G6 Voice Gateway Hardware Installation Guide
Transcript of G6 Voice Gateway Hardware Installation Guide
Installation & Configuration
Operation
Maintenance & Troubleshooting
Performance Management
G6 Voice Gateway
HardwareInstallation Guide
Provides instructions for mounting ashelf, installing cards, grounding,
powering on, and connecting aG6 Voice Gateway.
pn 630-00001-02 TN01013100 Hardware Installation Guide
General Bandwidth, G6, VoBroadband, and VoCable are trademarks of General Bandwidth, Inc. All other trademarks are owned by their respective companies.
© 2000, 2001 General Bandwidth, Inc.
All rights including translation into other languages, reserved under the Universal Copyright Convention, the Berne Convention, or the Protection of Literary and Artistic Works, and the International and Pan American Copyright Conventions. Any use of the software and/or associated documentation, including reproduction, modification, distribution, republication, transmission, re-transmission, modification, or public showing, without the prior written permission of an authorized General Bandwidth representative, is strictly prohibited.
This document and any software and programs mentioned in this document, whether delivered electronically or via other media, are the sole property of General Bandwidth, Inc. and are sold under a license agreement. Reproduction or modification of the software or documentation by an means is prohibited without the express written consent of an authorized General Bandwidth representative.
Contents
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
G6 Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Card Cage and Card Slots. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
System Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Ethernet 10/100 Base-T Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5Serial Craft Port on the SCM Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7SCM Status LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Access Network Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8ANM Card Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9ANM Status LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Telephony Port Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
TPM Card Redundancy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11TPM Status LEDs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Cable Interfaces. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
SCM-CI Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Preliminary Beta Release—Subject to Change iii
CIM-DS3 and CIM-DS1/T1 Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
System Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Unpacking and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Unpack and Inspect for Damage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Inventory the Package Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Returning a Shelf or Component . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Installing the Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Standards Compliance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Aisle Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Rack Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Ventilation Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
G6 Shelf Dimensions (U.S.). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29Tools and Supplies Required. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Safety Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Install the G6 Shelf. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Grounding, Cabling, and Applying Power . . . . . . . . . . . . . . . . . . 33
Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
iv Hardware Installation Guide
Contents
Grounding Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Tools and Supplies Required. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Safety Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Ground the G6 Shelf . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
Connect the G6 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Connect the G6 Management Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Connect the External Timing Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
Connect the G6 Shelf to the Power Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
Power Up the Shelf . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Start Up the System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Run Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Cable the Telephony Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Connect to the Network Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49Color Coding Wire Scheme . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51Connect to the CPE Side . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53CPE Side Environments. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
DSLAM Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55ATM Switch Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56CMTS Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
Adding Module Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Tools and Supplies Required. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
Safety Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
Preliminary Beta Release—Subject to Change v
Installing G6 Module Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
Prepare the Slot . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
Install the SCM Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60
Install an ANM Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64
Install a TPM Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67
CIM Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .70
Install a CIM Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71
Cover Empty Slots . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
Connect the Line Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74
Secure the Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74
Removing Module Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Tools and Supplies Required. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
Safety Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
Remove a Frontside Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76
Remove a CIM Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78
Cover Empty Slots . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79
List of Figures
G6 Voice Gateway Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
vi Hardware Installation Guide
Contents
Transient Ground Connection (Chassis Back View) . . . . . . . . . . . . . . . . . . . . . . .3ESD Jack (Chassis Front View). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4SCM Card Faceplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5SCM-CI Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64-Port DS3-ANM Card Faceplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9T1-TPM Card Faceplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11A & B Management Ports on SCM-CI Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . .13Alarm and Events Pins on SCM-CI Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14BITS and CC Timing Pins on SCM-CI Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . .15Power and Transient Ground on SCM-CI Panel . . . . . . . . . . . . . . . . . . . . . . . . .15CIM Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17G6 Shipping Packaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22G6 Voice Gateway Chassis (Front View). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .253 NEBS Compliant G6 Chassis Mid-Mounted in a Rack . . . . . . . . . . . . . . . . . . .28Frame Ground Connection to the Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35Power and Transient Ground on SCM-CI Panel . . . . . . . . . . . . . . . . . . . . . . . . .35Alarm and Events Pins on SCM-CI Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37A & B Management Ports on SCM-CI Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . .38BITS and CC Timing Pins on SCM-CI Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . .39Adding a Ferrite Bead to Each Timing Wire Bundle . . . . . . . . . . . . . . . . . . . . . .41BITS and CC Timing Pins on SCM-CI Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . .42Power Connectors on the SCM-CI Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43Power Through an In-Rack Fuse and Alarm Panel . . . . . . . . . . . . . . . . . . . . . . .44Power Connection To a Remote Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45Network-Side Connection to a Class 5 Switch. . . . . . . . . . . . . . . . . . . . . . . . . . .47CPE-Side Connection to an ATM Switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .50CPE-Side Connection through a DSLAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51CPE-Side Connection through an ATM Switch . . . . . . . . . . . . . . . . . . . . . . . . . .52CPE-Side Connection through an ATM Switch . . . . . . . . . . . . . . . . . . . . . . . . . .52SCM Installation (Chassis Front View) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58ANM Installation (Chassis Front View) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61TPM Installation (Chassis Front View). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63CIM Installation (Chassis Rear View) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66Frontside Card Removal (Chassis Front View) . . . . . . . . . . . . . . . . . . . . . . . . . .71CIM Card Removal (Chassis Rear View). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
Preliminary Beta Release—Subject to Change vii
viii Hardware Installation Guide
Preface
The Hardware Installation Guide is written to guide installation personnel in setting up the G6™ Voice Gateway. Only qualified installers who are familiar with safety precautions for electronic components and equipment should perform this installation. The installation includes the following tasks:
Unpacking the G6 Voice Gateway and accessories necessary for installation
Mounting the gateway in a rack or cabinet
Connecting the gateway to the management stations
Connecting the gateway to the central office alarms
Connecting the gateway to the power source
Powering up the gateway
Installing any additional cards into the gateway
Related Documents
The Hardware Installation Guide is part of the General Bandwidth G6 Voice Gateway product documentation library. Following is a list of the documents in the library.
Installation & Configuration
These documents describe how to mount, install, set up, and configure the G6 Voice Gateway, its components, and the GenView™ EMS software. The installation and
Preliminary Beta Release—Subject to Change ix
Related Documents
configuration documents contain step-by-step installation, configuration, and setup instructions for hardware and software.
Hardware Installation Guide
This guide describes the procedures to unpack, inspect, mount, install, cable, and power up a G6 Voice Gateway and its components. The guide provides step-by-step procedures for each installation and setup task. The guide provides illustration of the procedures in order to facilitate installation. The Hardware Installation Guide is written primarily for an audience that includes central office technicians (COTs).
