GLOBAL PX - Swegon
Transcript of GLOBAL PX - Swegon
Ventilation unit with counterflow plate heat exchanger for commercial applications. Well-suited for both newly constructed buildings and renovation projects.
Maximum airflow of 7080m³/h or 1960l/s
Temperature efficiency ≥ 90% (-10°C/+22°C)
Tempeature efficiency ≥83% acc. EN308
Energy-efficient and quiet EC fans with composite or aluminum blades
For installation indoors or outoors
Premium control technique with touchscreen HMI “TAC-touch”.
Ventilation unit with plate heat exchanger
GLOBAL PX
MAIN ADVANTAGES
DOUBLE FLOW HIGH PERFORMANCE VENTILATION UNITSSince 1997, Lemmens has specialised in the design and manufacture of dual flow ventilation units with energy recovery.From the outset, it adopted the principle that “energy recovery means the search for efficiency… it is therefore absurd to seek to recover heat energy without seeking to minimize power consumption”.It opted for the systematic integration of fans equipped with high performance DC motors (TAC technology). With this technology, the HR line anticipated the most demanding levels of energy requirements to come, such as those set by the new standards ErP2018.Over time, it has developed more extensive and effective control. The most recent (TAC5) is at the forefront of the technology, due both to its internal functionality and its opening via communication (Modbus, TCP/IP, BACnet, KNX).
PLUG-AND-PLAY UNITSThe GLOBAL ventilation units are supplied as plug and play devices. The basic functions are pre-programmed and accessories are pre-installed, pre-wired and pre-configured in factory. Once the remote control module has been connected, all that needs to be done is to switch the unit on and to change the pre-configured parameters if needed.
ACCESS – FOR OPERATORSThe units’ generously sized doors ensure easy access. All of the components are easily accessible, inluded the bypass damper and actuator.
SUMMER AND NIGHT TIME COOLINGA modulating 100% bypass is a standard feature on GLOBAL units equipped with counterflow plate heat exchangers. It allows us to ensure the freecooling function and is automatically controlled based upon indoor and outdoor temperatures. The modulating bypass can also be configured to help defrosting of the heat exchanger. All of the components are easily accessible and can be cleaned with a mild detergent.
DAMPERSThe GLOBAL PX units can be factory-fitted with motorised supply air and exhaust air dampers. If so, the TAC controller activates a fan start-up delay when the unit is started. As an option, a spring return actuator is available.
CONTROL MODULESThe integrated TAC5 control system can be connected to: Touchscreen HMI with 4,3” capacitive touchscreen. For configuring and controlling the operation of a heat recovery unit. SAT BA/KW extension of the main controller. Used for extra functions for which inputs and outputs are not included as standard in the control unit of the air handling unit. SAT MODBUS configuration, visual display and controlling the operation via MODBUS RTU.SAT KNX configuration, visual display and controlling via KNX.TCP/IP module communication via the internet (MODBUS TCP/IP protocol) and the heat recovery devices. Web pages are used for the configuration, visual display and operation.BACnet gateway configuration, visual display and controlling via BACnet IP.
TAC5 CONTROLLERThe control equipment is completely integrated into the GLOB-AL PX air handling unit. The controller controls and regulates the temperatures, airflows and other functions. The controller is pre-configured in factory with default settings. The GLOBAL unit has built-in control equipment that can be operated from the hand-held micro terminal in the form of a touchscreen. The safety isolating switch is located on the outside. The electrical and control system is completely integrated into the air han-dling unit. The microprocessor-based equipment controls and regulates temperatures, airfl ows and other functions. A large number of functions are built into the system and are simple to activate. The air handling unit can be automatically controlled in several ways via the built-in timer or main control system, however it can also be demand-controlled e.g. via a CO2sensor. Manual control is also possible.A large number of functions and
settings can be activated/entered via a main control system.
HMI TACtouchThe hand-held user interface is a 4.3” touchscreen and is very very simple and user friendly. The HMI is rendering on-site commissioning intuitive and simple by means of the com-missioning menu. The HMI is equipped with a 2 meter long connection cable and magnets. By means of the magnets, the HMI can be easily fixed on to any metallic surface. The preset values are stored and will not be unaffected in the event of a power failure.
4 GLOBAL PX
UNIT OVERVIEWGENERAL DESCRIPTION GLOBAL PX
EN1886 CERTIFICATIONEN1886 classification: T3(M)/TB2(M)/F9(R)/L2(R)/D1(R)(*). Optionally available: T2/TB2/F9/L2/D1. The selection software uses the Eurovent certified selection software as sup-plied by our supplier of the counterflow plate heat exchangers and the filters. All relevant Eurovent certification diplomas are published on the technical datasheet as generated by our selection software. The selection software is availbable for download.
CIRCULAR DUCT CONNECTIONSThe duct connections for sizes 04, 05, 06, 08 and 10 are circular and with rubber sealing. The units can be combined with motorised dampers.
FILTERSAll GLOBAL PX units are equipped with bag filters. The filter material is glass fibre. The function of the filter is to keep both the air and the heat exchanger clean. The fresh air bag filter is of class ePM1≥70%, the extract air bag filter is of class ePM10≥50%. An ePM1≥50% filter on the extract air side is not available since this would have a negative influence on the energy consumption. The filters are mounted in locking guide rails in order to facilitate filter replacement and cleaning of the filter sec-tion. The filters guiderials are compliant to the requirements for filter bypass leakage to Class ePM1≥80% (F9) (EN1886). The filter monitor-ing function is integrated in the standard con-figuration of the TAC5 controller. Optionally, a G4 / COARSE prefilter. All the filters are classi-fied both according to ISO EN 16890 and ISO EN 779 and are Eurovent certified: 08.10.44.
BASE FRAMEThe GLOBAL PX units are prefitted with a base frame. The base frame is self supporting. The height of the base frame is 125mm. The base frame has 48mm holes to facilitate lifting by a crane; the base frame has openings in order to facilitate horizontal transport by means of a pallet truck.
INTERNAL PRE-FILTERSPrefilters installed inside the air handling unit can be ordered as optional accessory. Prefil-ters are used when the outdoor air is heavily polluted and it is desirable to prevent the fine filters inside the GLOBAL unit from becom-ing clogged after a short period of use. The prefilters are of Class G4 compact filters. The prefilters are mouted in locking guide rails in order to facilitated removal and inspection.The prefilters guiderials are compliant to the requirements for filter bypass leakage according to EN1886: Class F9. The prefilter monitoring function is integrated in the standard configu-ration of the TAC5 controller.
RECTANGULAR DUCT CONNECTIONSThe standard duct connections (15mm) for sizes 12, 13, 14, 16 and up are rectangular. For the units with rectangular duct connections, several optional accessories are available: Adapter rec-tangular/circular, 20mm slip clamps or even a 30mm connection frame (METU). The units can be fitted with motorised dampers and flexible sleeves.
(*) T/TB Classes according tests on modelboxes (M), F/L/D classes according to tests on real units (R)
GLOBAL PX 5
HIGH PERFORMANCE FANSAs standard, the direct-driven EC fans are equipped with composite fan blades. Option-ally, aluminum fan blades are available. The ad-vantage of the composite fan blades are lower weight and bionically designed rotor blades for almost noiseless conveyance of air. The blades are made from 100% recyclable bio-polyam-ides. All of this is finally resulting in a better SFP value. The fans are dynamically balanced according to ISO1940. Both fans are located at the outdoor air side of the plate heat exchang-er, thus drastically reduding the sound levels emitted to the building. The electronically com-mutated (EC) external rotor motor is equipped with an integrated EC controller. The fan motor protection class is IP54. The powerful EC fans ensure that sufficient external pressure is avail-able, even for high airflows. The efficiency level fulfills the ErP2018 requirements. The fans are dynamically balanced. The balancing of the fans is accordingly the ISO1940 standard and is classified G6.3.
INTERNAL WATER HEATING COIL - IBAThe unit can be equipped with an internal water heating coil. The coil is physically located between the plate heat exchanger and the supply air outlet. The water coil has internal water connections and is deliverd with stainless steel flexible connections in order to connect it to the hydraulical system on the outside of the unit. The water coil is equipped with an anti-frost protection temperature sensor, which is mounted on the surface of the coil.
PLATE HEAT EXCHANGERThe plate heat exchanger is a conterflow heat exchanger , made of seawater-resistant aluminium, with a temperature efficiency ≥91% (EN308). The bypass is proportion-ally controlled in order to meet the need for both heating and cooling and can be used in the frost protection control strategy. In order to minimise the risk of frost build-up, the heat exchanger blocks are installed under an angle. This will facilitate the evacuation of condensate thus minising the risk of ice build-up inside of the heat exchanger. The heat exchangers are both Eurovent (Certificate n° 05.03.243) and VDI6022 certified.
