GENERATOR - Steadypower.com...GENERATOR DOCKING STATIONS // 2 One of the biggest stories in power...

5
GENERATOR DOCKING STATIONS

Transcript of GENERATOR - Steadypower.com...GENERATOR DOCKING STATIONS // 2 One of the biggest stories in power...

Page 1: GENERATOR - Steadypower.com...GENERATOR DOCKING STATIONS // 2 One of the biggest stories in power distribution is a spe-cialized power distribution box—what we at HIPOWER SYSTEMS

GENERATORDOCKING STATIONS

Page 2: GENERATOR - Steadypower.com...GENERATOR DOCKING STATIONS // 2 One of the biggest stories in power distribution is a spe-cialized power distribution box—what we at HIPOWER SYSTEMS

GENERATOR DOCKING STATIONS // 2

One of the biggest stories in power distribution is a spe-cialized power distribution box—what we at HIPOWER SYSTEMS call a generator docking stations (GDS)—that is specifically designed to be connected quickly and easily to a portable (mobile; roll-up) generator. (Note that there is no industry standard name for these devices, so we will refer to them as GDSs.)

The boxes themselves are not mobile. Rather, they are stationary power distribution units hardwired into a facility’s power supply infrastructure. They offer the ultimate protection for operations where power is truly mission-critical—where the facility cannot be without

power for even a few seconds, no matter what. These units enable companies to quickly and easily bring in re-placements for backup generators so they can be taken down for service or maintenance, or to act as a “backup for the backup” in the event of a power outage. Since their introduction to the market, many companies are finding other, valuable uses for GDSs that go beyond the most mission-critical operations.

Unlike transfer switches, which generally connect a per-manent, external standby generator to a facility’s power connection for quick switching to generator power, a GDS is mounted on the building (or placed on a nearby

1

2

pad) to create a “quick connect” link between the transfer switch or other disconnect and a mobile generator. If a facility wants or needs to obtain additional power for any reason, having a previously installed, externally mounted GDS enables them to connect a portable generator, located in a nearby alley or other external location, to the building’s disconnect via simple cam-style connections. Some of these units also can incorporate male or female cam-style connections, enabling either input of power to service the building or output of power for other uses.

3

4

CONNECTION SYSTEM

1 Portable Generator

2 4/0 Feeder Cable

3 Generator Docking Station

4 Transfer Switch

5 To Building Electrical Panel

5

LEFTGenerator Docking Stationconnections.

GENERATORDOCKING STATIONS

Page 3: GENERATOR - Steadypower.com...GENERATOR DOCKING STATIONS // 2 One of the biggest stories in power distribution is a spe-cialized power distribution box—what we at HIPOWER SYSTEMS

GENERATOR DOCKING STATIONS // 4

100/400A Camlok Gutter Panel

• 0.090” aluminum NEMA 3R enclosure, powder-coated ANSI 61 gray.

• Indoor/outdoor rated with corrosion-resistant hardware.

• Main swing door with 1/4 turn padlockable latch.

• Easy-to-remove gland plate to access permanent connection lugs.

• One set of male or female 400A 16 Series stud-type, pa-nel-mount Camlok devices.

• Color-coded snap-back covers.

• Electrical color code can be ordered to match any low voltage configuration.

Overall dimensions*

• 16.25”W x 8.125”D x 8.125”H (Approximately 20 lbs.)*All measurements are approximate and for estimation purposes only.

Specifications & Standards

• UL Industrial Control Panel Enclosure Listed C/UL (Canada listed).

100/400A Camlok Gutter Panel Features

• Aluminum, NEMA 250 Type 3R enclosure with polyurethanepowder coat.

• Compact wall-mountable design, full CAD drawing availableupon request.

• 100 percent ground of phase size.

• For use as a quick connection port to permanently installedswitch gear or other similar electrical equipment such as automatic transfer switches, manual transfer switches, dou-ble-throw safety switches, UPS systems, interlocked switch boards or bolt switches.

• Can be used as a quick connection port or junction point to access and service a stationary generator.

GENERATOR DOCKING STATION400/800A

CAMLOK GUTTER PANEL100/400A

1

GENERATOR DOCKING STATION400/800A

CAMLOK GUTTER PANEL100/400A

2

1

Our durableGenerator docking stations solutions are resistant toshock, impact, corrosion and weather

KVA Primary Secondary Amps Main

- 120Y208V 120Y208V 100/400A No

- 277Y480V 277Y480V 100/400A No

- 347Y600V 347Y600V 100/400A No

TECHNICAL DATA

2

400/800A Generator Docking Station

• 0.090” aluminum NEMA 3R enclosure, powder-coated ANSI 61 gray.

• Indoor/outdoor rated with corrosion-resistant hardware.

• Main swing door with 1/4 turn padlockable latch.

• Easy-to-remove gland plate to access permanent connection lugs.

• Up to two sets of male or female 400A 16 Series stud-type, panel-mount Camlok devices.

• Color-coded snap-back covers.

• Electrical color code can be ordered to match any low voltage configuration.

Overall dimensions*

• 19.0”W x 15.125”D x 30.0”H + 24.0” with leg kit (Approxi-mate 90lbs)

*All measurements are approximate and for estimation purposes only.

Specifications & Standards

• UL Industrial Control Panel Enclosure Listed C/UL (Canada listed).