Software Installation & StartUp Guide
This guide describes the procedures to install updated system software for a G6 Voice Gateway and start up the gateway. The guide provides step-by-step procedures for each installation and startup task. The system software resides on the G6 cards when they are shipped. The startup tasks are performed from the command line interface after the hardware installation. Reinstalling the software is necessary only when upgrading the system software. The audiences for which the Software Installation & StartUp Guide is written are software installers, network operators (NOs), network engineers, or central office technicians (COTs).
GenView EMS Installation & Configuration Guide
This guide describes the requirements and procedures to install and configure the GenView EMS software to manage the G6 Voice Gateway system. The guide provides step-by-step procedures for the EMS server and management station installation and configuration tasks. The guide illustrates the GenView screens and menus in order to facilitate installation and
x Hardware Installation Guide
Preface
configuration. The audiences for which the GenView EMS Installation & Configuration Guide is written are software installers, network operations center technicians (NOCTs), or network operators (NOs).
System Integration Guide
This guide describes the procedures to integrate one or more G6 Voice Gateways into an operational network environment. The audiences for which the System Integration Guide is written are network operators (NO) or network engineers.
Operation These documents describe how to operate the G6 Voice Gateway through the GenView EMS software and the command line interface. The operation documents contain step-by-step instructions and operational information.
CLI Operation Guide & Commands Reference
This guide describes the procedures to operate and manage a G6 Voice Gateway system and the traffic flow through the gateway using the system software’s command line interface (CLI). The audiences for which the CLI Operation Guide & Commands Reference is written are network operators (NOs) or network operations center technicians (NOCTs). The CLI runs on a management console at the installation site or from a management station, typically at the network operations center (NOC). This guide also contains a reference listing of all system commands available from the CLI.
Preliminary Beta Release—Subject to Change xi
Related Documents
GenView EMS Operation Guide
This guide describes the procedures to operate and manage one or more G6 Voice Gateways and the traffic flow through the G6 system using the graphical GenView EMS software. The guide provides step-by-step procedures for element management, fault monitoring, performance monitoring, and performance management within the GenView EMS. Whenever appropriate, the guide presents alternative management methods. The operation guide also lists the hardware and software requirements for the EMS in specific operating environments. The audiences for which the GenView EMS Operation Guide is written are network operators (NOs) or network operations center technicians (NOCTs). The EMS client runs on a management station, typically at the network operations center (NOC).
Subscriber Provisioning Guide
This guide describes the procedures to provision subscribers either through the graphical GenView EMS software or through the command line interface. The audiences for which the Subscriber Provisioning Guide is written are network planners, network operators (NOs), or network operations center technicians (NOCTs).
Maintenance & Troubleshooting
These documents describe how to maintain and troubleshoot the G6 Voice Gateway. The maintenance and troubleshooting documents contain step-by-step instructions and reference information.
Alarms & Events Reference Guide
This reference describes the alarms and events that can occur on a G6 Voice Gateway operating in a network environment. The audiences for which the Alarms and
xii Hardware Installation Guide
Preface
Events Reference is written are network operators (NOs), network operations center technicians (NOCTs), network troubleshooters, and network engineers. Refer to the Alarms & Events Reference in conjunction with the Troubleshooting Guide to troubleshoot a G6 shelf or system. Refer to the Alarms & Events Reference in conjunction with the GenView EMS Operation Guide for normal operation.
Troubleshooting Guide
This guide describes the procedures to troubleshoot a G6 Voice Gateway operating in a network environment. The guide provides information and step-by-step procedures for how to isolate problems in the network, determine a root cause, and repair the problem. The audiences for which the Troubleshooting Guide is written are network operators (NOs), network operations center technicians (NOCTs), network troubleshooters, and network engineers. Refer to the Alarms & Events Reference in conjunction with the Troubleshooting Guide to troubleshoot a G6 shelf or system.
Maintenance Guide
This guide describes the routine procedures required to maintain a G6 Voice Gateway while it is operating in a network environment. The audiences for which the Maintenance Guide is written are central office technicians (COTs) and other maintenance or installation personnel.
Performance Management
Performance management documents describe how to optimize the performance of the G6 Voice Gateway.
Preliminary Beta Release—Subject to Change xiii
Organization
Traffic Planning & Performance Management
This guide describes principles, techniques, and procedures to optimize and fine tune the G6 Voice Gateway performance in a network environment. The guide also describes how the G6 Voice Gateway fits into the overall network architecture.
The guide provides information to help network and traffic planners integrate the G6 Voice Gateway system into a network and ensure its optimal performance, efficiency, and traffic flow across the network. The guide relates design and performance principles and techniques with specific procedures available through the GenView EMS. The audiences for which the Traffic Planning and Performance Management Guide is written are traffic planners, network planners, network engineers, network troubleshooters, and network operators (NOs).
Organization Overview describes General Bandwidth G6 Voice Gateway system components.
Unpacking and Inspection provides guidelines for unpacking, inventorying, and inspecting the G6 Voice Gateway components shipped against the configuration shipped to the customer.
Installing the Chassis describes the procedures to install the G6 in a Central Office environment.
Grounding the Chassis and Applying Power describes the procedures for the grounding and applying power to the G6 Voice Gateway system.
Verifying Communication with the CLI is a detailed and illustrated procedure on connecting a terminal through the serial connector, or a PC through the ethernet connector.
xiv Hardware Installation Guide
Preface
Running Diagnostics (Beta release) is a detailed diagnostics procedure that will be provided when the programs become available.
Adding Module Cards provides instructions on how to install additional modules into the G6 chassis.
Removing Module Cards provides instructions on how to remove modules from the G6 chassis.
Safety and Precaution Notations
This document uses the following symbols and notations to identify important personal and equipment safety precautions as well as possibly hazardous situations for people, property, or equipment.
Warnings Warnings throughout this document identify and precede potentially dangerous procedures or situations. For your personal safety, please heed all warnings and employ all standard safety practices.
WARNING! POTENTIAL DANGER!
Warnings identify a possible danger or hazard that can cause personal injury or substantial damage to property or equipment.
DANGER! SHOCK HAZARD!
A G6 shelf uses −48 VDC for primary power. This voltage is sufficient to overcome skin resistance and supplies a level of current that can be fatal.
Use extreme caution when working around this volt-age during installation, operation, testing, and main-tenance.
Remove the voltage at its point of distribution to the gateway before you connect or disconnect power to the gateway.