INTERNAL ELECTRICAL HEA-TING COIL - KWOUT / KWINThe GLOBAL PX units can be factory-fitted with an integrated electric heater for pre-heat-ing and an electric heater element for post-heating. The capacity of the coil is modulated in order to maintain a constant temperature in either the suppy air or in the extract air. The electrical post or pre- heating coil are equipped with two overheating protections, one with manual reset and one with automati-cal reset. When the electrical coil is configured, the coil is stopped immediately when the unit is stoppped, however, the fans are kept running for 90 seconds to allow electrical coil to cool down.
UNIT CASINGThe casing of the GLOBAL PX units is fabricated of aluminum profiled sections held together by synthetic corners. The outer skin is made of painted steel sheet, RAL7016. The inner skin is made of galvanized sheet steel. The panel thickness is 50mm with intervening insula-tion consisting of mineral wool. The doors are hung on four hinges, two on every side, with integrated handles.
EN1886 casing performance:
Air leakage, class: L2Thermal bridges: TB2Thermal transmission: T3 (optionally T2)Mechanical strength: D1Filter bypass leakage: F9
EXTERNAL COILS - EBAThe GLOBAL PX units can be configured with external coils, fitted in a 50mm insulated casing. Those coils can be water-based of dx heating and/or cooling coils. The capacity of the coil is modulated in order to maintain a constant temperature in either the suppy air or in the extract air. The water heating coil is ready-to-connect and delivered with a 3-way valve controlled by the TAC controller. The TAC5 control system allows for any GLOBAL PX unit to control any combination of coils (water or dx) in cooling only, heating only or change over or cooling and heating.
CONTROL OPTIONS
Touchscreen HMI
BACnet gateway
MODBUS RTU / ETHERNET
WIFI
AVAILABLE OPTIONS � Internal electrical post heating coil (KWout)
� Internal electrical pre-heating coil (KWin)
� Internal water post heating coil (IBA)
� Exteral post heating/cooling coil (EBA)
� Motorised dampers (CT)
� Flexible sleeve 20mm (MS20)
� Flexible sleeve 30mm (MS30)
� Slip clamps 20mm (SC20)
� Air inlet/Outlet with grill (AU)
� Roof for outdoor installation (OUT)
� External 2nd filterstage (EFI)
SAT3
GLOBAL PXseries
KNX
� EN1886 classifiaction: T3/TB2/F9/L2/D1
� Optional: T2/TB2/F9/L2/D1
� Eurovent certified counterflow high efficiency plate heat exchangers.
� Optional integrated electrical pre-heating coil. Fully integrated modu-lating capacity control.
� Optional integrated post-heating coil; electrical or water based. Fully inte-grated modulating capacity control.
� Innovative TACtouch touchscreen interface with intuitive commissioning menu and integrated contextual aid.
� EC plug fans with composite blades for optimised efficiency and low noise levels. Aluminum fan blades available as an option.
� All doors are double-hinged. Thus facilitating access to all components in restricted spaces.
� 3 full-sized doors for easy access.
� RAL7016 galvanized steel sheet con-struction with 50mm mineral wool thermal insulation.
� Robust constuction with aluminum profiles.
� Circular duct connections with dou-ble rubber seal.
� Plug-and-play prewired unit. The complete unit with all of its acces-sories are pre-installed, pre-wired and pre-configured in factory.
� Bag filters for both supply and extract air. EPM1≥70% for fresh air intake and ePM10≥50% for extract air. A COARSE prefilter on fresh air intake available as an option.
� Open structured base frame, facili-tating easy handling on site.
� 48mm holes in 125mm high base-frame for lifting purposes.
� General high level of finishing; possi-bility to adjust door alignement and pressure exerted by the hinges.
� Proven TAC5 controller with precon-figuration.
� Max airflow of 7080 m³/h (1960l/s) for size “26”
� ERP2018 optimised design
� Standard VDI6022 compliant
� ISO EN16890 compliant
� ISO EN 16798-3 compliant
� Selection software available for free download
MAIN ADVANTAGES
8 GLOBAL PX
Flexible For a wide variety oF solutions THE CORRECT OPERATING MODE IS AN IMPORTANT FACTOR
AIRFLOW OR PRESSUREWhether the ventilation system is operated on the basis of constant pressure or constant airflow or via a 0–10V control system depends on the area of application and the specific on-site requirements. The integrated master/slave control system ensures that operation is always well-balanced.
THE ADVANTAGES IN DETAIL
� Sufficiently high reserve pressure � Constant airflow � Demand control: constant airflow linked to a 0–10 V signal
� Constant pressure via an external pressure sensor
Constant airflow modeA typical area of application is non-residential buildings, e.g. offices and business premises as well as schools, nurseries and sports halls with stable volumes of air.
Demand control modeAlternatively, the airflow can be automatically adapted in line with the ventilation requirements and on a user-specific basis via the 0–10 V input, e.g. by means of a CO2 sensor, or the control system can be used via the customer‘s building service management/instrumentation and control system.
Constant pressure modeA prime example is undoubtedly apartment buildings with the opportunity to control the ventilation in individual apartments separately. The pressure remains constant even when the ventilation is increased or decreased in one apartment as required, by means of an airflow control unit.The airflow stays the same in all the other apartments, i.e. the ventilation system always runs within the ideal range. An external pressure sensor is required for constant pressure mode.
THE 3 MAIN OPERATING MODES:
Constant Airflow mode The airflow is kept constant, irrespective of external changes in pressure.
Demand control modeA linear voltage/airflow ratio. The airflow can be controlled via a 0–10 Volt signal.
Constant pressure mode The pressure is kept constant, regardless of external changes in pressure. A pressure sensor is required.
1350
Pa
m3/h
154
m3/h
Pa
185
Sonde
V
m3/h m3/h
Pa
900 9000
10
2205
1800
2000
1000
ppm
sensor
GLOBAL PX 9
unit overview OPTIONAL CONTROL MODULES
Remote control with touchscreen display and integrated timer with 6 actions per day and ‘off day’ functionality. For configuring and controlling the operation of 1 heat recovery unit. The comissing menu, alarm history and maintenance menu are all of them focussed on
Touchscreen REMOTE CONTROL
efficient operation.
Article CID
TACtouch 372096
Interface for configuration, visual display and controlling the operation via MODBUS RTU
SAT MODBUSArticle CID
SAT MODBUS 025006
Interface for configuration, visual display and controlling the operation via MODBUS TCP/IP
SAT ETHERNETArticle CID
SAT Ethernet 025072
For communicating with the heat recovery devices via a BACnet TCP/IP protocol. Up to four units can ben integrated through the interface. The optional SAT Ethernet interface is required.
BACnet gatewayArticle CID
BACnet 025095
The Wifi interface with MODBUS TCP/IP, allows for a wireless connection to the air handling unit. Typically this accessory would be used in order to control the unit with the smart phone application.
SAT WifiArticle CID
SAT wifi 025071
Interface for configuration, visual display and controlling the operation via KNX
SAT KNXArticle CID
KNX 025045
The SAT3 combined with the TAC5 controller allows signalling the following with 2 free of potential contacts: Fan is actually running and alarm on a pre-set pressure variation. This status is expressed by closing the contact
SAT3Article CID
SAT3 370005
Used for external cooling, heating, change over or electrical coils.
SAT BA/KWArticle CID
SAT BA/KW 025007
FRESH AIR BAG FILTER ePM1≥70%
FILTER CLASS(G4 PREFILTER OPTIONAL)
EC PLUG FAN WITH COMPOSITE FAN BLADES
(ALUMINUM BLADES OPTINAL)
INTEGRATED TAC5 CONTROLLER
EASY ACCESS HINGES
HIGH EFFICIENCY COUNTERFLOW PLATE
HEAT EXCHANGER
BASE FRAME FOR EASY ON SITE TRANSPORT
INTEGRATED POST HEATING (WATER/
ELECTRICAL)
EXTRACT AIR BAG FILTER ePM10≥50%
FILTER CLASS
MODULATING 100% BYPASS
1
2
3
4
5
6
7
8
9
1
24
GLOBAL PX SERIES
67
3
9
1
5
8
Airflow (m3/h)
90
91
92
93
94
95
96
97
98
0
100
200
300
400
500
600
700
800
900
200 300 400 500 600 700 800
Pa max SFP=2,5 kW/m³s SFP=2 kW/m³s SFP=1,5 kW/m³s ∩th
12 GLOBAL PX
GENERAL TECHNICAL SPECIFICATIONS
Ava
ilabl
e ex
tern
al p
ress
ure
(Pa)
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
Thermal efficiency (%
)
04GLOBAL PX 04
• AIR VOLUME 200 - 800 m³/h
55 - 220 l/s
• DIMENSIONS (H x W x D) 1465 x 1680 x 610
• WEIGHT 330 kg
• POWER CONNECTION 1 x 230 V
• MAX CURRENT 5.3 A
• RECOMMENDED FUSES D6A / AC3 / 10kA
• FILTER CLASS (SUPPLY / EXTRACT) ePM1 70% / ePM10 50%
• STANDARD DUCT CONNECTIONS (15MM) N.A.
• SLIP CLAMP DUCT CONNECTIONS (20MM) N.A.
