www.systemcontrol.com.au 1 GASGUARD 1 Automatic Gas Safety System Consisting of Gas safety shut off valve and Gas safety control panel Ref:30429-0809 Automatic testing of the down-stream installation to check that all valves are closed and that pipework and fittings are gas tight before each system start-up. Protection from accidental or intentional misuse by students or users. Short testing time, with automatic start-up if no leakage was detected from previous operation. Easy installation and wiring due to combined gas valve block design and pre- wired system. Easy commissioning and trouble-shooting using logic diagram. Remote control by BMS, if required. Function according to AS5601 when Fire Suppressant System is installed. All safety components are AGA approved.

Transcript of GASGUARD 1 - Home | QR...(3) Operation gas flow must be less than recommend Max. gas flow. (4) Power...

Page 1: GASGUARD 1 - Home | QR...(3) Operation gas flow must be less than recommend Max. gas flow. (4) Power consumption at holding time when 240V AC power supplied. 4, Order Example: L0200-0501RWBK

www.systemcontrol.com.au 1

GASGUARD 1

Automatic Gas Safety System Consisting of Gas safety shut off valve and Gas safety control panel

Ref:30429-0809

• Automatic testing of the down-stream installationto check that all valves are closed and that pipeworkand fittings are gas tight before each system start-up.

• Protection from accidental or intentional misuse by students or users.

• Short testing time, with automatic start-up if no leakage was detected fromprevious operation.

• Easy installation and wiring due to combined gas valve block design and pre-wired system.

• Easy commissioning and trouble-shooting using logic diagram.

• Remote control by BMS, if required.

• Function according to AS5601 when Fire Suppressant System is installed.

• All safety components are AGA approved.

Page 2: GASGUARD 1 - Home | QR...(3) Operation gas flow must be less than recommend Max. gas flow. (4) Power consumption at holding time when 240V AC power supplied. 4, Order Example: L0200-0501RWBK

GASGUARD 1 Installation And Commissioning Instruction   

Page 3: GASGUARD 1 - Home | QR...(3) Operation gas flow must be less than recommend Max. gas flow. (4) Power consumption at holding time when 240V AC power supplied. 4, Order Example: L0200-0501RWBK

www.systemcontrol.com.au 2

Laboratory Workbench

GASGUARD 1 GASGUARD 1 safety system is to be installed on the gas supply to a college or commercial laboratory, school learning space, commercial kitchen, boiler room or similar installation.1

Example of application in a school or laboratory The standard GASGUARD 1 can be installed inside or outside of the room. A ball valve and pressure regulator should be installed upstream of each GASGUAD safety systems.

Learning Space

The GASGUARD 1 is to be operated by qualified or trained person with key switch.

Before each start-up, the GASGUARD will automatically check the entire downstream installation for leakage and for adequate gas pressure. The GASGUARD will only supply gas once all gas outlets are closed. If required, the control panel can be supplied with an integral Emergency Shut-off button or these can be fitted remotely.

Kitchen

Teaching

Laboratory

GASGUARD 1

Page 4: GASGUARD 1 - Home | QR...(3) Operation gas flow must be less than recommend Max. gas flow. (4) Power consumption at holding time when 240V AC power supplied. 4, Order Example: L0200-0501RWBK

www.systemcontrol.com.au 3

ASGUARD Example of application in a commercial building or factory

A central GASGUARD 1 can be installed in the Gas Meter Room. It can be activated manually, interlocked with the Fire Services system or remotely by BMS. A Ball Valve, Gas Filter Pressure Regulator may be installed up-stream.

FQ

CentralShut-off System

Kitchen

BoilerRoom

Workshop

For the commercial building management

GASGUARD 1 can be used as gas safety system for kitchens, boiler rooms, work shops, and other gas installations.

Before every system start up, the GASGUARD will automatically check the entire down-stream installation for leaks, tight closing of valves and adequate supply pressure. The GASGUARD will only supply gas once all gas outlets are closed and The integrity of the pipework is proved.