Preliminary Beta Release—Subject to Change xv
General Precautions
Cautions
General Precautions
This section presents general precautions that you should observe while working with or operating the G6 Voice Gateway. Several precautions are presented here. Where a precaution applies to a specific procedure, it is repeated along with the procedure to which it applies.
Observe the following safety precautions during all phases of installation, operation, service, and repair of the G6 Voice Gateway. Failure to comply with these precautions, or with specific warnings elsewhere in this document, violates safety standards of design, manufacture, and intended use of this equipment. General Bandwidth, Inc. assumes no liability for the customer’s failure to comply with these requirements.
Ground the Equipment
To minimize shock hazards, the G6 shelf must be connected to frame ground.
Precautionary Steps RequiredCautions identify possible hazards that can result in several consequences.
damage to property or equipment
interruption of network service
reduction of data transfer, traffic flow, or otherwise reduced network efficiency or effectiveness
CautionDo not apply power to the G6 shelf until you have completed all the installation procedures.
xvi Hardware Installation Guide
Preface
Ground Yourself
To minimize damage to the G6 Voice Gateway, you must ground yourself and discharge built-up static electricity before working with a G6 shelf.
Dangerous Procedure Warnings
Warnings, such as the examples that follow, precede potentially dangerous procedures throughout this manual. Follow the instructions contained in all warnings. You should also employ all other safety precautions which you deem necessary for installing, operating, and servicing the G6 Voice Gateway in your operating environment.
The following safety precautions represent warnings of certain dangers of which General Bandwidth, Inc., is aware. You, as the user of this product, should follow these warnings and all other safety precautions necessary for the safe operation of the G6 Voice Gateway in your operating environment.
Electrostatic CautionThe G6 Voice Gateway and its cards can be dam-aged by static electricity that builds up on work sur-faces and on your body. Static is produced by the movement and is released as an electrostatic dis-charge (ESD) when you touch an object.
Always observe ESD precautions whenever you are working with the G6 Voice Gateway. Always wear a grounded wrist strap to prevent ESD. Connect the wrist strap to one of the ground connectors on the G6 Voice Gateway chassis. The chassis must be prop-erly connected to frame ground.
Preliminary Beta Release—Subject to Change xvii
We’d Like to Hear From You
Do Not Service or Adjust Alone
The G6 Voice Gateway is heavy and requires two people to lift it. Also, do not attempt internal service or adjustment unless another person capable of rendering first aid and resuscitation is present.
Do Not Substitute Parts or Modify Equipment
Because of the danger of introducing additional hazards, do not install substitute parts or perform any unauthorized modification of the equipment. Contact your local General Bandwidth representative for service and repair, to ensure that safety features are maintained.
We’d Like to Hear From You
You can be instrumental in helping us in the on-going process of improving our technical literature. So, if you find anything about our documentation that is incorrect or does not completely suit your needs, please forward your comments to:
Customer Information Development ManagerGeneral Bandwidth12303 Technology Blvd.Austin, TX [email protected]
Caution Lifting!The G6 chassis weighs about 120 pounds (54 kg) when fully populated. A fully-populated shelf has a shipping weight of 130 pounds (59 kg), including packing material and the pallet to which it is strapped.
Two people are required to lift a fully-populated chas-sis. Grasp the chassis from the bottom and use both hands. To prevent injury, keep your back straight and lift with your legs, not your back.
xviii Hardware Installation Guide
1C H A P T E R
Overview
This chapter provides an overview of the General Bandwidth G6 Voice Gateway hardware components. Each G6 chassis must include at least one system control module (SCM), which performs overall control functions and manages the flow of information between the other system modules. An optional second SCM provides system redundancy for the shelf. (This feature will be supported in a later release.) Figure 1 shows the G6 Voice Gateway chassis.
Figure 1. G6 Voice Gateway Chassis
Preliminary Beta Release—Subject to Change 1
G6 Chassis
G6 Chassis The G6 chassis is 13 U (22.75 inches) tall, 17.5 inches wide (without mounting ears). The NEBS compliant version is 12 inches deep, which includes external network connectors (T1 Champs and BNCs) accessible from the rear of the chassis.
Mounting The G6 chassis can mount in a 23-inch or 19-inch (cable and wireless) rack or cabinet, using EIA or WECO standard mounting hole patterns. The card cage can be front-mounted or mid-mounted. Both 23-inch and 19-inch mounting ears are supplied with the unit, with the 23-inch mid-mount being the attached standard.
Cooling The chassis uses forced convection fans to cool from the bottom to the top of the cardcage. The 3-fan assembly (color-coded with purple latches) runs at 40VDC for noise reduction and reliability.
If the environment temperature rises to 41ºC (105ºF) the fan controller increases the rotational speed of the fans to 48VDC. In cases of fan failure (low rpm), the fan controller increases the rotational speed of the remaining fans to 48VDC to compensate. This process maintains a constant air flow throughout the G6 chassis.
An alarm on the fan tray and on the GenView EMS indicates a fan failure. A fully-loaded G6 shelf can run for 20 minutes with a single operating fan or with the fan tray removed, to allow for fan replacement or maintenance.
2 Hardware Installation Guide
Overview
The fan assembly module is hot-swappable and can be removed or replaced with power applied to the chassis. The following chart describes the LEDs on the fan assembly module.
Grounding The chassis includes a frame ground connector (on the back of the NEBS compliant chassis or the front of the ETSI compliant chassis). Frame grounding is effected via a ground wire attached to the rack. The SCM-CI panel on the back of the chassis includes a transient ground connector.
Figure 2. Transient Ground Connector (Chassis Back View)
ESD jacks on the front and back of the chassis provide ESD grounding. Anyone working on the G6 shelf or components should wear and plug in a wrist grounding strap while handling any of the module cards.
LEDSolidGreen
FlashingGreen
SolidYellow
Off
Status Fan module is operational
Tach limits and thermal limits not tripped
At least one thermal limit has been reached
Fan requires maintenance
No power to the fan mod-ule, power failure, fan module not present, or LED failure
Preliminary Beta Release—Subject to Change 3
Card Cage and Card Slots
Figure 3. ESD Jack (Chassis Front View)
Card Cage and Card Slots
A full-populated G6 Voice Gateway includes 2 system control module (SCM) cards and 16 module cards. As many as 14 of the module cards can be telephony port module (TPM) cards. As many as 6 can be access network module (ANM) cards.
ANM cards can be installed in card slots 1–6 and TPM cards in slots 3–8 and 11–18. For each TPM or ANM card in the system, a cable interface module (CIM) card is required in the same slot on the back of the chassis. The partner CIMs for most cards provide the cabling connections out to the telephony network. Cards that support fiber connections include the network connectors on the front of the module card and use CIM blanks.
