Geoff Cronshaw

51
The IEE tutorial workshop on Earthing & Bonding techniques for electrical installations. Presentation by: Geoff Cronshaw, Chief Engineer, Standards and Compliance, IEE.

description

Electrical books

Transcript of Geoff Cronshaw

Page 1: Geoff Cronshaw

The IEE tutorial workshop on Earthing & Bonding techniques for electrical installations.

Presentation by:Geoff Cronshaw,

Chief Engineer, Standards and Compliance,IEE.

Page 2: Geoff Cronshaw

IEE tutorial workshop

1. Overview of earthed and unearthed electrical systems.

2. Performance requirements of BS 7671.3. Type of earthing systems, advantages,

disadvantages, and applications of different systems, use of RCD’s.

Page 3: Geoff Cronshaw

1. Overview of earthed and unearthed electrical systems• It is necessary to determine the type of system, i.e.TN-S,

TN-C-S, TT, etc, of which the proposed installation will form a part, before proceeding with the installation design.

• A distributor is required on request to provide a statement on the type of earthing (Reg 28 of the Electricity Safety, Quality and Continuity Regulations) and unless inappropriate for reasons of safety, the distributor is required to make available his supply neutral conductor or protective conductor for connection to the consumer’s earth terminal (Reg 24).

Page 4: Geoff Cronshaw

• For a low voltage supply given in accordance with the Electricity Safety, Quality and Continuity Regulations 2002 the supply system will be TN-S, TN-C-S(PME) or TT, and most commonly for new supplies TN-C-S.

• TN-C and IT systems are both very uncommon in the UK, the former because it requires an exemption from the Electricity Safety, Quality and Continuity Regulations which invoke special installation arrangements and the latter because the source is not directly earthed and this is not permitted for a low voltage public supply in the UK (Reg 8).

• For TN-S, TN-C-S and TT systems the following explanations should aid a full understanding of the earthing arrangements and their scope of application. The nomenclature of these system types is as follows: T = Earth (from the French word Terre) N = Neutral S = Separate C = Combined

Page 5: Geoff Cronshaw

TN-S system earthingsystem

Exposed-conductive-

part

installation equipment

(origin ofinstallation)

source of supply installation

T

N-S

L

NPE

542-01-02

source earth

(separate neutral (N) and protective conductors (PE) throughout the system)

Page 6: Geoff Cronshaw

L LN N

kWh

S7 6E 165456

TN-SElectricitycompanyisolator

Mainearthingterminal 100 A LABEL - Safety Electrical

Connection. Do not remove

LABEL - Safety ElectricalConnection. Do not remove

metal gas pipe

gas meter

Waterservice pipe

Gasservice pipe

main switch

metal water pipe

circuit protective conductors

Page 7: Geoff Cronshaw

TN-S system

A TN-S system has the neutral of the source of energy connected with earth at one point only, at or as near as is reasonably practicable to the source, and the consumer’s earthing terminal is typically connected to the metallic sheath or armour of the distributor’s service cable into the premises or to a separate protective conductor of, for instance, an overhead supply

Page 8: Geoff Cronshaw

TN-C-S system earthing

sourceearth

(combined neutral andprotective conductor (PEN)in source of supply, withPME applied)

TN-C

additionalsource electrode

(separate neutral (N) andprotective conductors (PE)within installation)

S

linkNPE

542-01-03

L

PEN

Page 9: Geoff Cronshaw

TN-C-S

L LN N

kWh

S7 6E 165456

circuit protective conductors

Electricitycompanyisolator

Mainearthingterminal

100 ALABEL - Safety Electrical

Connection. Do not remove

LABEL - Safety ElectricalConnection. Do not remove

metal gas pipe

gas meter

Waterservice pipe

Gasservice pipe

main switch

metal water pipe

Page 10: Geoff Cronshaw

TN-C-S system

A TN-C-S system has the supply neutral conductor of a distribution main connected with earth at source and at intervals along its run. This is usually referred to as protective multiple earthing (PME). With this arrangement the distributor’s neutral conductor is also used to return earth fault currents arising in the consumer’s installation safely to the source. To achieve this, the distributor will provide a consumer’s earthing terminal which is linked to the incoming neutral conductor.