Commercial Kitchen

Commercial Boiler Room

GASGUARD 1

Page 5: GASGUARD 1 - Home | QR...(3) Operation gas flow must be less than recommend Max. gas flow. (4) Power consumption at holding time when 240V AC power supplied. 4, Order Example: L0200-0501RWBK

www.systemcontrol.com.au 4

Installation and accessories GASGUARD can be connected to any safety interlock such as: emergency stop button, fire alarm system, fan pressure switch, gas leakage detector. GASGUARD can be remotely controlled by BMS.

Filter Regu GASGUARD

L0200P

GLD

PS

BMS Building management systemESB Emergency stop buttonGLD Gas leakage detectorPS Pressure switch for fanFAS Fire alarm system

BMS

ESB FAS

Ball valve

OPSO regulator Gas detector Stop button pressure switch Stop button

Optional accessory

Order No. Name Description L0201** Emergency stop button Twist/Key reset GFK *** Gas filter Optional diameter from 15-200mm. DG *** Pressure switch Optional pressure range up to 50kpa TCSE126KM(KG) Gas detector Wall fixed sensor and panel (KM for NG, KG for LPG) TCSE301A Alarm Siren and flashing lamp 230V AC (12V DC is optional)

Please contact SCE for additional product information

GASGUARD 1

Page 6: GASGUARD 1 - Home | QR...(3) Operation gas flow must be less than recommend Max. gas flow. (4) Power consumption at holding time when 240V AC power supplied. 4, Order Example: L0200-0501RWBK

www.systemcontrol.com.au 5

Technical data

Type of gas: Natural gas, LPG(gaseous), Biologically produced methane (Max. 0.1%-by-vol. H2S) or air; other gases on request. The gas must be dry in all temperature and must not contain condensate.. Inlet pressure Pe Max.: 35 kPa ( For higher pressure please go to GASGUARD 3) Operating time: Quick opening time ≤1s

Quick closing time <1s

Storage temperature: 0-60℃ Working ambient temperature: -20- +60℃ No condensation permitted. Safety valve: A Class AG3968 Main voltage: 240V AC, +5/-15%, 50/60HZ;

120V AC, +5/-15%, 50/60HZ; 24V DC, ±20% Duty cycle: 100% Power factor of valve coil: cosØ=1 BMS interface: 24V DC. Cable gland: M20×1.5 Electrical connection: Terminal Max. 1.5mm² or plug with socket to EN 175301-803. Enclosure: IP 54 Switch frequency: Arbitrary. Valve housing: Aluminum, Valve seal: NBR Connection: Rp20-Rp65 Position indication contact rating: 240V AC, 3A Panel material: Plastic (special on request)

Wiring diagram

Easy installation thanks to pre-wired 2m cable with plug between the control panel and gas valves by SCE. Interlock circuit for external Emergency Shut-off buttons. Options include - 24V DC interface for BMS or Fire Services panel. Voltage free feedback showing main valve position for BMS Reserved terminals for additional safety interlock: emergency stop button, exhaust fan pressure switch, gas detector, etc.

GASGUARD 1

Page 7: GASGUARD 1 - Home | QR...(3) Operation gas flow must be less than recommend Max. gas flow. (4) Power consumption at holding time when 240V AC power supplied. 4, Order Example: L0200-0501RWBK

www.systemcontrol.com.au 6

Control panel and main valve dimensions

GASGUARD 1 gas flow rate and pressure drop

1, Natural gas sg=0.62 2, LPG sg=1.65 3, Air sg=1.00

Max. ∆P≤0.25kpa of GASGUARD is recommended. The pressure drop can’t be higher than 10% of inlet pressure. 1kpa=10mbar

GASGUARD 1

Main valve dimension

GASGUARD type Connection(thread) Dimensions (mm)

Weight(kg) Rp(inch) Rp(mm) L E F H1(S) H2 L0200-0201RWBK(S) 3/4 20 91 115 23 140(159) 32 2.5 L0200-0251RWBK(S) 1 25 91 115 23 140(159) 32 2.4 L0200-0321RWBK(S) 11/4 32 127 128 29 164(185) 47 4.8 L0200-0401RWBK(S) 11/2 40 127 128 29 164(185) 47 4.7 L0200-0501RWBK(S) 2 50 155 136 36 229(250) 59 8.2 L0200-0651RWBK(S) 21/2 65 155 136 36 229(250) 59 8.0

