    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

  • 8/12/2019 Gen Protn Philosophy&Settings

    2/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    CLASSIFICATION OF TRIPPING

    CLASSIFICATION OF TRIPPING

    Objective is to trip only the absolutely essential so that

    - Damage is minimum

    - Overspeeding of the TG due to sudden load throw off is avoided

    - Impact of tripping of large set on the grid is minimum

    - Auxiliaries if possible are kept energised and time to restart the unit is

    minimum

  • 8/12/2019 Gen Protn Philosophy&Settings

    3/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    CLASS-A TRIPPING

    CLASS-A TRIPPING

    This is adopted for those electrical faults of Generator and Generator

    transformer and unit auxiliary transformer for which tripping can not

    be delayed.

    This leads to simultaneous tripping of

    - Generator Transformer HV side CB

    - Field Circuit Breaker

    - LV side incomer breakers of UAT

    - Auto changeover from unit to station for unit auxiliaries and

    tripping of turbine

  • 8/12/2019 Gen Protn Philosophy&Settings

    4/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    CLASS-B TRIPPING

    CLASS-B TRIPPING

    This is adopted for all turbine faults (Mechanical) and for some

    electrical faults of Generator, Generator transformer and unit auxiliary

    transformer for which it is safe to trip the turbine.

    Subsequently the Generator is tripped through low forward power

    interlock

    Ensures that unit does not overspeed due to trapped steam in the

    turbine during the shutdown and also the loss of power to the grid from

    the Generator is not sudden.

  • 8/12/2019 Gen Protn Philosophy&Settings

    5/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    CLASS-C TRIPPING

    CLASS-C TRIPPING

    This is adopted for all faults beyond the Generator system which can be

    cleared by tripping of Generator transformer HV side CB alone.

    In this case the TG set runs with HP-LP bypass system in operation and

    the Generator continues to feed the unit auxiliary load through unit

    auxiliary transformers.

  • 8/12/2019 Gen Protn Philosophy&Settings

    6/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    Class CGenerator Pole slipping Relay

    Without Under voltageClass BGenerator Field Failure Relay

    I stage alarmClass B II stageGenerator Rotor Earth Fault Relay

    I stage alarmClass C After some

    time (say 30mins) II stage

    Generator Under frequency Relay

    I stage alarmClass BGenerator Transformer Overfluxing Relay

    Class AGenerator Stator E/F Relay (95%)

    Class AGenerator Stator E/F Relay (100%)

    Class AUnit Overall Differential Relay

    Class AGenerator Transformer Differential Relay

    For interlock in Class B

    tripping

    Generator Low Forward Power Relay

    Class AGenerator Differential Relay

    REMARKSTRIPPING MODEPROTECTIVE RELAY

    TYPICAL CLASSIFICATION OF TRIPPING

    TYPICAL CLASSIFICATION OF TRIPPING

  • 8/12/2019 Gen Protn Philosophy&Settings

    7/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    I-stage alarmClass C II-stageGenerator Transformer Winding Temperature Device

    Class AUnit Auxiliary Transformer H.V. side O/C Relays (Backuup)

    I-stage alarmClass A II-stageGenerator Transformer Buchholz Relay

    For alarmGenerator Definite time O/C Relay

    I-stage alarmClass CGenerator Negative Sequence Current Relay

    Class AUnit Auxiliary Transformer Differential Relay

    Class BGenerator Transformer H.V. side Backup E/F relay

    Class CGenerator Transformer H.V. side Backup O/C relay

    Class AGenerator Voltage Restrained Relay

    Class CGenerator Distance Backup Impedance Relay

    I-stage alarmClass C II-stageGenerator Transformer Oil Temperature Device

    Class AGenerator Reverse Power Relay

    REMARKSTRIPPING MODEPROTECTIVE RELAY

    TYPICAL CLASSIFICATION OF TRIPPINGTYPICAL CLASSIFICATION OF TRIPPING

  • 8/12/2019 Gen Protn Philosophy&Settings

    8/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    TYPICAL CLASSIFICATION OF TRIPPINGTYPICAL CLASSIFICATION OF TRIPPING

    AlarmUnit Auxiliary Transformer(s) Oil Level Device

    I-stage alarm

    II-stage-trip unit switch

    gear incomer breaker(s)

    and Auto change-over.