Page 11: Geoff Cronshaw

TT system earthing

consumer’searth

T T

542-01-04

sourceearth

Page 12: Geoff Cronshaw

TT

Earth Rod

L LN N

kWh

S7 6E 165456

Electricity Supply(usually overhead)

Electricitycompanyisolator

Mainearthingterminal

100 A

LABEL - Safety ElectricalConnection. Do not remove

LABEL - Safety ElectricalConnection. Do not remove

metal gas pipe

gas meter

Waterservice pipe

Gasservice pipe

main switch

metal water pipe

circuit protective conductors

Page 13: Geoff Cronshaw

TT system

A TT system has the neutral of the source of energy connected as for TN-S, but no facility is provided by the distributor for the consumer’s earthing. With TT, the consumer must provide his or her own connection to earth, i.e. by installing a suitable earth electrode local to the installation.

Page 14: Geoff Cronshaw

2. Performance requirementsof BS 7671

• A wide variety of types of earth electrode are recognised by BS 7671. The most suitable type for a particular system will dependupon a number of factors, the single most important of these being the soil resistivity of the ground. If earth rods are to be driven it may be necessary to go down several metres before a good conductive layer is reached, especially where the water table is low. Rods can only be as effective as the contact they make with the surrounding material. Thus, they should be driven into virgin ground, not disturbed (backfilled) ground. Where it is necessary to drive two or more rods and connect them together to achieve a satisfactory result, the separation between rods should be at least equal to their combined driven depth to obtain maximum advantage from each rod.

Page 15: Geoff Cronshaw

• In some locations low soil resistivity is found to be concentrated in the topsoil layer, beneath which there may be rock or other impervious strata which prevents the deep driving of rods, or a deep layer of high resistivity. Only a test or known information about the ground can reveal this kind of information. In such circumstances, the installation of copper earth tapes, or pipes or plates, would be most likely to provide a satisfactory earth electrode..

Page 16: Geoff Cronshaw

• Closely spaced buildings may sometimes make it difficult to find ground suitable for driving an earth electrode. Electrodes which employ suitable structural or other underground metalwork, or the metal reinforcement of concrete embedded in the ground may then be of particular advantage. Whatever form an earth electrode takes, the possibility of soil drying and freezing, and of corrosion, must be taken into account. Preferably, testing of an earth electrode should be carried out under the least favourable conditions, i.e. after prolonged dry weather. Further information on earthing principles and practice can be found in BS 7430 : 1998 ‘Code of Practice for Earthing’ (formerly CP 1013: 1965).

Page 17: Geoff Cronshaw

• Earthing conductors - The earthing conductor of an installation is part of the earth current path. It is therefore important that the conductor is adequately sized and, particularly where buried partly in the ground, of suitable material and adequately protected against corrosion and mechanical damage.

• The size of an earthing conductor is arrived at in basically the same way as for a circuit protective conductor, except that Table 54A of BS 7671 must be applied to any buried earthing conductor. For a TN-C-S (PME) supply, the designer will additionally require it to be no smaller than the main bonding conductors.

Page 18: Geoff Cronshaw

• Sizing of circuit protective conductors.There are several factors which may influence or determine the size required for a circuit protective conductor. A minimum cross-sectional area of 2.5 mm2

copper is required for any separate circuit protective conductor, i.e. one which is not part of a cable or formed by a wiring enclosure or contained in such an enclosure.

An example would be a bare or insulated copper conductor clipped to a surface, run on a cable tray or fixed to the outside of a wiring enclosure. Such a circuit protective conductor must also be suitably protected if it is liable to suffer mechanical damage or chemical deterioration or be damaged by electro-dynamic effects produced by passing earth fault current through it. If mechanical protection is not provided the minimum size is 4 mm2 copper or equivalent.

Page 19: Geoff Cronshaw

• BS 7671 provides two methods for sizing protective conductors including earthing conductors (see also Table 54A). The easier method is to determine the protective conductor size from Table 54G, but this may produce a larger size than is strictly necessary, since it employs a simple relationship to the cross-sectional area of the phase conductor(s).

