4DTA4.8ECG2, PL2DS, 3phase, AutoGen
www.powerlinkworld.com | [email protected] 6/7
Specification may change without prior notice. For more info,please contact PowerLink or your local distributors.
RP Series / 2017-11-01
Optional Configuration
Alternator
PMGAnti-condensationHeaterWinding TemperatureMeasurement
Control System
PLC-7420 ControlSystemPLC-8610 ControlSystemLeak Protection Device
Fuel System
External Fuel FillingDeviceFuel Level GaugeFuel Three-Way ValueAuto Refilling DieselSystem
Lubrication System
Auto Refilling Oil SystemLube Oil PreheaterLube Oil TemperatureSensor
Cooling System
45℃ Radiator40℃ RadiatorSupplied with Coolant
Air intake system
Forced Air Inlet SystemIntake Air PreheatingSystem
Exhaust system
Residential Silencer
Voltage
415/240V400/230V380/220V220-240V-SINGLEPHASE220/127V480/277V440/254V
Wheel Braking System
Trailer-Roadside TypeTrailer-Off-Road TypeTrailer SuspensionSystem
Safety protection devices
RCD ProtectionImbalanced Three-phaseWarning/DowntimeSpark-extinguishingDeviceAnti-lightning InstallationSecure TransportationOpen the Door ShutdownProtectionExtinguisherExplosion-proof LampNo-skid FloorRest Area
High-tech configuration
Remote ControlRemote Communicationand DiagnosisRemote MonitorAuto Start-Stop SystemAlert MessageNotificationMaintenance CycleNotification
Optional configuration
Three-way CatalyticConverterEngine Triple PaintedGenset ParallelInstallationExternal Fuel TankSECC Base FrameStainless Steel ExhaustSystem4 Poles Circuit BreakerATSQuick ConnectorFuel Leaking Protection
Technical documents
Genset Parts ManualEngine Parts ManualGenset Tools Package
Engine
Jacket Water Heater220/240VOil HeaterBlock HeaterHeavy Duty Air Filter
-
GMP80PX/ 100002493980kVA, Open Type, 4DTA4.8ECG2, PL2DS, 3phase, AutoGen
www.powerlinkworld.com | [email protected] 7/7