GE Molded Case Circuit Breakers TEYLine Circuit …...GE Molded Case Circuit Breakers K120 0 Line...

3
GE Molded Case Circuit Breakers * TEYLine Circuit Breakers 15-100 amperes 277 Vac, Single-Pole 250Vd.c 480Y/277 Vac, Two- and Three-Pole 60/7 5 °C Conductor Ratings UL listed as HACR type Bolt-On Mounting Base for TEY (For 1-, 2-, or 3-Pole) Description Accepts one three-pole or three single-pole breakers. Base assemblies stack together with no loss of one pole per inch spacing. Catalog Number TEY3B List Price, GO-1 35B $31.50 The TEY is a one-inch wide per pole, compact, "bolt-on" circuit breaker for use on grounded 480Y/277 Vac systems. The bolt-on mounting base, shown in the accessory table below, makes the TEY suitable for varied applications as a lug-lug breaker. UL Listed Interrupting Ratings (rms symmetrical kilo-amperes) System Voltage Single-pole Two-pole Three-pole 120 Vac 65 240 Vac 14 65 65 277 Vac 14 480Y/277 Vac 14 14 125 Vdc 10 10 250 Vdc 10 Ampere Rating 15 20 30 40 50 60 70 80 90 100 Single-Pole Catalog Number TEY115® TEY120® TEY130 TEY140 TEY150 TEY160 TEY170 TEY180 TEY190 TEY1100 List Price GO-135B $ 72.00 72.00 72.00 72.00 72.00 72.00 142.00 142.00 142.00 142.00 Two-Pole Catalog Number TEY215 TEY220 TEY230 TEY240 TEY250 TEY260 TEY270 TEY280 TEY290 TEY2100 Ust Price GO-135B $216.00 216.00 216.00 216.00 216.00 216.00 352.00 352.00 352.00 352.00 Three-Pole Catalog Number TEY315 TEY320 TEY330 TEY340 TEY350 TEY360 TEY370 TEY380 TEY390 TEY3100 List Price GO-135B $316.00 316.00 316.00 316.00 316.00 316.00 424.00 424.00 424.00 424.00 Internal Accessories For TEY (Two- and Three-Pole Breaker Only—Factory Installed Only) Auxiliary Switch, Single-Pole (6A at 240 Vac. 1 M at 1 25 Vdc, ViA at 250 Vdc, "A" switch (normally open) "B" switch (normally closed) "AB" switch (both) Shunt Trip 1 20-277 Vac control voltage Add suffix to Breaker Catalog Number ASIA AS1B ASAB ST12 List Price Adder, GO-135B $148.00 148.00 ' 288.00 358.00 Available Wire Ranges Circuit Breaker (load lug) 15, 20A 30-60A 70-1OOA Bolt-on Mounting Base, Cat. No. TEY3B (line lugs) #14, #12Cu #12, #10 Al #10-6Cu #8-4 Al #4-1 Cu #2-1/0 Al #14-1/0 Cu #12-1/0 Al CD Single-pole, 15 and 20 amp breakers are also UL listed as switching duty breakers, suitable for switching 120, 240, or 277 Volts ac. Prices and data subject to change without notice 1999 Issue 4-17

Transcript of GE Molded Case Circuit Breakers TEYLine Circuit …...GE Molded Case Circuit Breakers K120 0 Line...

GE Molded Case Circuit Breakers

* TEYLine Circuit Breakers15-100 amperes

277 Vac, Single-Pole250Vd.c

480Y/277 Vac, Two- and Three-Pole60/7 5 °C Conductor Ratings

UL listed as HACR type

Bolt-On Mounting Base for TEY(For 1-, 2-, or 3-Pole)

Description

Accepts one three-pole or threesingle-pole breakers. Base assembliesstack together with no loss of one poleper inch spacing.

CatalogNumber

TEY3B

ListPrice, GO-1 35B

$31.50

The TEY is a one-inch wide per pole, compact, "bolt-on" circuitbreaker for use on grounded 480Y/277 Vac systems. The bolt-onmounting base, shown in the accessory table below, makes theTEY suitable for varied applications as a lug-lug breaker.

UL Listed Interrupting Ratings(rms symmetrical kilo-amperes)

System Voltage

Single-poleTwo-poleThree-pole

120 Vac

65

240 Vac

146565

277 Vac14

480Y/277 Vac

1414

125 Vdc

1010

250 Vdc

10

AmpereRating

152030405060708090

100

Single-Pole

CatalogNumber

TEY115®TEY120®TEY130TEY140TEY150TEY160TEY170TEY180TEY190TEY1100

ListPrice

GO-135B

$ 72.0072.0072.0072.0072.0072.00

142.00142.00142.00142.00

Two-Pole

CatalogNumber

TEY215TEY220TEY230TEY240TEY250TEY260TEY270TEY280TEY290TEY2100

UstPrice

GO-135B

$216.00216.00216.00216.00216.00216.00352.00352.00352.00352.00

Three-Pole

CatalogNumber

TEY315TEY320TEY330TEY340TEY350TEY360TEY370TEY380TEY390TEY3100

ListPrice

GO-135B

$316.00316.00316.00316.00316.00316.00424.00424.00424.00424.00

Internal Accessories For TEY(Two- and Three-Pole Breaker Only—Factory Installed Only)

Auxiliary Switch, Single-Pole(6A at 240 Vac. 1M at 1 25 Vdc, ViA at 250 Vdc,

"A" switch (normally open)"B" switch (normally closed)"AB" switch (both)

Shunt Trip1 20-277 Vac control voltage

Add suffix toBreaker

Catalog Number

ASIAAS1BASAB

ST12

ListPrice Adder,

GO-135B

$148.00148.00

' 288.00

358.00

Available Wire RangesCircuit Breaker (load lug)15, 20A

30-60A

70-1 OOA

Bolt-on Mounting Base,Cat. No. TEY3B (line lugs)

#14, #12Cu#12, #10 Al

#10-6Cu#8-4 Al

#4-1 Cu#2-1/0 Al

#14-1/0 Cu#12-1/0 Al

CD Single-pole, 15 and 20 amp breakers are also UL listed as switchingduty breakers, suitable for switching 120, 240, or 277 Volts ac.

Prices and data subject to change without notice 1999 Issue 4-17

GE Molded Case Circuit Breakers

K1200 Line• Thermal Magnetic Circuit Breakers• Magnetic Breakers• Molded-Case SwitchesThese breakers are available only with interchangeable trip units.Two frame sizes are available, the 800 ampere frame (300 to 800amperes) and the 1200 ampere frame (600 to 1200 amperes). Tripunits are not interchangeable between frames.

"Complete Circuit Breaker" price includes frame, trip, Cu/AI line,and load lugs. Units will be shipped unassembled unless specified"must be factory assembled." If line lugs are not required on thebreaker, eliminate "WL" from catalog number and subtract priceof line lugs.

To order the frame, trip, and lugs separately, select the requiredcomponents from table. Magnetic circuit breakers must beordered as components. A complete breaker consists of frame,trip and one line and one load lug per pole. Price of ordering"Complete Circuit Breaker" vs. frame, trip, and line and load lugsseparately is the same.

Molded-case switches can also be ordered as complete units(designated Type TKMA—Y) or as separate components. Theyare UL listed only as complete units. To indicate required lugs,see the table below.

x Unless otherwise noted, all circuit breakers are UL listed in FileE-11592. Molded-case switches are UL listed in File E-57546.R Frame—1000/1600/2000 Amp Molded-Case Circuit Breakers• Solid-state MicroVersaTrip Plus™ or MicroVersaTrip PM™

Trip Unit• Interchangeable trip unit via rating plugs• 65 and 100 kA ratings available• Standard and 100% rated versions• Uses standard Power Break* accessories• Stationary/manual onlyCurrent Limiting Circuit Breakers• 150, 225, 400 and 600 ampere frame sizes• UL listed interrupting ratings are 200 kA at 240 and 480 volts ac

maximum and 50 kA at 600 volts ac maximum• Thermal magnetic constructionCircuit Breakers with MicroVersaTrip' Trip Units• Solid-state construction with MicroVersaTrip RMS-9 digital rms

sensing microprocessor trip units.• Available in J and K frame construction with ampere ratings from

60-1200A.For ordering information see pages 4-36 through 4-41. UL listed,File E-11592. All breakers are UL listed in File E-11592.Tri-Break' Line• Integrally Fused Thermal Magnetic Circuit Breakers• Integrally Fused Magnetic Circuit Breakers• Integrally Fused Molded-Case Switches

Molded Case Circuit BreakersThese breakers are available in four types. Type TB1 (15-100amperes) catalog numbers include frame, trip, line and load lugs,and current limiters all factory assembled. Types TB4 (125 to 400amperes), TB6 (300 to 600 amperes) and TB8 (600 to 800 amperes)include frame, trip and limiters, factory assembled, but do notinclude line or load lugs. If line and load lugs are required, orderseparately. Unless otherwise noted, TB1, TB4, TB6, and TB8breaker components are UL listed in File E-42263. Fusedmolded-case switches are UL listed in File E-57546.Mag-Break9 Line• Magnetic only circuit breakers (motor circuit protectors)

These breakers are available only with noninterchangeableadjustable magnetic trip, in frame Types E, F, J, K, and Tri-Break.All breakers are shipped factory assembled, complete with Cu/AIline and load lugs.

All magnetic only circuit breakers and limiters are UL ComponentRecognized in Files E-11592 and E-66390, respectively, unlessotherwise noted.

AccessoriesOrder accessories from the appropriate table:

Thermal Magnetic Circuit Breakers, Magnetic Circuit Breakers, andMolded-Case Switches®—pages 4-48 to 4-65.MicroVersaTrip RMS-9 or 4-function Solid-State Circuit Breakers— .pages 4-48 to 4-65.

© Installation of accessories in molded-case switches requires dummytrip; see page 4-51 for information. Dummy trip not required forTri-Break or Q Line molded-case switches.

Spectra RMS™ Breakers—pages 4-47 to 4-65.Spectra RMS™ Breakers with MicroVersaTrip Plus™ Trip Units orMicroVersaTrip PM™ Trip Units—pages 4-32 to 4-35 and 4-47 to 4-65.

Molded-Case Circuit Breaker and SwitchTerminal Configuration CodeOrder standard Cu/AI lugs by using suffix codes presented. Order lugsseparately if special lugs are required. For optional lugs, see page 4-62.

Breaker/SwitchType

TQD/TJD

Molded CaseBreakers,ThermalMagneticMoldedCaseSwitchSpectra RMS™BreakersJ.K.MicroVersaTrip"BreakersMine Duty™BreakersMag- Break*Breakers

Suffix

BlankLoadLugsOnly

LoadLugsOnly

Line andLoadLugsNo

Lugs

NoLugs

NoLugs

Line andLoad Lugs

WL

Line andLoad Lugs

Line andLoad Lugs

-

XL

-

-

NoLugs

X2LineLugsOnly

LineLugsOnly

LineLugsOnly

LL

NoLugs

NoLugs

LoadLugsOnly

Order Lugs Separately

Order Lugs Separately

Order Lugs Separately

- - - —

For E 150 circuit breakers suffix XL is used to specify "no lugs".

Data subject to change without notice 1999 Issue 4-3

pi N II

GE Molded Case Circuit Breakerst. VERTICAL Molded Case Circuit Breakers

Quick Reference GuideRatings do not apply to molded-case switches.

TJJ, TJK, THJK TFJ, TFK, THFK

E150 (UL File E-11592; Fixed Thermal Magnetic Trip Unit; CSA LR 57114)

Jlte^

CircuitBreakerType

TEY®

TEB®

TED®

THED®

TEL®

AmpereRating

15-100

10-1009>

10-100

15-10010-150

15-30

15-100

15-1001 1 0 - 1 5 0

-15-150

No.Poles

12

3

1

2

3

1

2 '

3

1

2

3

3

MaximumVoltage Rating

ac277

120

277,347®480

600

277,347®

480

480,600

600

do125

250

125

250

125

250

500

125

250

-

UL Listed Interrupting Ratings—rms Symmetrical Amps (In Thousands)ac Voltage

12065

10

-

-

120/240

-

-

100

240

14

65

10

18

65

65

42

100

277

14

1 4

-

14

65

-

-

480

-

-

10

1 8

25

65

600

-

-

1 4

18

25

do Voltage1251 01 0—

5——

10

20®

-

-

250

1 0

5

10

10

20®

10

-

500®—

10

-

Dimensions(In.)

H

5'/4

65/ie

6^16

65/16

65/ie

W

1

2

3

1%

2%'

4Vfr

1%

23/4

41*

1%

41/a

4'/B

D

3'/18

3%

3%

3%

ytte

A

-

24'/64

Z"A>

2"/tn

27/16

B

-

2'%4

21%4

21s/64

2'%2

c

-

"/16

__

1 '/16

——

"/,6

11/16

E

-

s%2

23/32

2%2

2%2

Approx.Ship Wt./Std. Pack

26 lb/2424 lb/1 2

28 lb/8

26 lb/24

24lb/1228 lb/8

26 lb/24

24lb/12

28 lb/8

3Vz lb/1

"225 (UL File E-11592; TFJ, Fixed Thermal Magnetic Trip Unit; TFK, THFK: Interchangeable Thermal Mag. Trip Unit; CSA LR 40350)

CircuitBreaker

Type

TFJ®

TFK®

THFK®

TFL®

AmpereRating

70-225

70-250

70-225

70-225

70-225

No.Poles

2

3

2

3

2

3

3

MaximumVoltage Rating

ac480

600

480

600

480

600

600

dc

250

500

250

250

-

UL Listed Interrupting Ratings —rms Symmetrical Amps (In Thousands)ac Voltage

120

-

120/240

100

240

25

25

65

100

277

-

480

22

22

25

65

600

1 8

_

18

1 8

25

dc Voltage125

-

2501 0

10®

10

20®

-

500®—

10

_

-

Dimensions(in.)

H

10'/8

101*

10'/B

101*

W

41*

4%

41*

'41*

D

3'Vie

31yi«

3^18

3«/16

A

3%

3%

37/6

3%

B

3'/B

3%

3%

3%

C

"/16

"/,e

"/16

11/16

E

1 3 /16 •

1*i6

1Vie

1*ie

Approx.Ship Wt./Std. Pack

10 lb/1

12 lb/110 lb/112 lb/110 lb/112 lb/1

-

J600 (UL File E-11592; TJJ, Fixed Thermal Magnetic Trip Unit; TJK, THJK: Interchangeable Thermal Mag. Trip Unit; CSA LR 40350)

TJK4

THJK4

250-600

250-600

2

3

2

3

2

3

2

3

600

600

250

500

250

500

250

250

-

42

65

30

35

2210

20

10

20®

40

40

-

' 20®

20

_

81/4

3'3/16

3%

315/16 3^16

3«/16

1% 1*6

16lb/117'/2lb/1

18 lb/120 lb/116 lb/1

17Vzlb/1

18 lb/120 lb/1

K1200 (UL File E-11592; Interchangeable Thermal Magnetic Trip Unit; CSA LR 40350)

TKM8

TKM12

THKM12

2

3

2

3

2

3

2

3

600250

500

250

42

65 35

.2210

20 <D

40®

22

—8'/4

5'/2

5/2

SQ/IB

5"/16

1%

1%

%

%

33 lb/1

39 lb/138 lb/1

41VMW133 lb/139 lb/138 lb/1

41 14 lb/1

UL listed with poles in seriesfor 500 Vdc ungroundedbattery applications.

© All UL listed as HACR type.® 10 amp not UL listed.

® UL listed/CSA Certified for10kA @ 347 Vac (TED) and18kA@ 347V (THED). Alsorated 10kA @ 480V but notUL listed.

© UL listed at 10,000 amps.® Discontinued© Also 10,000 amps at 500 Volts

dc. Not UL listed.

500 Vdc on TJJ only.

(continued on page 4-8)

Data subject to change without notice 1999 Issue 4-7