• The second method involves a formula calculation. The formula is commonly referred to as the ‘adiabatic equation’ and is the same as that used for short-circuit current calculations (see Regulation 434-03-03). It assumes that no heat is dissipated from the protective conductor during an earth fault and therefore errs on the safe side. Even so, application of the formula will in many instances result in a protective conductor having a smaller csa than that of the live conductors of the associated circuit. This is quite acceptable.

Page 20: Geoff Cronshaw

• Regulation 543-01-03 states :543-01-03 The cross-sectional area, where calculated, shall

be not less than the value determined by the following formula or shall be obtained by reference to BS 7454:

where:S is the nominal cross-sectional area of the conductor in mm2.I is the value in amperes (rms. for a.c.) of fault current for a fault of negligible

impedance, which can flow through the associated protective device, due account being taken of the current limiting effect of the circuit impedances and the limiting capability (I2 t) of that protective device. Account shall be taken of the effect, on the resistance of circuit conductors, of their temperature rise as a result of overcurrent - see Regulation 413-02-05.

t is the operating time of the disconnecting device in seconds corresponding to the fault current I amperes.

k is a factor taking account of the resistivity, temperature coefficient and heat capacity of the conductor material, and the appropriate initial and final temperatures.

ktIS

2=

Page 21: Geoff Cronshaw

3. Type of earthing systems, advantages, disadvantages, and applications of different systems, use of RCD’s.

Page 22: Geoff Cronshaw

Protective multiple earthing (PME). Such a supply system is described in BS 7671 as TN-C-S.• The Electricity Safety, Quality and Continuity

Regulations 2002 permit the distributor to combine neutral and protective functions in a single conductor provided that, in addition to the neutral to earth connection at the supply transformer, there are one or more other connections with earth.

• This protective multiple earthing (PME) has been almost universally adopted by supply companies in the UK as an effective and reliable method of providing their customers with an earth connection. Such a supply system is described in BS 7671 as TN-C-S.

Page 23: Geoff Cronshaw

PME earth terminal

L N PEprotectiveconductor

Additionalearth

PME earthterminal

L1

L2

L3

PEN

Source earth

Customer’s installation

Page 24: Geoff Cronshaw

• However, under certain supply system fault conditions (external to the installation) a potential can develop between the conductive parts connected to the PME earth terminal and the general mass of earth.

• Supply systemThere are multiple earthing points on the supply network, and providing bonding within the building complies with BS 7671 it is unlikely that such a potential as described above would in itself constitute a hazard.

• Additional earth electrode for PME supplies.• In the unlikely event of the PEN conductor of the

supply becoming open circuit, touch voltages perhaps causing some discomfort may arise on exposed metal in customers installations downstream of the open circuit.

Page 25: Geoff Cronshaw

• The effect can be mitigated by connection of a suitable earth electrode to the main earth terminal of the customers installation. The value of the resistance to-earth necessary to limit the touch voltages to a given value depends on the load and the network parameters:

RConsumer’sinstallation

RA

RL

Vp

N

RB

PEN Open-circuitPEN

eLine L

Vs

PEN

PE

Page 26: Geoff Cronshaw

Where:

Vs is the nominal supply (source) voltage

Vp is the touch voltage

Re is the external supply resistance

RL is the load resistance (Vs2 / wattage)

RA is the resistance of the additional earth electrode including parallel earth (e.g. water and gas pipes)

RB is the resistance to earth of the neutral point of the power supply.

Page 27: Geoff Cronshaw

• Special locationsThe Electricity Association provides guidance on PME in its Engineering Recommendation G12/3, ‘Requirements for the application of protective multiple earthing to low voltage networks’. The guidance given in this Section is based on Part 6 of G12/3.

• Remote supplies.A physically isolated building may be supplied via both a long LV distribution main and a long individual service. If these circumstances are coupled with an unbalanced load a potential difference will be evident between the PME terminal and true earth.

• This rise in neutral potential is transferred to metalwork connected to the PME terminal, and may be noticeable in such locations as shower areas, where simultaneous contact with true earth (a wet concrete floor) and the PME terminal (shower pipes) may be possible.