Page 8: GASGUARD 1 - Home | QR...(3) Operation gas flow must be less than recommend Max. gas flow. (4) Power consumption at holding time when 240V AC power supplied. 4, Order Example: L0200-0501RWBK

www.systemcontrol.com.au 7

How to select a GASGUARD 1? 1, Information requirement: Please click below information to size a GASGUARD 1,

1, Application: Laboratory □ Kitchen □ Boiler room □ Building management □ other ___________

2, Gas type: Nat gas □ LP gas □ other ____________

3, Gas pressure: 2.75kpa □ 5kpa □ 7kpa □ 35kpa □ other ________ kPa

4, Max. gas flow: ______________MJ/h or _______________m3/h

5, Gas pipe diameter: 20mm □ 25mm □ 32mm □ 40mm □ 50mm □ 65mm □ other ________ mm

6, Power supply: 240V AC □ 24V DC □ Other__________________

7, BMS or fire alarm control signal: 240V AC □ 24VDC □

8, Voltage free valve position feedback signal to BMS: Yes □ No □

9, Optional or special requirement: _____________________________________________________ __________________________________________________________________________________

2, Standard models GASGUARD 1:

3, GASGUARD 1L Laboratory Version:

Remark:

(1) All valves are BSP thread connection (2) When the gas pressure higher than 35kPa or diameter bigger than 65mm, please go to GASGUARD 2 or 3 (3) Operation gas flow must be less than recommend Max. gas flow. (4) Power consumption at holding time when 240V AC power supplied.

4, Order Example: L0200-0501RWBK

* If “none”, this specification is omitted Special requirement for GASGUARD contact System Control Engineering for more information.

Order No. Valve size(1)

Pe Max. kPa(2)

V Max. Gas flow @ 0.25kpa ∆P(3) Power consumption W(4) NG LPG

m3/h MJ/h m3/h MJ/h L0200-0201RWBK(S)* Rp20 35 17 650 10 800 38 L0200-0251RWBK(S)* Rp25 35 20 750 12 950 38 L0200-0321RWBK(S)* Rp32 35 40 1500 25 2000 61 L0200-0401RWBK(S)* Rp40 35 50 1700 30 2400 61 L0200-0500RWBK(S)* Rp50 35 80 3000 50 4000 71 L0200-0650RWBK(S)* Rp65 35 85 3200 50 4000 71

Order No. Valve size(1)

Pe Max. kPa

V Max. Gas flow @ 0.1kpa ∆P(3) Power consumption W(4) NG LPG

m3/h MJ/h m3/h MJ/h L0200-0251LRW Rp25 10 12 450 7 550 38

GASGUARD 1

Page 9: GASGUARD 1 - Home | QR...(3) Operation gas flow must be less than recommend Max. gas flow. (4) Power consumption at holding time when 240V AC power supplied. 4, Order Example: L0200-0501RWBK

GASGUARD 1 Installation And Commissioning Instruction   

GASGUARD 1 Installation And Commissioning Instruction

 System Control Engineering Pty Ltd 

Ref: 34129 

Page 10: GASGUARD 1 - Home | QR...(3) Operation gas flow must be less than recommend Max. gas flow. (4) Power consumption at holding time when 240V AC power supplied. 4, Order Example: L0200-0501RWBK

GASGUARD 1 Installation And Commissioning Instruction   

www.systemcontrol.com.au 

GASGUARD 1 ‐Gas Safety Shut Off System Installation and Commissioning Instructions 

Please read this introduction and the valve manual before any operation and keep in a safe place. 

Warning:   All the work set out in these operating 

instructions must be completed by authorized trained personnel! Incorrect installation, adjustment, modification, operation or maintenance may cause injury or material damage.       

Check delivery Check the quantity of products are match 

your order. No visible damage to goods  Check before installation Main power voltage, electric power 

consumption, ambient temperature, enclosure, inlet gas pressure and installation position‐see label on the valve and control panel. 

Valve installation position Valve can be installed in vertical position or horizontal position, but not upside down. The valve must at a min. distance of 20mm from any material whatsoevers.  

Check the gas flow direction before fasting to pipe 

Tightness test on the up and down stream pipe, shut off all gas appliances before starting the GASGUARD 

Pe max: 50kpa 

Caution: The solenoid bodies on the valves heat up during operation. Coil temperature depends on the ambient temperature. 