    Unit Auxiliary Transformer(s) Oil Temperature

    Devices

    I-stage alarm

    II-stage-trip unit switch

    gear incomer breaker(s)

    and Auto change-over to

    station service

    Unit Auxiliary Transformer(s) Oil Temperature

    Device(s)

    I-stage alarmClass CUnit Auxiliary Transformer Buchholz Relay(s)

    AlarmGenerator Transformer Oil Level Device

    REMARKSTRIPPING MODEPROTECTIVE RELAY

  • 8/12/2019 Gen Protn Philosophy&Settings

    9/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    TYPICAL GROUPING OF RELAYSTYPICAL GROUPING OF RELAYS

    GROUP-I

    - Generator Differential Relay

    - Generator Transformer Differential Relay

    - Generator Stator Earth Fault Relay for protection of 100% stator winding

    - Generator Over-voltage Relay

    - Generator Underfrequency Relay

    - Generator Rotor Earth Fault Relay

    - Generator Field Failure Relay

    - Generator Low Forward Power Relay

    - Generator Reverse Power Relay

    - Generator voltage restrained O/C Relay

    - Generator Transformer HV side O/C Relay (for backup protection)

    - Unit Auxiliary Transformer(s) Differential Relay(s)

    - Generator Negative Phase Sequence Current Relay

  • 8/12/2019 Gen Protn Philosophy&Settings

    10/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    TYPICAL GROUPING OF RELAYSTYPICAL GROUPING OF RELAYS

    GROUP-II

    - Unit overall Differential Relay

    - Generator Stator Earth Fault Relay for protection of 95% startor winding.

    - Generator Transformer Overfluxing Relay

    - Generator Overvoltage Relay.

    - Generator Rotor Earth Fault Relay.

    - Generator Field Failure Relay.

    - Generator Pole Slipping Relay.

    - Generator Low Forward Power Relay.

    - Generator Reverse Power Relay.

    - Generator Distance Backup Relay.

    - Generator HV standby Earth Fault Relay.

    - Unit Aux Transformer(s) H.V. side overcurrent Relay (for back up protection)

    - Generator Negative Phase Sequence Current Relay.

    - Generator definite time over-current Relay.

  • 8/12/2019 Gen Protn Philosophy&Settings

    11/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

  • 8/12/2019 Gen Protn Philosophy&Settings

    12/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    GeneratorData :

    Rated MVA : 247 MVA

    Rated kV : 15.75kV

    Full load current : 9065A

    Sub-transient Reactance Xd : 21.4%

    Neutral Grounding Transformer :

    25 kVA, 15.75 kV/240 V, Resistor: 0.5 ohms, 280A.

    Field Circuit Voltage : 600V

    Negative Sequence Particulars :

    1) A symmetrical short circuit performance is given by 12t 2) Continuous negative sequence withstand current of generator-5%

    which implies that maximum difference between the line current

    is about 10%.

    SYSTEM DETAILSSYSTEM DETAILS

  • 8/12/2019 Gen Protn Philosophy&Settings

    13/52

  • 8/12/2019 Gen Protn Philosophy&Settings

    14/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    b) 400 kV side CT : 500/ 1 A, RCT= 3 , Vk=1000 V

    class PS, star connection

    c) Neutral side CT : 500/1 A, PS, Vk=1000 V,RCT=3

    3) RLLead resistance : One way lead resistance of 15 m, 2.5 mm2

    single cable is 0.1 (looping done in CT

    Marshalling box)

    SYSTEM DETAILSSYSTEM DETAILS

  • 8/12/2019 Gen Protn Philosophy&Settings

    15/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    Relay particulars:

    Type : RAGEA

    RXIG 95% Relay : 5-15V; 50 Hz.

    RXIG 100% Relay : 0.4-1.2V, 150 Hz.