Page 28: Geoff Cronshaw

• G12/3 recommends that such floors should incorporate a metal grid connected to the supplementary bonding within the shower/bathing area. Certainly, if there is a grid in the floor it must be connected to the local supplementary bonding. An alternative approach would be not to use the PME earthing terminal and to afford protection by means of RCDs and an independent earth electrode, that is, treat as part of a TT system.

• Sports pavilionsWhere no shower area exists nor is likely to exist in a sports pavilion, PME may be offered provided the appropriate metalwork is bonded. Where a shower exists PME should only be applied where there is an earth grid in the floor of the shower area, supplementary bonded to accessible metal pipework, etc. An alternative would be to plumb the installation in plastic pipes.

Page 29: Geoff Cronshaw

• Swimming poolsSwimming pools supplied with their own dedicated service should be protected with an RCD. All metalwork should be bonded and connected to an earth electrode. Where a swimming pool forms part of a residence, all metalwork and pipes supplying the pool should be connected to an earth electrode and segregated from the rest of the building. An RCD should then be used to protect the supplies to the pool area and the swimming pool installation treated as part of a TT system. Where segregation of pipes and metalwork around a pool is impracticable, e.g. in an indoor pool, the installation of a metal grid around the pool and the supplementary bonding of adjacent metalwork is recommended together with an RCD in addition to PME.Additional earth electrode for PME supplies.

Page 30: Geoff Cronshaw

• Agricultural and horticultural premisesA PME terminal may be used in these premises provided main equipotential bonding has been carried out and the additional measures required by Section605 of BS 7671 have been provided, e.g. reduced disconnection times, supplementary bonding, RCD protection. The general principles to be adopted for separate buildings utilizing a PME terminal are as follows: (i) each separate building should have a designated

main earthing terminal within the building(ii) any main equipotential bonding required in a

separate building to external services, structural metalwork, etc, should be connected to the designated earth terminal. The cross-sectional area of the bonding conductor should be selected from Table 54H of BS 7671 using the electricity distributor’s supply neutral conductor as reference.

Page 31: Geoff Cronshaw

• Livestock/dairiesParticular care must be taken in areas where livestock are housed as they are sensitive to small potential differences.

• Building and construction sites, quarries, etcIt may be difficult to satisfy the electricity distributors bonding requirements because of the large number of parts of the building works that are extraneous-conductive-parts. In these circumstances a PME earthing terminal may not be provided. Regional electricity companies may be prepared to offer a TN-S supply to large sites requiring their own substation where the earthing terminal can be connected directly to the transformer neutral. For quarries, see also below.

Page 32: Geoff Cronshaw

• Caravan park and marinasRegulation 9(4) of the Electricity Safety, Quality and Continuity Regulations does not allow the combined neutral and protective conductor to be connected electrically to any metalwork in a caravan or boat. This prevents PME terminals being used for caravans or boat mooring supplies, although they may be used for fixed premises on the sites, such as the site owner’s living premises and any bars or shops, etc. Account is taken of this in Section 608 of BS 7671 with respect to caravans, and also will be for marinas when a section is included in the standard. The extension of PME to toilets and amenity blocks is not recommended as there is a high probability of people going barefoot and being in good contact with true earth through wet concrete floors.

Page 33: Geoff Cronshaw

Typical site distribution for a PME supply, separation from PME earth at main distribution board

PEN NPE

Main Board Distributor

RCDRCD

100 mA or greaterRCD in insulatedenclosure

Pitchoutlets

pitch supply

general purpose30 mA RCD

Installation earthing tobe separated from the

PME earthing

Resistance areas of installationand supply earthing to be

separated

TNC Supply (PME)

L L

Page 34: Geoff Cronshaw

Typical site distribution for a PME supply, separation from PME earth at pitch supply point

PEN L

Main Board Distributor pitch supply point

RCD

Cable protective conductor (armour/sheath) separated from RCD earth and caravan protective conductors

Overcurrent device to disconnect O.4 s

Pitchoutlets

30 mA RCD

Isolator TNC Supply (PME)

PE N L

Page 35: Geoff Cronshaw

• Petrol filling stationsThe reference publication is “Guidance for the design, construction, modification and maintenance of petrol filling stations”, published by the APEA and the Institute of Petroleum, which recommends a TT supply for hazardous areas.A separate earth electrode and RCD or other alternative arrangement is required to ensure the segregation of petrol filling area earthing and that of the PME earth of the distribution network. A PME earth may be used for permanent buildings such as shops and restaurants.Additional earth electrode for PME supplies.