400/800A Generator Docking Station Features

• Aluminum, NEMA 250 Type 3R enclosure with polyurethane powder coat.

• Corrosion-resistant material designed for industrial and harsh environments.

• Listed and labeled as defined in NFPA 70, marked for inten-ded application.

• For use as a quick connection port to permanently installed switch gear or other similar electrical equipment such as automatic transfer switches, manual transfer switches, dou-ble-throw safety switches, UPS systems, interlocked switch boards or bolt switches.

• Can be used as a quick connection port or junction point to access and service a stationary generator.

KVA Primary Secondary Amps Main

- 120Y208V 120Y208V 400/800A No

- 277Y480V 277Y480V 400/800A No

- 347Y600V 347Y600V 400/800A No

TECHNICAL DATA

Page 4: GENERATOR - Steadypower.com...GENERATOR DOCKING STATIONS // 2 One of the biggest stories in power distribution is a spe-cialized power distribution box—what we at HIPOWER SYSTEMS

GENERATOR DOCKING STATIONS // 6

GENERATOR DOCKING STATION1200/3200A

4

Available in both wall-mount and pad-mount styles. An array of accessories completes the package.

GENERATOR DOCKING STATION600/800A

3

600/800A Generator Docking Station

• 0.090” aluminum NEMA 3R enclosure, powder-coated ANSI 61 gray.

• Indoor/outdoor rated with corrosion-resistant hardware.

• Padlockable main door with two 1/4 turn latches.

• Easy-to-remove gland plate to access permanent connection lugs.

• Two sets of male 400A 16 Series Camloks with color-coded snap covers.

• Camlok color code can be ordered to match any low voltage configuration.

• Bottom-access cable trap system with rodent trap door.

Overall dimensions*

• 19.0”W x 15.125”D x 30.0”H (Approximately 90 lbs.) *All measurements are approximate and for estimation purposes only.

Specifications & Standards

• UL Industrial Control Panel Enclosure Listed C/UL (Canada listed).

600/800A Generator Docking Station Panel Features

• Aluminum, NEMA 250 Type 3R enclosure with polyurethane powder coat.

• Corrosion-resistant material designed for industrial and harsh environments.

• Listed and labeled as defined in NFPA 70, marked for inten-ded application.

• For use as a quick connection port to permanently installed switch gear or other similar electrical equipment such as automatic transfer switches, manual transfer switches, double-throw safety switches, UPS systems, interlocked switch boards or bolt switches.

• Can be used as a quick connection port or junction point to access and service a stationary generator.

GENERATOR DOCKING STATION1200/3200A

GENERATOR DOCKING STATION600/800A

3

KVA Primary Secondary Amps Main

- 120Y208V 120Y208V 600/800A No

- 277Y480V 277Y480V 600/800A No

- 347Y600V 347Y600V 600/800A No

TECHNICAL DATA

4

1200/3200A Generator Docking Station

• 0.090” aluminum NEMA 3R enclosure, powder-coated ANSI 61 gray.

• Indoor/outdoor rated with corrosion-resistant hardware.

• Main swing door with 1/4 turn padlockable latch.

• Easy-to-remove gland plate to access permanent connection lugs.

• Ten sets of male 400A 16 Series Camloks with color-coded snap covers.

• Camlok color code can be ordered to match any low voltage configuration.

• Optional stainless steel leg kit for pad-mount applications.

Overall dimensions*

• 38.0”W x 19.25”D x 43.0”H (Approximately 318 lbs.) *All measurements are approximate and for estimation purposes only.

Specifications & Standards

• UL Industrial Control Panel Enclosure Listed C/UL (Canada listed).

1200/3200A Generator Docking Station Features

• Aluminum, NEMA 250 Type 3R enclosure with polyurethane powder coat.

• Corrosion-resistant material designed for industrial and harsh environments.

• Listed and labeled as defined in NFPA 70, marked for inten-ded application.

• For use as a quick connection port to permanently installed switch gear or other similar electrical equipment such as automatic transfer switches, manual transfer switches, dou-ble-throw safety switches, UPS systems, interlocked switch boards or bolt switches.

• Can be used as a quick connection port or junction point to access and service a stationary generator.

KVA Primary Secondary Amps Main

- 120Y208V 120Y208V 1200A/3200A No

- 277Y480V 277Y480V 1200A/3200A No

- 347Y600V 347Y600V 1200A/3200A No

TECHNICAL DATA

Page 5: GENERATOR - Steadypower.com...GENERATOR DOCKING STATIONS // 2 One of the biggest stories in power distribution is a spe-cialized power distribution box—what we at HIPOWER SYSTEMS

Beyond its extensive selection of quality power distribution products and assembles, HIPOWER SYSTEMS prides itself on being a complete provider in every way. We continually explore new technologies and solutions to bring power innovations to market. We stringently monitor

our design, engineering and manufacturing processes and those of our suppliers to ensure product excellence. We also focus intently on providing the highest levels of customer service and satisfaction, because we value and honor the faith you place in our company.

MADE IN THE USA

HIMOINSA POWER SYSTEMS, INC. 16002 West 110th Street, Lenexa, KS 66219-1312 Tel: 913 495 5557 | Fax: 913 495 5575 www. hipowersystems.com

Made in the USA

www.hipowersystems.com