    RXEG Supervision Relay : 40-120 V

    RXKE1 for 95% Element : 20ms-99s

    RXKE1 for 100% Element : 20ms- 99s

    Auxiliary Voltage : 220 V DC

    GENERATOR 100% EARTH FAULT RELAYGENERATOR 100% EARTH FAULT RELAY

  • 8/12/2019 Gen Protn Philosophy&Settings

    16/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    Calculations:

    95% Element:

    When a fault occurs on the high voltage side of a / Y step-up transformer,There is no voltage

    displacement of the generator neutral due to Zero Sequence currents. But still a small generatorneutral voltage exists for an External ground fault due to a small capacitive coupling between

    primary and secondary of the generator step-up transformer. If the data to Calculate this small

    neutral voltage is not available, then relay sensitivity Is restricted to about 4-5%.

    Also, the 95% relay of RAGEA is suitable for operation at lower frequency and thus can act as a

    reliable earth fault protection during start-up. It Operates with increased sensitivity down to about

    25 Hz, the operating value being about 0.6x set voltage. At still lower frequency of 10Hz, the relay

    operates at 0.8 x set voltage.

    Secondary side voltage of grounding transformer for a fault on generator terminal is 240/ 3 = 138V.

    From experience it is found that, a setting of 5.4 V of the voltage gives adequate discrimination

    against such faults.

    GENERATOR 100% EARTH FAULT RELAYGENERATOR 100% EARTH FAULT RELAY

  • 8/12/2019 Gen Protn Philosophy&Settings

    17/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    Time delay setting need to be selected considering PT fuse operating time in case of a fault ongenerator PT. This delay also gives stability against relay picking up from stray voltages.

    Delay of about 1-2 secs is recommened.

    100% Element:

    Setting of this relay is approx. 50% of 3rdharmonic voltage measured across the Generator

    grounding transformer.

    Typical value of this 3rdharmonic voltage = 1-2V

    Setting should be adjusted at site depending on actual measured value.

    Time delay of 2 secs. Can be set.

    Supervision Relay:

    This is usually set about 80% of rated voltage, approx. 90 V.

    GENERATOR 100% EARTH FAULT RELAYGENERATOR 100% EARTH FAULT RELAY

  • 8/12/2019 Gen Protn Philosophy&Settings

    18/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    Recommended Settings :

    95% Relay : 5.4 V,1 sec.

    100% Relay : 0.5 V, 2 sec.

    Supervision Relay : 90 V

    GENERATOR 100% EARTH FAULT RELAYGENERATOR 100% EARTH FAULT RELAY

  • 8/12/2019 Gen Protn Philosophy&Settings

    19/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    Rated MVA = 247 MVA

    Rated kV = 15.75 kV

    Rated Load Impedance = 15.75/ 247 = 1.0043 prim.

    CTR / PTR = ( 10000 / 5 ) / ( 15.75 x 10/ 110 ) = 13.97

    Setting of RAKZB = 70 % of Rated Load Impedance

    = 0.7 x 1.0043 x 13.97 = 9.82sec.

    Forward Reach = Reverse Reach

    ZF= ZR= 9.82 sec.

    ZF= ZR= ( 0.2 f / la 3 ) x ( A / B ) f = 50 Hz. Ia= ln= 5 A

    ( A / B ) = 8.5

    Choose A = 80, then B = 9.4

    GENERATOR BACK-UP IMPEDANCE PROTECTION-RAKZBGENERATOR BACK-UP IMPEDANCE PROTECTION-RAKZB

  • 8/12/2019 Gen Protn Philosophy&Settings

    20/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    Type : RXNB

    Operating Value : Approx. 5 Kat Ux = 0 V and

    : Approx. 245 Kat Ux = 600 V

    The relay operates for an insulation resistance Rxdependent upon Uxwhen

    ( ( Ux+ 48 ) / 2.5 ) 14 K= Rx

    U1 : supply Voltage

    Um : Super imposed voltage between the negative pole of the field

    winding and the earth

    Ux : Field voltage between the fault location & negative pole of the field wdg.

    Rx : Insulation Resistance between the field windind & the earth at the fault

    location.

    Ij : Current in the measuring circuit.

    ROTOR EARTH FAULT RELAY- RXNBROTOR EARTH FAULT RELAY- RXNB

  • 8/12/2019 Gen Protn Philosophy&Settings

    21/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    ROTOR EARTH FAULT RELAY- RXNBROTOR EARTH FAULT RELAY- RXNB

  • 8/12/2019 Gen Protn Philosophy&Settings

    22/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    Delay on pick-up : Approx. 11sec.