The cardcage meets GR-63 and GR-1089 requirements and draws a maximum of 425 watts, in compliance with NEBS regulations. A gasket on the side of each telephony card and CIM provides EMI protection for the card.
4 Hardware Installation Guide
Overview
System Control Module
The SCM card performs overall system control functions as well as the ATM switching functions. The SCM manages the flow and synchronization of information to the other system modules. A G6 shelf supports a primary SCM card in card slot 9 and a hot standby in card slot 10. In a G6 shelf with redundant SCMs, the standby SCM continuously monitors all system activity and checks the operation decisions of the active SCM. If the standby SCM detects a fault, it assumes active control and removes the previously-active SCM from the bus. The now active SCM in slot 10 generates an alarm for the now inactive SCM in slot 9.
Figure 4. SCM Card Faceplate
Ethernet 10/100 Base-T Port
The SCM-CI panel provides cabling connections for both SCM cards in a redundant controller configuration. The panel includes two Ethernet connectors (10/100Base-T). The Ethernet ports provide an interface for network
Status LEDActive/Standby LED
Alarm Cutoff SwitchLED Test Switch
Serial Craft Port
Alarm LEDs
Preliminary Beta Release—Subject to Change 5
System Control Module
management and system configuration. The two Ethernet connectors in a redundant-SCM configuration connect to separate Ethernet LANs. The SCM-CI is not field replaceable.
Figure 5. SCM-CI Panel
6 Hardware Installation Guide
Overview
Serial Craft Port on the SCM Card
A serial craft port on the front panel of each SCM card provides a means for updating, maintaining, and troubleshooting the system by craft personnel at the gateway installation site. The port uses a 9-pin D-sub connector and has the following operating parameters.
SCM Status LEDs
The SCM faceplate contains LED status indicators, two push button switches, and a connector for a serial craft interface.
The following chart describes the LEDs on the system control module (SCM) cards. The LED test button on the SCM card sequences through all LEDs on all cards in the G6 shelf for test puroses.
Baud Rate Data Bits Parity Stop BitsFlow
Control
9600 8 None 1 None
LEDSolidGreen
FlashingGreen
SolidYellow
FlashingYellow
Off
Status Normaloperation
SCM card is booting SCM card has
failedCard is tagged for removal
No power is present, a power failure has occurred, or no software is present on the SCM
Active/Standby SCM card is the active (primary) SCM
SCM card is the standby (redundant) SCM
Preliminary Beta Release—Subject to Change 7
System Control Module
Access Network Module
An access network module (ANM) card provides an interface to an ATM backbone network, digital subscriber line access module (DSLAM), or cable modem termination system (CMTS). ANM cards exchange connection-oriented, variable bit rate AAL2 or AAL5 traffic. AAL2 supports isochronous video or voice traffic over ATM. AAL5 supports IP traffic over ATM or LAN emulation (LANE) for an ATM-based LAN backbone. AAL5 has a low overhead also provides error recovery. ANM cards currently support DS3 framing.
Critical A critical sys-tem alarm or event has occurred
No system alarm has occurred
Major A major sys-tem alarm or event has occurred
Minor A minor sys-tem alarm or event has occurred
LEDSolidGreen
FlashingGreen
SolidYellow
FlashingYellow
Off
8 Hardware Installation Guide
Overview
Figure 6. 4-Port DS3 ANM Card Faceplate
Different CIM cards paired with an ANM card support different framing specifications (DS3, for example), transmission line types (T3 at 44.736 Mbps or E3 at 34.368 Mbps, for example), and network connections (paired BNCs). The 4-port DS3 CIM supports as many as 4 network connections to a DSLAM or an ATM backbone.
ANM Card Redundancy
The ANM cards use a 1:1 sparing scheme for redundancy. Installing a secondary, sparing card (and CIM) provides a redundant ANM interface (hot standby). Each standby ANM card provides hot standby for a single ANM card in the G6 shelf. The hot standby card typically resides in the card slot adjacent to the primary ANM card. A CIM-DS3 card installed along with the standby ANM enables routing of DS3 traffic from a failed
Status LEDActive/Standby LED
DS3 Port LEDs
Preliminary Beta Release—Subject to Change 9
System Control Module
ANM card through the sparing bus to its standby ANM card. A “Y” cable for each DS3 line connects the line to both the active and standby CIM-DS3 card.
ANM Status LEDs
Each 4-port DS3 ANM has 10 faceplate LEDs to provide line and module information. There is one status LED, an active/standby LED, and one transmit and receive port status LED pair for each DS3 line.
The following chart describes the LEDs on an ANM card.
LEDSolidGreen
FlashingGreen
SolidYellow
FlashingYellow
Off
Status Normaloperation
ANM card is booting
(1)ANM card is in the locked (soft-ware) state-for removal or service
(2)ANM card has failed or the CIM and ANM card do not match
Card is tagged for removal
No power is present, a power failure has occurred, or no software is present
Active/Standby ANM card is an active ANM
ANM card is a standby (redundant) ANM
RX (Receive Signal Status)
Receive line is active
Receive line is in loopback mode
A loss of sig-nal (LOS), LCD, or AIS alarm has occurred
ANM card is not yet equipped (Status & Active/Standby LEDs are off)
No signal is present
TX (Receive Signal Status)
Transmit line is active
Transmit line is in loopback mode
An alarm has occurred at the far end (FERF)
No signal is present
10 Hardware Installation Guide
Overview
Telephony Port Module
A telephony port module (TPM) provides a high-speed interface to the Public Switched Telephone Network (PSTN) via the GR-303, TR-008, ISDN PRI, or V5.2 line protocol.
Figure 7. DS1/T1 TPM Card Faceplate
Different CIM cards paired with a TPM card support different framing specifications (DS1, for example), transmission line types (T1 at 1.54 Mbps or E1 at 2.048 Mbps, for example), and network connections (Champ for T1 or BNC for E1, for example). The TPM cards and CIMs currently support T1 transmissions using DS1 framing. The CIM-T1 card supports 10 T1 lines.
TPM Card Redundancy
The TPM cards use a 1:N sparing scheme for redundancy. Installing a secondary, sparing TPM card (and CIM) provides a redundant TPM interface (hot
Status LEDActive/Standby LED
DS1 Port LEDs
Preliminary Beta Release—Subject to Change 11
Telephony Port Module
standby). One standby TPM card provides hot standby for all TPM cards in the G6 shelf. The hot standby card typically resides in card slot 18. A CIM-SPARE card installed in slot 18 enables routing of DS1 traffic from a failed TPM card through the sparing bus to the TPM standby card.
