GLOBAL STANDARD Page 1 of 18 METAL-OXIDE POLYMER-HOUSED SURGE ARRESTERS WITHOUT GAPS FOR A.C. SYSTEMS FOR SUBSTATIONS FROM 12KV TO 245 KV GSCH005 Rev. 01 05/07/2017 Copyright 2017. All rights reserved. METAL-OXIDE POLYMER-HOUSED SURGE ARRESTERS WITHOUT GAPS FOR A.C. SYSTEMS FOR SUBSTATIONS FROM 12KV TO 245 KV This document is intellectual property of Enel SpA; reproduction or distribution of its contents in any way or by any means whatsoever is subject to the prior approval of the above mentioned company which will safeguard its rights under the civil and penal codes. Countries’ I&N Elaborated by Argentina E.Klymenco, Hugo Merino Brazil V. Galvao, Vanderlei Robadey Carvalho Chile H. C. Rother Salazar, Manuel Alejandro Gutierrez Toro Colombia C. A. Rincon Alvarez, Jose H. Gomez Cuevas Iberia C. Llovich Badia, Juan M. Rey Italy Roberto Emma, Luigi Foddai Peru Roberto L. Sanchez Vargas, Luis Auqui Fernandez Romania M. Domnicu, Sandici Virginia Ileana Adriana Elaborated by Verified by Approved by Solution Development Center Juan M. Rey C. Llovich Badia C. Llovich Badia Global I&N NT/NCS - J. M. Rey Sanchez F. Giammanco Revision Data List of modifications 01 -

Transcript of Global Standard - Metal-Oxide Polymer-Housed Surge ...

GLOBAL STANDARD Page 1 of 18

METAL-OXIDE POLYMER-HOUSED SURGE ARRESTERS WITHOUT GAPS FOR A.C. SYSTEMS FOR SUBSTATIONS

FROM 12KV TO 245 KV

GSCH005 Rev. 01

05/07/2017

Copyright 2017. All rights reserved.

METAL-OXIDE POLYMER-HOUSED SURGE ARRESTERS WITHOUT GAPS FOR A.C. SYSTEMS FOR SUBSTATIONS FROM 12KV TO 245 KV

This document is intellectual property of Enel SpA; reproduction or distribution of its contents in any way or by any means whatsoever is subject to the prior approval of the above mentioned company which will safeguard its rights under the civil and penal codes.

Countries’ I&N Elaborated by

Argentina E.Klymenco, Hugo Merino

Brazil V. Galvao, Vanderlei Robadey Carvalho

Chile H. C. Rother Salazar, Manuel Alejandro Gutierrez Toro

Colombia C. A. Rincon Alvarez, Jose H. Gomez Cuevas

Iberia C. Llovich Badia, Juan M. Rey

Italy Roberto Emma, Luigi Foddai

Peru Roberto L. Sanchez Vargas, Luis Auqui Fernandez

Romania M. Domnicu, Sandici Virginia Ileana Adriana

Elaborated by Verified by Approved by

Solution Development Center

Juan M. Rey C. Llovich Badia C. Llovich Badia

Global I&N – NT/NCS - J. M. Rey Sanchez F. Giammanco

Revision Data List of modifications 01 -

GLOBAL STANDARD Page 2 of 18

METAL-OXIDE POLYMER-HOUSED SURGE ARRESTERS WITHOUT GAPS FOR A.C. SYSTEMS FOR SUBSTATIONS

FROM 12KV TO 245 KV

GSCH005 Rev. 01

05/07/2017

Copyright 2017. All rights reserved.

INDEX

1 SCOPE ........................................................................................................................................................... 4

2 DEFINITIONS ................................................................................................................................................. 4

3 LIST OF COMPONENTS ............................................................................................................................... 5

4 REFERENCE LAWS AND STANDARDS ..................................................................................................... 5

4.1 Laws ........................................................................................................................................................... 5

4.1.1 Latam ................................................................................................................................................. 5

4.1.2 Spain .................................................................................................................................................. 5

4.1.3 Italy .................................................................................................................................................... 5

4.1.4 Romania ............................................................................................................................................ 5

4.2 Standards .................................................................................................................................................. 5

4.2.1 Common Standards ........................................................................................................................... 5

4.2.2 Specific Standards ............................................................................................................................. 6

5 SERVICE CONDITIONS ................................................................................................................................ 6

5.1 General services conditions .................................................................................................................... 6

5.2 Specific services conditions ................................................................................................................... 6

5.2.1 Endesa Distribución ........................................................................................................................... 6

5.2.2 Enel Distribuzione and Enel Distributie ............................................................................................. 6

5.2.3 Latam ................................................................................................................................................. 7

6 TECHNICAL CHARACTERISTIC .................................................................................................................. 8

7 CONSTRUCTION CHARACTERISTICS ....................................................................................................... 9

7.1 General characteristics ............................................................................................................................ 9

7.2 Specific characteristics .......................................................................................................................... 10

7.2.1 Endesa Distribución ......................................................................................................................... 10

7.2.2 E-distribuzione and E-distributie ...................................................................................................... 10