    Maximum permissible

    Field circuit voltage : 600V continuous, 1500v for 9 sec Bias circuit voltage : 240VK10%, 50Hz.

    Auxiliary voltage : 240V DC

    Recommended settings :

    The relay has fixed settings as described.

    ROTOR EARTH FAULT RELAY- RXNBROTOR EARTH FAULT RELAY- RXNB

  • 8/12/2019 Gen Protn Philosophy&Settings

    23/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    GENERATOR NEGATIVE SEQUENCE PROTECTION (RARIB)GENERATOR NEGATIVE SEQUENCE PROTECTION (RARIB)

    Relay particulars:

    Type : RARIB

    Operating according to t : (In / I2) K where In = rated primary current of Auxiliary CT

    K = 1-63secs.

    Operating value start : 4-16%

    Alarm element : 3-9%

    Time delay of alarm : 6secs.

    Cooling down time : (K x 170)/2 where a is a constant which is internally

    reconnectible in complete steps between 0 and 6

    Auxiliary Voltage : 220 V DC

    CT details : 10000/5A

  • 8/12/2019 Gen Protn Philosophy&Settings

    24/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    GENERATOR NEGATIVE SEQUENCE PROTECTION (RARIB)GENERATOR NEGATIVE SEQUENCE PROTECTION (RARIB)

    Calculations:

    Secondary current corresponding to full load = 4.53A

    Setting IM= (4.53/5) x In= 0.906 Inwhere Inis set to 5A.

    Recommended settings:

    IM = 0.906 x 5AK = 8 on relay (System Details)

    Alarm relay = 4% of IM

    Trip relay = 8% of IM

    Time lag relay for delayed alarm : 6secs.

    Cooling down time constant : 2.6 x K

    In the absence of valid data of the machine, this has been set at the lowest value.

    This is not field adjustable.

  • 8/12/2019 Gen Protn Philosophy&Settings

    25/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    GENERATOR DIFFERENTIAL RELAYGENERATOR DIFFERENTIAL RELAY

    Relay Particulars :

    Type : RADHA

    Rating : 5A

    Operating Voltage : 40/50V

    Operating Current : 20mAAuxiliary Voltage : 220V DC

    System Details :

    CT Details : 10000/5A, RCT=1.5

    Vk=600V

    CT lead resistance RL : Pilot wire loop resistance from CT to interconnection point

    of CT leads at Bus duct=0.2 (One way length is 15m,

    2.5mmcs)

  • 8/12/2019 Gen Protn Philosophy&Settings

    26/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    GENERATOR DIFFERENTIAL RELAYGENERATOR DIFFERENTIAL RELAY

    Calculations:

    1) Maximum through fault current = 1/Xd = 1/0.214=4.67 pu

    Base Current = 9.065KA If= 4.67 x 9.065KA = 42.33KA

    CT sec. Current Ik= 21.2A

    Maximum rms voltage that will develop across the relay for this through fault

    current = Ik(RCT+RL)

    = 36.04V

    Normally a setting of 110% of this voltage will provide full stability against external

    fault.

    1.1 x 36.04 = 39.65V

    A relay version of 40-50V to be selected & to be set at 40 V

    Minimum knee point voltage requirement : Vk= 2 x 40 = 80V

    Minimum Primary operating current : Ip= n1(IR+ Im+ Ires)

  • 8/12/2019 Gen Protn Philosophy&Settings

    27/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    GENERATOR DIFFERENTIAL RELAYGENERATOR DIFFERENTIAL RELAY

    Where IR = Relay operating current = 0.02A

    Im = Magnetising current of CT at set value

    = 0.005 A (assumed)

    Ires = 5mA for MXA 983-B at 70V

    Ip = 10000/5 (0.02 + 0.05 + 0.005) = 150A

    Recommended settings:

    40 V

  • 8/12/2019 Gen Protn Philosophy&Settings

    28/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    LOSS OF EXCITATION RELAY (RAGPC)LOSS OF EXCITATION RELAY (RAGPC)

    Relay particulars:

    Type : RAGPC

    Rating : 5A

    Scale Ranges : RXPE40 Directional Relay : 1-4A

    : RXIG Overcurrentl Relay : 2.5-7.5A

    : RXEG2 Under Voltage Relay : 40-120V

    System Particulars:

    The generator is capable of delivering 247 MVA continuously at 15.75kV terminal

    voltage, 9065 A stator current and 3 kg/cmhydrogen pressure with cold gastemperature not exceeding 40C and distillate termperature at inlet of stator wdg notexceeding 40C. The generator capability curve is as per enclosed diagram.