TPM Status LEDs
Each T1 TPM has 12 faceplate LEDs to provide line and module information. There is one status LED, an active/standby LED, and one port status LED for each T1 line.
The following chart describes the LEDs on a TPM card.
LEDSolidGreen
FlashingGreen
SolidYellow
FlashingYellow
Off
Status Normaloperation
TPM card is booting
(1)TPM card is in the locked (soft-ware) state-for removal or service
(2)TPM card has failed or the CIM and TPM card do not match
Card is tagged for removal
No power is present, a power failure has occurred, or no software is present
Active/Standby TPM card is an active TPM
TPM card is the standby (redundant) TPM
T1 Line Status T1 line is active
T1 line is in loopback mode
An alarm has occurred at the far end
TPM card is not yet equipped (Status & Active/Standby LEDs are off)
No T1 signal is present
12 Hardware Installation Guide
Overview
Cable Interfaces Each ANM or TPM card requires a separate card to provide the electrical and cable interfaces. The two SCM cards have a common cable interface. Cable interfaces support management, network, alarm, and power connections.
SCM-CI Panel The SCM-CI services both the active and standby SCM.The SCM-CI panel includes two management ports with RJ-45 10/100Base-T Ethernet connectors. For redundancy, connect each management port to the GenView EMS via a different LAN. Figure 8 shows the primary (A, on the right) and standby (B) management port connectors on the SCM-CI panel.
Figure 8. A & B Management Ports on SCM-CI Panel
Preliminary Beta Release—Subject to Change 13
Cable Interfaces
There are 24 fuse and alarm panel (FAP) wire-wrap pins on the SCM-CI to provide 12 relay closures. Each pin contains EMI egress filtering and GR-1089 surge protection. Only the active SCM can send an alarm. Figure 9 shows the audible, visible, and E2A alarm and events pins on the SCM-CI panel.
Figure 9. Alarm and Events Pins on SCM-CI Panel
BITS and CC timing inputs can be connected to the SCM-CI. The inputs are provided on wire-wrap pins. BITS inputs are terminated with 100 ohms. CC inputs are terminated with 133 ohms. Thus, the G6 shelf supports termination even if no SCM cards are present, per GR-1244 requirements. BITS and CC inputs are protected against GR-1089 surge voltages. Figure 10 shows the BITS and CC external timing pins on the SCM-CI panel.
14 Hardware Installation Guide
Overview
Figure 10. BITS and CC Timing Pins on SCM-CI Panel
The SCM-CI panel provides a redundant 48V power interface for the chassis. The transformer on the SCM-CI minimizes EMI egress. The power connectors also have intra-building surge protection to meet GR-1089 requirements. Figure 11 shows the power connector block on the SCM-CI panel.
Figure 11. Power Connector on SCM-CI Panel
Preliminary Beta Release—Subject to Change 15
Cable Interfaces
The following chart summarizes the SCM-CI ports and connectors. An EEPROM on the SCM-CI stores a unique serial ID for the G6 chassis. After installation, the active SCM accesses the EEPROM for this information, and provides it to the GenView Element Management System (EMS).
CIM-DS3 and CIM-DS1/T1 Cards
The CIM-DS3 cards include 4 BNC network interface connectors. Each pair of 75-ohm BNC connectors (transmit and receive) supports one DS3 port. Both receive and transmit DS3 interfaces are differentially surge protected.
The CIM-DS1/T1 cards include a 50-pin Champ network interface connector to support 10 T1 lines. Each T1 interface on the CIM-DS1/T1 contains fuses and primary protection to tolerate lighting and surge protection for external wiring.
Figure 12 shows the CIM-DS1/T1 and CIM-DS3 card connectors.
CautionThe SCM-CI is mounted in the chassis during factory assembly. The SCM-CI cannot be removed from the chassis without taking the entire G6 Voice Gateway out of service. The SCM-CI is not field replaceable.
16 Hardware Installation Guide
Overview
Figure 12. CIM Cards
The following chart summarizes the CIM-DS3 and CIM-DS1/T1 ports and connectors.
CIM-DS1/T1Network Ports
CIM-DS3Network Ports
Connectors 1 8
Connector Type
50-pin right-angled Champ
75Ω BNC
Ports10 T1 ports 4 DS3 ports
(each requires 2 connectors)
Status LED
50-pin T1 connector
Status LED
CIM-DS1/T1 Card CIM-DS3 Card
BNC DS3 connectors
Wire-tie fastener
Preliminary Beta Release—Subject to Change 17
System Software
The status LED on the CIM card corresponds to the status card on the ANM or TPM card. The following chart shows the meanings for the status LED on the CIM cards.
The CIM-DS3s and CIM-DS1/T1s also include a wire-tie fastener and hold-down for local cable strain relief and cable management.
System Software
The G6 Voice Gateway stores system software in flash memory on the SCM cards, ANM cards, and TPM cards. In a redundant SCM configuration, all software can be dynamically updated without affecting the performance of the G6 Voice Gateway (in service). Two methods are available to dynamically update the system software.
Software can be downloaded via TFTP from a management console at the gateway installation site. The console connects to the serial craft port on the front of the SCM card.
Software can be downloaded via TFTP or through the GenView EMS from a management station at the network operation center (NOC). The management station connects via an Ethernet LAN to the 100Base-T Ethernet port on the back of the chassis.
LEDSolidGreen
SolidYellow
FlashingYellow
Off
Status Normal operation
CIM card has failed or the CIM and ANM or TPM card do not match
CIM card is tagged for removal
No power is present or a power failure has occurred
18 Hardware Installation Guide
Overview
Updates to the TPM or ANM system software are also through the craft port or Ethernet port. In-service TPM or ANM system software updates require a redundant TPM or ANM configuration, respectively.
The SCM stores all provisioning information in local nonvolatile memory. In the event of a power loss, the G6 Voice Gateway retains provisioning information.
Preliminary Beta Release—Subject to Change 19
System Software
20 Hardware Installation Guide
2C H A P T E R
Unpacking andInspection
This chapter provides general guidelines for unpacking the G6 Voice Gateway chassis and its components. Verify that all ordered equipment, cards, cables, and so forth are included. If any items are missing or you need additional information, contact General Bandwidth at [email protected] or call 888 GENBAND (888 436-2263).
Unpack and Inspect for Damage
Each G6 Voice Gateway chassis is securely packaged in a heavy-duty crate. General Bandwidth can ship your chassis with all cards installed or with the cards separate. If packaged separately, the module cards are packaged in a smaller box inside anti-static bags.