• CIRCULAR DUCT CONNECTIONS Ø315
• OPERATING RANGE -20 ... +50 °C
• EN1886 CLASSIFICATION T3 / TB2 / F9 / L2 / D1
• IMPELLOR MATERIAL COMPOSITE
AIR VOLUME ABSORBED POWER SFP THERMAL DRY
EFFICIENCYTHERMAL WET
EFFICIENCYT AFTER HEAT EXCHANGER
SOUNDPRESSURE
Conditions :
1. All values at 200Pa external pressure.
2. T° after heat exchanger at -10°C, 90%RH and +22°C, 50% HR.
3. Thermal wet efficiency at -10°C, 90%RH and +22°C, 50% HR.
4.Sound pressure for ducted unit in free field conditions at 3m.
5. All data for composite fans variant
m3/h l/s W W/m3/h % % °C dB(A)
500 140 239 1,72 86,6 92,4 20,1 25,1
600 165 288 1,73 85,7 93,6 20,0 25,9
700 195 350 1,80 84,9 93,1 19,8 27,3
800 222 419 1,89 84,2 92,7 19,7 28,5
DIMENSIONS (mm)
GLOBAL PX 13
Outdoor air Extract airSupply air Exhaust air
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
GLOBAL PX 04 GLOBAL PX : dimensiOns
GLOBAL PX 04
Left hand versionRight hand version
GLOBAL PX 04
Airflow (m3/h)
90
91
92
93
94
95
96
97
98
0
100
200
300
400
500
600
700
800
900
200 300 400 500 600 700 800 900 1000
Pa max SFP=2,5 kW/m³s SFP=2 kW/m³s SFP=1,5 kW/m³s ∩th
14 GLOBAL PX
GENERAL TECHNICAL SPECIFICATIONS
Ava
ilabl
e ex
tern
al p
ress
ure
(Pa)
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
Thermal efficiency (%
)
05GLOBAL PX 05
• AIR VOLUME 200 - 1060 m³/h
55 - 295 l/s
• DIMENSIONS (H x W x D) 1465 x 1680 x 610
• WEIGHT 330 kg
• POWER CONNECTION 1 x 230 V
• MAX CURRENT 5.3 A
• RECOMMENDED FUSES D6A / AC3 / 10kA
• FILTER CLASS (SUPPLY / EXTRACT) ePM1 70% / ePM10 50%
• STANDARD DUCT CONNECTIONS (15MM) N.A.
• SLIP CLAMP DUCT CONNECTIONS (20MM) N.A.
• CIRCULAR DUCT CONNECTIONS Ø 315
• OPERATING RANGE -20 ... +50 °C
• EN1886 CLASSIFICATION T3 / TB2 / F9 / L2 / D1
• IMPELLOR MATERIAL COMPOSITE
AIR VOLUME ABSORBED POWER SFP THERMAL DRY
EFFICIENCYTHERMAL WET
EFFICIENCYT AFTER HEAT EXCHANGER
SOUNDPRESSURE
Conditions :
1. All values at 200Pa external pressure.
2. T° after heat exchanger at -10°C, 90%RH and +22°C, 50% HR.
3. Thermal wet efficiency at -10°C, 90%RH and +22°C, 50% HR.
4.Sound pressure for ducted unit in free field conditions at 3m.
5. All data for composite fans variant
m3/h l/s W W/m3/h % % °C dB(A)
600 165 286 1,72 86 93 19,9 25,9
800 220 412 1,85 84 92 19,6 28,5
900 250 496 1,98 84 92 18,6 28,9
1000 277 587 2,11 83 92 18,5 27,9
DIMENSIONS (mm)
GLOBAL PX 15
Outdoor air Extract airSupply air Exhaust air
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
GLOBAL PX 05 GLOBAL PX : dimensiOns
GLOBAL PX 05
GLOBAL PX 05
Left hand versionRight hand version
Airflow (m3/h)
90
91
92
93
94
95
96
97
98
0
100
200
300
400
500
600
700
800
900
200 300 400 500 600 700 800 900 1000 1100 1200 1300
Pa max SFP=2,5 kW/m³s SFP=2 kW/m³s SFP=1,5 kW/m³s ∩th
16 GLOBAL PX
GENERAL TECHNICAL SPECIFICATIONS
Ava
ilabl
e ex
tern
al p
ress
ure
(Pa)
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
Thermal efficiency (%
)
06GLOBAL PX 06
• AIR VOLUME 200 - 1380 m³/h
55 - 380 l/s
• DIMENSIONS (H x W x D) 1465 x 1680 x815
• WEIGHT 370 kg
• POWER CONNECTION 1 x 230 V
• MAX CURRENT 5.3 A
• RECOMMENDED FUSES D6A / AC3 / 10kA
• FILTER CLASS (SUPPLY / EXTRACT) ePM1 70% / ePM10 50%
• STANDARD DUCT CONNECTIONS (15MM) N.A.
• SLIP CLAMP DUCT CONNECTIONS (20MM) N.A.
• CIRCULAR DUCT CONNECTIONS Ø 400
• OPERATING RANGE -20 ... +50 °C
• EN1886 CLASSIFICATION T3 / TB2 / F9 / L2 / D1
• IMPELLOR MATERIAL COMPOSITE
AIR VOLUME ABSORBED POWER SFP THERMAL DRY
EFFICIENCYTHERMAL WET
EFFICIENCYT AFTER HEAT EXCHANGER
SOUNDPRESSURE
Conditions :
1. All values at 200Pa external pressure.
2. T° after heat exchanger at -10°C, 90%RH and +22°C, 50% HR.
3. Thermal wet efficiency at -10°C, 90%RH and +22°C, 50% HR.
4.Sound pressure for ducted unit in free field conditions at 3m.
5. All data for composite fans variant
m3/h l/s W W/m3/h % % °C dB(A)
800 220 318 1,43 86,6 94,2 20,1 23,2
1000 275 422 1,52 85,5 93,5 19,9 23,3
1200 335 546 1,64 84,5 92,9 19,7 24,3
1350 365 661 1,76 83,9 92,5 19,6 25,2
DIMENSIONS (mm)
GLOBAL PX 17
Outdoor air Extract airSupply air Exhaust air
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
GLOBAL PX 06 GLOBAL PX : dimensiOns
GLOBAL PX 06
GLOBAL PX 06
Left hand versionRight hand version
Airflow (m3/h)
90
91
92
93
94
95
96
97
98
0
100
200
300
400
500
600
700
800
900
200 400 600 800 1000 1200 1400 1600
Pa max SFP=2,5 kW/m³s SFP=2 kW/m³s SFP=1,5 kW/m³s ∩th
18 GLOBAL PX
GENERAL TECHNICAL SPECIFICATIONS
Ava
ilabl
e ex
tern
al p
ress
ure
(Pa)
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
Thermal efficiency (%
)
08GLOBAL PX 08
• AIR VOLUME 200 - 1680 m³/h
55 - 465 l/s
• DIMENSIONS (H x W x D) 1465 x 1680 x 815
• WEIGHT 370 kg
• POWER CONNECTION 1 x 230 V
• MAX CURRENT 5.3 A
• RECOMMENDED FUSES D6A / AC3 / 10kA
• FILTER CLASS (SUPPLY / EXTRACT) ePM1 70% / ePM10 50%
• STANDARD DUCT CONNECTIONS (15MM) N.A.
• SLIP CLAMP DUCT CONNECTIONS (20MM) N.A.
• CIRCULAR DUCT CONNECTIONS Ø 400
• OPERATING RANGE -20 ... +50 °C
• EN1886 CLASSIFICATION T3 / TB2 / F9 / L2 / D1
• IMPELLOR MATERIAL COMPOSITE
AIR VOLUME ABSORBED POWER SFP THERMAL DRY
EFFICIENCYTHERMAL WET
EFFICIENCYT AFTER HEAT EXCHANGER
SOUNDPRESSURE
Conditions :
1. All values at 200Pa external pressure.
2. T° after heat exchanger at -10°C, 90%RH and +22°C, 50% HR.
3. Thermal wet efficiency at -10°C, 90%RH and +22°C, 50% HR.
4.Sound pressure for ducted unit in free field conditions at 3m.
5. All data for composite fans variant
m3/h l/s W W/m3/h % % °C dB(A)
1000 280 421 1,52 85 93 19,0 23,3
1200 330 545 1,64 84 93 18,8 24,3
1400 390 704 1,81 84 92 18,6 25,7
1600 445 895 1,02 83 92 18,5 27,3
DIMENSIONS (mm)
GLOBAL PX 19
Outdoor air Extract airSupply air Exhaust air
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
GLOBAL PX 08 GLOBAL PX : dimensiOns
GLOBAL PX 08
GLOBAL PX 08
Left hand versionRight hand version
Airflow (m3/h)
90
91
92
93
94
95
96
97
98
0
100
200
300
400
500
600
700
250 450 650 850 1050 1250 1450 1650 1850
Pa max SFP=2,5 kW/m³s SFP=2 kW/m³s SFP=1,5 kW/m³s ∩th
20 GLOBAL PX
GENERAL TECHNICAL SPECIFICATIONS
Ava
ilabl
e ex
tern
al p
ress
ure
(Pa)
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
Thermal efficiency (%
)
GGLOBAL PX 10
• AIR VOLUME 250 - 1860 m³/h
70 - 515 l/s
• DIMENSIONS (H x W x D) 1465 x 1680 x 995
• WEIGHT 410 kg
• POWER CONNECTION 1 x 230 V
• MAX CURRENT 4.9 A
• RECOMMENDED FUSES D6A / AC3 / 10kA
• FILTER CLASS (SUPPLY / EXTRACT) ePM1 70% / ePM10 50%
• STANDARD DUCT CONNECTIONS (15MM) N.A.