Caution! Valve PeMax. is 50kpa, operating PeMax. is 35kPa.Any over pressure operation will cause unrepairable damage to the valves. 

Caution! Do not clamp the unit in a 

vice. This could cause external leakage. Only secure the flange by holding the octagon with a suitable spanner. 

Page 11: GASGUARD 1 - Home | QR...(3) Operation gas flow must be less than recommend Max. gas flow. (4) Power consumption at holding time when 240V AC power supplied. 4, Order Example: L0200-0501RWBK

GASGUARD 1 Installation And Commissioning Instruction   

www.systemcontrol.com.au 

System Adjustment The bypass valve VBY and Pressure switch DG are pre‐set by manufacture. 

Commissioning and Troubleshooting 

 

 Please see the file of GASGUARD Commissioning and Troubleshooting. Important! Before commissioning, the down stream pipe pressure must be released and all pipes must be leak‐proof. 

Maintenance of System 

Test For Internal and External leakage Check for any external leaking in the pipe and valve connections and the valve body. Check for any internal leaking of the valve, if so, change to a new valve. 

Function Check Follow the instruction of Commissioning and Trouble‐ shooting to do the function check. 

Control Panel Installation Wall mounting panel dimension and screw size see below. 

Wiring GASGUARD prewired with 2m lead with 3pin plug for power supply. If no power point is available change to hard wire. 1m (Lab version) or 2m prewired cable with quick connection plug from the valves to panel, 2m extension cable is optional (L0200‐PC03). 

Wire Selection 

Wire size is Max. 1.5mm2   Flexible wire is recommended. 

The unit MUST be protected from water and U.V.

For more details of valves and control panel, see the Kromschroeder product instructions and SCE wiring drawing. 

Caution! In order to ensure smooth and 

safe operation: check the inlet and outlet tightness and function of the GASGUARD every year.  

Caution! Commission may only be carried out by an authorised fitter or authorised person. The unit may only be released for unsupervised operation once commissioning has been completed correctly. 

Page 12: GASGUARD 1 - Home | QR...(3) Operation gas flow must be less than recommend Max. gas flow. (4) Power consumption at holding time when 240V AC power supplied. 4, Order Example: L0200-0501RWBK

No

No

No

No No

No

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Check valve is installed with correct voltage coil and gas flow direction.

No Yes

Is leakage test OK for all of the down- stream gas pipework?

Install the valve properly by following the instructions

Test & fix any leakage point on the pipe.

Is GASGUARD wired correctly? Rewire following the wiring diagram

Relieve down stream pipe pressure and shut off all gas appliances

Reset all safety interlocks: fire alarm system, Emergency stop button, BMS, etc.

Turn on the GASGUARD by key switch

Is the “Power ON” and the “Gas OFF”

lamp on?

If only “Gas OFF” is lit, check the “Power ON” globe

“Power ON” and “Gas ON” light immediately. Check the valve for any internal leakage

If only “Power ON” is lit, reset the stop button on panel or check “Gas OFF” lamp

Are you ready?

No light on? Check the power supply, interlock or fuse

GASGUARD Commissioning and Troubleshooting Follow the procedure below to commission your GASGUARD correctly …… and safely.

• All installation and wiring must be carried out by a licensed plumber and electrician!• All the work described in these instructions may only be completed by authorized, trained personnel!• Warning! Incorrect installation, adjustment, modification, operation or maintenance may cause injury or material damage

Page 13: GASGUARD 1 - Home | QR...(3) Operation gas flow must be less than recommend Max. gas flow. (4) Power consumption at holding time when 240V AC power supplied. 4, Order Example: L0200-0501RWBK

No

Yes Yes

YesYes

Yes

Yes

Yes

Turn on the gas appliances to check system is functioning correctly

If fitted, turn off and reset system using “Stop button” to check

If fitted, turn off and reset system using interlocks or BMS.

Shut off system and relieve down steam gas pressure, restart system, double check the testing time.

Check for any down stream leakage (pipe fittings, appliance turned on etc.) or bypass valve not functioning.

You have set up the GASGUARD properly

No No Press and hold “Start” button.

“Gas ON” is Lit .