    CT Details : 10000/5A, RCT=1.5 , Vk=600V, Class : PS

  • 8/12/2019 Gen Protn Philosophy&Settings

    29/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    LOSS OF EXCITATION RELAY (RAGPC)LOSS OF EXCITATION RELAY (RAGPC)

    PT Details : 15.75kV /110V, 200VA, 3P / 0.5M

    Calculations:

    The characteristic of RXPE40 unit super- imposed on generator capability curve is

    shown in the diagram. The setting of RXPE should correspond to about 70 MVA

    as can be seen from the diagram.This corresponds to a secondary current of 1.28A.

    The undervoltage and overcurrent relays are usually set at about 85% of Unand 115%

    if Inrespectively.

    Recommended settings:

    For under voltage relay RXEG2

    Setting Range : 85-90% of Un(=110 V)

    Recommended Setting : 95V (86% of Un)

  • 8/12/2019 Gen Protn Philosophy&Settings

    30/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    LOSS OF EXCITATION RELAY (RAGPC)LOSS OF EXCITATION RELAY (RAGPC)

    2) For Overcurrent relay RXIG2

    Setting Range : 110-115% of In(=5A)

    Recommended Setting : 5.75A (115% of In)

    3) For Directional relay RXPE40

    Recommended Setting : 1.28A

  • 8/12/2019 Gen Protn Philosophy&Settings

    31/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    GENERATOR CAPABILITY CURVE & LOSS OF EXCITATION RELAY CH.GENERATOR CAPABILITY CURVE & LOSS OF EXCITATION RELAY CH.

  • 8/12/2019 Gen Protn Philosophy&Settings

    32/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    GENERATOR TRANSFORMER OVER-ALL DIFFERENTIAL RELAYGENERATOR TRANSFORMER OVER-ALL DIFFERENTIAL RELAY

    Relay particulars:

    Type : RADSB

    Rating : 5A

    Auxiliary Voltage : 220 V DC

    Restraint Operating value : Settable at 20, 25, 32, 40 or 50% of In

    Unrestraint Operating value : Reconnectible to 8, 13 0r 20 times In

    Calculations:

    For determining auxiliary Ct requirement

    In1on 15,75 kV side = (250 x 10) / (3 x 15.75)KA

    = 9164.56A

    In2on 420 kV side = (250 x 10) / (3 x 420)KA

    = 343.67A

  • 8/12/2019 Gen Protn Philosophy&Settings

    33/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    GENERATOR TRANSFORMER OVER-ALL DIFFERENTIAL RELAYGENERATOR TRANSFORMER OVER-ALL DIFFERENTIAL RELAY

    In1= (5/10000) x 9164 = 4.58A

    In2= (1/500) x343.7 = 0.687

    Ratio of auxiliary CT = 0.687 / (4.58/ 3 )

    = 0.687 / 2.64

    Vk=30 x In (RICTS) = 30 x (5/ 3) x RICTS

    = 30 x RICTS

    Setting Calculations:

    a) Operating current setting :

    Maximum tap changing position : 5%

    According to the designers recommendation a minimum current sensitivity of

    about 15% greater than the worst turns ratio mismatch at the tap changer should

    normally be selected.

  • 8/12/2019 Gen Protn Philosophy&Settings

    34/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    GENERATOR TRANSFORMER OVER-ALL DIFFERENTIAL RELAYGENERATOR TRANSFORMER OVER-ALL DIFFERENTIAL RELAY

    Therefore, for 5% variation of taps operating current setting of 20% gives enough

    margin for CT unbalance and other errors.

    b) Unrestricted operating current setting:

    This feature is to provide instantaneous tripping in the event of severe internal

    faults.