7.2.3 Latam ............................................................................................................................................... 10

7.3 Insulators ................................................................................................................................................. 10

7.4 HV terminals ............................................................................................................................................ 10

7.4.1 Endesa Distribución and Latam....................................................................................................... 10

7.4.2 E-distribuizone and E-distributie ...................................................................................................... 10

7.5 Grounding ................................................................................................................................................ 10

7.6 Protective treatments ............................................................................................................................. 11

7.6.1 Latam specific requirements............................................................................................................ 11

7.7 Dimensional characteristics .................................................................................................................. 11

7.8 Support .................................................................................................................................................... 11

7.9 Nameplates .............................................................................................................................................. 11

8 TESTING ...................................................................................................................................................... 12

GLOBAL STANDARD Page 3 of 18

METAL-OXIDE POLYMER-HOUSED SURGE ARRESTERS WITHOUT GAPS FOR A.C. SYSTEMS FOR SUBSTATIONS

FROM 12KV TO 245 KV

GSCH005 Rev. 01

05/07/2017

Copyright 2017. All rights reserved.

8.1 General information ................................................................................................................................ 12

8.2 Type tests ................................................................................................................................................ 12

8.2.1 Insulation withstand tests on arrester housing. ............................................................................... 12

8.2.2 Residual voltage tests ..................................................................................................................... 12

8.2.3 Test to verify long term stability under continuous operating voltage ............................................. 12

8.2.4 Test to verify the repetitive charge transfer rating, Qrs ................................................................... 12

8.2.5 Heat dissipation behavior of test sample ......................................................................................... 12

8.2.6 Operating Duty tests ........................................................................................................................ 12

8.2.7 (IEC 60099-4, par 10.8.7)Power frecuency voltage versus time test .............................................. 12

8.2.8 Short-circuit tests ............................................................................................................................. 12

8.2.9 Test of the bending moment ............................................................................................................ 12

8.2.10 Environmental tests ......................................................................................................................... 12

8.2.11 Radio interference voltage (RIV) test .............................................................................................. 13

8.2.12 Test to verify the dielectric withstand of internal components ......................................................... 13

8.2.13 Test of internal grading components ............................................................................................... 13

8.2.14 Weather ageing test ........................................................................................................................ 13

8.3 Routine tests and acceptance tests ...................................................................................................... 13

8.3.1 Routine tests .................................................................................................................................... 13

8.3.2 Acceptance tests ............................................................................................................................. 13

9 CONFORMITY ASSESSMENT ................................................................................................................... 13

9.1 Packing, transport, storage and installation/testing ........................................................................... 13

9.1.1 Specific requirement for Endesa ..................................................................................................... 14

ANNEX A – DIMENSIONAL DRAWINGS ........................................................................................................ 15

A.1 – E-distribuzione – E-distributie .............................................................................................................. 15

ANNEX B – TENDER’S TECHNICAL DOCUMENTATION ............................................................................. 16

ANNEX C – COMPONENT LIST ...................................................................................................................... 17

GLOBAL STANDARD Page 4 of 18

METAL-OXIDE POLYMER-HOUSED SURGE ARRESTERS WITHOUT GAPS FOR A.C. SYSTEMS FOR SUBSTATIONS

FROM 12KV TO 245 KV

GSCH005 Rev. 01

05/07/2017

Copyright 2017. All rights reserved.

1 SCOPE

The scope of this document is to provide technical requirements for the supply of HV surge arresters for system from 12 kV to 245 kV in the Enel Group Distribution companies, listed below:

Ampla (Brazil)

Chilectra (Chile)

Codensa (Colombia)

Coelce (Brazil)

Edelnor (Perù)

Edesur (Argentine)

Endesa Distribución Eléctrica (Spain)

E-distributie Banat (Romania)

E-distributie Dobrogea (Romania)

E-distributie Muntenia (Romania)

E-distribuzione (Italy)

Note: the indication "Latam" refers to the Enel Group Distribution companies in South America. Some requirements are applicable only to one or more companies, therefore, depending on the destination of the surge arresters, the supplied equipment shall comply these specific requirements.

2 DEFINITIONS

Station class arrester: arresters intended for use in station to protect the equipment from transient overvoltages, typically but not only intended for use on system of Us ≥ 72,5 kV. Distributión class arrester: arrester intended for use on distribution systems, typically of Us≤ 52 kV, to protect components primarily from the effects of lightning. Rated voltage of an arrester (Ur): maximum permissible 10 s power-frequency r.m.s. overvoltage that can be applied between the arrester, as verified in the TOV test and the operating duty test. Continuous operating voltage of an arrester (Uc): designed permissible r.m.s. value of power-frequency voltage that may be applied continuously between the arrester terminals in accordance with IEC 60099-4 Rated frequency of an arrester: frequency of the power system on which the arrester is designed to used. Steep current impulse: current impulse with a virtual front time of 1 µs with limits in the adjustment of equipment such that the measured values are from 0,9 µs to 1,1 µs and the virtual time to half-value on the tail is not longer than 20 µs. Lightning current impulse: 8/20 current impulse with limits on the adjustment of equipment such that the measured values are from 7 µs to 9 µs for the virtual front time and from 18 µs to 22 µs for the time to half-value on the tail. Nominal discharge current of an arrester (In): peak value of lightning current impulse which is used to classify an arrester in accordance with IEC 60099-4. High current impulse of an arrester: peak value discharge current having a 4/10 impulse shape which is used to test the stability of the arrester on direct lightning strokes.