Yes

No

Check function of main gas valve

Name _______________________

Signature_____________________

Date: ___/___/_______

Service Phone: ________________

Company :_____________________

______________________________

Write down the testing time on the side label

“Gas ON” is not lit after pressing the “Start” button for long period

“Gas OFF” lamp off, but “Gas ON” not lit. Check the “Gas ON” globe

Check the gas supply pressure

www.systemcontrol.com.au Ref: 30441 - 0809

Page 14: GASGUARD 1 - Home | QR...(3) Operation gas flow must be less than recommend Max. gas flow. (4) Power consumption at holding time when 240V AC power supplied. 4, Order Example: L0200-0501RWBK

9 P

IN p

lug

SY

ST

EM

C

ON

TR

OL

E

NG

INE

ER

ING

AC

N 0

06

491

88

1

P

TY

LT

DA

BN

61

81

5 3

05

49

6

ME

LB

OU

RN

E

S

YD

NE

Y

B

RIS

BA

NE

A

DE

LA

IDE

AU

CK

LA

ND

ww

w.s

yste

mcon

tro

l.com

.au

DA

TE

:1

9-0

3-2

01

1

DR

AW

N:

SC

E

RE

VIS

ION

PA

GE

:1

NE

XT

DW

G N

o.

39648

DA

TE

OF

:1

EN

12

34

5N

67

811

12

13

910

14

15

16

E

B2

CN

CN

O

EB

Sta

nd

ard

24

V D

C c

on

tro

l sig

na

l fr

om

BM

S

or

fire

ala

rm s

yste

m,

Mo

ve

po

we

r su

pp

ly fro

m te

rmin

al 2

to

term

ina

l 1

EB

E

me

rgency S

top B

utton

VB

B

ypass G

as V

alv

e

VM

Main

Gas V

alv

e

PS

P

ressure

Sw

itch

CP

I C

lose P

ositio

n Indic

ation

Sw

itch

B1 B

ridge

B2 B

ridge

Op

tio

nal

Vo

ltag

e

fre

e v

alv

e p

ositio

n

fee

db

ack f

or

bu

ildin

g

ma

na

ge

me

nt

syste

m

GA

SG

UA

RD

Co

ntr

ol

Pan

el &

Eq

uip

me

nt

Wir

ing

L0

20

0-P

VM

CP

IP

S

CN

C

NO

NC

NO

C

Ne

w T

erm

ina

l #

Wir

e s

ize

to t

he

pa

ne

l: f

lexib

le w

ire

1-1

.5m

m2

NL

24

0V

AC

2m

pre

wir

ed c

ab

le f

rom

co

ntr

ol p

an

elto

valv

es,

1m

fo

r L

ab v

ers

ion

1,

Mo

ve

po

wer

su

pply

fro

m t

erm

ina

l 2

to t

erm

ina

l 1

wh

en

24

V D

C c

on

ne

cte

d t

o t

erm

inal1

5 &

16

fro

m

fire

serv

ice

s p

an

el.

2,R

em

ove

lin

kB

2 W

he

n c

on

ne

cting

an

y

rem

ote

sa

fety

in

terl

ock s

uch

as e

me

rgen

cy

sto

p b

utt

on

s,

fan

sw

itche

s,

flo

w s

witch

es,

gas d

ete

cto

rse

tc.

3.2

m le

ad

With

3 p

in p

lug f

or

po

we

r sup

ply

.

Gas in

let

CO

NT

RO

L P

AN

EL

Page 15: GASGUARD 1 - Home | QR...(3) Operation gas flow must be less than recommend Max. gas flow. (4) Power consumption at holding time when 240V AC power supplied. 4, Order Example: L0200-0501RWBK

SYST

EM C

ON

TRO

L E

NG

INEE

RIN

GAC

N 0

06 4

91 8

81

PT

Y LT

DAB

N 6

1 81

5 30

5 49

6M

ELB

OU

RN

E

S

YDN

EY

B

RIS

BA

NE

AD

ELA

IDE

AU

CK

LAN

Dw

ww

.sys

tem

cont

rol.c

om.a

u

DAT

E:03

08

2009

DR

AWN

: SC

E

REV

ISIO

NPA

GE:

1

NEX

T

DW

G N

o. 3

4127

DAT

E

OF:

