GENERAL SPECIFICATION Psonic-S1 - 流量計なら … GBM006E-2 Flow Range ※ Reference value of...
Transcript of GENERAL SPECIFICATION Psonic-S1 - 流量計なら … GBM006E-2 Flow Range ※ Reference value of...
Clamp-On Type Ultrasonic Flowmeter for Liquid Measurement
Psonic-S1 GENERAL SPECIFICATION
GS.No.GBM006E-2
Head Office (Tokyo): Phone. 81-3-3360-5121. Fax. 81-3-3365-8605 Beijing Office: Phone. 86-10-5867-4711. Fax. 86-10-5867-4713Overseas Branch Offices: Seoul, Singapore and Taipei
http://www.oval.co.jp
Liquid
GENERALThe Psonic-S1 is a clamp-on type ultrasonic flowmeter developed for liquid measurement. It has sensors laid on the outside of the pipe to accept incoming ultrasonic waves.It calculates the flowrate by measuring the propagation time of ultrasonic wave from the fact that the propagation time of ultrasonic pulse changes with the velocity of the liquid. The ultrasonic flowmeter can measure a variety of fluids including industrial water, agricultural water, wastewater, seawater, purified water, and water solution.
FEATURES 1. Clamp-on type flowmeter requires neither disconnecting
the pipe nor stopping the flow when installing the sensor. In addition, because there is no pressure loss, the cost for installing and operating the flowmeter is low.
2. Small and lightweight design facilitates installation.3. By use of dedicated PC communication software
(UFWconfig), setting of the flowmeter is easy.4. Though it is a low-priced flowmeter, it has the functions
equivalent to higher-level models including log and self-diagnosis.
PRINCIPLE of MEASUREMENT Principle of Operation
Propagation time difference method is to obtain flow velocity V in a pipe from time difference Δt between propagation time td of ultrasonic waves transmitted from the upstream sensor to the downstream sensor and propagation time tu of ultrasonic waves transmitted from the downstream sensor to the upstream sensor.
td= +τL
C+Vcosθ
tu= +τL
C-VcosθL: Length of propagation path of ultrasonic pulse
: Fixed delay timeC: Sonic velocity in fluid
Δt=tu-td=2LVcosθ
C2
Propagation time difference Δt is expressed by flow velocity V in the following equation.
Sensor end
Oscillator
LiningPipe wall
Flow velocity V
Flow direction
P1
P2
Ld
Shoe
θ
Therefore, flow velocity V can be expressed as shown below by propagation time difference Δt.
V= ・ΔtC2
2LcosθAlso by using arithmetic average t0 of tu and td for sonic velocity C, the arithmetic expression of flow velocity can be expressed as shown below.
V= ・ΔtL
2(t0-τ)2cosθFlow velocity V obtained here is the average flow velocity on the measurement line between sensors; therefore, it is different from average flow velocity V at the cross section of the pipe. Accordingly, flowrate Q is then given by the following equation by using flowrate compensation coefficient k.
Q= ・AV・A=Vk
Transmission method and Reflection method
In case of V method (reflection method), the length of propagation path is twice that of Z method (transmission method); therefore, the propagation time is set longer and is more advantageous in measurement accuracy. However, which method to be adopted shall be determined by the bore size, piping material, etc.
Sensor end P1 P1 P2
Sensor end P2Z method (transmission method) measurement
V method (reflection method) measurement
V VL
θ θ θPipe undermeasurement
�
GBM006E-2Psonic-S1
STANDARD SPECIFICATIONS Sensor Specifications
Item Description
Applicable fluids
Homogeneous fluids where ultrasonic wave can propagate (clean water, waste water, industrial water, river water, ocean water, purified water, etc.)Turbidity: 10000mg/L (degree) max.Note) The fluid must not contain bubble. Note) Cannot support slurry.Note) For application to fluid other than water, contact OVAL office.
Fluid temp. range -20 to 60°C (fluid and ambient)Nominal size 25mm to 600mm
Piping materials
Steel pipe, SUS pipe, polyvinyl pipe, ductile cast-iron pipe, copper pipe, or other pipe made of material that can transmit ultrasonic wave steadily※1: Maximum applicable bore size may not satis by the requirement depending on the material or status of piping.※2: In case of lining pipes, the lining must contact with the main pipe.(Lining material is tar epoxy or mortar, or the like.)