    Recommended unrestrained relay setting to take care of inrush currents on

    switching, from experience based on full load current equal to normal relay rating.

    In pratice such a situation arises in case of this transformer when an external

    close-in fault is cleared.

    13 % 13%

    When energised from

    HV side LV side

    Y-(LV) Any

    Transformer Transformer

    Connection Size

  • 8/12/2019 Gen Protn Philosophy&Settings

    35/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    GENERATOR TRANSFORMER OVER-ALL DIFFERENTIAL RELAYGENERATOR TRANSFORMER OVER-ALL DIFFERENTIAL RELAY

    Recommended settings:

    Maximum pick-up current setting = 20% of In

    Unrestrained operating current setting = 13 times In

  • 8/12/2019 Gen Protn Philosophy&Settings

    36/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    GENERATOR TRANSFORMER HV WINDING RESTRICTED EARTH

    FAULT RELAY

    GENERATOR TRANSFORMER HV WINDING RESTRICTED EARTH

    FAULT RELAYRelay particulars:

    Type : RADHD

    Rating : 1A

    Operating Voltage : 10/15V

    Operating Voltage : 20mAAuxiliary Voltage : 220V DC

    Calculations:

    Maximum through fault current = (250 x 1) / (3 x 420 x 0.145)

    = 2370A

    If = 2370 / 500 = 4.74A

    Minimum relay = If (RCT+ 2RL) = 4.74 (3 + 0.2)

    Operating Voltage = 15.17V

  • 8/12/2019 Gen Protn Philosophy&Settings

    37/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    GENERATOR TRANSFORMER HV WINDING RESTRICTED EARTH

    FAULT RELAY

    GENERATOR TRANSFORMER HV WINDING RESTRICTED EARTH

    FAULT RELAY

    Thus, setting can be = 15V

    Minimum Knee point voltage of CT = =2 x 15V = 30V

    Recommended settings:

    Voltage setting = 15V

  • 8/12/2019 Gen Protn Philosophy&Settings

    38/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    GENERATOR TRANSFORMER OVER-FLUXING RELAYGENERATOR TRANSFORMER OVER-FLUXING RELAY

    Relay particulars:

    Type : RATUB

    Rating : 110V, 50Hz AC

    Setting Range : Start, Alarm 1.5 to 3V / Hz

    Calculations:

    Following are some comments regarding setting of RATUB

    1 ) Transformer can withstand 10% of rise in V /Hz continuously

    Therefore setting U/ f start can be selected as

    1.09 x (Un/fn) = 1.09 x (110/50) = 2.4V/Hz

    2) Plot of transformer U/f withstand characteristics on RATUB characteristics gives

    K = 2 as the one giving

  • 8/12/2019 Gen Protn Philosophy&Settings

    39/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    GENERATOR TRANSFORMER OVER-FLUXING RELAYGENERATOR TRANSFORMER OVER-FLUXING RELAY

    Operating times lower than transformer withstand time for rise in U/f up to

    1.35 x (Un/fn). Characteristics of transformer super-imposed on relay characteristics

    is shown in diagram.

    3) Beyond 1.35 x (Un/fn) rise in U/f operating time of RATUB varies from 6 to 2.2 secs at

    K=2, whereas transformer requires instantaneous tripping. Usually instantaneous

    element of O/V relay set suitably takes care of these conditions.

    4) Alarm unit can be set at same value as trip, 2.4V/Hz and time setting can be at

    3.5 secs.

    However if instantaneous tripping is desired from RATUB itself alarm unit can be

    used for this purpose in which case setting of this unit will be 1.35 x (Un/fn)=1.35 x

    (110/50) = 3V/Hz with delay set at 0.1 secs.

  • 8/12/2019 Gen Protn Philosophy&Settings

    40/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    GENERATOR TRANSFORMER OVER-FLUXING RELAYGENERATOR TRANSFORMER OVER-FLUXING RELAY

    Recommended settings:

    (U / f) start = 2.4V / Hz

    K = 2

    (U / f) alarm = 2.4V / Hz with time delay 3.5 secs.

  • 8/12/2019 Gen Protn Philosophy&Settings

    41/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    THE OPERATING TIME t AS A FUNCTION OF THE RELATIONSHIP BETWEEN THE ACTUAL

    EXCITATION ANS THE SET STARTING VALUE, FOR DIFFERENT TIME CONSTANTS K.