• SLIP CLAMP DUCT CONNECTIONS (20MM) N.A.
• CIRCULAR DUCT CONNECTIONS Ø 400
• OPERATING RANGE -20 ... +50 °C
• EN1886 CLASSIFICATION T3 / TB2 / F9 / L2 / D1
• IMPELLOR MATERIAL COMPOSITE
AIR VOLUME ABSORBED POWER SFP THERMAL DRY
EFFICIENCYTHERMAL WET
EFFICIENCYT AFTER HEAT EXCHANGER
SOUNDPRESSURE
Conditions :
1. All values at 200Pa external pressure.
2. T° after heat exchanger at -10°C, 90%RH and +22°C, 50% HR.
3. Thermal wet efficiency at -10°C, 90%RH and +22°C, 50% HR.
4.Sound pressure for ducted unit in free field conditions at 3m.
5. All data for composite fans variant
m3/h l/s W W/m3/h % % °C dB(A)
1300 360 561 1,55 85 93 18,9 23,9
1500 415 700 1,68 84 93 18,7 25,6
1700 470 862 1,83 84 93 18,7 27,5
1800 415 954 1,91 84 92 18,6 28,2
DIMENSIONS (mm)
GLOBAL PX 21
Outdoor air Extract airSupply air Exhaust air
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
GLOBAL PX 10 GLOBAL PX : dimensiOns
GLOBAL PX 10
GLOBAL PX 10
Left hand versionRight hand version
Airflow (m3/h)
90
91
92
93
94
95
96
97
98
0
100
200
300
400
500
600
700
800
900
400 600 800 1000 1200 1400 1600 1800 2000 2200
Pa max SFP=2,5 kW/m³s SFP=2 kW/m³s SFP=1,5 kW/m³s ∩th
22 GLOBAL PX
GENERAL TECHNICAL SPECIFICATIONS
Ava
ilabl
e ex
tern
al p
ress
ure
(Pa)
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
Thermal efficiency (%
)
12GLOBAL PX 12
• AIR VOLUME 400 - 2300 m³/h
110 - 640 l/s
• DIMENSIONS (H x W x D) 1465 x 1680 x 1182
• WEIGHT 420 kg
• POWER CONNECTION 1 x 230 V
• MAX CURRENT 7.7 A
• RECOMMENDED FUSES D10A / AC3 / 10kA
• FILTER CLASS (SUPPLY / EXTRACT) ePM1 70% / ePM10 50%
• STANDARD DUCT CONNECTIONS (15MM) 547 x 1069 mm
• SLIP CLAMP DUCT CONNECTIONS (20MM) 600 x 1100 mm
• CIRCULAR DUCT CONNECTIONS Ø 400
• OPERATING RANGE -20 ... +50 °C
• EN1886 CLASSIFICATION T3 / TB2 / F9 / L2 / D1
• IMPELLOR MATERIAL COMPOSITE
AIR VOLUME ABSORBED POWER SFP THERMAL DRY
EFFICIENCYTHERMAL WET
EFFICIENCYT AFTER HEAT EXCHANGER
SOUNDPRESSURE
Conditions :
1. All values at 200Pa external pressure.
2. T° after heat exchanger at -10°C, 90%RH and +22°C, 50% HR.
3. Thermal wet efficiency at -10°C, 90%RH and +22°C, 50% HR.
4.Sound pressure for ducted unit in free field conditions at 3m.
5. All data for composite fans variant
m3/h l/s W W/m3/h % % °C dB(A)
1500 415 554 1,33 86 94 19,9 23,5
1900 525 776 1,47 84 93 18,7 25,3
2100 583 912 1,58 84 93 18,7 26,6
2300 638 1066 1,67 83 92 18,6 27,6
DIMENSIONS (mm)
GLOBAL PX 23
Outdoor air Extract airSupply air Exhaust air
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
GLOBAL PX 12 GLOBAL PX : dimensiOns
GLOBAL PX 12
GLOBAL PX 12
Left hand versionRight hand version
Airflow (m3/h)
90
91
92
93
94
95
96
97
98
0
100
200
300
400
500
600
700
800
900
400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800
Pa max SFP=2,5 kW/m³s SFP=2 kW/m³s SFP=1,5 kW/m³s ∩th
24 GLOBAL PX
GENERAL TECHNICAL SPECIFICATIONS
Ava
ilabl
e ex
tern
al p
ress
ure
(Pa)
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
Thermal efficiency (%
)
13GLOBAL PX 13
• AIR VOLUME 400 - 2530 m³/h
110 - 700 l/s
• DIMENSIONS (H x W x D) 1465 x 1680 x 1182 mm
• WEIGHT 420 kg
• POWER CONNECTION 1 x 230 V
• MAX CURRENT 7.7 A
• RECOMMENDED FUSES D10A / AC3 / 10kA
• FILTER CLASS (SUPPLY / EXTRACT) ePM1 70% / ePM10 50%
• STANDARD DUCT CONNECTIONS (15MM) 1069 x 547 mm
• SLIP CLAMP DUCT CONNECTIONS (20MM) 1100 x 600 mm
• CIRCULAR DUCT CONNECTIONS Ø 400
• OPERATING RANGE -20 ... +50 °C
• EN1886 CLASSIFICATION T3 / TB2 / F9 / L2 / D1
• IMPELLOR MATERIAL COMPOSITE
AIR VOLUME ABSORBED POWER SFP THERMAL DRY
EFFICIENCYTHERMAL WET
EFFICIENCYT AFTER HEAT EXCHANGER
SOUNDPRESSURE
Conditions :
1. All values at 200Pa external pressure.
2. T° after heat exchanger at -10°C, 90%RH and +22°C, 50% HR.
3. Thermal wet efficiency at -10°C, 90%RH and +22°C, 50% HR.
4.Sound pressure for ducted unit in free field conditions at 3m.
5. All data for composite fans variant
m3/h l/s W W/m3/h % % °C dB(A)
2200 610 987 1,62 84 92 18,6 27,1
2400 666 1148 1,72 83 92 18,5 28,1
2600 722 1329 1,84 83 92 18,4 29,3
2800 777 1527 1,96 82 92 18,4 30,8
DIMENSIONS (mm)
GLOBAL PX 25
Outdoor air Extract airSupply air Exhaust air
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
GLOBAL PX 12 GLOBAL PX : dimensiOns
GLOBAL PX 13
GLOBAL PX 13
Left hand versionRight hand version
Airflow (m3/h)
90
91
92
93
94
95
96
97
98
0
100
200
300
400
500
600
700
800
900
300 500 700 900 1100 1300 1500 1700 1900 2100 2300 2500 2700 2900
Pa max SFP=2,5 kW/m³s SFP=2 kW/m³s SFP=1,5 kW/m³s ∩th
26 GLOBAL PX
GENERAL TECHNICAL SPECIFICATIONS
Ava
ilabl
e ex
tern
al p
ress
ure
(Pa)
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
Thermal efficiency (%
)
14GLOBAL PX 14
• AIR VOLUME 300 - 3000 m³/h
85 - 830 l/s
• DIMENSIONS (H x W x D) 1465 x 1680 x 1382
• WEIGHT 480 kg
• POWER CONNECTION 1 x 230 V
• MAX CURRENT 7.7 A
• RECOMMENDED FUSES D10A / AC3 / 10kA
• FILTER CLASS (SUPPLY / EXTRACT) ePM1 70% / ePM10 50%
• STANDARD DUCT CONNECTIONS (15MM) 547 x 1269 mm
• SLIP CLAMP DUCT CONNECTIONS (20MM) 600 x 1300 mm
• CIRCULAR DUCT CONNECTIONS N.A.
• OPERATING RANGE -20 ... +50 °C
• EN1886 CLASSIFICATION T3 / TB2 / F9 / L2 / D1
• IMPELLOR MATERIAL COMPOSITE
AIR VOLUME ABSORBED POWER SFP THERMAL DRY
EFFICIENCYTHERMAL WET
EFFICIENCYT AFTER HEAT EXCHANGER
SOUNDPRESSURE
Conditions :
1. All values at 200Pa external pressure.
2. T° after heat exchanger at -10°C, 90%RH and +22°C, 50% HR.
3. Thermal wet efficiency at -10°C, 90%RH and +22°C, 50% HR.
4.Sound pressure for ducted unit in free field conditions at 3m.