Flow metering range 0 to ±10m/sNumber of metering lines 1 line
Metering system Ultrasonic pulse transmission time difference system
Factory calibration accuracy
25mm to 40mm ±2.5% of reading (±0.025m/s at a flowrate less than 1m/s)50mm to 90mm ±2.0% of reading (±0.020m/s at a flowrate less than 1m/s)100mm to 250mm ±1.5% of reading (±0.015m/s at a flowrate less than 1m/s)300mm to 600mm ±1.0% of reading (±0.010m/s at a flowrate less than 1m/s)
Note) Specification when measures volume flow.Note) The pipe must be full of liquid and the flowrate distribution must be ideal.Note) The flowrate must be 0.3m/s or more with specified length of straight pipe secured.
Sensor material Resin (PBC, PMMA)Protection class Standard: IP65 (Option: IP67)
Transmitter SpecificationsItem Description
Transmitter mounting configuration Separately mounted type
Power supply Standard: AC100 to 230V ± 10%, 50/60Hz ± 2HzOption: DC24V ± 20%
Power consumption 19VA max. at 100VAC, 23VA max. at 200VAC, 9W max. at 24VDCOperating temp. range -10 to +50°COperating humidity range 90%RH max. (without dew condensation)
Protection class IP65Installation environment Direct sunlight, radiation heat, corrosive atmosphere, and explosive atmosphere must be avoided.
Housing material ABS resin (Color: white gray)
Analog output
Number of channels 1 channelOutput content Instantaneous flowrate
Output type 4 to 20mA, 20.8mA at burnoutMax. allowable load resistance: 600Ω, insulated output
Output accuracy ±0.2%F.S.
Contact output
Output content Contact pulse, alarm, forward and reverse flow judgmentOutput type Photocoupler outputContact capacity DC48V, 0.4AMax. output rate 25Hz (Selected from among pulse widths 20, 100, 500, and 1000ms)
USB communicationFunctions Sets flowmeter by PC communication software (UFWconfig). Displays measurement value,
Displays receiving waveform, Reads log dataUSB cable length 3m max.Connector USB B terminal (hot plugging available)
Optional input (1) Analog input: 4 to 20mA, 1 output(2) Digital communication: RS-485 (MODBUS-RTU), Transmission length: 1km max.
Functions
(1) Logging function: Instantaneous mass flow, Instantaneous flowrate, Forward and reverse total value, Measurement status, Error status, etc. Period: 0 to 3600s (Initial value: 60s)
(2) Low flowrate cutoff: Settable at option (Initial value: 0)(3) Self diagnostic function(4) Simulated output: Analog current output, Total pulse count output
Display 16-digit, 2-line LCD display with backlightInstantaneous mass flow, Flowrate, Forward total flowrate, Reverse total flowrate, Status code, etc.
Explosionproof specifications Nonexplosionproof
�
GBM006E-2Psonic-S1
DEVICE DIFFERENCE CHARACTERISTICS(Reference) Nominal size: 300 to 600mm
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0
-0.5
-1.0
-1.5
-2.0
-2.5
-3.0
-3.5
-4.0
-4.5
-5.00 1 2 3 4 5 6 7 8 9 10
Flow velocity (m/s)
Range of factory calibration accuracy±1.0% of meter reading (±0.010m/s for flow velocity less than 1m/s)
Instrumental error (%)
PRODUCT CODE EXPLANATION
ItemCode No.
Description① ② ③ ④ − ⑤ − ⑥ ⑦ ⑧ ⑨ ⑩
Model U P S 1 − Ultrasonic flowmeter Psonic S1
Power supplyA − AC 100 to 230V ± 10%, 50/60Hz ± 2HzD − DC 24V ± 20% (※1)
Control No. 1 Always 1
Sensor2 IP65 sensor3 IP67 sensor (※1)
Sensor cable 3 30m x 2 pcs.
Option input/output
0 None1 Digital communication (RS-485 MODBUS-RTU)2 Analog input (1ch)3 Digital communication, Analog input
Optional parts
0 None1 PC communication software (※2)2 Mounting plate (For wall-mount, 50A stand pipe)3 PC communication software, mounting plate (For wall-mount, 50A stand pipe) (※2)
(※1): Same as code (9) and (10), optional item.(※2): PC communication software (UFWConfig) is available for Windows 7, Vista, and XP.
�
GBM006E-2Psonic-S1
Flow Range※ Reference value of maximum flowrate at each nominal size with pipe inner diameter = nominal size※ Actual maximum flowrate differs depending on the inner diameter of the pipe to be used.
Transmitter
Power supplyAC100 to 230V±10% 50/60Hz ±2HzDC24V±20% (Option)
Analog output (DC4 to 20mA)(Max. allowable load resistance 600Ω)
DC4 to 20mA current receiving device such as indicator and recorder
Integration counter, etc.(Selected by integration, alarm, etc.)