    THE OPERATING TIME t AS A FUNCTION OF THE RELATIONSHIP BETWEEN THE ACTUAL

    EXCITATION ANS THE SET STARTING VALUE, FOR DIFFERENT TIME CONSTANTS K.

  • 8/12/2019 Gen Protn Philosophy&Settings

    42/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    INTERTURN FAULT PROTECTIONINTERTURN FAULT PROTECTION

    Relay particulars:

    Type : RXIG28

    Range : 5-15V

    Aux PT details:

    PT-1 : 145.5V/200V, 3P, 15VA

    PT-2 : 3.25V/65V, 3P, 15VA

    Calculations:

    Voltage per turn per slot = 131.25V

    In case of split windings

    Vfor a single turn fault = 131.25/2=65.645V

  • 8/12/2019 Gen Protn Philosophy&Settings

    43/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    INTERTURN FAULT PROTECTIONINTERTURN FAULT PROTECTION

    VBA = 65.625 *(110/3) *[3/(15.74*10)]

    VCD = 0.46 *65/3.25 = 9.2V

    The relay can be set at 50% of the voltage developed across the relay for a single turn

    Fault.

    Recommended Setting:

    RXIG28 setting = 5V

  • 8/12/2019 Gen Protn Philosophy&Settings

    44/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    LIST OF REQUESTED PROTECTIVE FUNCTIONS * DIVIDED

    UP INTO TWO SYSTEMS

    LIST OF REQUESTED PROTECTIVE FUNCTIONS * DIVIDED

    UP INTO TWO SYSTEMS

    A B

    X

    X

    X

    X

    X

    X

    X

    X

    X

    Generator Differential

    Over all Differential

    Minimum Impedance

    (or alternatively)Overcurrent/Undervoltage

    (for thyristor excitation)

    (or option)

    Overcurrent

    Negative sequence

    Thermal90% Stator Earth Fault

    Neutral Disp.

    100% stator earth fault

    87G

    87T

    21

    51/27

    51

    46

    4959

    64

    Generator stator

    Short circuits

    Assymetry

    Stator overload

    Earth fault stator

    SYSTEMPROTECTION FUNCTIONSANSITYPE OF FAULT

  • 8/12/2019 Gen Protn Philosophy&Settings

    45/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    A B

    X

    X

    X X

    X

    X X

    X

    X

    X

    X X

    Mini reactance

    Pole slip

    Reverse power (double protection for large

    Generators)

    Max. frequency

    Min. frequencyOvervoltage or overcurrent

    Undervoltage

    Overfluxing Volt/Hz

    Overvoltage

    ThermalBridge measuring hardware combined with

    Voltage function

    40

    78/21

    32

    81

    8159

    27

    24

    59

    4964R

    Generator stator

    Loss of excitation

    Out of step

    Monitoring

    Over speed

    Blade fatigueInterturn fault

    Lower voltages

    Mag. Circuit

    Higher voltage

    Generator Rotor

    Rotor OverloadRotor ground

    SYSTEMPROTECTION FUNCTIONSANSITYPE OF FAULT

  • 8/12/2019 Gen Protn Philosophy&Settings

    46/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    Example : Definite list must be prepared in accordance with electrical scheme andinstallation requirements.

    A B

    X

    X

    X

    X

    X

    X

    X

    X

    X

    Transformer Differential

    Overcurrent

    Earth Fault Overcurrent

    Restricted Earth Fault

    Transformer Differential

    Overcurrent

    Overload

    Residual Overcurrent (possible option in

    acc. With requirements)

    Restricted Earth Fault (possible option in

    acc. With requirements)

    87T

    50/51

    51N

    87N

    87T

    50/51

    49

    (51N)

    (87N)

