Gas Management Systems Medical Vacuum Systems … … · Benefits Medical Vacuum Systems | 03 The...

4
Medical Vacuum Systems Gas Management Systems Dräger plans, builds, maintains and certifies high-quality vacuum systems for medical applications. All systems can be tailored to suit any hospital's needs and feature highly reliable components and redundant design. At the heart of the vacuum system, the Dräger Medical Vacuum Control (MVC™) ensures medical-grade quality and offers a wide range of monitoring and alarm functions. MT-5166-2004 Bacteria double filter Secretion trap Distribution systems MVC™ Medical Vacuum Control Vacuum receiver Pumps Oil-lubricated rotary vane vacuum pumps Exhaust Air To hospital system

Transcript of Gas Management Systems Medical Vacuum Systems … … · Benefits Medical Vacuum Systems | 03 The...

Medical Vacuum SystemsGas Management Systems

Dräger plans, builds, maintains and certifies high-quality vacuum systemsfor medical applications. All systems can be tailored to suit any hospital'sneeds and feature highly reliable components and redundant design.At the heart of the vacuum system, the Dräger Medical Vacuum Control(MVC™) ensures medical-grade quality and offers a wide range ofmonitoring and alarm functions.

MT-

5166

-200

4Bacteria double filterSecretion trap Distribution systems

MVC™Medical Vacuum

Control

Vacuum receiverPumpsOil-lubricated rotary vane vacuum pumps

Exhaust Air

To hospital system

Benefits

02 | Medical Vacuum Systems

50 Years of experience

Vacuum generation is an essential component of the supply system for medical gases in any hospital, and areliable vacuum supply is indispensable in everyday clinical routine. Dräger has more than 50 years’ experiencein the development and manufacturing of fully automatic vacuum systems, which are used to aspirate fluids andsecretions in the OR, on the ICU and on regular treatment wards. Dräger offers its customers comprehensiveplanning, project management, installation and service from a single source. We use only proven qualityproducts that conform to all relevant statutory regulations and standards.

Uncompromising reliability

The combination of high-quality components and intelligent system design ensures reliable operation andguarantees the vacuum supply even in the case of component malfunctions. All key components, such aspumps, filters and contactors, are backed up with identical reserve units in a redundant design based onrelevant standards and thorough risk assessment. Built-in safety features can counter critical incidents, suchas short circuits, overloads or cable breaks. This redundancy also allows maintenance of the system withoutinterrupting the vacuum supply. Comprehensive alarm and monitoring functionality gives the operator constantfeedback on the status of the system and informs immediately in case of any operational or emergency alarm.In addition, the fully automatic, PLC-based system (programmable logic control), which includes base-loadswitchover, is backed up by mechanical pressure switches for maximum supply continuity.

System design

Quality and reliability are top priorities for our medical supply systems. That is why we emphasize absolutecompliance with all pertinent regulations and quality guidelines during the project planning and installationphases of all systems. Dräger builds vacuum plants according to ISO 7396-1. This quality approach is also validfor every single component of the system.

User friendly

Thanks to the MVC, Dräger vacuum systems are extremely user friendly. The constant control of the vacuumsupply using state-of-the-art sensors combined with PLC ensure fully automatic operation. An integrated,multilingual text display provides comprehensive information on alarm status, operational status and serviceintervals, keeping you informed as to the condition of your system at a glance.

Modular design

The precision-engineered, modular design of Dräger vacuum systems can be tailored exactly to any hospital'sneeds. At the core of the system, two to four oil-free or oil-lubricated pumps with performance ratingsranging from 1.1 kW to 18.5 kW provide the required vacuum at the specified redundancy level. All othersystem components, such as receivers, bacterial filters and secretion traps, are chosen to match the systemdimensions.

Benefits

Medical Vacuum Systems | 03

The PLC-based control panel can be programmed according to system configuration and operational demandsto provide optimal system operation and satisfy individual hospital requirements.

Alarm integration

The Medical Vacuum Control monitors and switches the vacuum pumps to ensure an even aggregate load andalert you to any system malfunction as early as possible. Both control and alarm signals can be transferred toexternal systems via potentialfree contacts, or be fed directly to the optional Dräger Alarm Management System(AMS).

AMS manages all the alarms that the Gas Management System can provide and can also transfer those alarmsto your existing building management system.

MVC™

Designed and manufactured by Dräger, the MVC is a medical vacuum control system that can be seamlesslyintegrated into the Dräger alarm management system. It gives you the peace of mind of knowing that everythingis under complete control.

Technical Data

04 | Medical Vacuum Systems

CORPORATE HEADQUARTERSDrägerwerk AG & Co. KGaAMoislinger Allee 53–5523558 Lübeck, Germanywww.draeger.com

Manufacturer:Dräger Medical GmbHMoislinger Allee 53-5523558 Lübeck, Germany

REGION EUROPE CENTRALAND EUROPE NORTHDräger Medical GmbHMoislinger Allee 53-5523558 Lübeck, GermanyTel +49 451 882 0Fax +49 451 882 [email protected]

REGION EUROPE SOUTHDräger Médical S.A.S.Parc de Haute Technologied'Antony 225, rue Georges Besse92182 Antony Cedex, FranceTel +33 1 46 11 56 00Fax +33 1 40 96 97 [email protected]

REGION MIDDLE EAST, AFRICADräger Medical GmbHBranch OfficeP.O. Box 505108Dubai, United Arab EmiratesTel +971 4 4294 600Fax +971 4 4294 [email protected]

REGION ASIA / PACIFICDraeger MedicalSouth East Asia Pte Ltd.25 International Business Park#04-27/29 German CentreSingapore 609916, SingaporeTel +65 6572 4388Fax +65 6572 [email protected]

REGION CENTRALAND SOUTH AMERICADräger Panama ComercialS. de R.L.Complejo Business Park,V tower, 10th floorPanama CityTel +507 377 9100Fax +507 377 [email protected]

Locate your RegionalSales Representative at:www.draeger.com/contact

The quality management system at Dräger Medical GmbH is certified according toISO 13485, ISO 9001 and Annex II.3 of Directive 93/42/EEC (Medical devices).

As of August 2015

Dräger Medical GmbH changesto Drägerwerk AG & Co. KGaA

90 6

6 96

0 |

15-0

4-2

| C

omm

unic

atio

ns &

Sal

es M

arke

ting

| P

P |

LE

| P

rinte

d in

Ger

man

y |

Chl

orin

e-fr

ee –

env

ironm

enta

lly c

ompa

tible

| S

ubje

ct t

o m

odifi

catio

ns |

© 2

015

Drä

gerw

erk

AG

& C

o. K

GaA

Oil-lubricated or oil-free rotary vane vacuum pumps

Suction capacity at 70% Vac approx. 200 to 3600 l/Min

Electrical power rating 1.1 to 18.5 kW

MVC (Medical Vacuum Control)

Power ranges 1.1-4 kW, 4-15 kW, 15-18.5 kW per pump

Voltage 220-240 V / 380-400 V

Frequency 50 Hz / 60 Hz

Number of pumps 2, 3, 4

Protection class IP 55

EMC EN61000-6-X

Electrical safety EN60204-1

Vacuum receiver

Capacity 500 to 3000 liter

Bacteria double filter avoids contamination of pumps, tank and waste air. High-

performance interchangeable filter for suspended particles class

H13, in coated aluminum body with quick-release fastener;

penetration rate < 0,04% acc. to EN 1822-1

Secretion traps protect vacuum plants from secretion or fluids, which could

accidentally reach the distribution systems