MODBUS-RTU compliant device
Setting, monitoring, etc. by PC communication software
Contact output (no-voltage contact)(Contact capacity 48V, 0.4A)
Digital communication* Option (RS-485)
Pressure gauge, etc.Analog input (DC4 to 20mA)
Input resistance: 300Ωmax.Max. allowable input current: 25mA( )
* Option
USB communicationCable length: 3m max.
Upstream side
Flow direction
Downstream side
Sensor
Coaxial cable30m max.
Mounting bracket
BASIC CONFIGURATION
Nominal size (mm) Max. flowrate (m3/h)
25 17.640 45.250 70.665 11980 180
Nominal size (mm) Max. flowrate (m3/h)
100 282125 441150 636200 1130250 1760
Nominal size (mm) Max. flowrate (m3/h)
300 2540350 3460400 4520500 7060600 10100
�
GBM006E-2Psonic-S1
(226)
210
170
(296
)
251
218
4-External mounting foot (Accessory)
4.6 x 22.8 long hole
(119)
35
3083
20
65
Stainless beltSensor mounting by stainless belt (65mm or more)
Sensor mounting by thumbscrew (50mm or less)
188
75
135
Clamping device
Holding fixture
Thumbscrew
Coaxial cableSensorRetaining plate
44
36
34
32
(34)
DIMENSIONS (Unit: mm)
Transmitter
Sensor Sensor mount※ Which mounting method, V method or Z method, to be adopted is determined
by bore size, piping material, etc.
�
GBM006E-2Psonic-S1
CONNECTION AND WIRING SPECIFICATIONS Appearance of Terminal Unit
Terminal assignmentName Terminal No. Description
Power Input AC-IN L, NTB1
AC power input (Connect "N" to ground and "L" to ungrounded side.)Power Input DC-IN +, − DC power input (Optional)
Protective Earth Protection grounding terminal With AC power specifications, power cable connected to grounding wire
Functional Earth Functional grounding terminal With DC power specifications, power cable connected to grounding wire
Contact Output +, − TB2 Contact output4-20mA Output +, − TB3 Analog outputAnalog Input +, − TB4 Analog input (Optional)RS-485 +, −, Shild TB5 TB6 RS-485 (MODBUS-RTU) output
Transducer Cable Up, Down − Connection to sensor. Upstream sensor connected to "UP" and downstream sensor to "Down"
Analog output terminal
TB3 4-20mA Output
TB3
Analog input terminal
TB4Analog Intput
TB4
* Option
RS-485 terminal
TB5, TB6
Contact Output
TB5
* Option
TB6
Contact output terminal
TB2
TB1
Power input terminal (depending on spec.)
TB1
AC power specification
RS-485
DC power specification
Power Input
Power Input
TB1
Functional grounding terminal
Protection grounding terminal (depending on spec.)
AC power specification
Functional grounding terminal
DC power specification
Sensor end terminal
Left: Up side, Right: Down side
Transducer Cable
�
GBM006E-2Psonic-S1
Precautions on Wiring(1) The cable grounding holes under the transmitter case are blocked by "seal pins" at the time of shipment. Remove the seal
pin from the hole as necessary when wiring is required.
The typical tightening torque for connecting cable ground is 1.5N・m.
(2) Turn off the main power before starting wiring.(3) Isolate the coaxial cable used for connection between transmitter and sensor from the power line or the like. Lay the
coaxial cable so that power equipment cannot approach it.(4) For the wiring between transmitter and external equipment, refer to page 6.(5) Connect the coaxial cable to the "Up" side of the upstream sensor and to the "Down" side of the downstream sensor.(6) Be sure to adopt the power supply for instrumentation. Never share the power supply with motive application.(7) Pay full attention to the polarity when implementing wiring.(8) Use shielded wires for power and output wirings.(9) Use the equipment in the grounding environment better than D class.
PRECAUTIONS ON INSTALLATION
Installing the TransmitterSelect the installation place in consideration of the following requirements.(1) Ambient temperature -10 to +50°C and away from heater or direct sunlight(2) A place not exposed to wind and rain for a long time(3) A place not exposed to dust and corrosive atmosphere(4) A place convenient for maintenance and check(5) A place where the distance between transmitter and sensor can be connected by the coaxial cable of 30m long(6) A place without a risk of inductive interference by power equipment and relevant wirings
Piping Layout (Reference)
同同同同同同同同同同同同
Transmitter
Sensor
Thick steel power line tube
(30m or less)
Flowmeter cabin (pit)
5D min. 10D min.