5. All data for composite fans variant
m3/h l/s W W/m3/h % % °C dB(A)
2400 665 1014 1,52 84 93 18,8 27,1
2600 720 1172 1,62 84 93 18,7 28,3
2800 777 1347 1,73 84 92 18,6 29,6
3000 833 1541 1,85 83 92 18,5 31,1
DIMENSIONS (mm)
GLOBAL PX 27
Outdoor air Extract airSupply air Exhaust air
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
GLOBAL PX 14 GLOBAL PX : dimensiOns
GLOBAL PX 14
GLOBAL PX 14
Left hand versionRight hand version
Airflow (m3/h)
90
91
92
93
94
95
96
97
98
0
100
200
300
400
500
600
700
800
900
300 700 1100 1500 1900 2300 2700 3100
Pa max SFP=2,5 kW/m³s SFP=2 kW/m³s SFP=1,5 kW/m³s ∩th
28 GLOBAL PX
GENERAL TECHNICAL SPECIFICATIONS
Ava
ilabl
e ex
tern
al p
ress
ure
(Pa)
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
Thermal efficiency (%
)
16GLOBAL PX 16
• AIR VOLUME 300 - 3230 m³/h
85 - 895 l/s
• DIMENSIONS (H x W x D) 1465 x 1680 x 1640
• WEIGHT 520 kg
• POWER CONNECTION 1 x 230 V
• MAX CURRENT 7.7 A
• RECOMMENDED FUSES D10A / AC3 / 10kA
• FILTER CLASS (SUPPLY / EXTRACT) ePM1 70% / ePM10 50%
• STANDARD DUCT CONNECTIONS (15MM) 583 x 1105 mm
• SLIP CLAMP DUCT CONNECTIONS (20MM) 600 x 1600 mm
• CIRCULAR DUCT CONNECTIONS N.A.
• OPERATING RANGE -20 ... +50 °C
• EN1886 CLASSIFICATION T3 / TB2 / F9 / L2 / D1
• IMPELLOR MATERIAL COMPOSITE
AIR VOLUME ABSORBED POWER SFP THERMAL DRY
EFFICIENCYTHERMAL WET
EFFICIENCYT AFTER HEAT EXCHANGER
SOUNDPRESSURE
Conditions :
1. All values at 200Pa external pressure.
2. T° after heat exchanger at -10°C, 90%RH and +22°C, 50% HR.
3. Thermal wet efficiency at -10°C, 90%RH and +22°C, 50% HR.
4.Sound pressure for ducted unit in free field conditions at 3m.
5. All data for composite fans variant
m3/h l/s W W/m3/h % % °C dB(A)
2700 750 1073 1,43 85 93 18,8 28,1
2900 805 1226 1,52 84 93 18,8 29,5
3100 860 1396 1,62 84 93 18,7 31,1
3200 888 1487 1,67 84 92 18,7 32
DIMENSIONS (mm)
GLOBAL PX 29
Outdoor air Extract airSupply air Exhaust air
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
GLOBAL PX 16 GLOBAL PX : dimensiOns
GLOBAL PX 16
GLOBAL PX 16
Left hand versionRight hand version
Airflow (m3/h)
30 GLOBAL PX
GENERAL TECHNICAL SPECIFICATIONS
Ava
ilabl
e ex
tern
al p
ress
ure
(Pa)
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
Thermal efficiency (%
)
• AIR VOLUME 400 - 4200 m³/h
115 - 1200 l/s
• DIMENSIONS (H x W x D) 1465 x 1880 x 2015
• WEIGHT 720 kg
• POWER CONNECTION 1 x 230 V
• MAX CURRENT 12,7 A
• RECOMMENDED FUSES D16A / AC3 / 10kA
• FILTER CLASS (SUPPLY / EXTRACT) ePM1 70% / ePM10 50%
• STANDARD DUCT CONNECTIONS (15MM) 583 x 1105 mm
• SLIP CLAMP DUCT CONNECTIONS (20MM) 2000 x 600
• CIRCULAR DUCT CONNECTIONS N.A.
• OPERATING RANGE -20 ... +50 °C
• EN1886 CLASSIFICATION T3 / TB2 / F9 / L2 / D1
• IMPELLOR MATERIAL COMPOSITE
AIR VOLUME ABSORBED POWER SFP THERMAL DRY
EFFICIENCYTHERMAL WET
EFFICIENCYT AFTER HEAT EXCHANGER
SOUNDPRESSURE
Conditions :
1. All values at 200Pa external pressure.
2. T° after heat exchanger at -10°C, 90%RH and +22°C, 50% HR.
3. Thermal wet efficiency at -10°C, 90%RH and +22°C, 50% HR.
4.Sound pressure for ducted unit in free field conditions at 3m.
5. All data for composite fans variant
m3/h l/s W W/m3/h % % °C dB(A)
3000 830 1274 1,53 84 90,3 18,9 26,7
3500 970 1659 1,71 83,2 89,9 18,7 28,8
4000 1110 2172 1,96 82,5 89,5 18,6 32,3
4200 1200 2410 2,07 82,2 89,4 18,6 33,3
18GLOBAL PX 18
DIMENSIONS (mm)
GLOBAL PX 31
Outdoor air Extract airSupply air Exhaust air
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
GLOBAL PX 18
GLOBAL PX 18
Right hand version Left hand version
1880
1340
125
Ø48 95
2015
1465
583
2126
110
583
1938
Ø32
Airflow (m3/h)
32 GLOBAL PX
GENERAL TECHNICAL SPECIFICATIONS
Ava
ilabl
e ex
tern
al p
ress
ure
(Pa)
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
Thermal efficiency (%
)
20GLOBAL PX 20
• AIR VOLUME 600-4700m³/h
167-1300l/s
• DIMENSIONS (H x W x D) 1825 x 2557 x 1640
• WEIGHT 930 kg
• POWER CONNECTION 1 x 230 V
• MAX CURRENT 12.7 A
• RECOMMENDED FUSES D16A / AC3 / 10kA
• FILTER CLASS (SUPPLY / EXTRACT) ePM1 70% / ePM10 50%
• STANDARD DUCT CONNECTIONS (15MM) 710 x 1560 mm
• SLIP CLAMP DUCT CONNECTIONS (20MM) 700x 1600 mm
• CIRCULAR DUCT CONNECTIONS N.A.
• OPERATING RANGE -20 ... +50 °C
• EN1886 CLASSIFICATION T3 / TB2 / F9 / L2 / D1
• IMPELLOR MATERIAL COMPOSITE
AIR VOLUME ABSORBED POWER SFP THERMAL DRY
EFFICIENCYTHERMAL WET
EFFICIENCYT AFTER HEAT EXCHANGER
SOUNDPRESSURE
Conditions :
1. All values at 200Pa external pressure.
2. T° after heat exchanger at -10°C, 90%RH and +22°C, 50% HR.
3. Thermal wet efficiency at -10°C, 90%RH and +22°C, 50% HR.
4.Sound pressure for ducted unit in free field conditions at 3m.
5. All data for composite fans variant
m3/h l/s W W/m3/h % % °C dB(A)
3000 830 1089 1,31 85 91 19,1 26,1
3500 970 1405 1,45 84 90,3 18,9 28,8
4000 1110 1805 1,63 83,2 89,9 18,8 32,4
4500 1250 2313 1,85 82,5 89,6 18,7 35
88
90
92
94
96
98
0
100
200
300
400
500
600
700
800
900
1000
600 1000 1400 1800 2200 2600 3000 3400 3800 4200 4600
Pa max SFP=2,5 kW/m³s SFP=2 kW/m³s SFP=1,5 kW/m³s ∩th
DIMENSIONS (mm)
GLOBAL PX 33
Outdoor air Extract airSupply air Exhaust air
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
GLOBAL PX 20 GLOBAL PX : dimensiOns
GLOBAL PX 20
GLOBAL PX 20
Left hand versionRight hand version
Airflow (m3/h)
34 GLOBAL PX
GENERAL TECHNICAL SPECIFICATIONS
Ava
ilabl
e ex
tern
al p
ress
ure
(Pa)
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
Thermal efficiency (%
)
24GLOBAL PX 24
• AIR VOLUME 600 - 6260 m³/h
170 - 1740 l/s
• DIMENSIONS (H x W x D) 1825 x 2557 x 2015
• WEIGHT 1120kg
• POWER CONNECTION 3 x 400 V + N
• MAX CURRENT 6.5 A
• RECOMMENDED FUSES D10A / AC3 / 10kA
• FILTER CLASS (SUPPLY / EXTRACT) ePM1 70% / ePM10 50%
• STANDARD DUCT CONNECTIONS (15MM) 713 x 1938 mm
• SLIP CLAMP DUCT CONNECTIONS (20MM) 700 x 1900 mm
• CIRCULAR DUCT CONNECTIONS N.A.