GLOBAL STANDARD Page 5 of 18

METAL-OXIDE POLYMER-HOUSED SURGE ARRESTERS WITHOUT GAPS FOR A.C. SYSTEMS FOR SUBSTATIONS

FROM 12KV TO 245 KV

GSCH005 Rev. 01

05/07/2017

Copyright 2017. All rights reserved.

Switching current impulse of an arrester: peak value of discharge current a virtual front time greater than 30 µs but less than 100 µs and a virtual time to half-value on the tail of roughly twice the virtual front time.

Reference voltage of an arrester (Uref): peak value of power-frequency voltage divide by 2, which is obtained when the reference current flows through the arrester. Residual voltage of an arrester (Ures): peak value of voltage that appears between the terminals of an arrester during the passage of discharge current. Protective characteristics of an arrester: a combination of lightning impulse protection level (LIPL), switching impulse protection level (SIPL) and steep current impulse protection level (STIPL).

3 LIST OF COMPONENTS

The complete list of the equipment with their main characteristics is in Annex C (Common list of HV Surge arrester)

4 REFERENCE LAWS AND STANDARDS

4.1 Laws

4.1.1 Latam

4.1.1.1. Brazil:

NR-10 - SEGURANÇA EM INSTALAÇÕES E SERVIÇOS EM ELETRICIDADE

4.1.2 Spain

R.D. 337/2014: Reglamento sobre condiciones técnicas y garantías de seguridad en instalaciones eléctricas de alta tensión. R.D. 614/2001: Disposiciones mínimas para la protección de la salud y seguridad de los trabajadores frente al riesgo eléctrico.

4.1.3 Italy

D.Lgs n. 81 of the 9th of April 2008 and subseguent modifications

4.1.4 Romania

NTE 001/03/00 Normativ privind alegerea izolației coordonarea izolației și protecția instalațiilor electroenergetice impotriva supratensiunilor (Standard on choosing insulation, insulation coordination and overvoltage protection against electric installations).

4.2 Standards

The below listed reference documents shall be intended in the edition in force at the contract date (amendment included).

4.2.1 Common Standards

For Latin America destinations the reference standard are the IEC/ISO, whilst for Europe destinations the reference standard are the correspondent European standards (EN). IEC 60099-4: “Metal-oxide surge arresters without gaps for a.c. systems”.-

GLOBAL STANDARD Page 6 of 18

METAL-OXIDE POLYMER-HOUSED SURGE ARRESTERS WITHOUT GAPS FOR A.C. SYSTEMS FOR SUBSTATIONS

FROM 12KV TO 245 KV

GSCH005 Rev. 01

05/07/2017

Copyright 2017. All rights reserved.

IEC 60071-2: “Insulation co-ordination – Applications guide” IEC 61462: “Composite insulators: hollow insulators for use in outdoor and indoor electrical equipment” ISO 2178: “Non-magnetic coatings on magnetic substrates - Measurement of coating thickness - Magnetic method” CEI 7-6: “Requirements for checking hot galvanizing by immersion on ferrous components used in lines and electrical installations”.IEC 60507: “Artificial pollution tests on high-voltage insulators to be used on a.c. systems” IEC TS 60815: Selection and dimensioning of high-voltage insulators intended for use in polluted conditions

4.2.2 Specific Standards

4.2.2.1. Latam

4.2.2.2. Endesa Distribución

4.2.2.3. E-distribuzione:

ENEL DY 2052 (2005): “Prescrizioni per il collaudo di scaricatori ad ossido metallico senza spinterometri per Cabine Primarie”

4.2.2.4. E-distributie Banat, Dobrogea, Muntenia (Romania):

FT-189_ MAT (2015) ,,Descarcatoare cu oxizi metalici 110 kV DY-557-RO Ed. 2 Statie de transformare.Descarcatoare MT cu oxizi metalici curent de descarcare 10 kV cu carcasa in material Organic cu dispozitiv de conectare

5 SERVICE CONDITIONS

5.1 General services conditions

The reference service conditions are the normal service conditions of IEC 60099-4, with the further indications include in 5.2.

5.2 Specific services conditions

5.2.1 Endesa Distribución

a) Pollution level: Type d (Heavy) or type e (very Heavy)

5.2.2 Enel Distribuzione and Enel Distributie

a) Pollution level: Type d (Heavy); 43,3 mm/kV (RUSCD)

b) Seismic qualification level: AF5 (IEC/TR 62271-300)

GLOBAL STANDARD Page 7 of 18

METAL-OXIDE POLYMER-HOUSED SURGE ARRESTERS WITHOUT GAPS FOR A.C. SYSTEMS FOR SUBSTATIONS

FROM 12KV TO 245 KV

GSCH005 Rev. 01

05/07/2017

Copyright 2017. All rights reserved.