1D

imen

sion

sfo

r GA

SGU

AR

Dco

ntro

l pan

el

L020

0-P

Key

Sw

itch

Stop

but

ton

Pow

er O

nPr

ess

& H

old

for

star

tR

eady

to T

est

Gas

On

whe

n Li

t

SCE

GA

SGU

AR

D

200m

m

120mmG

as O

ff w

hen

Lit

Off

O

n

Opt

iona

l

75m

m125m

m4

of s

crew

to

open

the

pane

l

105m

m

Hei

ght w

ithou

t sto

p bu

tton

SCE

GA

SGU

AR

DC

ontr

ol p

anel

212m

m

108mm

5mm

Dia

met

er

Dim

ensi

ons

for m

ount

ing

Page 16: GASGUARD 1 - Home | QR...(3) Operation gas flow must be less than recommend Max. gas flow. (4) Power consumption at holding time when 240V AC power supplied. 4, Order Example: L0200-0501RWBK

SY

ST

EM

CO

NT

RO

LE

NG

INE

ER

ING

AC

N00

64

91

88

1P

TY

LT

DA

BN

61

81

53

05

49

6

ME

LB

OU

RN

ES

YD

NE

YB

RIS

BA

NE

AD

EL

AID

EA

UC

KL

AN

Dw

ww

.sys

tem

con

tro

l.com

.au

DA

TE

:0

30

82

00

9

DR

AW

N:

SC

E

RE

VIS

ION

PA

GE

:1

NE

XT

DW

GN

o.346

98

DA

TE

OF

:1M

ou

nti

ng

Tem

pla

tefo

rG

AS

GU

AR

DC

on

tro

lP

an

el

L0

20

0-P

1:1

SC

EG

AS

GU

AR

D

Co

ntr

olp

an

el

5m

mD

ia

212m

m

108mm

Scale

:fu

llsiz

e

Page 17: GASGUARD 1 - Home | QR...(3) Operation gas flow must be less than recommend Max. gas flow. (4) Power consumption at holding time when 240V AC power supplied. 4, Order Example: L0200-0501RWBK

www.systemcontrol.com.au 8

For additional information on this system or other products, please contact your loacal System Control Engineering Pty . Ltd. office or visit www.systemcontrol.com.au

We reserve the right to make technical modification in the interests progress

Victoria New South Wales Queensland South Australia New Zealand Tel: (03) 9845 0000 Tel: (02) 9838 9966 Tel: (07) 3801 4223 Tel: (08) 8401 9870 Tel:(09) 9636 1401 Fax: (03) 9878 5337 Fax: (02) 9838 8788 Fax: (07) 3801 4229 Fax: (08) 8312 4963 Fax:(09)9636 1525

Distributed by:

GASGUARD 1

Typical GASGUARD 2&3

Page 18: GASGUARD 1 - Home | QR...(3) Operation gas flow must be less than recommend Max. gas flow. (4) Power consumption at holding time when 240V AC power supplied. 4, Order Example: L0200-0501RWBK

GASGUARDOPERATING INSTRUCTIONS

- To be installed adjacent to the control panel -

1. Turn OFF all gas appliances and outlets which are served by this

GASGUARD

2. Check that the Inlet gas supply is turned ON

3. Turn the Key Switch ON. The WHITE Power On lamp will come on.

If the WHITE lamp does not come on, check any applicable circuit

breakers or contact your electrician.

4. Now, either the YELLOW or GREEN lamps should be lit.

If neither lamp is lit, reset any Emergency Stop switches or other

devices that are interlocked with the control panel. There may be one

on the top right of the panel and/or in locations remote from the panel.

5. If the GREEN, Gas On lamp is lit, the gas supply has automatically detected

that the system is good and you can use your gas appliances, as required.

6. If the YELLOW Ready to Test light is illuminated, press and hold the GREEN

button until this GREEN Gas On button is lit.

See below for the approximate time you must hold this button to

pressure test your system.

7. If the GREEN Gas On lamp does not come on, go to Step 1 and again check

that ALL gas appliances and valves are turned off.

8. If the above operations do not restore your gas supply, you may have a gas

leakage that must be checked by a qualified person.

Your Service Contact …………………………………………………………

Approximate Hold Time (Item 6) for this system …….. seconds / minutes