• OPERATING RANGE -20 ... +50 °C
• EN1886 CLASSIFICATION T3 / TB2 / F9 / L2 / D1
• IMPELLOR MATERIAL COMPOSITE
AIR VOLUME ABSORBED POWER SFP THERMAL DRY
EFFICIENCYTHERMAL WET
EFFICIENCYT AFTER HEAT EXCHANGER
SOUNDPRESSURE
Conditions :
1. All values at 200Pa external pressure.
2. T° after heat exchanger at -10°C, 90%RH and +22°C, 50% HR.
3. Thermal wet efficiency at -10°C, 90%RH and +22°C, 50% HR.
4.Sound pressure for ducted unit in free field conditions at 3m.
5. All data for composite fans variant
m3/h l/s W W/m3/h % % °C dB(A)
4500 1250 1790 1,43 83,8 90,3 18,9 27,9
5000 1390 2132 1,54 83,2 89,9 18,8 29,4
5500 1530 2532 1,66 82,6 89,6 18,7 31,5
6000 1670 3100 1,8 82,1 89,2 18,6 33,2
88
90
92
94
96
98
0
100
200
300
400
500
600
700
800
900
600 1000 1400 1800 2200 2600 3000 3400 3800 4200 4600 5000 5400 5800 6200
Pa max SFP=2,5 kW/m³s SFP=2 kW/m³s SFP=1,5 kW/m³s ∩th
DIMENSIONS (mm)
GLOBAL PX 35
Outdoor air Extract airSupply air Exhaust air
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
GLOBAL PX 24 GLOBAL PX : dimensiOns
GLOBAL PX 24
GLOBAL PX 24
Left hand versionRight hand version
Airflow (m3/h)
88
90
92
94
96
98
0
100
200
300
400
500
600
700
800
900
1000
600 1200 1800 2400 3000 3600 4200 4800 5400 6000 6600
Pa max SFP=2,5 kW/m³s SFP=2 kW/m³s SFP=1,5 kW/m³s ∩th
36 GLOBAL PX
GENERAL TECHNICAL SPECIFICATIONS
Ava
ilabl
e ex
tern
al p
ress
ure
(Pa)
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
Thermal efficiency (%
)
26GLOBAL PX 26
• AIR VOLUME 600 - 7080 m³/h
170 - 1960 l/s
• DIMENSIONS (H x W x D) 1825 x 2557 x 2396
• WEIGHT 1260kg
• POWER CONNECTION 3 x 400 V + N
• MAX CURRENT 6.5 A
• RECOMMENDED FUSES D10A / AC3 / 10kA
• FILTER CLASS (SUPPLY / EXTRACT) ePM1 70% / ePM10 50%
• STANDARD DUCT CONNECTIONS (15MM) 713 x 2318 mm
• SLIP CLAMP DUCT CONNECTIONS (20MM) 700 x 2300 mm
• CIRCULAR DUCT CONNECTIONS N.A.
• OPERATING RANGE -20 ... +50 °C
• EN1886 CLASSIFICATION T3 / TB2 / F9 / L2 / D1
• IMPELLOR MATERIAL COMPOSITE
AIR VOLUME ABSORBED POWER SFP THERMAL DRY
EFFICIENCYTHERMAL WET
EFFICIENCYT AFTER HEAT EXCHANGER
SOUNDPRESSURE
Conditions :
1. All values at 200Pa external pressure.
2. T° after heat exchanger at -10°C, 90%RH and +22°C, 50% HR.
3. Thermal wet efficiency at -10°C, 90%RH and +22°C, 50% HR.
4.Sound pressure for ducted unit in free field conditions at 3m.
5. All data for composite fans variant
m3/h l/s W W/m3/h % % °C dB(A)
5500 1530 2253 1,48 83,7 90,2 18,9 30,7
6000 1670 2640 1,58 83,2 89,9 18,8 33,0
6500 1810 3078 1,705 82,7 89,68 18,7 34,7
7000 1950 3563 1,83 82,3 89,45 18,6 36,7
DIMENSIONS (mm)
GLOBAL PX 37
Outdoor air Extract airSupply air Exhaust air
This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
GLOBAL PX 26 GLOBAL PX : dimensiOns
GLOBAL PX 26
GLOBAL PX 26
Left hand versionRight hand version
GLOBAL PX 39This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
CirCuLAr AdAPter (irs) GLOBAL PX series : ACCessOires
GLOBAL PX series
Specification: GLOBAL_XXX_XX_XXX_X_XXX
Heat exchanger: Plate heat exchanger (PX)
Unit size: 04, 05, 08, 10, 12, 13, 14, 16, ...
Duct connection:Supply air: Right (R) / Left (L)
Fan type: none = Composite, ALU = Aluminum
GLOBAL PX
CIRCULAR ADAPTER - IRS
MODEL CID DIMENSIONS[mm] LABEL
GLOBAL PX 12/13 8833158 1140 x 615 - DN500 IRS_1140-615_500
For units (AHU’s, external coils, ...) with rectangular connections, non insulated rectangular/circular adapters are available. The adapter is fabricated in galvanized sheet metal. The circular duct connection is fitted with a double rubber seal.
Specification: IRS_XXX-XXX_XXX
Frame outer dimensions
Circular size
40 GLOBAL PX This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
PrefiLter GLOBAL PX series : ACCessOires
fiLter rePLACements kits GLOBAL PX series : ACCessOires
The prefilter is installed in the outdoor air section and is physically located befor the fine filter. The prefilter is used in ventilation systems in which the outdoor air is heavily polluted and it is desirable to prevent the fine filter from becoming clogged after a short period of use. According EN-779, the prefilter is of class G4.
PRE FILTER
MODEL DIMENSIONS[mm]
GLOBAL PX 04/05/06/08 490 x 517 x 50
GLOBAL PX 10 592 x 592 x 50
GLOBAL PX 12/13/14 892 x 592 x 50
GLOBAL PX 16 592 x 592 x 50 (x2)
GLOBAL PX 18 892 x 592 x 50 (x2)
GLOBAL PX 20 592 x 692 x 380 (x2)
GLOBAL PX 24 592 x 692 x 380 (x2)340 x 692 x 380 (x1)
GLOBAL PX 26 592 x 692 x 380 (x3)
The function of the filter is to keep both the air and the heat exchanger clean. Filterclass supply air filter: ePM1≥70%. Filterclass extract air filter: ePM10≥50%. All filters are classi-fied both according to ISO EN779 and ISO EN 16890. To keep the heat exchanger clean, an ePM10≥50% filter class will suffice. ePM1≥50% filter sets are not available on the extract air side, so that there is no negative influence on the energy consumtion of the air handling unit.
FILTERS
MODEL FRESH AIR[mm]
EXTRACT AIR[mm] # of bags
GLOBAL PX 04/05/06/08 490 x 517 x 380 490 x 517 x 360 8 / 5.
GLOBAL PX 10 592 x 592 x 380 592 x 592 x 360 8 / 6
GLOBAL PX 12/13/14 892 x 592 x 360 892 x 592 x 360 12 / 9
GLOBAL PX 16 592 x 592 x 380 (x2) 592 x 592 x 360 (x2) 8 (x2) / 6 (x2)
GLOBAL PX 18 892 x 592 x 380 (x2) 892 x 592 x 360 (x2) 12 (x2) / 9 (x2)
GLOBAL PX 20 592 x 692 x 380 (x2) 592 x 692 x 360 (x2) 10 (x2) / 6 (x2)
GLOBAL PX 24 592 x 692 x 380 (x2)340 x 692 x 380 (x1)
592 x 692 x 380(x2)340 x 692 x 380 (x1)
10 (x2) / 4 x 16 (x2) / 3 (x1)
GLOBAL PX 26 592 x 692 x 380 (x3) 592 x 692 x 360 (x3) 10 (x3) / 6 (x3)
GLOBAL PX 41This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
eLeCtriCAL POst heAtinG (kWOut) GLOBAL PX series : ACCessOires
INTERNAL WATER POST HEATING - IBA
internAL WAter POst heAtinG (iBA) GLOBAL PX series : ACCessOires
MODEL CID Ø LABEL
GLOBAL PX 04/05 882271 1/2’’ IBA_2H_PX 05
GLOBAL PX 06/08 882272 1/2’’ IBA_2H_PX 06/08
GLOBAL PX 10 882273 1/2’’ IBA_2H_PX 10
GLOBAL PX 12 882274 1/2’’ IBA_2H_PX 13
GLOBAL PX 14 882275 1/2’’ IBA_2H_PX 14
GLOBAL PX 16 882276 1/2’’ IBA_2H_PX 16
GLOBAL PX 18 883486 1/2" IBA_2H_PX 18
GLOBAL PX 20 883315 3/4’’ IBA_2H_PX20
GLOBAL PX 24 883316 3/4’’ IBA_2H_PX24
GLOBAL PX 26 883317 3/4’’ IBA_2H_PX26
The IBA coil uses hot water for post-heating the supply air. The coil is integrated inside the unit and is located between the heat exchanger and the air outlet. The finned-tube heat exchangers consist of copper tubes and aluminum fins with a 2,5mm spacing. The male threaded pipe is made of brass. The coils are equipped with a plug for venting. The coils are classified PN16.