Carefully inspect the shipping container and the G6 Voice Gateway equipment for damage as you unpack it. Check both the inside and outside of the container.
Preliminary Beta Release—Subject to Change 21
Unpack and Inspect for Damage
To inspect the packaging and materials, refer to Figure 13 and follow these steps.
1 Inspect the exterior of the shipping container for obvious punctures, crushed corners, etc.
2 Remove each package and check for crushed or deformed packing material inside.
3 Check the module packages for crushed or deformed packaging.
22 Hardware Installation Guide
Unpacking and Inspection
Figure 13. G6 Shipping Packaging
If the box or equipment is visibly damaged, record the damage on the bill of lading. Have the transfer company’s agent acknowledge the damage by signing the bill of lading under the damage notation. Do not continue with G6 Voice Gateway installation if there is shipping damage. Notify the transfer company immediately about the damage and submit a claim. Then, refer to Returning a Shelf or Component for further instructions.
Preliminary Beta Release—Subject to Change 23
Inventory the Package Contents
Inventory the Package Contents
Follow these steps to take an inventory of the package contents an ensure that all ordered components are present and that you received all appropriate hardware components for the G6 shelf.
1 Remove accessory box and packaging material.
2 With the help of an assistant, carefully lift the G6 chassis from the package.
3 Compare the contents of the shipping container against the packing list.
4 If any components are missing, contact General Bandwidth Customer Support & Service at [email protected].
Returning a Shelf or Component
Follow these steps if you need to return a G6 shelf or component.
1 Login to the General Bandwidth customer extranet site (http://cust.genband.com) or call 888 GENBAND (888 436-2263) to obtain a return material authorization (RMA) number.
2 Repackage the equipment in the original container, along with a copy of the original bill of lading and
Caution! Lifting HazardThe G6 chassis weighs about 120 pounds (54 kg) when fully populated. A fully-populated shelf has a shipping weight of 130 pounds (59 kg), including packing material and the pallet to which it is strapped.
Two people are required to lift a fully populated chas-sis. Grasp the bottom of the chassis and lift with both hands. To prevent injury, keep your back straight and lift with your legs, not your back.
24 Hardware Installation Guide
Unpacking and Inspection
with the RMA number marked prominently on the outside of the container.
3 Follow the instructions on the website to return the packaged component or shelf to General Bandwidth.
Preliminary Beta Release—Subject to Change 25
Returning a Shelf or Component
26 Hardware Installation Guide
3C H A P T E R
Installing theChassis
This chapter describes the procedures for installing one or more General Bandwidth G6 Voice Gateway chassis (shelves) into a standard 23-inch or 19-inch mounting rack.
Figure 14. G6 Voice Gateway Chassis (Front View)
Standards Compliance
The G6 Voice Gateway complies with NEBS Level 3 for rack-mounted equipment designed and built for use in an environmentally controlled location, such as a switching center.
Preliminary Beta Release—Subject to Change 27
Aisle Requirements
The site preparation, safety and installation practices described in this chapter for a G6 Voice Gateway installation are based on the Telcordia Network Equipment Building Standards (NEBS).
Ensure that any additional preparation work not described in this document complies with local building and safety codes and with NEBS, as applicable.
Aisle Requirements
When installing a G6 Voice Gateway shelf into a mounting rack, be sure to allow enough room to access the rear of the unit for wiring/cabling purposes. Also allow enough front aisle space to install the G6 shelves from the front of the rack. Allow a minimum of 12 inches in the rear aisle and 12 inches in the front aisle. Whenever possible, follow the GR-63 aisle requirements.
Rack Requirements
Follow NEBS guidelines for installation distance from the closest surroundings. Also, many installations use a 1-foot rack unit (RU) fuse and alarm panel in the top mounting bay. You can install one, two, or three G6 shelves (Figure 15) in a standard or seismic 7-foot-tall, 19-inch or 23-inch relay rack.
Ventilation Considerations
The fan tray installs horizontally (Figure 14) at the bottom of the G6 Voice Gateway chassis. Leave at least a 1-RU space open below each shelf for proper ventilation.
The air filter tray is below the fan tray. Change the air filter monthly for proper filtration and operation.
The fans in the G6 Voice Gateway maintain a suitable operating temperature for the internal circuitry. Ensure that the air intake vents at the bottom of the chassis and the air exhaust vents on the top sides of the chassis are not obstructed in any way.
28 Hardware Installation Guide
Installing the Chassis
G6 Shelf Dimensions (U.S.)
The NEBS compliant G6 Voice Gateway chassis measures 22.75 inches tall × 17.5 inches wide × 11.025 inches deep (58 cm × 45 cm × 28 cm), without cables. The universal height measurement is 13 RU.
Network, power, and alarm cables connect through the rear of the unit. Including the external connectors (Champ for T1 and BNC for DS1) and allowing for cable bend, the depth is 12 inches. The chassis with the installed mounting ears fits into a 23-inch rack, mid mounted. A second set of ears is provided for mounting into a 19-inch rack. Both the 19-inch and the 23-inch ears support either mid mounting or front mounting.
Weight A G6 Voice Gateway shelf weighs approximately 120 pounds (54 kg) when it is fully-populated. The following chart shows the approximate weights of the front module cards, the cable interface module (CIM) cards, and the components.
Height Width1
1. Does not include mounting ears.
Depth2
2. Includes allowance for connectors and cable bend.
22.75 inches57.78 cm)
17.5 inches44.45 cm
12 inches30.48 cm1
Front Module Card
CIMChassis and
Midplane
Fully Populated
Shelf
3 pounds 1.36 kg
1 pound0.45 kg
20 pounds9.07 kg
120 pounds54 kg
Preliminary Beta Release—Subject to Change 29
G6 Shelf Dimensions (U.S.)
Figure 15. 3 NEBS Compliant G6 Chassis Mid-Mounted in a Rack
Tools and Supplies Required
Installing the G6 chassis into a rack requires only standard tools and supplies.
A flat-blade screwdriver and a Phillips #1 screwdriver
Wire cutters
Wire strippers
1 RU
13 RU
17.5 inches
22.75 inches
12 inches including cables
19 or 23-inch rack
30 Hardware Installation Guide
Installing the Chassis
Wire wrap tool
An antistatic ESD wrist grounding strap
A digital voltmeter
Cable ties and mounting screws supplied by General Bandwidth
Additional cable bundling material, such as cable ties or waxed twine (depending on the location cabling requirements)
Cable identification tags or equivalent markers
Safety Guidelines
Follow these guidelines for a safe installation.
Review the safety information in General Safety Precautions in the Preface of this guide.