5.2.3 Latam

a) Pollution level: IEC TS 60815

AMPLA CODENSA COELCE CHILECTRA EDELNOR EDESUR

SPS Class (IEC/TS 60815 series)

(e) Very Heavy

(c) Medium

(e) Very heavy

(c) Medium

(e) Very Heavy

(c) Medium

RUSCD (mm/kV) 53,7 34,7 53,7 34,7 53,7 34,7

b) Altitude: The reference altitude in Colombia is 2.850 ms

c) Seismic qualification level:

a. Chilectra ETGI-1020 b. Codensa AF3 (IEC/TR 62271-300) c. Edelnor AF5 (IEC/TR 62271-300)

GLOBAL STANDARD Page 8 of 18

METAL-OXIDE POLYMER-HOUSED SURGE ARRESTERS WITHOUT GAPS FOR A.C. SYSTEMS FOR SUBSTATIONS

FROM 12KV TO 245 KV

GSCH005 Rev. 01

05/07/2017

Copyright 2017. All rights reserved.

6 TECHNICAL CHARACTERISTIC

Mai

n v

olt

age

De

sign

atio

n

Insu

lati

on

leve

l

rate

d f

req

uen

cy (

Hz)

rate

d v

olt

aje

(U

r) (

kV)

con

tin

uo

us

op

era

tin

g vo

ltag

e (

Uc)

(kV

)

no

min

al d

isch

arge

cu

rre

nt

(In

) (k

A)

rate

d s

ho

rt-c

ircu

it c

urr

en

t

Re

sid

ual

vo

ltag

e f

or

ste

ep c

urr

en

t

imp

uls

e (

kV)

Re

sid

ual

vo

ltag

e f

or

lifh

tnin

g cu

rre

nt

imp

uls

e (

kV)

Re

sid

ual

vo

ltag

e f

or

swit

chin

g cu

rren

t

imp

uls

e (

kV)

Hig

h c

urr

ent

imp

uls

e (

kA)

Rat

ed

sta

tic

me

chan

ical

te

rmin

al lo

ad

(daN

)

EDE

220 kV SM 245/395-460/950-1050 50 192 154 10

40 kA 0,2s Clase A 710 633 499 100 125

110 kV SM 123/230-

275/550-650 50 96 77 10

31,5 kA 0,2s Clase

A 355 317 249 100

100

132 kV SM 145/230-

275/550-650 50 120 92 10

31,5 kA 0,2s Clase

A 444 396 312 100

100

50 kV SM 52/140/325

50 53 42 10

31,5 kA 0,2s Clase

A 196 175 138 100

50

66 kV SM 72,5/140/325

50 60 48 10

31,5 kA 0,2s Clase

A 222 198 156 100

50

45 kV SL 52/95/250 50 42 34 10

25 kA 0,2s Clase A 155 138 109 100

50

Neutro Trafo 220/MT

SM 245/275/650 50 146 117 10

40 kA 0,2s Clase A 540 483 380 100

125

Neutro Trafo 110/MT

SM 123/275/650 50 75 60 10

31,5 kA 0,2s Clase

A 278 254 195 100

100

Neutro Trafo 132/MT

SM 245/275/650 50 84 67 10

31,5 kA 0,2s Clase

A 310 276 218 100

100

Neutro Trafo 55/MT

SM 72,5/140/325 50 38 30 10

31,5 kA 0,2s Clase

A 139 127 98 100

50

Neutro Trafo 66/MT

SM 72,5/140/325 50 42 34 10

31,5 kA 0,2s Clase

A 155 142 109 100

50

E-Dist. 132 kV SL 132/450/750 50 132 94 10 31,5 kA 386 336 270 100

200

150 kV SL 150/450/750 50 158 110 10 31,5 kA 455 396 318 100 200

ENEL Rom 110 kV SL 123/230/550 50 96 72 10 40 kA 310 280 220 100

200

Neutro trafo 110/MT

SL 123/185/450 50 57 45,5 10 40 kA 222 200 190 100

200

CODENSA

220 kV SM 245/460/950 60 192 152 10 40 kA 489 452 381 100 200

115 kV SL 123/230/550 60 96 76 10 40 kA 266 226 185 100 200

34,5 kV SL 36/70/145 60 30 24 10 25 kA 81,2 100 78 100 50

13,2-11,4 kV SL 17,5/38-28/95-

95 60 12 8,7 10 25 kA 35,1 40 32,8 100 50

CHILECTRA

220 kV SM 245/395/1050 50 198 154 10 40 kA 554 502 455 100 125

110 kV SL 123/230/550 50 96 76 10 40 kA 284 250 220 100 100

23,5 kV SL 24/50/150 50 21 17 10 25 kA 73,2 55 45 100 50

GLOBAL STANDARD Page 9 of 18

METAL-OXIDE POLYMER-HOUSED SURGE ARRESTERS WITHOUT GAPS FOR A.C. SYSTEMS FOR SUBSTATIONS

FROM 12KV TO 245 KV

GSCH005 Rev. 01

05/07/2017

Copyright 2017. All rights reserved.

