GEP400-4 - Advanced Diesel Engineering Ltd · Motor Starting Capability* kVA 797 745 678 -...

4
Engine Make & Model: Perkins 2206C-E13TAG2 Circuit Breaker Type: 3 Pole MCCB Fuel Tank Capacity: litres (US gal) 867 (229.0) Frequency: 50 Hz 60 Hz Fuel Consumption, Prime: l/hr (US gal/hr) 76.3 (20.2) Engine Speed: RPM 1500 Alternator Model: LL6114B Base Frame Type: Heavy Duty Fabricated Steel Fuel Consumption, Standby : l/hr (US gal/hr) 84.4 (22.3) Output Ratings Generating Set Model Standby* 400.0 kVA 320.0 kW - - Prime* 350.0 kVA 280.0 kW - - 380-415V,50Hz * Refer to ratings definitions on page 4. Ratings at power factor. 0.8 GEP400-4 Technical Data Diesel Generator Set Exclusively from your Caterpillar® dealer EU Stage II Emissions Compliant

Transcript of GEP400-4 - Advanced Diesel Engineering Ltd · Motor Starting Capability* kVA 797 745 678 -...

Engine Make & Model: Perkins 2206C-E13TAG2

Circuit Breaker Type: 3 Pole MCCB

Fuel Tank Capacity: litres (US gal) 867 (229.0)

Frequency: 50 Hz 60 Hz

Fuel Consumption, Prime: l/hr (US gal/hr) 76.3 (20.2)

Engine Speed: RPM 1500

Alternator Model: LL6114B

Base Frame Type: Heavy Duty Fabricated Steel

Fuel Consumption, Standby : l/hr (US gal/hr) 84.4 (22.3)

Output Ratings

Generating Set Model Standby*

400.0 kVA

320.0 kW

-

-

Prime*

350.0 kVA

280.0 kW

-

-

380-415V,50Hz

* Refer to ratings definitions on page 4. Ratings at power factor.0.8

GEP400-4

Technical Data

Diesel Generator SetExclusively from your Caterpillar® dealer

EU Stage II Emissions Compliant

6.4 (25.7)

599.4 (21168)

Air Filter Type:

Combustion Air Flow:

m³/min (cfm) -Standby:

-Prime:

Max. Combustion Air Intake

Restriction: kPa (in H2O)

Paper Element 15"

26.2 (925)

25.2 (890)

Radiator Cooling Air Flow:

m³/min (cfm)

External Restriction to

Cooling Air Flow: Pa (in H2O) 125 (0.5)

Air System 60 Hz50 Hz

Moment of Inertia: kg m² (lb. in²) 2.77 (9465)

Governing Type:

Governing Class:

Compression Ratio:Displacement: l (cu.in)

Engine Electrical System:

-Voltage/Ground:

-Battery Charger Amps:

Weight: kg (lb) - Dry:

- Wet:

Cooling Method: Water

Electronic

ISO 8528 G2

16.3:1

12.5 (762.8)

Bore/Stroke: mm (in) 130.0 (5.1)/157.0 (6.2)

24/Negative

701301 (2868)

1351 (2978)

Induction:

Manufacturer: Perkins

Model: 2206C-E13TAG2

No. of Cylinders/Alignment: 6 / In Line

Cycle: 4 Stroke

Turbocharged Air To Air Charge Cooled

32.0Regenerative Power: kW-Prime: 2075.0 (300.9)

2357.0 (341.9)-Standby:BMEP: kPa (psi)

324.2 (435.0) -Prime:

-Standby:Gross Engine Power: kW (hp)

368.4 (494.0)

1500Engine Speed: RPM

Oil Pan l (US gal):

Total Oil Capacity l (US gal):

Oil Filter Type:

Oil Type:

Cooling Method:

Eco, Full Flow

40.0 (10.6)38.0 (10.0)

API CH4 SAE15W-40

Water

Prime

50 Hz 43.6 (11.5)60 Hz

60.8 (16.1)76.3 (20.2)84.4 (22.3)

(based on diesel fuel with a specific gravity of 0.85 and conforming to BS2869, Class A2)

Recommended Fuel:

Fuel Consumption: l/hr (US gal/hr)Class A2 Diesel

110%Load

75%Load

50%Load

100%Load

Fuel Filter Type: Replaceable Element

Standby

50 Hz 48.7 (12.9)67.6 (17.9)84.4 (22.3)

60 Hz

Level: dB

Silencer System: kPa (in Hg)

Pressure Drop Across

Silencer Noise Reduction

Silencer Type:

Pressure: kPa (in. Hg)

Max. Allowable Back

-Prime:

m³/min (cfm) -Standby:

Exhaust Gas Flow:

-Prime:

m³/min (cfm) -Standby:

Exhaust Gas Temperature: °C (°F)

243-6273 (1)Silencer Noise Reduction

1.87 (0.552)

13

10.0 (3.0)

72.0 (2543)

67.3 (2377)

630 (1166)

551 (1024)

Level 1Cooling System Capacity: l (US gal)

Water Pump Type:

Heat Rejected to Water &

Lube Oil: kW (Btu/min)

-Standby:

-Prime:

-Prime:

kW (Btu/min) -Standby:Heat Radiation to Room:

Radiator Fan Load: kW (hp)

131.3 (7467)

45.2 (11.9)Centrifugal

118.4 (6733)

35.0 (1990)

34.0 (1934)

12.0 (16.1)

Cooling system designed to operate in ambient conditions up to 50°C (122°F). Contact your local Olympian dealer for power ratings at specific site conditions.