    Step-up Transformer

    Short circuit

    Ground Fault

    Unit Transformer

    Short circuit

    Ground Fault

    SYSTEMPROTECTION FUNCTIONSANSITYPE OF FAULT

  • 8/12/2019 Gen Protn Philosophy&Settings

    47/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    DATA REQUIRED FOR RELAY SETTING CALCULATIONS FOR

    GENERATOR PROTECTIONS

    DATA REQUIRED FOR RELAY SETTING CALCULATIONS FOR

    GENERATOR PROTECTIONS

    1) Generator differential protection 87G-RADHA:

    a) Sub-transient reactance Xd

    b) CT secondary resistance RCT

    c) Lead resistance from CT to junction point RL

    2) Differential protection 87L-RADHA:

    a) Sub-transient reactance Xd

    b) Transformer reactance XT

    c) CT secondary resistance RCT

    d) Lead resistance from CT to junction point RL

    3) 100% Earth fault relay 64G1-RAGEA:

    a) 3rdHarmonic voltage across secondary of grounding transformer.

  • 8/12/2019 Gen Protn Philosophy&Settings

    48/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    DATA REQUIRED FOR RELAY SETTING CALCULATIONS FOR

    GENERATOR PROTECTIONS

    DATA REQUIRED FOR RELAY SETTING CALCULATIONS FOR

    GENERATOR PROTECTIONS

    4) Generator Overvoltage relay - 59G-RXEG:

    a) Overvoltage withstand values of the generator.

    5) Generator Inter-turn fault relay 50GI-RXIG:

    a) Unbalance in current for 1 turn short circuit.

    6) Loss of Excitation relay 40G-RAGPC:

    a) The generator capability curve.

    b) Impedance locus during loss of excitation

    c) Variation in machine voltage & current on loss of excitation

    7) Negative sequence protection 46G-RARIB:

    a) K- A constant in seconds that is the characteristic for the generator

    This constant represents the time during which a negative

    sequence current that is equivalent to the rated current of the

    generator, can be permitted.

  • 8/12/2019 Gen Protn Philosophy&Settings

    49/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    DATA REQUIRED FOR RELAY SETTING CALCULATIONS FOR

    GENERATOR PROTECTIONS

    DATA REQUIRED FOR RELAY SETTING CALCULATIONS FOR

    GENERATOR PROTECTIONS

    b) Continuous negative sequence withstand value.

    8) Under-frequency protection- 81G-RXFE:

    a) Generator manufacturers recommendations regarding under frequency

    trip.

    9) Over current relay 51-RXIG:

    a) Continuous withstand current of the unit.

    10) Generator Backup Impedance relay 21G-RAKZB:

    a) Philosophy adopted for setting:

    - to cover only transformer

    - to cover next outgoing line but not beyond, under all

    generation conditions

    - to set for 70% of maximum load impedance.

  • 8/12/2019 Gen Protn Philosophy&Settings

    50/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    DATA REQUIRED FOR RELAY SETTING CALCULATIONS FOR

    GENERATOR PROTECTIONS

    DATA REQUIRED FOR RELAY SETTING CALCULATIONS FOR

    GENERATOR PROTECTIONS

    11) Pole slipping relay:

    a) Impedance locus during pole slip.

    12) Over-all differential relay 87GT-RADSB:

    a) RCT, Vkof main CT.

    b) RL, Lead Resistance.

    13) Restricted Earth fault relay 64GT-RADHD:

    a) RCTof the main CT.

    b) RL, Lead Resistance.

    14) Over fluxing relay 99GT - RATUB:

    a) Over fluxing characteristics of the transformer.15) Transformer Ground fault relay 51NGT-CDG:

    a) Plug setting.

    b) Time setting.

  • 8/12/2019 Gen Protn Philosophy&Settings

    51/52

    GENERATOR PROTECTION Combiflex R

    ABB India

    Utilities - Automation

    DATA REQUIRED FOR RELAY SETTING CALCULATIONS FOR

    GENERATOR PROTECTIONS

    DATA REQUIRED FOR RELAY SETTING CALCULATIONS FOR

    GENERATOR PROTECTIONS

    16) Station Transf. Differential relay 87UTA & 87UTB-RADSB:

    a) RCT, Vkof main CT.

    b) RL, Lead Resistance.

    17) Station Transf. Overcurrent relay 51UTA CDG33:

    a) Plug setting.

    b) Time setting.

  • 8/12/2019 Gen Protn Philosophy&Settings

    52/52

    GENERATOR PROTECTION Combiflex R

    ABB India