Mai

n v

olt

age

De

sign

atio

n

Insu

lati

on

leve

l

rate

d f

req

uen

cy (

Hz)

rate

d v

olt

aje

(U

r) (

kV)

con

tin

uo

us

op

era

tin

g vo

ltag

e (

Uc)

(kV

)

no

min

al d

isch

arge

cu

rre

nt

(In

) (k

A)

rate

d s

ho

rt-c

ircu

it c

urr

en

t

Re

sid

ual

vo

ltag

e f

or

ste

ep c

urr

en

t

imp

uls

e (

kV)

Re

sid

ual

vo

ltag

e f

or

lifh

tnin

g cu

rre

nt

imp

uls

e (

kV)

Re

sid

ual

vo

ltag

e f

or

swit

chin

g cu

rren

t

imp

uls

e (

kV)

Hig

h c

urr

ent

imp

uls

e (

kA)

Rat

ed

sta

tic

me

chan

ical

te

rmin

al lo

ad

(daN

)

12,5 kV SL 17,5/38/110 50 12 8,7 10 25 kA 46,6 40 32,8 100

50

EDELNOR

220 kV SM 245/460/1050 60 198 154 10 40 kA 554 502 455 100 125

60 kV SL 72,5/140/325 60 60 48 10 40 KA 170 160 126 100 100

EDESUR

220 kV SH 245/395/950 50 198 154 20 40 kA - 502 455 100 125

132 kV SM 245/230/550 50 120 92 10 40 kA - 310 270 100 100

AMPLA

138 kV SM 145/275/650 60 120 92 10 40 kA - 310 270 100 100

69 kV SL 72,5/140/325 60 60 48 10 31,5 kA - 200 150 100 50

34,5 kV SL 36/70/170 60 30 24 10 25 kA - 100 78 100 50

13,8 kV-11,95 kV SL 17,5/38/95

60 12 10 10 25 kA - 40 32,8 100 50

COELCE

69 kV SL 72,5/140/350 60 60 48 10 25 kA - 200 150 100 50

13,8 kV SL 17,5/38/110 60 12 10 10 25 kA - 40 32,8 100 50

7 CONSTRUCTION CHARACTERISTICS

7.1 General characteristics

The surge arresters shall be manufactured in accordance with IEC 60099-4.The dimensional drawings, for E-distribuzione e E-distributie, are in annex A. The support, quoted separately, shall be always supplied when a seismic qualification level is required (see 5.2.), otherwise it’s an optional supply. If interface plates and other accessories are necessary to adapt the support to the civil works, they shall be included in the supply of the support and shall be preliminary approved by Enel Group Distribution companies. The HV surge arrester must be mounted on an insulating base, in order to isolate from earth, for connecting to surge counters and for measuring the surge arresters of the leakage current. Only for Brazil the surge counters is an optional supply for HV arresters, but all arresters shall be mounted on an insulating base or bracket, in order to isolate from earth. If it’s necessary an grading ring to modify electrostatically the voltage distribution along the arrester, it shall be included in the supply. The normal use, control and maintenance operations shall be performed with total workers safety.

GLOBAL STANDARD Page 10 of 18

METAL-OXIDE POLYMER-HOUSED SURGE ARRESTERS WITHOUT GAPS FOR A.C. SYSTEMS FOR SUBSTATIONS

FROM 12KV TO 245 KV

GSCH005 Rev. 01

05/07/2017

Copyright 2017. All rights reserved.

7.2 Specific characteristics

7.2.1 Endesa Distribución

The surge arrester shall be performed in one unit until 145 kV, and shall be performed in two units for higher voltages. Always, it makes in a unique column.

7.2.2 E-distribuzione and E-distributie

The surge arrester could be performed in one or more units connected in series. Always it makes in a unique column.

7.2.3 Latam

The surge arrester could be performed in one or more units connected in series. Always in a unique column.

7.3 Insulators

The insulators could be requested by Enel Group Distribution companies in composite materials. They shall be in light grey color and compliant with IEC 61462. The envelope shall be made of silicone rubber, HTV type (High Temperature Vulcanized) or LSR type (Liquid Silicone Rubber) and completely free of EPDM or other organic rubbers. The creepage distance must comply with IEC60815-2 and IEC 60815-3 part. 9.7 with no deviations

7.4 HV terminals

7.4.1 Endesa Distribución and Latam

The HV terminal shall be realized with corrosion resistant copper or aluminum alloy, in order to be interfaced with aluminum alloy clamps.

The HV terminals shall be compliant with fig. 3 (2x2 hole pattern) of IEC/TR 62271-301.

A (mm) B (mm) C (mm)

44,5 44,5 14,3

7.4.2 E-distribuizone and E-distributie

The HV terminal shall be realized with corrosion resistant copper or aluminum alloy, in order to be interfaced with aluminum alloy clamps. The HV terminals shall have Ø 40 ±0,25 X 80 min (mm) (fig. 1 of IEC/TR 62271-301) dimensions.

7.5 Grounding

The manufacturer shall ensure the equi-potentiality between all parts forming the equipment. At the base of each support upright two grounding points shall be provided, equipped with M12 stainless steel bolts (included in the supply).

GLOBAL STANDARD Page 11 of 18

METAL-OXIDE POLYMER-HOUSED SURGE ARRESTERS WITHOUT GAPS FOR A.C. SYSTEMS FOR SUBSTATIONS

FROM 12KV TO 245 KV

GSCH005 Rev. 01

05/07/2017

Copyright 2017. All rights reserved.

If interface plates are necessary to adapt the support to the civil works, they shall be designed taking into account the position of the external grounding connections.

7.6 Protective treatments

All external surfaces shall have an effective and enduring anti-corrosion protection. All iron parts (e.g. support, Control Box, bolts etc.) shall be in non-corrosive material or hot dip galvanized in compliance with ISO 1461. All processing shall be completed before the protective treatments. Protective treatments alternative to the hot dip galvanization could be accepted if the manufacturer prove its fitness. The metallic elements in contact between them shall be designed in order to avoid corrosion due to humidity galvanic effect.

7.6.1 Latam specific requirements.

In Brazil (Ampla y Coelce) and Perú (Edelnor) there is atmospheric corrosive environments "Very High" (C5- ISO 9223 and ISO 12944). Thus, control boxes or cabinets, bolts, etc.. shall be made of stainless

steel.

7.7 Dimensional characteristics

Specific dimensional requirements are shown in Annex A.

7.8 Support

The support is an optional supply.

7.9 Nameplates

The nameplates shall be in stainless steel. Alternative materials can be considered if the manufacturer proves the marking endurance respect to the ageing (this solution shall be approved by Enel Distribution companies).

In accordance with IEC 60099-4, nameplates shall include:

a) The manufacturer’s name o trade mark, type and identification of the complete arrester; b) Serial number; c) The year of manufacture; d) Type code of Enel; e) Rated voltage; f) Continuous operating voltage; g) Rated frequency; h) Nominal discharge current; i) Rated short-circuit withstand current in kiloamperes (kA) j) Designation k) Contamination withstand level of the enclosure.

GLOBAL STANDARD Page 12 of 18

METAL-OXIDE POLYMER-HOUSED SURGE ARRESTERS WITHOUT GAPS FOR A.C. SYSTEMS FOR SUBSTATIONS

FROM 12KV TO 245 KV

GSCH005 Rev. 01

05/07/2017

Copyright 2017. All rights reserved.

8 TESTING

8.1 General information

The tests will be performed according to Standards 60099-4. The tests to be performed on surge arrester are divided in:

Type tests;

Routine tests and acceptance tets;

Test requirements on polymer-housed surge arrester

8.2 Type tests

8.2.1 Insulation withstand tests on arrester housing.

(IEC 60099-4, par. 10.8.2)

8.2.2 Residual voltage tests

(IEC 60099-4, par. 10.8.3)

8.2.3 Test to verify long term stability under continuous operating voltage

(IEC 60099-4, par. 10.8.4)

8.2.4 Test to verify the repetitive charge transfer rating, Qrs

(IEC 60099-4, par. 10.8.5)

8.2.5 Heat dissipation behavior of test sample

(IEC 60099-4, par. 10.8.6)

8.2.6 Operating Duty tests

(IEC 60099-4, par 10.8.7)

8.2.7 Power frecuency voltage versus time test

(IEC 60099-4, par. 10.8.8)

8.2.8 Short-circuit tests

(IEC 60099-4, par. 10.8.10)

8.2.9 Test of the bending moment

(IEC 60099-4, par. 10.8.11)

8.2.10 Environmental tests

(IEC 60099-4, par. 10.8.12)

GLOBAL STANDARD Page 13 of 18

METAL-OXIDE POLYMER-HOUSED SURGE ARRESTERS WITHOUT GAPS FOR A.C. SYSTEMS FOR SUBSTATIONS

FROM 12KV TO 245 KV

GSCH005 Rev. 01

05/07/2017

Copyright 2017. All rights reserved.

8.2.11 Radio interference voltage (RIV) test

(IEC 60099-4, par. 10.8.14)

8.2.12 Test to verify the dielectric withstand of internal components

(IEC 60099-4, par. 10.8.15)

8.2.13 Test of internal grading components

(IEC 60099-4, par. 10.8.16)

8.2.14 Weather ageing test

(IEC 60099-4, par. 10.8.17)

8.3 Routine tests and acceptance tests

8.3.1 Routine tests

(IEC 60099-4, par. 9.1)

8.3.2 Acceptance tests

(IEC 60099-4, par. 9.2)

9 CONFORMITY ASSESSMENT The Technical Conformity Assessment will carry out in accordance with Global Standard GSCG002.

9.1 Packing, transport, storage and installation/testing

The surge arrester package shall be suitable to guarantee:

a) the protection during transport (including by ship, if necessary); b) an elevation from the ground at least of 100 mm; c) the external storage for at least three months.