Cooling System 60 Hz50 Hz

Performance 60 Hz50 Hz

Fuel System

Exhaust System

Lubrication systemPhysical Data

Engine Techncial Data

60 Hz50 Hz

tylerka
Text Box
Engine Technical Data

Data Item50 Hz 60 Hz

Motor Starting Capability* kVA 797 745 678 -

Reactances: Per Unit

Xd

X'd

X''d

2.987 3.216 3.563 -

0.172 0.185 0.205 -

0.120 0.130 0.143 -

Reactances shown are applicable to standby ratings.* Based on 30% voltage dip.** With optional Permanent Magnet generator or AREP excitation.

415/240V 400/230V 380/220V

Short Circuit Capacity** % 300 300 300 300 300 300 300 300 300

Manufacturer:

Model:

No. of Bearings:

Insulation Class:

Winding Pitch - Code:

Wires:

Ingress Protection Rating:

Excitation System:

AVR Model:

OLYMPIAN

LL6114B

1

H

2/3 - 6

12

IP23

SHUNT

R448

Overspeed: RPM

Voltage Regulation (steady state) (%):

Wave Form NEMA = TIF:

Wave Form IEC = THF:

Total Harmonic Content LL/LN:

Radio Interference:

Radiant Heat: kW (Btu/min)

-50 Hz:

-60 Hz:

Supression is in line with European Standard EN61000-6

24.1 (1371)

2.0%

2.0%

50

+/- 0.5

2250

Physical Data Operating Data

Alternator Performance Data

Alternator Technical Data

Consult your Olympian representative for more information

320.0400.0

320.0400.0

320.0400.0

kWkVA

280.0350.0

350.0 280.0

kWkVA

380/220V

415/240V

400/230V

280.0350.0

Technical Data Phase Ratings and Performance at 50 Hz, RPM15003

Voltage Prime Standby

Standby RatingThese ratings are applicable for supplying continuous electricalpower (at variable load) in the event of a utility power failure. Nooverload is permitted on these ratings. The alternator on this modelis peak continuous rated (as defined in ISO 8528-3).

Prime RatingThese ratings are applicable for supplying continuous electricalpower (at variable load) in lieu of commercially purchased power.There is no limitation to the annual hours of operation and thismodel can supply 10% overload power for 1 hour in 12 hours.

Standard Reference ConditionsNote: Standard reference conditions 25°C (77°F) air inlet temp,100m (328ft) A.S.L. 30% relative humidity. Fuel consumption dataat full load with diesel fuel with specific gravity of 0.85 andconforming to BS2869: 1998, Class A2.

Definitions

kWkVAkWkVA

Phase Ratings and Performance at 60 Hz, RPM3

Voltage Prime Standby

Weights & Dimensions

Weights: kg (lb)

Net (+ lube oil)

Wet (+ lube oil & coolant)

Fuel, lube oil & coolant 3443 (7591)

2715 (5986)

2670 (5886)

Dimensions: mm (in)

Height

Width

Length

2158 (85.0)

1110 (43.7)

3500 (137.8)

DocumentsA full set of operation and maintenance manuals and circuit wiring diagrams.

Quality StandardsBS4999, BS5000, BSEN60034, BSEN61000, IEC60034.

WarrantyAll equipment carries full manufacturer's warranty.

General Data

Market: International

CAT, CATERPILLAR, their respective logos and ''Caterpillar Yellow'', as well as corporate and productidentity used herein, are trademarks of Caterpillar and may not be used without permission.

Note: General configuration not to be usedfor installation. See general dimensiondrawings for detail.

tylerka
Text Box
LEHF6450-04 (05/09)
tylerka
Text Box
CAT, CATERPILLAR, OLYMPIAN, their respective logos, and "Caterpillar Yellow", as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
m.fisher
Typewritten Text
Telephone: +44 (0) 1977 658 100 Fax: +44 (0) 1977 608 111 E-mail: [email protected] Web: www.adeltd.co.uk
m.fisher
Typewritten Text
Advanced Diesel Engineering Ltd 14 Langthwaite Business Park South Kirkby, Pontefract West Yorkshire, WF9 3AP
m.fisher
Typewritten Text