Specification: IBA_XX-XX
Coil type & # of rows
Coil size
INTERNAL ELECTRICAL PRE- & POST HEATING - KWin & KWout
MODELCID
KWout3x400V
CIDKWout3x230V
CAPACITYKWout
CID KWin
3x400V
CIDKWin
3x230V
CAPACITYKWin
GLOBAL PX 04/05 882224 882230 3.0 kW 882236 882242 3.0 kW
GLOBAL PX 06/08 882225 882231 6.0 kW 882237 882243 6.0 kW
GLOBAL PX 10 882226 882232 7.5 kW 882238 882244 6.0 kW
GLOBAL PX 12/13 882227 882233 9.0 kW 882239 882245 9.0 kW
GLOBAL PX 14 882228 882234 9.0 kW 882240 882246 9.0 kW
GLOBAL PX 16 882229 882235 12.0 kW 882241 882247 12.0 kW
GLOBAL PX 18 883492 / 15.0 kW 883493 / 15.0 kW
GLOBAL PX 20 883364 / 15.0 kW 883367 / 15.0 kW
GLOBAL PX 24 883365 / 22.5 kW 883368 / 22.5 kW
GLOBAL PX 26 883366 / 22.5 kW 883369 / 22.5 kW
The electrical coil is used for post-heating the supply air. There are two overheating protections, one with manual reset (110°C) and one with automatic reset (75°C).
Specification: KW_XXX_XX-X_XX/XX
Pre/Post heating [IN/OUT]
Heating capacity [kW]
Supply voltage: 1=3x400V / 2=3x230V
Coil size
42 GLOBAL PX This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
EXTERNAL INSULATED CASING - ECA
MODEL CID DUCTCONNECTION
DUCTCONNECTION DIMENSIONS LABEL
GLOBAL PX 04/05 882277 530 x 505 DN315 670 x 697 x 815 ECA_530-505
GLOBAL PX 06/08 883070 735 x 505 DN400 670 x 697 x 815 ECA_735-505
GLOBAL PX 10 883073 915 x 580 DN400 670 x 772 x 995 ECA_915-580
GLOBAL PX12/13 883074 1105 x 580 / 670 x 772 x 1182 ECA_1105-580
GLOBAL PX14 882278 1305 x 580 / 670 x 772 x 1382 ECA_1305-580
GLOBAL PX 16 882279 1560 x 580 / 670 x 772 x 1640 ECA_1560-580
GLOBAL PX 18 883487 1935 x 580 / 670 x 772 x 2015 ECA_1935-580
GLOBAL PX 20 883076 1560 x 710 / 670 x 902 x 1640 ECA_1560-710
GLOBAL PX 24 883320 1935 x 710 / 670 x 902 x 2015 ECA_1935-710
GLOBAL PX 26 883321 2315 x 710 / 670 x 902 x 2395 ECA_2315-710
eXternAL insuLAted CAsinGs (eCA) GLOBAL PX series : ACCessOires
The external insulated casings are fabricated in galvanized steel sheet. the outer sheet is painted in RAL7016. The double-skin panels contain 30mm mineral wool. The casings can be use to integrate external cooling, heating, direct expansion coils (EBA) . The standard connection frame is 15mm, other connection frame types are available as an option: 20mm slip clamps, 30mm “METU” frame. The coil is mounted on a 125mm base frame.
Specification: ECA_XXX-XXX_XX/XX
Duct size [mm]
Casing size[mm]
GLOBAL PX 43This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
The EBA coil uses hot water for post-heating the supply air. The coil is to be integrated in an insulated casing ECA. The finned-tube heat exchangers consist of copper tubes and aluminum fins with 2,5mm spacing. The male threaded pipe is made of brass. The coils are equipped with a plug for venting. The coils are classified PN16.
Specification: EBA_XX_XX/XX
Function & # of rows Coil size
COILS FOR EXTERNAL INSULATED CASING - EBA
MODEL CID FUNCTION # ROWS VOLUME DIMENSIONS
[mm] Ø LABEL
GLOBAL PX 04/05 882286 HEATING 3 1,7 dm³ 440 x 500 x 130 1/2’’ EBA_4H_PX 05
GLOBAL PX 04/05 882287 COOLING 3 1,7 dm³ 440 x 500 x 130 1/2’’ EBA_4C_PX 05
GLOBAL PX 04/05 882288 DX 3 2,1dm³ 440 x 500 x 130 Ø22 / Ø16 EBA_4X_PX 05
GLOBAL PX 06/08 883077 HEATING 3 2,4 dm³ 440 x 705 x 130 1/2’’ EBA_4H_RX 08 - PX 06/08
GLOBAL PX 06/08 883078 COOLING 3 2,4 dm³ 440 x 705 x 130 1/2’’ EBA_4C_RX 08 - PX 06/08
GLOBAL PX 06/08 883079 DX 4 2,9 dm³ 440 x 705 x 130 Ø22 / Ø16 EBA_4X_RX 08 - PX 06/08
GLOBAL PX 10 882289 HEATING 4 4,0 dm³ 515 x 775 x 130 1/2’’ EBA_4H_PX 10
GLOBAL PX 10 882290 COOLING 4 4,0 dm³ 515 x 775 x 130 1/2’’ EBA_4C_PX 10
GLOBAL PX 10 882291 DX 4 3,7 dm³ 515 x 775 x 130 Ø22 / Ø16 EBA_4X_PX 10
GLOBAL PX 12/13 882292 HEATING 4 4,5 dm³ 515 x 885 x 130 1/2’’ EBA_4H_PX 12/13
GLOBAL PX 12/13 882293 COOLING 4 4,5 dm³ 515 x 885 x 138 1/2’’ EBA_4C_PX 12/13
GLOBAL PX 12/13 882294 DX 4 4,5 dm³ 515 x 885 x 130 Ø28 / Ø22 EBA_4X_PX 12/13
GLOBAL PX 14 882295 HEATING 4 5,5 dm³ 515 x 1072 x 130 3/4’’ EBA_4H_PX 14
GLOBAL PX 14 882296 COOLING 4 5,5 dm³ 515 x 1072 x 130 3/4’’ EBA_4C_PX 14
GLOBAL PX 14 882297 DX 4 5,5 dm³ 515 x 1072 x 130 Ø28 / Ø22 EBA_4X_PX 14
GLOBAL PX 16 882298 HEATING 4 6,5 dm³ 515 x 1530 x 130 3/4’’ EBA_4H_PX 16
GLOBAL PX 16 882299 COOLING 4 6,5 dm³ 515 x 1430 x 130 3/4’’ EBA_4C_PX 16
GLOBAL PX 16 882223 DX 4 7,6 dm³ 515 x 1430 x 130 Ø28 / Ø22 EBA_4X_PX 16
GLOBAL PX 18 883489 HEATING 4 6,2 515 x 1430 x 130 Ø3/4" EBA_4H_PX 18
GLOBAL PX 18 883490 COOLING 4 6,2 515 x 1430 x 130 Ø3/4" EBA_4C_PX 18
GLOBAL PX 18 883491 DX 3 5,4 515 x 1430 x 130 Ø28 / Ø22 EBA_4X_PX 18
GLOBAL PX 20 883322 HEATING 4 8,6 dm³ 645 x 1272 x 130 3/4’’ EBA_4H_PX 20
GLOBAL PX 20 883323 COOLING 4 8,6 dm³ 645 x 1272 x 130 3/4’’ EBA_4C_PX 20
GLOBAL PX 20 883324 DX 4 8,2 dm³ 645 x 1272 x 130 Ø26/ Ø22 EBA_4X_PX 20
GLOBAL PX 24 883325 HEATING 4 10,5 dm³ 645 x 1530 x 130 1’’ EBA_4H_PX 24
GLOBAL PX 24 883326 COOLING 4 10,5 dm³ 645 x 1530 x 130 1’’ EBA_4C_PX 24
GLOBAL PX 24 883327 DX 4 9,0 dm³ 645 x 1530 x 130 Ø35/ Ø28 EBA_4X_PX 24
GLOBAL PX 26 883328 HEATING 4 10,5 dm³ 645 x 1530 x 130 1’’ EBA_4H_PX 26
GLOBAL PX 26 883329 COOLING 4 10,5 dm³ 645 x 1530 x 130 1’’ EBA_4C_PX 26
GLOBAL PX 26 883330 DX 4 9,0 dm³ 645 x 1530 x 130 Ø35/ Ø28 EBA_4X_PX 26
COiLs fOr eXternAL insuLAted CAsinGs (eBA) GLOBAL PX series : ACCessOires
44 GLOBAL PX This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
The flexible sleeves type MS30 prevents the transmission of vibrations and noise along the ventilation ductwork. The sleeve is made of fibreglass and are classified “M0” for fire re-sistance, “Class B” for air tightness (EN 15727 and EN 1751). The operating range is from -30°C up to +110°C and for pressures up to 2000Pa. The 30mm “METU” connection frame is made from 1mm thick galvanized steel.