On external side of packaging, the following information shall be present

a) manufacturer name; b) manufacturing year/month; c) manufacturer designation type; d) manufacturer serial number; e) Enel component codification (i.e.: GSCH005/1 - 0505X); f) contract number; g) destination substation; h) total weight; i) lifting information (showing the points and the correct method of lifting); j) only for E-distribuzione, the bar code, in accordance with PVR006.

With each surge the following items shall be supplied in the local language of destination (items from 4 to 8 on paper):

a) the support structure (only if requested) with its anchor bolts to the civil works (stainless or hot dip galvanized steel, chemical or expansion type);

b) bolts to assembly the DS/ES poles to support structure

GLOBAL STANDARD Page 14 of 18

METAL-OXIDE POLYMER-HOUSED SURGE ARRESTERS WITHOUT GAPS FOR A.C. SYSTEMS FOR SUBSTATIONS

FROM 12KV TO 245 KV

GSCH005 Rev. 01

05/07/2017

Copyright 2017. All rights reserved.

c) list of documentation, materials and accessories supplied; d) overall dimensions drawing; e) electric diagram; f) surge arrester installation, use and maintenance handbook/manual; g) routine and commissioning tests:

a. routine (factory) test reports; b. reference values table (with tolerances);

h) one USB device containing the whole type A documentation (pdf file format).

9.1.1 Specific requirement for Endesa

The manufacturer must present the declaration of conformity in compliance with ITC-RAT 03 of the “Reglamento sobre condiciones técnicas y garantías de seguridad en instalaciones eléctricas de alta tensión, Real Decreto 337/2014.”

GLOBAL STANDARD Page 15 of 18

METAL-OXIDE POLYMER-HOUSED SURGE ARRESTERS WITHOUT GAPS FOR A.C. SYSTEMS FOR SUBSTATIONS

FROM 12KV TO 245 KV

GSCH005 Rev. 01

05/07/2017

Copyright 2017. All rights reserved.

ANNEX A – DIMENSIONAL DRAWINGS

A.1 – E-distribuzione – E-distributie

GLOBAL STANDARD Page 16 of 18

METAL-OXIDE POLYMER-HOUSED SURGE ARRESTERS WITHOUT GAPS FOR A.C. SYSTEMS FOR SUBSTATIONS

FROM 12KV TO 245 KV

GSCH005 Rev. 01

05/07/2017

Copyright 2017. All rights reserved.

ANNEX B – TENDER’S TECHNICAL DOCUMENTATION

GLOBAL STANDARD: GSH05X – HV Surge Arresters

TENDER:

SUPPLIER: FACTORY:

ENEL GROUP TYPE CODE: GSH05X/__ SUPPLIER MODEL:

TECHNICAL CHARACHTERISTIC STANDARD

REQUIREMENT SUPPLIER OFFER

Service conditions normal service conditions

of IEC 60099-4

Reference altitude (m) < 1.000

(2.850 for Colombia)

SPS Class (IEC/TS 60815 series) d) or e)

Ice coating (mm)

10

(22 for Romania)

Seismic qualification level See 5.2

Rated voltage See table in 6

Rated frequency fr (Hz) 50 or 60

Continuous operating voltage (kV) See table in 6

Nominal discharge current (kA) See table in 6

Rated short-cicuit current (kA) See table in 6

Residual voltage for steep current impulse (kV) See table in 6

Residual voltage for lifhtning current impulse (kV) See table in 6

Line discharge class See table in 6

Residual voltage for switching current impulse (kV) See table in 6

High current impulse (kA) See table in 6

Long-duration current impulse (2400 us) See table in 6

Rated static mechanical terminal load (daN) See table in 6

Dimensions See Annex A

To enclose an overall equipment drawing for

each Enel Group Distribution Company

GLOBAL STANDARD Page 17 of 18

METAL-OXIDE POLYMER-HOUSED SURGE ARRESTERS WITHOUT GAPS FOR A.C. SYSTEMS FOR SUBSTATIONS

FROM 12KV TO 245 KV

GSCH005 Rev. 01

05/07/2017

Copyright 2017. All rights reserved.

ANNEX C – COMPONENT LIST

Type code

Company Company

code

TAM Company

code

Highest system voltage

(kV) Designation

Rated frequency

(Hz)

Rated voltage

(Ur); (kV)

Continuous operating

voltage (Uc); (kV)

Nominal discharge

current (In); (kA)