• Mines and quarriesA supply taken to an underground shaft, or for use in the production side of a quarry, must have an earthing system which is segregated from any system bonded to the PME terminal.

Page 36: Geoff Cronshaw

• Supply terminating in a separate buildingOccasionally a service will terminate in a position remote from the building it supplies. The size of the PME bonding in the building supplied must be related to the size of the incoming supply cable, in accordance with Regulation 547-02-01 and Table 54H of BS 7671. If the size of the circuit protective conductor of the cable between the supply intake position and the building is less than that of the PME bonding conductor, a suitable additional conductor will have to be installed or the PME earth not used.

Page 37: Geoff Cronshaw

Supply terminating in a separate building

Main EquipotentialBonding to be relatedto the neutral of themain cable M

Main earthterminal

Supplier’scutout

BuildingSupplied

Remote supplytermination

Earthterminal

Sub main S

Main supplycable M

Size of protectiveconductor/armouring tobe related to the neutralof the main cable M

Page 38: Geoff Cronshaw

• PME and outside water tapsUnder an open-circuit supply neutral condition the potential of an outside water tap will rise above earth potential. A person coming into contact with the tap could receive an electric shock and the shock could be severe, if that person were barefooted. The probability of these two conditions occurring together is considered to be so small that the use of PME where a metal outside tap exists is not precluded. It is recommended, however, that a plastic insert be provided in the pipe to the outside water tap.

• High rise buildingsFor guidance on the application of PME to high rise buildings and building complexes, guidance should be sought from the electricity supply company and Engineering Recommendation G12/3.

Page 39: Geoff Cronshaw

• Highway power suppliesStreet electrical fixtures were exempted from the requirements of Regulation 7 of the former Electricity Supply Regulations 1988 as amended. The exemption allowed the minimum copper equivalent cross sectional area of the main equipotential bonding conductor to be reduced to 6 mm2 in specific circumstances. As the Electricity Safety, Quality and Continuity Regulations do not specify minimum sizes of main bonding conductors, it is to be presumed that it would be reasonable to allow the reduction in size for street lighting equipment in the same circumstances as before. Although BS 7671 at present has a minimum size of 10 mm2 for supply neutral conductors of 35 mm2 csa or less, it would seem appropriate to reduce the minimum size to 6 mm2 for supply neutral conductors of 6 mm2 csa or less, see Regulation 547-02. However, the departure from Part 5 would need to be recorded on the Electrical Installation certificate.

Page 40: Geoff Cronshaw

A TT system

• A TT system has the neutral of the source of energy connected as for TN-S, but no facility is provided by the distributor for the consumer’s earthing.

• With TT, the consumer must provide his or her own connection to earth, i.e. by installing a suitable earth electrode local to the installation. The circumstances in which a distributor will not provide a means of earthing for the consumer are usually where the distributor cannot guarantee the earth connection back to the source, e.g. a low voltage overhead supply, where there is the likelihood of the earth wire either becoming somehow disconnected or even stolen.

Page 41: Geoff Cronshaw

• A distributor also might not provide means of earthing for certain outdoor installations, e.g. a construction site temporary installation, leaving it to the consumer to make suitable and safe arrangements for which they are fully responsible. The electricity distributor is required to make available his supply neutral or protective conductor for connection to the consumer’s earth terminal, unless inappropriate for reasons of safety (Reg 24). Construction site, farm or swimming pool installations might be inappropriate unless additional precautions are taken, such as an additional earth electrode.

Page 42: Geoff Cronshaw

A TN-S system

• A TN-S system has the neutral of the source of energy connected with earth at one point only, at or as near as is reasonably practicable to the source, and the consumer’s earthing terminal is typically connected to the metallic sheath or armour of the distributor’s service cable into the premises or to a separate protective conductor of, for instance, an overhead supply.