Specification: MSXX_XXX-XXX
Connection frame width [mm]
Duct dimensions [mm]
MODEL CID DUCT SIZE[mm]
OUTER DIMENSIONS[mm] LABEL
GLOBAL PX 12/13 883102 1040 x 520 1100 x 580 MS30_1040-520
GLOBAL PX 14 882221 1245 x 520 1305 x 580 MS30_1245-520
GLOBAL PX 16 882148 1500 x 520 1560 x 580 MS30_1500-520
GLOBAL PX 18 883495 1875 x 520 1935 x 580 MS30_1875-520
GLOBAL PX 20 883104 1500-650 1560 x 710 MS30_1500-650
GLOBAL PX 24 883333 1875 x 650 1935 x 710 MS30_1875-650
GLOBAL PX 26 883334 2255 x 650 2315 x 710 MS30_2255-650
FLEXIBLE SLEEVE 30mm - MS30
FLEXIBLE SLEEVE 20mm - MS20
MODEL CID DUCT SIZE[mm]
OUTER DIMENSIONS[mm] LABEL
GLOBAL PX 04/05 450051 DN315 / MS_315
GLOBAL PX 06/08/10 450053 DN400 / MS_400
GLOBAL PX 12/13 883097 1060 x 540 1100 x 580 MS20_1060-540
GLOBAL PX14 882249 1520 x 540 1560 x 580 MS20_1520-540
GLOBAL PX 16 882249 1520 x 540 1560 x 580 MS20_1520-540
GLOBAL PX 18 883494 1895 x 540 1935 x 580 MS20_1895-540
GLOBAL PX 20 883099 1520 x 670 1560 x 710 MS20_1520-670
GLOBAL PX 24 883331 1895 x 670 1935 x 710 MS20_1895-670
GLOBAL PX 26 883332 2275 x 670 2315 x 710 MS20_2275-670
The flexible sleeves type MS20 prevents the transmission of vibrations and noise along the ventilation ductwork. The sleeve is made of fibreglass and are classified “M0” for fire resistance, “Class B” for air tightness (EN 15727 and EN 1751). The operating range is from -30°C up to +110°C and for pressures up to 2000Pa. The 20mm connection frame is made from 1mm thick galvanized steel.
Specification: MSXX_XXX-XXX
Connection frame width [mm]
Duct dimensions [mm]
fLeXiBLe sLeeve 30mm GLOBAL PX series : ACCessOires
fLeXiBLe sLeeve 20mm GLOBAL PX series : ACCessOires
GLOBAL PX 45This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
sLiP CLAmPs (sC20) GLOBAL PX series : ACCessOires
Connection frames for standardised 20mm slip-clamp jointing (slip-clamps must be ordered separately), for ease of installation and standardised duct dimensions.
Specification: SCXX_XXX-XXX
Connection frame width [mm]
Duct size[mm]
SLIP CLAMP CONNECTIONS 20mm- SC20
MODEL CID DUCT SIZE[mm] LABEL
GLOBAL PX 12/13 883112 1100 x 600 SC20_1100-600
GLOBAL PX 14 882151 1300 x 600 SC20_1300-600
GLOBAL PX 16 882152 1600 x 600 SC20_1600-600
GLOBAL PX 18 883497 2000 x 600 SC20_2000-600
GLOBAL PX 20 883114 1600 x 700 SC20_1600-700
GLOBAL PX 24 883337 2000 x 700 SC20_2000-700
GLOBAL PX 26 883338 2300 x 700 SC20_2300-700
46 GLOBAL PX This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
The CT dampers are used as shut-off dampers. Shut-off dampers are used if the air han-dling unit is idle during some period or if a water coil is used. The damper is premounted and prewired in factory. The dampers are made of galvanized steel, the blades of the rec-tangular dampers are made of extruded aluminum. The blades have rubber seals. Accord-ing EN 1751, air tightness of circular dampers is of class 3, the air tightness of rectangular dampers is of classe 2.
Specification: CTXX_XXX-XXX_1
Connection frame [mm]
Duct dimensions [mm]None = 0On/off = 1Spring return = 2
The roof for outdoor installation is supplied as a complete assembly kit to be mounted on site.
Specification: OUT_XXX-XXX
Roof size [mm]
ROOF FOR OUTDOOR INSTALLATION- OUT
MODEL CID DIMENSIONS[mm] LABEL
GLOBAL PX 04/05 882167 1670 x 750 OUT_1820-750
GLOBAL PX 06/08 882184 1820 x 955 OUT_1820-955
GLOBAL PX 10 883152 1820 x 1135 OUT_1820-1135
GLOBAL PX 12/13 883153 1820 x 1320 OUT_1820-1320
GLOBAL PX 14 882168 1820 x 1520 OUT_1820-1520
GLOBAL PX 16 882169 1820 x 1780 OUT_1820-1780
GLOBAL PX 18883506 2020 x 2155 OUT_2020-2155
883358 810 x 2155 OUT_810-2155
GLOBAL PX 20 883355 2690 x 1780 OUT_2690-1780
GLOBAL PX 24 883356 2690 x 2155 OUT_2690-2155
GLOBAL PX 26 883357 2690 x 2535 OUT_2690-2535
rOOf fOr OutdOOr instALLAtiOn(Out) GLOBAL PX series : ACCessOires
mOtOrised dAmPers (Ct) GLOBAL PX series : ACCessOires
MODEL CID DUCT SIZE[mm]
OUTER DIMENSIONS[mm] LABEL
GLOBAL PX 04/05 882863 DN315 DN315 CT_315
GLOBAL PX 06/08/10 882367 DN400 DN400 CT_400
GLOBAL PX 12/13 883107 1020 x 500 1100 x 580 CT40_1020-500
GLOBAL PX 14 882149 1225 x 500 1305 x 580 CT40_1225-500
GLOBAL PX 16 882150 1480 x 500 1560 x 580 CT40_1480-500
GLOBAL PX 18 883496 1855 x 500 1935 x 580 CT40_1855-500
GLOBAL PX 20 883109 1480 x 630 1560 x 710 CT40_1480-630
GLOBAL PX 24 883335 1855 x 630 1935 x 710 CT40_1855-630
GLOBAL PX 26 883336 2235 x 630 2315 x 710 CT40_2235-630
MOTORISED DAMPER - CT
GLOBAL PX 47This document is an overvieuw of technical specifications. Please refer to our selection software for detailed and updated information.
The exhaust air section is secured by means of screws to the air handling unit’s duct connection. The complete assembly is mounted and wired in factory.
Specification: AUe_XX/XX
Air hood connection size
The intake air section is secured by means of screws to the air handling unit’s duct connection. The complete assembly is mounted and wired in factory.
Specification: AUi_XX/XX
Air hood connection size
AIR INLET WITH PROTECTION GRILL - AUi
MODEL HOOD LABEL HOOD +DAMPER LABEL DIMENSIONS
[mm]
GLOBAL PX 04/05 883292 AUi_315 883288 AUCTi_315 340 x 600
GLOBAL PX 06/08/10 883293 AUi_400 883289 AUCTi_400 440 x 600
GLOBAL PX 12/13 883142 AUi_1110-585 883147 AUCTi_1110-585 1110 x 585
GLOBAL PX 14 882163 AUi_1310-585 882165 AUCTi_1310-585 1310 x 585
GLOBAL PX 16 882164 AUi_1565-585 882166 AUCTi_1565-585 1565 x 585
GLOBAL PX 18 883503 AUi_1940-585 883504 AUCTi_1940-585 1940 x 585
GLOBAL PX 20 883144 AUi_1565-715 883149 AUCTi_1565-715 1565 x 715
GLOBAL PX 24 883349 AUi_1940-715 883351 AUCTi_1940-715 1940 x 715
GLOBAL PX 26 883350 AUi_2320-715 883352 AUCTi_2320-715 2320-715
Air inLet(Aui) GLOBAL PX series : ACCessOires
Air OutLet (Aue) GLOBAL PX series : ACCessOires
AIR OUTLET WITH PROTECTION GRILL - AUe
MODEL HOOD LABEL HOOD +DAMPER LABEL DIMENSIONS
[mm]
GLOBAL PX 04/05 883294 AUe_315 883290 AUCTe_315 340 x 600
GLOBAL PX 06/08/10 883295 AUe_400 883291 AUCTe_400 440 x 600
GLOBAL PX 12/13 883260 AUi_1110-585 883265 AUCTe_1110-585 1110 x 585
GLOBAL PX 14 882163. AUi_1310-585 883205 AUCTe_1310-585 1310 x 585
GLOBAL PX 16 882164 AUi_1565-585 883206 AUCTe_1565-585 1565 x 585
GLOBAL PX 18 883506 AUe_1940-585 883505 AUCTe_1940-585 1940 x 585
GLOBAL PX 20 883144 AUi_1565-715 883267 AUCTe_1565-715 1565 x 715
GLOBAL PX 24 883349 AUi_1940-715 883353 AUCTe_1940-715 1940 x 715
GLOBAL PX 26 883350 AUi_2320-715 883354 AUCTe_2320-715 2320-715
NOTES: