GE INCUBATOR ADDITION ELECTRICAL GE...CLG CO COMM CONN CU DEMO DISC DN DWG EA ELEC ELEV EMER, EM EMT...
Transcript of GE INCUBATOR ADDITION ELECTRICAL GE...CLG CO COMM CONN CU DEMO DISC DN DWG EA ELEC ELEV EMER, EM EMT...
9/3/20
19 2:
19 P
MLA
ST S
AVED
: 29-
Aug-
19T:
\Jobs
\2019
053 G
E Inc
ubato
r\01 D
rawi
ngs\0
5 Elec
trical\
Sine
Sou
rce P
rojec
t\She
ets\E
E-00
1 ABB
REVI
ATIO
NS, G
.P.N
., LEG
END
& SH
EET
INDE
X.dw
g
9/3/2019
© COPYRIGHT DESIGN WEST ARCHITECTS 201954321
A
B
D
C
desi
gn w
est
arch
itect
s25
5 SO
UTH
300
WES
T79
5 NO
RTH
400
WES
TLO
GAN
UT
843
21SA
LT L
AKE
CITY
UT
841
03
PROJECT #:
DRAWN BY:
CHECKED BY:
ISSUED:
GE IN
CUBA
TOR
ADDI
TION
LOGA
N, U
TAH
8432
1
-
D. PATTON
S. SWENSON
09.03.2019
-
MARK
:DA
TE:
DESC
RIPT
ION:
ELECTRICAL ABBREVIATIONSAAFAFFAFGAFIAICALARCHASAWGBLDGBKBDCCABCATC/BCKTCLGCOCOMMCONNCUDEMODISCDNDWGEAELECELEVEMER, EMEMTEOLREQUIPEX, EXISTFBOFCUFFFIXTFLEXFLUORFTGFIGNDHPHVACIGIMCINISCJB, J-BOXKCMILKVAKW
AMPEREAMP FUSEABOVE FINISHED FLOORABOVE FINISHED GRADEARC-FAULT CIRCUIT-INTERRUPTERAMPERE INTERRUPTING CAPACITYALUMINUMARCHITECT(URAL)AMP SWITCHAMERICAN WIRE GAUGEBUILDINGBACKBOARDCONDUITCABINETCATALOG/CATEGORYCIRCUIT BREAKERCIRCUITCEILINGCONDUIT ONLYCOMMUNICATIONCONNECTIONCOPPERDEMOLITION/DEMOLISHDISCONNECTDOWNDRAWINGEACHELECTRICALELEVATOREMERGENCYELECTRICAL METALLIC TUBINGEND OF LINE RESISTOREQUIPMENTEXISTINGFURNISHED BY OTHERSFAN COIL UNITFINISHED FLOORFIXTUREFLEXIBLE METALLIC CONDUIT (STEEL)FLUORESCENTFEET OR FOOTGROUND FAULT INTERRUPTERGROUNDHORSEPOWERHEATING, VENTILATING & AIR CONDITIONINGISOLATED GROUNDINTERMEDIATE METAL CONDUITINCH(ES)SHORT CIRCUIT AMPERES, KAJUNCTION BOXTHOUSAND CIRCULAR MILSKILOVOLT AMPEREKILOWATT
LTGMAXMCBMECHMFRMINMLOMTDNECNECANEMANEUTNFCNCNICNLNONTSOCPPPHPNLPWRQTYRECEPREQ'DRGSCRMSCHEDSECTSPSNSPECSWSWBDSWGRSYSTEMPTELEXFMRT-STATTWPTWSPTYPUBCULUMCUNOVVAWW/WGWP
LIGHTINGMAXIMUMMAIN CIRCUIT BREAKERMECHANICALMANUFACTURERMINIMUMMAIN LUGS ONLYMOUNTEDNATIONAL ELECTRICAL CODENATIONAL ELECTRICAL CONTRACTOR'S ASSOCIATIONNATIONAL ELECTRICAL MANUFACTURERS ASSOCIATIONNEUTRALNATIONAL FIRE CODENORMALLY CLOSEDNOT IN CONTRACTNIGHT LITENORMALLY OPENNOT TO SCALEOVERCURRENT PROTECTIONPOLEPHASEPANELPOWERQUANTITYRECEPTACLEREQUIREDRIGID GALVANIZED STEEL CONDUITROOMSCHEDULESECTIONSINGLE POLESOLID NEUTRALSPECIFICATIONSWITCHSWITCHBOARDSWITCH GEARSYSTEMTEMPORARYTELEPHONETRANSFORMERTHERMOSTATTWISTED PAIRTWISTED SHEILDED PAIRTYPICALUNIFORM BUILDING CODEUNDERWRITERS LABORATORYUNIFORM MECHANICAL CODEUNLESS NOTED OTHERWISEVOLT OR VOLTAGEVOLT AMPEREWATTWITHWIRE GUARDUL LISTED WEATHERPROOF, NEMA 3R or 4
MS
FACP
F
J
3
4
ANN
WP
X
NAC
COMMUNICATIONS OUTLET (5" SQ x 2-7/8"D J-BOX; 1-GANG x 5/8"DMUD-RING; 1" CONDUIT, 1 CAT 6 CABLE)COMMUNICATIONS OUTLET (5" SQ x 2-7/8"D J-BOX; 1-GANG x 5/8"DMUD-RING; 1" CONDUIT, 2 CAT 6 CABLES)COMMUNICATIONS OUTLET (5" SQ x 2-7/8"D J-BOX; 1-GANG x 5/8"DMUD-RING; 1" CONDUIT; 3 CAT 6 CABLES)
TELEVISION OUTLET (5" SQ x 2-7/8"D J-BOX; 1-GANG x 5/8"DMUD-RING; 1" CONDUIT, 1-RG-6 COAX)
x COMMUNICATIONS OUTLET (5" SQ x 2-7/8"D J-BOX; 1-GANG x 5/8"DMUD-RING; 1" CONDUIT; x CAT 6 CABLES)
SECURITY
m MOTOR PROTECTIVE THERMAL SWITCH
x
x
EMERGENCY LIGHT
BATTERY PACK
EXIT LIGHT: CEILING - FACE(S) AS SHOWN
EXIT LIGHT: WALL - FACE(S) AS SHOWN
EXIT LIGHT: FACE SIDE
EXIT LIGHT: DIRECTIONAL ARROWS, DOUBLE FACE
RECESSED FIXTURE
STRIP LIGHT
LINEAR FIXTURE
EMERGENCY FIXTURE
WALL MOUNT FIXTURE
THREE WAY SWITCH
FOUR WAY SWITCH
MOTION SENSOR : INFRARED
DUPLEX OUTLET
DUPLEX OUTLET: GROUND FAULT INTERRUPTER
DUPLEX OUTLET: WEATHERPROOF
DOUBLE DUPLEX OUTLET
DOUBLE DUPLEX OUTLET: GROUND FAULT INTERRUPTER
SPECIAL OUTLET: SEE PANEL SCHEDULE
JUNCTION BOX
DISCONNECT; NO OVER-CURRENT PROTECTION
DISCONNECT WITH OVER-CURRENT PROTECTION (CIRCUITBREAKER STYLE OR AS SPECIFIED)
QUANTITY OF CONDUCTORS: SHORT LINES = PHASE /SWITCH,LONG LINES = NEUTRAL
HOME-RUN
DISTRIBUTION PANEL
PANELBOARD
COMMUNICATIONS RACK
PHONE BACKBOARD
FIRE ALARM CONTROL PANEL
FIRE ALARM REMOTE ANNUNCIATOR PANEL
NOTIFICATION APPLIANCE CIRCUIT PANEL
SMOKE DETECTOR
FIRE ALARM STROBE; "X" = MINIMUM CANDELA RATING
FIRE ALARM HORN AND STROBE; "X" = MINIMUM CANDELA RATING
FIRE ALARM PULL STATION
CCTV CAMERA : WALL MOUNT
ELECTRIC STRIKE (4SD J-BOX ABOVE CEILING; 1/2" CONDUIT STUBINTO DOOR FRAME)CARD READER (4SD J-BOX WALL; 4SD J-BOX ABOVE CEILING; 1/2"CONDUIT BETWEEN BOXES)
ES
CR
COMMUNICATIONS LADDER RACK. SEE SPECIFICATIONS AND / ORSCHEDULESLR#COMMUNICATIONS RACEWAY CABLE TRAY. SEE SPECIFICATIONSAND / OR SCHEDULESCT#
FSD FIRE SMOKE DAMPER
COMMUNICATIONS ENCLOSURE
CEILING MOUNTED FIRE ALARM HORN AND STROBE; "X" = MINIMUMCANDELA RATINGx
CCTV CAMERA : DOME TYPE CEILING MOUNT
CEILING MOUNTED FIRE ALARM STROBE; "X" = MINIMUM CANDELARATINGx
SECURITY SYSTEM HEAD END EQUIPMENTSEC
CCTV SECURITY MONITORMO
POWER AND DISTRIBUTION
COMMUNICATIONS
LIGHTING FIXTURES
LIGHTING CONTROLFIRE ALARM
BRANCH CIRCUITING
ELECTRICAL LEGEND
DOUBLE DUPLEX OUTLET: ISOLATED GROUND - ORANGE DEVICEAND PLATE UNLESS OTHERWISE SPECIFIED
SINGLE POLE SWITCH; "x" INDICATES SWITCH GROUP
METER / METER SOCKET
S OCCUPANCY SENSOR: DUAL TECHNOLOGY
S OCCUPANCY SENSOR: PASSIVE INFRARED
DT
PR
COMMUNICATIONS OUTLET: WIRELESS ACCESS POINT (5" SQ x2-7/8"D J-BOX; 1-GANG x 5/8"D MUD-RING; 1" CONDUIT, 1 CAT 6 CABLE)WAP
xCDy COMMUNICATIONS RACEWAY: "x" CONDUITS OF "y" DIAMETER
CMJ COMMUNICATIONS RACEWAY; OPEN D-RINGS OR J-HOOKS. SEEDETAILS AND SPECIFICATIONS
DETAIL CALL-OUT; TOP "X" REFERS TO DETAIL NUMBER & BOTTOM"XXX" REFERS TO SHEET NUMBER
ANNOTATIONS
XXXX
FACELESS GFCI PROTECTION DEVICE
GENERAL WALL-MOUNTED BOX HEIGHT DETAIL
BAR STRAPS+XX = TOP OF BOX
XX = MIDDLE OF BOX
-XX = BOTTOM OF BOX
LIGHT FIXTURE LOCATED IN IECC DAY-LIGHTING ZONEDL
LSX/SYDIGITAL LIGHTING CONTROL SWITCH; SX = SWITCH CONTROLTYPE #1; SY = SWITCH CONTROL TYPE #2; ETC.
WPIUDUPLEX OUTLET: WEATHERPROOF-IN-USE COVER
COMBINATION DISCONNECT/MOTOR STARTER WITH OVERCURRENTPROTECTION (CIRCUIT BREAKER STYLE OR AS SPECIFIED)
COMBINATION DISCONNECT/MOTOR STARTER; NO OVER-CURRENTPROTECTION
DUPLEX RECEPTACLE WITH (2)USB; LEVITON T5832 SERIES OREQUIVALENTUSB
FACELESS DEVICE WITH (4)USB; LEVITON USB4P SERIES OREQUIVALENTUSB U
# KEYED NOTE CALLOUT
EQUIPMENT CALLOUT
PRODUCTION EQUIPMENT CALLOUT
#-#
#-#
WALL MOUNT OCCUPANCY SENSOR: VACANCY SENSOR FUNCTION
S OCCUPANCY SENSOR: VACANCY SENSOR FUNCTIONVS
WALL MOUNT OCCUPANCY SENSOR: OCCUPANCY SENSORFUNCTION
S OCCUPANCY SENSOR: OCCUPANCY SENSOR FUNCTIONOS
VS
OS
REFER TO POWER, LIGHTING AND COMMUNICATIONS PLANS FOR SPECIFIC DIMENSIONS.SEE GENERAL NOTES AND SPECIFICATIONS WHERE NO HEIGHTS ARE INDICATED.
GENERAL PROJECT NOTES1. ALL ELECTRICAL INSTALLATIONS TO CONFORM TO THE LATEST NEC AND LOCAL CODES.
2. ELECTRICAL CONTRACTOR'S PROJECT MANAGER AND ON-SITE PROJECT FOREMAN SHALL REVIEW VENDORSUBMITTALS FOR ACCURACY PRIOR TO SUBMITTING TO ENGINEER. INACCURACIES SHALL BE CORRECTED PRIOR TOENGINEER SUBMITTAL.
3. SUBMITTALS FOR EACH SYSTEM WILL BE REVIEWED BY ENGINEER UP TO TWO TIMES--ONE FULL SUBMITTAL FOROVERALL COMPLIANCE AND ONE RESUBMITTAL. ADDITIONAL REVIEWS WILL BE CHARGED TO CONTRACTOR ATENGINEER'S STANDARD BILLING RATE.
4. SUBMITTALS TO ENGINEER SHALL INCLUDE ALL SPECIFIED SYSTEMS IN FIRST SUBMITTAL. PARTIAL SUBMITTALS WILLBE RETURNED TO CONTRACTOR AS INCOMPLETE AND WILL BE CONSIDERED ONE OF TWO INCLUDED SUBMITTALREVIEWS.
5. THE CLARITY OF RECORD DRAWING CHANGES MADE BY THE CONTRACTOR SHALL BE EQUAL TO THE ORIGINALDRAWINGS AS JUDGED BY THE ARCHITECT OR THE RECORD SET WILL BE RETURNED TO THE CONTRACTOR FORCLARIFICATION.
6. WHEN THE GENERAL CONTRACT CALLS FOR “RECORD” OR “AS-BUILT” DRAWINGS TO BE FURNISHED BY THECONTRACTOR AT JOB COMPLETION, THE ELECTRICAL CONTRACTOR SHALL BE REQUIRED TO FURNISH A COMPLETESET OF “BLUE-PRINT READY” AUTOCAD ELECTRICAL DRAWINGS FOR ALL CONTRACTOR GENERATED CHANGES FROMTHE DRAWINGS OF A CLARITY EQUAL TO THE ORIGINAL DRAWINGS AS JUDGED BY THE ENGINEER. CONTACTARCHITECT FOR DISKS OR REPRODUCIBLE ORIGINAL MEDIA. PROVIDE DRAWINGS ON CD IN AUTOCAD FORMAT.
7. DO NOT SCALE ELECTRICAL FLOOR PLANS. SEE ARCHITECTURAL DRAWINGS FOR ACCURATE DIMENSIONS AND FLOORPLANS.
8. ELECTRICAL DEVICES CANNOT BE SHOWN TO SCALE AND SOMETIMES OVERLAP BUILDING ELEMENTS. REFER TOARCHITECTURAL ELEVATIONS FOR ACCURATE MOUNTING LOCATIONS
9. PANEL INDEXES SHALL INCLUDE ALL PERTINENT INFORMATION ON THE PANEL SCHEDULES INCLUDING INFORMATIONON LIGHTS AND OUTLETS. DO NOT SIMPLY COPY THE CIRCUIT DESCRIPTION COLUMN. INDEXES TO BE TYPEWRITTEN.
10. COORDINATE MOUNTING HEIGHT AND LOCATION OF ALL OUTLETS, SWITCHES, AUXILIARY EQUIPMENT, AND OTHERDEVICES WITH THE ARCHITECTURAL DRAWINGS. PRIOR TO INSTALLATION, REVIEW WITH THE GENERAL CONTRACTORTHE LOCATION OF MILLWORK AS A FINAL CHECK TO PREVENT COVERING OF ELECTRICAL ITEMS.
11. MOUNTING HEIGHT OF GENERAL PURPOSE OUTLETS AND SWITCHES SHALL BE 16” TO BOTTOM AND 48” TO TOPRESPECTIVELY UNLESS OTHERWISE NOTED.
12. ALL ELECTRICAL EQUIPMENT SHALL BE LOCATED SO AS NOT TO INTERFERE WITH WOOD TRIM AND MOLDINGS. THEELECTRICAL CONTRACTOR SHALL REVIEW FINISH SCHEDULES AND ARCHITECTURAL DETAILS BEFORE ROUGH-IN OFOUTLET OR SWITCH BOXES TO PREVENT BOXES AND PLATES FROM BEING PLACED BEHIND OR IN TRIMS ANDMOLDINGS. REFER SPECIAL CONDITIONS TO ARCHITECT PRIOR TO ROUGH-IN.
13. CIRCUIT WIRE SIZES MUST, AT MINIMUM, MATCH NEC REQUIRED CONDUUCTOR SIZES FOR CORRESPONDINGOVERCURRENT PROCTECTIVE DEVICES. VERIFY WITH PANEL SCHEDULES BEFORE PULLING WIRE.
14. HOME RUNS MUST BE RUN EXACTLY AS SHOWN ON PLANS UNLESS OTHERWISE NOTED. DO NOT COMBINE HOME RUNSINTO ONE CONDUIT THAT ARE NOT SHOWN COMBINED ON THE DRAWINGS.
15. THE ELECTRICAL CONTRACTOR SHALL RUN BRANCH CIRCUIT CONDUITS IN ATTIC SPACES IN A NEAT ANDWORKMANLIKE MANNER SO AS TO CONSERVE OPEN SPACES AS MUCH AS POSSIBLE. HVAC DUCTWORK ANDPLUMBING SHALL HAVE LOCATION PRIORITY OVER BRANCH CIRCUIT CONDUIT RUNS.
16. CIRCUIT WIRING SHALL BE INSTALLED AS SHOWN ON THE DRAWINGS. ANY DEVIATIONS SHALL BE INITIATED BY ACHANGE ORDER FROM THE ARCHITECT. OTHERWISE THE RECORD SET SHALL MATCH THE CONSTRUCTION SET.
17. PROVIDE AN EQUIPMENT GROUNDING CONDUCTOR, PULLED INTO THE CONDUIT WITH THE PHASE CONDUCTOR, IN ALLSERVICE, FEEDER, AND BRANCH CIRCUITS.
18. PROVIDE A NEUTRAL CONDUCTOR FOR EACH BREAKER TRIP HANDLE. NEUTRALS SHALL NOT BE SHARED BETWEENBRANCH CIRCUITS.
19. ALL CIRCUITS TO BE MINIMUM #12 CU IN MINIMUM 3/4” CONDUIT UNLESS OTHERWISE NOTED.
20. MC CABLE IS NOT AN APPROVED ALTERNATE TO CONDUCTORS IN CONDUIT.
21. DO NOT INSTALL MORE THAN THREE PHASE CONDUCTORS IN ANY HOME-RUN CONDUITS UNLESS SPECIFICALLYINDICATED ON DRAWINGS.
22. IDENTIFY ALL OUTLET COVER PLATES WITH THE PANEL AND CIRCUIT NUMBER.
23. DO NOT INSTALL ELECTRICAL BOXES BACK-TO-BACK IN PARTITION WALLS. LOCATE DEVICES ON OPPOSITE SIDES OFSTUD OR PROVIDE MINIMUM 12” HORIZONTAL SEPARATION.
24. A GFI OUTLET SHALL BE INSTALLED AT EACH LOCATION DESIGNATED BY “GFI” ON THE DRAWINGS. DOWNSTREAMPROTECTION BY A GFI OUTLET UPSTREAM IS NOT ALLOWED.
25. OUTLETS, SWITCHES, AND COVER PLATES TO BE COLOR CODED (BROWN, WHITE, IVORY, OR GRAY) TO THE WALL THEYARE MOUNTED ON AS DIRECTED BY THE ARCHITECT.
26. ALL CONVENIENCE OUTLETS MUST BE MOUNTED FLUSH WITH THE COVER PLATE AND SECURED FIRMLY TO THEOUTLET BOX.
27. REMOVE ALL OLD AND/OR UNUSED EXISTING CONDUIT AND ELECTRICAL APPARATUS FROM EXTERIOR OR INTERIOREXPOSED SURFACES.
28. WHERE EXISTING ELECTRICAL EQUIPMENT IS TO REMAIN BUT THE SURFACE THAT IT IS MOUNTED ON IS TO BEREWORKED UNDER OTHER CONTRACTS, THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO REMOVE ANDINSTALL OR MODIFY THE EXISTING EQUIPMENT AS REQUIRED TO MEET THE DESIGN INTENT. SEE ARCHITECTURALDRAWINGS FOR ROOF, CEILINGS, WALLS, SOFFITS, FLOORS, ETC.
29. REMOVE ALL UNUSED CONDUITS AND CIRCUITS IN THE DEMOLTIONED AREA AS THEY ARE IDENTIFIED AS UNUSED ORABANDONED.
30. REMOVE ALL EXISTING ELECTRICAL DEVICES, EQUIPMENT, AND APPARATUS AS THEY ARE IDENTIFIED AS UNUSED ORABANDONED.
31. RELOCATE EXISTING CONDUITS AND CIRCUITS AS REQUIRED THAT ARE PRESENTLY SERVING EQUIPMENT THAT ISINTENDED TO REMAIN IN SERVICE BUT SAID CONDUITS ARE CURRENTLY RUNNING THROUGH AREAS TO BEDEMOLITIONED.
32. WHERE EXISTING CONDUIT RUNS ARE RE-USED BY SPECIAL PERMISSION FROM THE ARCHITECT, A SEPARATE GREEN,INSULATED GROUND WIRE SHALL BE PULLED IN THE CONDUIT AND BONDED AT EACH END AS REQUIRED.
33. ALL PATCH, REPAIR, REPAINT AND COVER UP REQUIRED AS A RESULT OF ELECTRICAL REMODEL IS TO BE THERESPONSIBILITY OF THE ELECTRICAL CONTRACTOR, BUT ACTUAL WORK IS TO BE PERFORMED BY QUALIFIEDPERSONNEL.
34. RE-ROUTE EXISTING CIRCUIT CONDUITS AS REQUIRED AT ALL AREAS WHERE EXISTING WALLS ARE TO BEDEMOLITIONED OR HAVE DOORWAYS CUT IN THEM. PLAN ON AN AVERAGE OF ONE, 3/4” CONDUIT RELOCATION FOREACH PENETRATION OR WALL REMOVAL.
35. FIELD VERIFY CONDITIONS FOR NEW WIRING. SURFACE RACEWAYS MUST RECEIVE PRIOR APPROVAL FROM THEARCHITECT BEFORE BID AND MUST BE PAINTED TO MATCH THE SURFACE ON WHICH THEY ARE MOUNTED.
36. ALL RECESSED LIGHT FIXTURES MUST CONFORM TO NEC 410
37. ALL RECESSED LIGHT FIXTURES THAT PENETRATE THE BUILDING THERMAL ENVELOPE SHALL BE SEALED WITH AGASKET OR CAULK BETWEEN THE HOUSING AND INTERIOR WALL OR CEILING COVERING
38. COORDINATE LOCATION OF CEILING LIGHT FIXTURES WITH THE REFLECTED CEILING PLAN.
39. FIXTURE COUNTS SHOWN ON DRAWINGS ARE FOR REFERENCE ONLY. CONTRACTOR IS RESPONSIBLE TO VERIFYFIXTURE COUNTS AS PART OF BIDDING PROCESS.
40. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO REVIEW ALL SWITCH LOCATIONS WITH THE GENERALCONTRACTOR PRIOR TO ROUGH-IN TO PREVENT ANY SWITCHES FROM BEING LOCATED ON THE WRONG SIDE OF THEDOOR.
41. COORDINATE LOCATION OF EXIT LIGHTS WITH ARCHITECT.
42. VERIFY FIXTURE COUNT WITH REFLECTED CEILING PLAN.
43. REFER TO MECHANICAL PLANS FOR EXACT LOCATION OF MECHANICAL EQUIPMENT.
44. ELECTRICAL CONTRACTOR SHALL FURNISH ALL MOTOR DISCONNECTS, STARTERS, AND CONTROL STATIONS FORMECHANICAL EQUIPMENT UNLESS THE SAME IS FURNISHED AS AN INTEGRAL PART OF THE EQUIPMENT. VERIFY WITHMECHANICAL CONTRACTOR PRIOR TO BID.
45. THERMOSTAT AND CONTROL WIRING FOR MECHANICAL EQUIPMENT BY MECHANICAL CONTRACTOR.
46. PROVIDE SAFETY DISCONNECTS AS REQUIRED AT ALL CONNECTIONS TO MECHANICAL EQUIPMENT. PROVIDE RATINGSPER NAMEPLATE INFORMATION OF EQUIPMENT SERVED.
47. DISCONNECT SWITCHES ARE SHOWN IN APPROXIMATE LOCATIONS ONLY. CONTRACTOR SHALL FIELD VERIFYLOCATION OF ALL ELECTRICAL SWITCHES AND MOTOR CONTROL FOR PROPER CODE CLEARANCES. NOTIFYARCHITECT IMMEDIATELY OF ANY CONFLICTS WITH OTHER TRADES REGARDING PROPER EQUIPMENT CLEARANCES.
48. ALL DISCONNECT SWITCHES FOR MOTORS SHALL BE RATED A MINIMUM OF 22000 AIC UNLESS OTHERWISE SHOWN.
49. COORDINATE LOCATION OF THERMOSTATS, SENSORS, AND ATC JUNCTION BOXES WITH MECHANICAL CONTRACTORBEFORE INSTALLATION.
50. BEFORE RUNNING CONDUITS, PLACING OUTLETS OR ORDERING EQUIPMENT, THE CONTRACTOR SHALL REVIEW THESPECIFICATIONS AND DESIGN AND SHOP DRAWINGS OF THE OTHER TRADES SERVED BY THE CONDUIT, OUTLETS,AND/OR EQUIPMENT.
51. PROVIDE NEUTRAL CONNECTION TO 208/240/480V, SINGLE-PHASE EQUIPMENT. RUN SEPARATE GROUND WIRE TO ALLOUTDOOR UNITS AND BOND TO THE EQUIPMENT GROUND LUG.
52. ELECTRICAL CONTRACTOR SHALL INSTALL A PULL STRING IN ALL COMMUNICATIONS, SECURITY, AND OTHER LOWVOLTAGE CONDUITS FOR USE BY LOW VOLTAGE SYSTEM CONTRACTOR.
53. ELECTRICAL CONTRACTOR SHALL INSTALL A PULL STRING IN ALL UNUSED POWER AND LIGHTING CONDUITS.
54. BID TO RUN FIRE ALARM RACEWAYS CONCEALED. ANY SURFACE RACEWAYS (WIREMOLD #700 ONLY) MUST BE PRIORAPPROVED BY THE ARCHITECT/OWNER AND PAINTED TO MATCH THE SURFACE IT IS MOUNTED ON.
55. COORDINATE LOCATION OF ALL FIRE ALARM DEVICES WITH NFPA AND ADA REQUIREMENTS. COORDINATE LOCATIONSWITH MILLWORK AS REQUIRED.
56. WHERE THERE ARE CONFLICTS IN THE DRAWINGS AND/OR SPECIFICATIONS THE CONTRACTOR SHALL NOTIFY THEARCHITECT/ENGINEER PRIOR TO BID. WHERE NO NOTIFICATION IS GIVEN THE MORE STRINGENT INTERPRETATION(GENERALLY INTERPRETED TO BE THE MORE COSTLY) WILL BE ENFORCED.
ABBREVIATIONS,G.P.N., LEGEND &SHEET INDEX
EE-001
SHEET INDEX# Sheet Title
EE-001 ABBREVIATIONS, G.P.N., LEGEND & SHEET INDEXED-101 ELECTRICAL DEMOLITION PLANEP-100 ELECTRICAL PLANSEP-602 ELECTRICAL SCHEDULES
Filtration
Agamma
UP
Mechanical Room
Maintenance Shop
Mechanical Room
Biochemistry
Processing
Maintenance
Lab
Centrifuge
Com
pone
ntS
tagi
ng
Office
Metrology
Airlock143.2
164
162
163
144.2
136
141
142.2
140
144.1144.3
144
142.
1
143.
1
ING
2
M CK 1
VLM
ASST
HRU 1
2
3 3 3 3 3 333333
3 3 3 3 3 3
3
22
2
M1 M2
1P11
1P13SS SS
1P15
1P16
1P10
1P8
E1DP1
1P2
GENERATOR
w
"2P8
A"
66
666
3PCPC
c c c
c
w
FG-1
M
FG-1
M
FG-1
M
PS-1
FG-1
M
PFC-
1
FG-1
M
FG-1
M
G-1W FG
-1W
HSD-
3
SM-1
SM-2
LP-1
LP-2
SM-2
LP-2
SM-2
LP-2
OH-1D
1. EXISTING PANELS TO REMAIN.
2. REMOVE EXISTING FIXTURES AND/OR LIGHTING CONTROL AS INDICATED.
3. DISCONNECT EXISTING EQUIPMENT FOR REMOVAL.
4. REMOVE EXISTING OUTLETS AS INDICATED.
5. REMOVE EXISTING COMMUNICATIONS DEVICES AS INDICATED.
6. REMOVE EXISTING FIRE ALARM DEVICES AS INDICATED.
7. REMOVE EXISTING ELECTRONIC SYSTEMS DEVICES AS INDICATED.
8. REMOVE EXISTING CONTROL EQUIPMENT SERVING EQUIPMENT TO BEREMOVED.
9. ROOM NOT ACCESSIBLE FOR EXISTING CONDITION DOCUMENTATION.REMOVE ALL EXISTING ELECTRICAL INSTALLATIONS AS REQUIRED.
1. DEMOLITION PLAN IS ENGINEER'S ATTEMPT TO ASSIST BIDDERS INESTIMATING REMOVAL COSTS OF EXISTING EQUIPMENT. PLAN IS NOTINTENDED TO BE ALL-INCLUSIVE, AND IT IS THE BIDDERS RESPONSIBILITYTO VERIFY ALL EXISTING EQUIPMENT AND DEVICES TO BE REMOVEDPRIOR TO BIDDING.
2. EXISTING ITEMS TO BE REMOVED ARE INDICATED AS BOLD/DASHED. ITEMSTO REMAIN ARE SHOWN AS LIGHT/SOLID.
3. MAINTAIN CIRCUIT CONTINUITY FOR DEVICES DOWNSTREAM OF ITEMS TOBE REMOVED.
4. WHERE DEVICES ARE SHOWN TO BE REMOVED, COMPLETELY REMOVEALL RACEWAYS, BOXES AND CONDUCTORS TO PANEL OR TO FIRST J-BOXTO REMAIN ACTIVE IN CIRCUIT PATH.
SHEET KEYED NOTES
GENERAL NOTES
1 1
1
11
22
3
9/3/20
19 2:
20 P
MLA
ST S
AVED
: 29-
Aug-
19T:
\Jobs
\2019
053 G
E Inc
ubato
r\01 D
rawi
ngs\0
5 Elec
trical\
Sine
Sou
rce P
rojec
t\She
ets\E
D-10
1 ELE
CTRI
CAL D
EMOL
ITIO
N PL
AN.dw
g
9/3/2019
© COPYRIGHT DESIGN WEST ARCHITECTS 201954321
A
B
D
C
desi
gn w
est
arch
itect
s25
5 SO
UTH
300
WES
T79
5 NO
RTH
400
WES
TLO
GAN
UT
843
21SA
LT L
AKE
CITY
UT
841
03
PROJECT #:
DRAWN BY:
CHECKED BY:
ISSUED:
GE IN
CUBA
TOR
ADDI
TION
LOGA
N, U
TAH
8432
1
-
D. PATTON
S. SWENSON
09.03.2019
-
MARK
:DA
TE:
DESC
RIPT
ION:
NORTH
ELECTRICALDEMOLITION PLAN
ED-101 1/8" = 1'-0"
A1 ELECTRICAL DEMOLITION PLAN
1. CONNECT FIXTURE TO EM CIRCUIT INDICATED. CONNECT BALLAST/DRIVERTO OPERATE WITH SWITCHES IN NORMAL MODE. PROVIDE AUTOMATICSWITCHING DEVICE (LATS) FOR FIXTURE AS REQUIRED. FIXTURES ON ACOMMON SWITCH SHALL BE CONNECTED TO A SINGLE SWITCHING DEVICEWITH APPROPRIATE RATINGS. LATS SHOWN FOR INTENT ONLY. LOCATEDEVICES IN ACCESSIBLE LOCATION ON OR NEAR FIRST CONTROLLEDFIXTURE. PROVIDE ACCESS DOORS WHERE REQUIRED.
2. CONNECT TO EXISTING EM CIRCUIT INDICATED.
3. PROVIDE ROUGH-IN FOR DOOR ACCESS CONTROL. VERIFY REQUIREMENTSWITH OWNER SECURITY REP PRIOR TO ROUGH-IN.
4. PROVIDE 4SD J-BOX AND 3/4" CONDUIT TO CCTV HEAD-END. VERIFYCAMERA AND HEAD-END LOCATION WITH OWNER PRIOR TO ROUGH-IN.CABLING BY OWNER.
5. PROVIDE NEW FIRE ALARM DEVICES AS INDICATED. INTEGRATE INTOEXISTING SYSTEM AS REQUIRED.
6. PROVIDE FIRE ALARM OVERRIDE OF ACCESS CONTROLLED DOOR TORELEASE DOOR ON ALARM.
7. PROVIDE CEILING OUTLET FOR WIRELESS ACCESS POINT. COORDINATEWITH OWNERS I.T. PERSONNEL PRIOR TO ROUGH-IN.
8. PROVIDE 4SD J-BOX WITH 1/2" CONDUIT TO NEAREST COMARK PANEL FOROWNER TEMPERATURE MONITORING. VERIFY LOCATIONS WITH OWNERPRIOR TO ROUGH-IN.
1. ARCHITECTURAL CEILINGS SHOWN FOR CONTRACTOR CONVENIENCE INBIDDING INSTALLATION REQUIREMENTS. REFER TO ARCHITECTURALDRAWINGS FOR ADDITIONAL INFORMATION.
2. CONTRACTOR TO FURNISH OCCUPANCY SENSORS WITH COVERAGEPATTERNS APPROPRIATE FOR THEIR INSTALLED LOCATIONS. COORDINATEWITH EQUIPMENT SUPPLIER PRIOR TO BID.
3. CONNECT OCCUPANCY SENSORS TO ENABLE ALL SWITCHES INCONTROLLED SPACE.
4. CONNECT OCCUPANCY SENSORS, BATTERY BALLASTS, EXIT SIGNS, ETC.TO UNSWITCHED SOURCE CONDUCTOR.
5. SEE POWER PLAN FOR ELECTRICAL DISTRIBUTION, EQUIPMENT ANDLIGHTING RELAY PANEL LOCATIONS.
6. EXISTING LIGHTING, ELECTRICAL AND ELECTRONIC DEVICES SHOWNLIGHT. NEW DEVICES SHOWN DARK.
7. NEW DEVICES SHOWN ON EXISTING WALLS SHALL FINISH FLUSH WITHWALL UNLESS OTHERWISE NOTED. CUT, PATCH AND REPAIR SURFACESAS REQUIRED.
8. ALL NEW LIGHTING CONTROLS (SWITCH, OCCUPANCY SENSORS, DIMMERS,ETC.) SHALL BE LITHONIA N-LIGHT, WATTSTOPPER DLM, DOUGLASS DIALOGOR OTHER SIMILIAR SYSTEM THAT ALLOWS SWITCHES AND SENSORS TOCOMMUNICATE TO MEET MANUAL ON, AUTO OFF REQUIREMENTS OFENERGY CODE.
9. COORDINATE ALL SWITCH, OUTLET, LIGHT AND OTHER DEVICE LOCATIONSWITH ARCHITECTURAL ELEMENTS (CABINETS, WINDOWS ETC.) PRIOR TOROUGH IN. REVIEW ARCHITECTURAL INTERIOR ELEVATIONS PRIOR TOROUGH-IN OF EACH AREA FOR ADDITIONAL INFORMATION.
10. PROVIDE 4SD J-BOX WITH 1 GANG MUD RING AND 1" CONDUIT TOACCESSIBLE CEILING SPACE FOR ALL VOICE/DATA/COMBO OUTLETSSHOWN ON FLOOR PLANS. PROVIDE INSULATED THROAT CONNECTORS ONBOTH ENDS OF CONDUIT. COMMUNICATIONS CABLING PROVIDED BYOWNER.
11. ALL CONDUIT SHALL BE RAN OVERHEAD UNLESS OTHERWISE NOTED.
12. SEE SYMBOL SCHEDULE FOR COMMUNICATIONS CABLING AND ROUGH-INREQUIREMENTS.
13. CANDELA RATINGS FOR STROBE DEVICES ARE MINIMUM REQUIREDVALUES. FIRE ALARM CONTRACTOR SHALL ADJUST MANUFACTURER'SSTANDARD CANDELA RATINGS AS NECESSARY TO MEET OR EXCEEDMINIMUM REQUIREMENTS.
14. FIRE ALARM ANNUNCIATION DEVICE LOCATIONS ARE BASED ON CODEREQUIRED LAYOUTS. COORDINATE WITH ENGINEER PRIOR TO RELOCATINGANY DEVICES. ALTERNATE LOCATIONS AFFECT DEVICE CANDELA RATINGS.
15. INTEGRATE NEW FIRE ALARM DEVICES INTO EXISTING SYSTEM. PROVIDEALL UPGRADES TO EXISTING FIRE ALARM SYSTEM NEEDED FOR COMPLETESYSTEM EXPANSION. COORDINATE WITH EQUIPMENT REPS PRIOR TO BID.
16. ALL FIRE ALARM CONDUITS AND BOXES TO BE IDENTIFIED AS FOLLOWS:a) CONCEALED: FACTORY APPLIED RED.b) EXPOSED: FIELD PAINTED TO MATCH ADJACENT SURFACE.
17. PROVIDE SYNCHRONIZATION OF ALL VISUAL NOTIFICATION APPLIANCECIRCUITS. PROVIDE ALL REQUIRED SYNC MODULES. PROVIDE AMULTI-SYNC MODE SLAVE CONNECTION BETWEEN ALL SYNC MODULES.
18. DESIGN AND FIELD VERIFY AUDIBILITY SETTINGS OF NOTIFICATIONAPPLIANCES. FIELD MEASURE SOUND PRESSURE LEVELS AND REPLACEHORN-STROBES WITH STROBE ONLY DEVICES WERE REQUIRED.
SHEET KEYED NOTES
GENERAL NOTES
Filtration
UP
Maintenance
Centrifuge
Com
pone
ntS
tagi
ng
Office
142.2
144.3
144
142.
1
143.
1
ING
2
VLM
ASST
HRU 1
2
3 3 3 3 3 333333
3 3 3 3 3 3
3
22
2
66
3
OW3-L3K
TO EXTERIOREM
2
EX-1B
ELTS
EX-1BEX-1B
2,LF-L44
LATS
1
6,LF-L6K2,LF-L6K(B)
1
LATS
1
6,LF-L6K2,LF-L6K(B)
1P15-7
1
Filtration
UP
Maintenance
Centrifuge
Com
pone
ntS
tagi
ng
Office
142.2
144.3
144
142.
1
143.
1
ING
2
VLM
ASST
HRU 1
SS SS
1P15
1P16
w
c FG-1
W
+30
+78
+78
+78 +78
1P15-33,351P15-37,39,41
FC-4
FC-3
1P16-14
1P16-20
1P15-33FC-2
FC-1 1P16-2
1P16-8
1P15-39,41
1P15-41
Filtration
UP
Maintenance
Centrifuge
Com
pone
ntS
tagi
ng
Office
142.2
144.3
144
142.
1
143.
1
ING
2
VLM
ASST
HRU 1
w
88
WAP7
4
8
WAP7
4
8
4
4
WAP7
CRES
MS
SEC
1CD16
3
F
5
955
955
9/3/20
19 2:
23 P
MLA
ST S
AVED
: 3-S
ep-1
9T:
\Jobs
\2019
053 G
E Inc
ubato
r\01 D
rawi
ngs\0
5 Elec
trical\
Sine
Sou
rce P
rojec
t\She
ets\E
P-10
0 ELE
CTRI
CAL P
LANS
.dwg
9/3/2019
© COPYRIGHT DESIGN WEST ARCHITECTS 201954321
A
B
D
C
desi
gn w
est
arch
itect
s25
5 SO
UTH
300
WES
T79
5 NO
RTH
400
WES
TLO
GAN
UT
843
21SA
LT L
AKE
CITY
UT
841
03
PROJECT #:
DRAWN BY:
CHECKED BY:
ISSUED:
GE IN
CUBA
TOR
ADDI
TION
LOGA
N, U
TAH
8432
1
-
D. PATTON
S. SWENSON
09.03.2019
-
MARK
:DA
TE:
DESC
RIPT
ION:
NORTH
ELECTRICAL PLANS
EP-100 1/8" = 1'-0"
A1 PARTIAL LIGHTING PLAN 1/8" = 1'-0"
A2 PARTIAL POWER PLAN 1/8" = 1'-0"
A4 PARTIAL ELECTRONIC SYSTEMS PLAN
LIGHT FIXTURE SCHEDULETYPE MANUFACTURER/CATALOG NO. DESCRIPTION MOUNTING POWER LAMPS
EX- 1B DUAL LITE NV3-G-EN-W-CVS EXIT SIGN; SINGLE FACE; UNIVERSAL MOUNTING; WHITE, WALL OR CEILING 3W LEDSURE-LITES CCX7-0-70-G-WH-SD THERMOPLASTIC HOUSING; SELF DIAGNOSTICS; WIRE GUARD 1-FACELIGHTOLIER LT-N-U-G-W-SD WHERE NOTED ON DRAWINGSLITHONIA LQM S W 3 G 120/277 EL N SD
EELP XE-2-GW-EM-SDEXITRONIXMCPHILBEN CXXL-3-G-W
LF- L44 LITHONIA CPANL-1X4-24/33/44-40K-M4-1X4CFMK 2X4 FLAT PANEL; FLANGE MOUNT; MULTI-VOLT, ELECTRONIC, DIMMABLE DRIVER; FLANGE 28 W 4400 LUMENEQUIVALENT ONLY WITH PRIOR OWNER APPROVAL FLANGE MOUNTING KIT NOMINAL LED
4000K
LF- L6K LITHONIA CPANL-2X4-40/50/60-40K-M2-2X4CFMK 2X4 FLAT PANEL; FLANGE MOUNT; MULTI-VOLT, ELECTRONIC, DIMMABLE DRIVER; FLANGE 53 W 6000 LUMENEQUIVALENT ONLY WITH PRIOR OWNER APPROVAL FLANGE MOUNTING KIT NOMINAL LED
4000K
OW3- L3K LITHONIA WSTLED-P2-40K-VFW-MVOLT-SCBA EXTERIOR WALL TRAPEZOID; LED LAMPING; TYPE 3 OPTICAL WALL 25 W 3000 LUMENOR EQUIVALENT DISTRIBUTION; MULTI-VOLT, DIMMABLE DRIVER NOMINAL LED
4000K
NOTES
MECHANICAL EQUIPMENT SCHEDULE
SYM DESCRIPTION LOAD VOLTS PHASEFIRE ALARMSHUTDOWN
CONTROLCIRCUITS
BY* STARTER
BY
SAFETYDISCONNECT
BY REMARKS
FC- 1 FAN COIL UNIT 30.9 MCA35 MOCP 208 3 NO MECH MECH MECH
FC- 2 FAN COIL UNIT 30.9 MCA35 MOCP 208 3 NO MECH MECH MECH
FC- 3 FAN COIL UNIT 30.9 MCA35 MOCP 208 3 NO MECH MECH MECH
FC- 4 FAN COIL UNIT 30.9 MCA35 MOCP 208 3 NO MECH MECH MECH
OH- 1D OH DOOR OPENER: DEMO 1/2 HP 120 1
* ELECTRICAL CONTRACTOR VERIFY SINGLE SPEED OR TWO SPEED STARTERS WITH MECHANICAL DRAWINGS.
LOCATION MOUNTINGPANEL 1P15 TYPE NQOD 3 Ø 4 WIRE 120/208 VOLTS
STAGING FLUSHNEW REMARKS 143.1 HALL X SURFACE
X EXISTING -ALL CIRCUITS CONSIDERED EXISTING UNLESS OTHERWISE INDICATED IN THESE DRAWINGS1 NEMA RATING 225 AMP MAINX BOLT ON BREAKERS X LUGS
ISOLATED GROUND BUS BREAKERSURGE PROTECT (SPD)
No. BRKR CIRCUIT DESCRIPTION L O MWIRE/CND CIRC.
LOADCIRC.LOAD
WIRE/CNDL O M CIRCUIT DESCRIPTION BRKR No.
A P P N G C A B C P N G C A P1 20 1 LTG: FREEZER, THAW ROOM 14 EX EX EX EX 2880 2880 EX EX EX EX 1 30A, 120V, TWIST LOCK 30 1 23 20 1 LTG: PACKAGING 11 EX EX EX EX 2880 2880 EX EX EX EX 1 30A, 120V, TWIST LOCK 30 1 45 20 1 LTG: PACKAGING 12 EX EX EX EX 360 360 EX EX EX EX 2 GFI CO'S: STAGING 20 1 67 20 1 LTG: INCUBATOR 16 12S 12S 12S 3/4S 848 1208 360 EX EX EX EX 2 CO'S: PACKAGING 20 1 89 20 1 SPARE 360 360 EX EX EX EX 2 CO'S: PACKAGING 20 1 1011 20 1 SPARE 180 180 EX EX EX EX 1 DROP CORD: PACKAGING 20 1 1213 20 1 SPARE 180 180 EX EX EX EX 1 DROP CORD: PACKAGING 20 1 1415 20 1 SPARE 540 540 EX EX EX EX 3 CO'S: PACKAGING 20 1 1617 20 1 SPARE 540 540 EX EX EX EX 3 CO'S: PACKAGING 20 1 1819 20 1 SPARE 540 540 EX EX EX EX 3 CO'S: PACKAGING 20 1 2021 20 1 SPARE 180 180 EX EX EX EX 1 GFI CO: EXTERIOR 20 1 2223 20 1 SPARE 1176 1176 EX EX EX EX 1 OH DOOR: PACKAGING 20 1 2425 20 1 SPARE 229 229 EX EX EX EX 2 FREEZER HEAT TRACE 20 1 2627 20 1 SPARE 1824 1824 EX EX EX EX 1 CONDENSATE PUMP 30 2 2829 20 1 SPARE 1824 1824 EX 1 - - - 3031 20 1 SPARE 360 360 EX EX EX EX 2 CO'S: THAW ROOM EQUIP 20 1 3233 20 1 PLUGS: E INC N 2 12S 12S 12S 3/4S 360 888 528 EX EX EX EX 2 RADIANT/UNIT HEATER 20 1 3435 20 1 PLUGS: E INC S 2 12S 12S 12S 3/4S 360 1522 1162 EX EX EX EX 2 CIRC FAN, RAD HEAT PUMP 20 1 3637 20 1 PLUGS: W INC S 2 12S 12S 12S 3/4S 360 360 SPARE 20 1 3839 20 1 PLUGS: W INC N 2 12S 12S 12S 3/4S 360 360 SPARE 20 1 4041 20 1 PLUGS: INC VESTIBULE 2 12S 12S 12S 3/4S 360 360 SPARE 20 1 42
TOTALS 5757 7032 5962AIC 25000
SCCR 25000FEEDER SEE ONE-LINE AMPS/PHASE 48 59 50 PARALLEL RUNS SEE ONE-LINE
BREAKER CODES A=ARC-FAULT; G=GROUND FAULT; H=HACR; L=LOCKING HANDLE; S=SHUNT TRIP; R=RED PAINTED HANDLE
WIRE CODESI=ADD'L ISO GROUND TO MATCH SAFETY GROUND; S=UNLESS OTHERWISE SPECIFIED
GENERAL CODES1LIN=SEE ONE-LINE DIAGRAM
LOCATION MOUNTINGPANEL 1P16 TYPE NQOD 3 Ø 4 WIRE 120/208 VOLTS
FLUSHX NEW REMARKS X SURFACE
EXISTING -ALL CIRCUITS CONSIDERED EXISTING UNLESS OTHERWISE INDICATED IN THESE DRAWINGS1 NEMA RATING -+=PROVIDE NEW BREAKER IN EXISTING PANEL 400 AMP MAINX BOLT ON BREAKERS -*=VERIFY WITH EQUIPMENT NAMEPLATE AND/OR SUBMITTAL PRIOR TO GEAR RELEASE LUGS
ISOLATED GROUND BUS X BREAKERSURGE PROTECT (SPD)
No. BRKR CIRCUIT DESCRIPTION L O MWIRE/CND CIRC.
LOADCIRC.LOAD
WIRE/CNDL O M CIRCUIT DESCRIPTION BRKR No.
A P P N G C A B C P N G C A P1 20 3 HIGH SPEED DOORS: FREEZER 2 EX EX EX EX 1104 4812 3708 10 10 10 3/4 1 INC FAN COIL (FC-1) +35H* 3 23 - - - 2 EX 1104 4812 3708 10 1 - - - 45 - - - 2 EX 1104 4812 3708 10 1 - - - 67 20 3 HIGH SPEED DOORS: FREEZER 2 EX EX EX EX 1104 4812 3708 10 10 10 3/4 1 INC FAN COIL (FC-2) +35H* 3 89 - - - 2 EX 1104 4812 3708 10 1 - - - 1011 - - - 2 EX 1104 4812 3708 10 1 - - - 1213 20 3 HIGH SPEED DOORS: AGAMMA 3 EX EX EX EX 1656 5364 3708 10 10 10 3/4 1 INC FAN COIL (FC-3) +35H* 3 1415 - - - 3 EX 1656 5364 3708 10 1 - - - 1617 - - - 3 EX 1656 5364 3708 10 1 - - - 1819 20 3 HIGH SPEED DOORS: FILTRATION 2 EX EX EX EX 1104 4812 3708 10 10 10 3/4 1 INC FAN COIL (FC-4) +35H* 3 2021 - - - 2 EX 1104 4812 3708 10 1 - - - 2223 - - - 2 EX 1104 4812 3708 10 1 - - - 2425 30 3 CLEAN ROOM COND. UNIT 1 EX EX EX EX 1800 6300 4500 EX EX EX EX 1 THAW ROOM CONDENSER 70 3 2627 - - - 1 EX 1800 6300 4500 EX 1 - - - 2829 - - - 1 EX 1800 6300 4500 EX 1 - - - 3031 30 3 CLEAN ROOM COND. UNIT 1 EX EX EX EX 1800 3804 2004 EX EX EX EX 1 PRODUCT COOLER UNIT 30 3 3233 - - - 1 EX 1800 3804 2004 EX 1 - - - 3435 - - - 1 EX 1800 3804 2004 EX 1 - - - 3637 20 3 AIR HANDLER 1 EX EX EX EX 1272 1272 SPACE 3839 - - - 1 EX 1272 1272 SPACE 4041 - - - 1 EX 1272 1272 SPACE 42
TOTALS 31176 31176 31176AIC 42000
SCCR 42000FEEDER SEE ONE-LINE AMPS/PHASE 260 260 260 PARALLEL RUNS SEE ONE-LINE
BREAKER CODES A=ARC-FAULT; G=GROUND FAULT; H=HACR; L=LOCKING HANDLE; S=SHUNT TRIP; R=RED PAINTED HANDLE
WIRE CODESI=ADD'L ISO GROUND TO MATCH SAFETY GROUND; S=UNLESS OTHERWISE SPECIFIED
GENERAL CODES1LIN=SEE ONE-LINE DIAGRAM
9/3/20
19 2:
21 P
MLA
ST S
AVED
: 29-
Aug-
19T:
\Jobs
\2019
053 G
E Inc
ubato
r\01 D
rawi
ngs\0
5 Elec
trical\
Sine
Sou
rce P
rojec
t\She
ets\E
P-60
2 ELE
CTRI
CAL S
CHED
ULES
.dwg
9/3/2019
© COPYRIGHT DESIGN WEST ARCHITECTS 201954321
A
B
D
C
desi
gn w
est
arch
itect
s25
5 SO
UTH
300
WES
T79
5 NO
RTH
400
WES
TLO
GAN
UT
843
21SA
LT L
AKE
CITY
UT
841
03
PROJECT #:
DRAWN BY:
CHECKED BY:
ISSUED:
GE IN
CUBA
TOR
ADDI
TION
LOGA
N, U
TAH
8432
1
-
D. PATTON
S. SWENSON
09.03.2019
-
MARK
:DA
TE:
DESC
RIPT
ION:
ELECTRICALSCHEDULES
EP-602