Flow
90°bent
(Note)
(Note)
Pipe (Inner dia. D)
Valve
Pump
Pump
Power supply
Output signal
(Note) If there are pump, valve, shrinkage pipe, expanding pipe, junction pipe or the like upstream or downstream of the flow, consult with OVAL office.
Cable trough
Output Pump
Coaxial cable
�
GBM006E-2Psonic-S1
Selecting the place to mount the sensorSelect the place in consideration of the following conditions.The performance of the ultrasonic flowmeter is greatly dependent on the mounting accuracy of the sensor. Pay full attention when installing the sensor.(1) Select the place for installing the sensor where the pipe is completely filled with fluid even if the flow is suspended.(2) Generally, straight pipe meeting the piping requirements and required straight pipe length shown in page 9 is required
upstream and downstream the mounting location of the sensor.(3) Select the piping place where there is little obstruction in the flow. If there are factors that may cause disturbance in the flow such as pump, valve, shrinkage pipe, expanding pipe, joint pipe
or the like in the upstream or downstream of the pipe, consult with OVAL office.(4) In some case, air pocket or deposit may exist just above and below the measurement pipe. Avoid these places when
installing a sensor. Also avoid a junction place such as flange or welded part and select the flat and smooth surface of the pipe as much as
possible.(5) When installing the sensor, select the place where ambient temperature is -20 to 60°C and away from heat generating
equipment and not exposed to direct sunlight.(6) When installing the sensor, avoid the environment that may be exposed to wind and rain for a long time. Otherwise,
deterioration in the performance of the sensor may be accelerated.
Problem Piping condition Remarks
Air pocketPoorly filled pipe
When rising piping is used, installing the sensor at the places (2) and (3) may cause air pocket or poorly filled pipe, resulting in measurement error.Install the sensor in the place of (1).
Poorly filled pipeIf the downstream side of the sensor location is open to the air, poorly filled pipe may be caused.
DepositIf there is deposit or accumulation in the sensor location, measurement error may occur.
Air trappingIf air trapping occurs in the tank located upstream the sensor position, poorly filled pipe may be caused.
Flow direction
Flow direction
Flow direction
Flow direction
Air pocket
② Improper③ Improper
Improper
Improper
Open
①
Improper
Deposit
�
GBM006E-2Psonic-S1
Category Upstream side straight pipe length Downstream side straight pipe length
�0°bent
Tee
Expanding pipe
Shrinkage pipe
Valves
Pump
[D is nominal size of a pipe.]
10D以上
10D以上
0.5D以上
1.5D以上
D
10D以上
L>=10DL>=5D
L>=5D
L>=5DL>=10D
L>=50D
L>=10DL>=30D
L>=10DL>=50D
L>=30D
検出器
仕切弁逆止弁
P
STRAIGHT PIPE LENGTH REQUIRED
Sensor
10D min.
10D min.
10D min.
1.5D min.
Gate valveCheck valve
0.5D min.
10
GBM006E-2Psonic-S1
PC COMMUNICATION SOFTWARE
By the use of PC communication software, setup, changing various kinds of setting information, waveform monitoring, etc. are available with this flowmeter. Here, outline of the major functions is introduced.
You can read, display, and save the log data as a file from the flowmeter. On the display, you can check the instantaneous flowrate, instantaneous flow velocity, forward and reverse integrated value, measurement status, error status, and analog value every day and hour and select any data row for graph display.
You can check the receiving waveforms of ultrasonic waves in the UP side and DOWN side, respectively. In addition, the peak value of the receiving waveform is indicated by level to facilitate judgment on whether ultrasonic wave reception is good or bad.The gain value is adjusted to the most appropriate value by the automatic gain control function.
(1) Measurement information of flowmeterYou can read instantaneous flowrate, flow velocity, output status, measurement status, error code, and gain value as measurement information in real time.
(2) Trend graph of measurement valueTrend graph can be displayed.With horizontal axis as measurement time, you can set the vertical axis at your option from the following items.(Forward and reverse flow integrated value, reverse flow integrated value, instantaneous flowrate, instantaneous flow velocity, and analog value)
(1) Setup wizardInitial setting is available by the entry of various kinds of information on specifications as guided by the setup wizard.
(2) Individual settingApart from the setup wizard, checking and changing the parameters and saving and reading the set parameters are possible.