Pay close attention to any notes and comply with cautions and warnings throughout the installation procedures.
Comply with all applicable safety requirements, practices, and standards cited in NEBS.
Comply with your organization’s safety guidelines.
Caution!Only trained and qualified personnel should be allowed to install or replace this equipment.
Preliminary Beta Release—Subject to Change 31
Install the G6 Shelf
Install the G6 Shelf
Follow these steps to install a G6 Voice Gateway chassis into a mounting rack.
1 Ensure that the mounting ears on the chassis are properly located for your rack installation. If you are installing into a 19-inch rack or mounting the ears at the front of the chassis instead of the middle, change or relocate the mounting ears.
2 From the front of the rack, slide the chassis into the rack.
3 Fasten the chassis to the rack with at least 3 of the provided rack mounting screws on each side.
Caution! Lifting HazardThe G6 chassis weighs about 120 pounds (54 kg) when fully populated. A fully-populated shelf has a shipping weight of 130 pounds (59 kg), including packing material and the pallet to which it is strapped.
Two people are required to lift a fully populated chas-sis. Grasp the bottom of the chassis and lift with both hands. To prevent injury, keep your back straight and lift with your legs, not your back.
WARNING! POTENTIAL DANGER!
To prevent bodily injury when mounting or servicing this unit in a rack, you must take special precautions to ensure that the system remains stable. These guidelines are provided to ensure your safety.
If the rack is provided with stabilizing devices, install the stabilizers before mounting or servicing the unit in the rack.
Mount the unit at the bottom of the rack if it is the only (or first) unit in the rack.
When mounting this unit in a partially filled rack, load the rack from the bottom to the top with the heaviest component at the bottom of the rack.
32 Hardware Installation Guide
4C H A P T E R
Grounding,Cabling, and
Applying Power
This chapter describes how to ground the General Bandwidth G6 Voice Gateway chassis and then apply power to the G6 shelf.
Power Requirements
The G6 Voice Gateway uses a distributed power system. The midplane busses the power mains (redundant –48 VDC A and B rails) to each functional module in the chassis. Each module contains a DC/DC power circuit to convert the –48 VDC to the levels required by the components on that module. In the event of a power failure in the common power circuit on a module, the failure is isolated to the defective module and the module’s functionality is transferred to other resources in the system.
WARNING! POTENTIAL DANGER!
Do not work on the system, connect cables, or dis-connect cables during periods of lightning activity.
Before working on equipment that is connected to power lines, remove jewelry (including rings, neck-laces, and watches). Metal objects will heat up when connected to power and ground and can cause seri-ous burns or become welded to the terminals.
Preliminary Beta Release—Subject to Change 33
Grounding Requirements
Grounding Requirements
There are three grounds in the G6 Voice Gateway: frame ground, logic ground, and transient ground. The chassis includes frame ground for electromagnetic interference (EMI) suppression. The chassis has frame ground in the mounting holes, RJ-45 shields, BITS shields, and the outer layer of the sheet metal. Logic ground protects the logic components. Logic and frame ground are AC coupled on the midplane.
Transient ground provides lightning and surge protection for the G6 Voice Gateway. The G6 CIMs contain protection circuits for transient ground. The rack in which the G6 shelf is mounted must be connected to earth-ground.
Tools and Supplies Required
Installing the G6 chassis into a rack requires only standard tools and supplies.
An antistatic ESD wrist grounding strap
A digital voltmeter
A flat-blade screwdriver
Wire cutters
Wire strippers
Sufficient 26, 24, or 22 AWG shielded, solid-gauge coated or tinned copper wire to connect the alarm and event pins to the fuse and alarm panel (green or color-coded if appropriate for the installation)
Sufficient 26, 24, or 22 AWG shielded, solid-gauge coated or tinned copper wire to connect the BITS or CC pins to the BITS panel or composite clock source (green or color-coded if appropriate for the installation)
Two ferrite beads for the timing-wire bundles (supplied with the accessories)
34 Hardware Installation Guide
Grounding, Cabling, and Applying Power
Sufficient 22-8 AWG solid-gauge wire to connect the frame ground lug on the chassis to frame ground on the rack (color-coded black if appropriate for the installation)
Sufficient 22-12 AWG solid-gauge wire to connect the transient ground block on the chassis to the building transient ground (color-coded black if appropriate for the installation)
Sufficient 22-12 AWG shielded, solid-gauge, coated or tinned copper wire to connect the primary and secondary positive power block on the chassis to the positive terminals of the primary and redundant power supplies for the shelf (color-coded red if appropriate for the installation)
Sufficient 22-12 AWG shielded, solid-gauge, coated or tinned copper wire to connect the primary and secondary negative power block on the chassis to the negative terminals of the primary and redundant power supplies for the shelf (color-coded black if appropriate for the installation)
Cable ties and mounting screws supplied by General Bandwidth
Additional cable bundling material, such as cable ties or waxed twine (depending on the location cabling requirements)
Cable identification tags or equivalent markers
Safety Guidelines
Follow these guidelines for a safe installation.
Review the safety information in General Safety Precautions in the Preface of this guide.
Pay close attention to any notes and comply with cautions and warnings throughout the installation procedures.
Preliminary Beta Release—Subject to Change 35
Ground the G6 Shelf
Comply with all applicable safety requirements, practices, and standards cited in NEBS.
Comply with your organization’s safety guidelines.
Ground the G6 Shelf
When installing a chassis, always connect the frame ground before any other connections. Always disconnect the frame ground last. Figure 16 shows frame grounding.
1 Connect the grounding wire packaged with the chassis to the metal grounding lug on the chassis.
2 Connect the other end of the grounding wire to the rack. This provides frame ground to the chassis.
Caution!
Allow only trained and qualified personnel to install or replace this equipment.
WARNING! ELECTRICAL HAZARD
Before connecting or disconnecting ground wires to the chassis, ensure that power is removed from the DC circuit. Use a voltmeter to test for 0 (zero) voltage at the power terminals on the chassis.
Caution!
If the rack is painted, ensure that all paint has been scraped off at the point of the grounding connection.
NoteIf the rack is painted, ensure that all the paint has been scraped at the point of the ground-ing connection.
36 Hardware Installation Guide
Grounding, Cabling, and Applying Power
Figure 16. Frame Ground Connection to the Rack
Connect (wire wrap) a transient ground wire from the transient grounding block on the chassis to the building transient ground.