Page 43: Geoff Cronshaw

• Large consumers may have one or more HV/LV transformers dedicated to their installation and installed adjacent to or within their premises. In such situations the usual form of system earthing is TN-S. It is not necessary for the star (neutral) point of the transformer LV secondary to be brought out at the transformer cable box in order to earth this point. The usual and most convenient means of earthing the source neutral is for the connection to earth to be made at the first accessible position in the LV system at which the neutral is terminated, i.e. LV feeder pillar or main LV switchboard.

Page 44: Geoff Cronshaw

Use of RCD’s

• Supplementary protection by residual current devices.• With specific exceptions, supplementary protection by

a residual current device must be provided in every circuit intended or reasonably expected to supply portable equipment for use outdoors.

• Residual current devices do not prevent shock currents flowing through the body, for a current must flow to earth for the residual current device to detect. However, provided the residual current device is sufficiently sensitive and functionally tested periodically it will operate sufficiently quickly to prevent injury.

Page 45: Geoff Cronshaw

• Automatic disconnection of supply• BS 7671 prescribes automatic disconnection of the

supply to any circuit, i.e. distribution circuit or final circuit, in which an earth fault may occur. This is irrespective of how successful the earthing and bonding provisions may be in keeping down the magnitude of voltages that may appear between exposed-conductive-parts and extraneous-conductive-parts conductive-parts during an earth fault, since, even if there is no shock risk, thermal damage may be caused to conductors or their surroundings if earth fault current is allowed to persist. Whatever the type of system, the operating characteristic of each device for automatic disconnection and the relevant impedance of the associated circuit should be properly co-ordinated to achieve the required disconnection time.

Page 46: Geoff Cronshaw

• For installations supplied at nominal voltages (Uo) in the range 121 - 277 V to earth the prescribed maximum disconnection times are generally 0.4 s or 5 s, but are 0.2 s for some special locations.

• An RCD may be used to provide indirect shock protection in TN systems where the earth fault loop impedance (Zs) is insufficiently low to operate a fuse or circuit-breaker within the prescribed disconnection time. An RCD may also be required for installations or locations of increased shock risk, such as those in Part 6 of BS 7671. Where more than one RCD is used they and their circuits should be segregated, or if RCDsare used in series the upstream device needs to be time delayed or S type and the downstream a type for general use, both to BS EN 61008 or BS EN 61009 to achieve discrimination.

Page 47: Geoff Cronshaw

Mixed disconnection times

• The requirements for mixed disconnection times apply for any final circuits supplied from the same distribution board, distribution circuit or sub-main. This includes adjacent boards supplied from a common circuit or with a common bonding connection.

• Mixed disconnection times within an installation can give rise to a particular problem. Consider two final circuits of an installation as shown below:

Page 48: Geoff Cronshaw

Final circuits having 'mixed' disconnection times (Regulation 413-02-13)

distributionboard

L

circuit B

circuit A

fixedLoad B

load A(indoors)

Uf

protectiveconductorin cord

If

further equipotentialbonding conductor(if necessary)

N

E

main earthingterminal

Rc

main equipotentialbondingconductor

earth

extraneous-conductive-part

exposed-conductive-part

250 V

Page 49: Geoff Cronshaw

• Other ways of avoiding or overcoming the problem could include: (i) design all circuits supplied from a common

distribution board or distribution circuit to achieve disconnection within 0.4 s

(ii) use RCD (RCCB or RCBO) protection. This would have to include, in the example illustrated, fixed equipment circuit B. Fitting an RCD to socket-outlet circuit A would not solve the possible problem, since the RCD would be unaffected by the appearance of the voltage Uf and any current this might send through the body of a person who makes simultaneous contact with the exposed-conductive-part of load A and the nearby extraneous-conductive-part.Additional earth electrode for PME supplies.

Page 50: Geoff Cronshaw

• Automatic disconnection in a TT system Other than in exceptional circumstances in which steel reinforcement of underground concrete or similar structure is available for use, in TT systems it is often difficult and costly to achieve a sufficiently low earth electrode resistance for overcurrent devices to be used for indirect shock protection.

Page 51: Geoff Cronshaw

We have covered a brief overview of earthing.

Thank you for listening, and have you any questions?