Checking the measurement status
Checking receiving waveform
Log data
Various kinds of settings
Transmitter USB port connector
Specifications required by PCOperating System: Windows7, Vista, XPPort: USB port
11
GBM006E-2Psonic-S1
OPTION Sunshade cover for sensor
This is a sunshade cover for protecting the plastic sensor against direct sunlight when the instrument is installed outdoors.
Specifications of pipe integrated type : Shipment with piping (inline type) is also possible. (Built-to-order production)
High-accuracy actual flow calibration and traceability are obtainable with the inline type.
Various kinds of customization are available as required for piping. Contact OVAL representative.
・Available piping specifications Nominal size : 25 to 200 mm
Material : Stainless steel, Steel, PVC
Category : JIS pipe (product with lining is available)
Sunshade cover for sensor
Configuration example of pipe integration type :
195
M4 screw
Support rod Sunshade cover
Holder
86
55 (59.
5)
GBM006E-2Psonic-S1
The specification as of Mar., 2013 is stated in this GS Sheet. Specifications and design are subject to change without notice.
Sales Representative:
初版 改訂 印刷12.05 13.03
GS.No.GBM006E
1. Purpose of use
2. Fluid to be measured (※)
□ Water
□ Other ( )
When you select Other, write the property value of the fluid used regularly below.
・Sonic velocity of fluid ( m/s) ・Density of fluid ( kg/m3) ・Dynamic viscosity ( mm2/s)
3. Applicable pipe (※)
(1) Bore size
□ 25mm □ 40mm □ 50mm □ 65mm □ 80mm □ 100mm □ 125mm □ 150mm □ 200mm □ 250mm □ 300mm □ 350mm □ 400mm □ 500mm □ 600mm □ Other ( )
(2) Material
□ Steel pipe □ SUS pipe □ Polyvinyl chloride □ Ductile cast iron pipe □ Copper pipe □ Other ( ) If you select Other, write the sonic velocity of the pipe used regularly below. ・Sonic velocity of pipe ( m/s)
(3) Lining
□ None □ Epoxy □ Mortar □ Rubber □ PVC □ Other ( ) When you select Other, write the sonic velocity of the lining used regularly below. ・Sonic velocity of lining ( m/s)
(4) Actual measurement value ( * )
・Pipe outer diameter ( mm) ・Pipe thickness ( mm) ・Thickness of lining ( mm)
(5) Sensor mounting method
□ V method □ Z method
4. Condition for use Min. Regular Max.
(1) Flow range (※)(2) Flow velocity range m/s m/s m/s(3) Fluid temp. (※) °C °C °C(4) Fluid pressure MPa[G] MPa[G] MPa[G](5) Ambient temp. °C °C °C(6) Ambient humidity % RH % RH % RH
5. Unit (※)
(1) Unit of flow
Unit of flow (Numerator) : □ L/ □ m3/ □ g/ □ t/ Unit of flow time (Denominator) : □ /s □ /min □ /h □ /D
(2) Unit of integration (Pulse weight) : ( ) □ L □ m3 □ g □ t
6. Output signal (※)
(1) Analog output □ Used □ Not used
・4mA flow value ( ) ・20mA flow value ( )
※Settable range: −99999 ~ +999999
※Unit of flow is the same as the unit of flow in item 5 (1).
(2) Contact output □ Used □ Not used
・Detail of contact output □ Always open □ Always closed □ Forward integrated pulse □ Reverse integrated pulse □ No wave alarm □ Failure alarm □ No wave and failure alarm □ Forward and reverse judgment output
※Integrated pulse width
□ 20ms □ 100ms □ 500ms □ 1000ms ※Max. output frequency = 25Hz
・Inversion of contact
□ OFF □ ON ※OFF: a contact operation, ON: b contact operation
7. Alarm (※)
□ Used □ Not used ・Upper alarm level ( ) ・Lower alarm level ( ) ※Settable range: −99999 ~ +999999
※Unit of flow is the same as the unit of flow in item 5 (1).
8. Low flow cutoff (※)
□ Used □ Not used ( )
※Settable range: −99999 ~ +999999
※Unit of flow is the same as the unit of flow in item 5 (1).
9. Selecting option ※ Multiple choice permitted
□ DC power supply spec.: 24VDC±20% □ PC comm. software: UFW config □ Analog input: 4 to 20mA, 1 input □ Parameter setting: Major parameters are set by OVAL. □ Digital communication: RS-485 (MODBUS-RTU) output
10. Remarks
When you make inquiries, please state the following:(Fill in the blanks or check □ with mark.) ※ When you select "Parameter setting" for option, be sure to full in the place marked (※).