Pollution level (mm) Housed

GSCH005/001 EDE 6701231 170023 245 SM 50 192 154 10 6125 polymer

GSCH005/002 EDE 6701232 170024 145 SM 50 120 92 10 3625 polymer

GSCH005/003 EDE 6701233 170025 123 SM 50 96 77 10 3625 polymer

GSCH005/004 EDE 6701234 170026 72,5 SM 50 60 48 10 1813 polymer

GSCH005/005 EDE 6701235 170027 60 SM 50 53 42 10 1813 polymer

GSCH005/006 EDE 6701236 170028 52 SL 50 42 34 10 1300 polymer

GSCH005/007 EDE 6701749 170029 245 SM 50 146 117 10 3625 polymer

GSCH005/008 EDE 6701750 170120 123 SM 50 75 60 10 3625 polymer

GSCH005/009 EDE 6701751 170121 145 SM 50 84 67 10 3625 polymer

GSCH005/010 EDE 6701752 170122 72,5 SM 50 42 34 10 1813 polymer

GSCH005/011 EDE 6701753 170123 60,5 SM 50 38 30 10 1813 polymer

GSCH005/012 EDE 6704914 170092 245 SM 50 192 154 10 7595 polymer

GSCH005/013 EDE 6705241 170093 245 SM 50 146 117 10 4495 polymer

GSCH005/014 EDE 6705242 170094 145 SM 50 120 92 10 4495 polymer

GSCH005/015 EDE 6705243 170095 145 SM 50 84 67 10 4495 polymer

GSCH005/016 EDE 6705244 170096 123 SM 50 96 77 10 4495 polymer

GSCH005/017 EDE 6705245 170097 123 SM 50 75 60 10 4495 polymer

GSCH005/018 EDE 6705246 170098 72,5 SM 50 60 48 10 2248 polymer

GSCH005/019 EDE 6705247 170099 72,5 SM 50 42 34 10 2248 polymer

GSCH005/020 EDE 6705248 170110 60 SM 50 53 42 10 2248 polymer

GSCH005/021 EDE 6705249 170111 60.5 SM 50 38 30 10 2248 polymer

GSCH005/022 EDE 6705250 170112 52 SL 50 42 34 10 1612 polymer

GSCH005/023 EDE 6706805 170040 - - 50 - - - - -

GSCH005/100 E-DIST. 170105 150 SL 50 132 94 10 - polymer

GSCH005/101 E-DIST. 170135 170 SL 50 158 110 10 - polymer

GSCH005/102 E- DIST. 221280 Support - - - - -

GSCH005/103 E- DIST. 221281 Support - - - - -

GSCH005/200 Enel Rom 617303 123 SL 50 96 72 10 3625 polymer

GSCH005/201 Enel Rom 617304 123 SL 50 57 45,5 10 3625 polymer

GSCH005/300 AMPLA 4545929 36 SL 60 30 24 10 34,7 kVmm/kV Polymer

GSCH005/301 AMPLA 4545932 72,5 SL 60 60 48 10 34,7 kVmm/kV Polymer

GSCH005/302 AMPLA 4545944 15 SL 60 12 10 10 34,7 kVmm/kV Polymer

GSCH005/303 AMPLA 4660197 145 SM 60 120 92 10 34,7 kVmm/kV Polymer

GSCH005/304 AMPLA/COELCE surge counter 60

GSCH005/400 COELCE 6771010 15 SL 60 12 10 10 >=560 Polymer

GSCH005/401 COELCE 6771008 72,5 SL 60 60 48 10 >=2139 Polymer

GLOBAL STANDARD Page 18 of 18

METAL-OXIDE POLYMER-HOUSED SURGE ARRESTERS WITHOUT GAPS FOR A.C. SYSTEMS FOR SUBSTATIONS

FROM 12KV TO 245 KV

GSCH005 Rev. 01

05/07/2017

Copyright 2017. All rights reserved.

GSCH005/500 CODENSA 220 SM 60 192 152 10 6625 Polymer

GSCH005/501 CODENSA 6787485 115 SL 60 96 76 10 4370 Polymer

GSCH005/502 CODENSA 6787483 13,2-11,4 SL 60 12 8,7 10 765 Polymer

GSCH005/503 CODENSA 6787484 34,5 SL 60 30 24 10 1029 Polymer

GSCH005/504 CODENSA 6781248 13,2-11,4 SL 60 12 8,7 10 765 Polymer

GSCH005/505 CODENSA 6781249 34,5 SL 60 30 24 10 1029 Polymer

GSCH005/600 EDELNOR 6757563 245 SM 60 198 158 10 7595 polymer

GSCH005/601 EDELNOR 6800940 72,5 SL 60 60 48 10 2248 polymer

GSCH005/700 EDESUR 0108-0563 145 SM 50 120 90 10 34,7 mm/kV Polymer

GSCH005/701 EDESUR 0108-0564 245 SH 50 198 150 20 34,7 mm/kV Polymer

GSCH005/800 CHILECTRA 6753286 245 SM 50 198 154 10 4900 Polymer

GSCH005/801 CHILECTRA 6788802 123 SM 50 96 76 10 2460 Polymer

GSCH005/802 CHILECTRA 6788803 24 SL 50 21 17 10 480 Polymer

GSCH005/803 CHILECTRA 6788804 17,5 SL 50 12 8,7 10 350 Polymer

GSCH005/804 CHILECTRA 6750037 13,2 SL 50 15 12,7 10 355 Polymer

GSCH005/805 CHILECTRA 6755739 25,3 SL 50 27 22 10 560 Polymer