Figure 17. Transient Ground Connectionl
3 Use an appropriate tie-wrap to tie down the transient ground cable to the chassis. Label the cable.
4 Use a digital multimeter (DMM) to verify the ground.
5 Touch a digital multimeter (set to resistance, Ω) to an unpainted part of the chassis and to the common ground in an unpainted part of the rack to verify that the chassis is grounded. (If the multimeter is set for sound, the beep indicates a good ground. Otherwise, visually check to ensure that a ground connection is made.)
Preliminary Beta Release—Subject to Change 37
Connect the G6 Alarms
Connect the G6 Alarms
This procedure shows how to connect the alarms on the G6 shelf to a fuse and alarm panel that is properly connected to the aisle alarm system. Use a cable stripper and wire-wrap tool to prepare and connect the cables.
The SCM-CI includes 24 fuse and alarm panel (FAP) wire-wrap pins, providing 12 relay closures. Each pin contains EMI egress filtering and GR-1089 surge protection.
The audible alarms are set up to connect (through the fuse and alarm panel) to a horn or other audible alarm device at the installation site. The alarm cut off button (ACO) on the SCM card turns off an audible alarm. The visual alarms connect to aisle lights or other visible alarm devices at the installation site. The E2A alarms provide input to the management stations via the EMS.
The SCM-CI busses the alarms together from both SCMs in a redundant controller configuration. Only the active SCM can send an alarm.
Follow these steps to connect the G6 Voice Gateway alarms to the alarm connectors on the fuse and alarm panel (FAP).
1 For the critical audible alarm, connect an alarm wire from pin 1 (+ high) on the audible alarm block on the chassis to the corresponding alarm pin on the FAP.
2 To complete the relay, connect a second wire from pin 2 (– low) to the corresponding alarm pin on the FAP.
Audible Visual E2A
Critical Critical Critical
Major problem Major problem Major problem
Minor problem Minor problem Minor problem
Miscellaneous problem
Miscellaneous problem
Miscellaneous problem
38 Hardware Installation Guide
Grounding, Cabling, and Applying Power
3 Repeat steps 1 and 2 for the other three audible alarms (major, minor, and miscellaneous).
4 Complete steps 1–3 for the visual and E2A alarms.
5 Bundle the alarm cables together. Use an appropriate tie-wrap to tie down the alarm cable bundle to the chassis. Label the cables to identify them.
Figure 18 shows an example of a critical, audible alarm connection to a4 fuse and alarm panel.
Figure 18. Alarm and Events Pins on SCM-CI Panel
Preliminary Beta Release—Subject to Change 39
Connect the G6 Management Ports
Connect the G6 Management Ports
Follow these steps to connect the G6 Voice Gateway management ports to the management stations and management consoles on the primary and redundant LANs. Figure 19 shows the management port connections to the LANs.
1 Connect the Ethernet RJ-45 connector for the primary LAN connection to management port A (labeled 10/100-A) on the SCM-CI panel on the back of the chassis.
2 Connect the Ethernet RJ-45 connector for the redundant LAN connection to management port B (labeled 10/100-B).
3 Use an appropriate tie-wrap to tie down the Ethernet management cables to the chassis. Color code and/or label the cables to identify them as Management Ports A and B.
40 Hardware Installation Guide
Grounding, Cabling, and Applying Power
Figure 19. A & B Management Ports on SCM-CI Panel
Connect the External Timing Ports
A building interface timing system (BITS) provides a T1-formatted signal to carry timing. BITS is the preferred and most reliable timing source for a gateway. The A and B blocks provide redundant timing pins for both SCMs in a chassis. Figure 20 shows the external timing pins on the SCM-CI panel on the back of the chassis. Figure 21 shows an example of timing pins connected to the BITS.
Preliminary Beta Release—Subject to Change 41
Connect the External Timing Ports
Figure 20. BITS and CC Timing Pins on SCM-CI Panel
Follow these steps to connect the external timing pins on the G6 Voice Gateway to a BITS.
1 Connect a timing wire to the primary tip timing pin (TIP on the A timing pin block).
2 Connect a timing wire to the primary ring timing pin (RING on the A timing pin block).
3 Connect a timing wire to the primary sleeve timing pin (SLEEVE on the A timing pin block).
4 Connect the primary tip timing wire to the primary tip pin on the timing panel.
5 Connect the primary ring timing wire to the primary ring pin on the timing panel.
NoteConsult the wiring standards for your installation to determine sleeve wire ter-mination requirements. Many installa-tions use a bare wire and terminate it only at the source.
42 Hardware Installation Guide
Grounding, Cabling, and Applying Power
6 Connect the primary sleeve timing wire to the primary sleeve (shield) pin on the timing panel.
7 Repeat steps 1 through 7 for the redundant timing pins.
8 If appropriate for your installation, bundle the timing cables together. Use an appropriate tie-wrap to tie down the timing cable bundle to the chassis. Label the cables to identify them.
Timing can also be provided externally from a T1/DS1 line, a DS3 line, or from a composite clock (CC). If timing is from a T1 or DS3, the G6 Voice Gateway receives the timing from a line connected to a T1 or DS3 port without further connections.
If BITS is connected, any simultaneous T1 and DS3 timing sources are secondary. The gateway does not support simultaneous BITS and CC timing sources.
If timing is from a CC, connect the timing pins exactly as described in the previous steps, but connecting the CC timing pins to the composite clock instead of to the BITS.
If all external timing sources are lost, the G6 Voice Gateway bases timing on the last source for up to 28 hours to allow for maintenance or updates to the timing system.
Preliminary Beta Release—Subject to Change 43
Connect the G6 Shelf to the Power Source
Figure 21. BITS and CC Timing Pins on SCM-CI Panel
Connect the G6 Shelf to the Power Source
Before connecting the G6 shelf to the power source, verify that the power source is properly grounded and falls within the internal power supply ratings. The input –48V supply bus is protected by circuit breakers mounted on the rear lower panel of the G6 shelf. Each power supply has an internal major fault circuit protection fuse soldered in place (factory replaceable only) and rated at 25 A, 125 V. The G6 shelf incorporates a power supply monitor to monitor the power supply levels in each of the modules and manage the main hardware reset function on each module.
This procedure shows how to connect the power on the G6 shelf through a fuse and alarm panel that is properly connected to the power source. Using a small flat-head
44 Hardware Installation Guide
Grounding, Cabling, and Applying Power
screwdriver and the appropriate power wires, follow these steps to connect the G6 shelf to the power connectors on the fuse and alarm panel. Figure 22 shows the power connectors on the SCM-CI panel of the chassis.
1 Connect the negative (black in many systems) wire from the Rail A primary power source to the primary negative connector (A) on the power terminal block on the SCM-CI on the back of the chassis.
2 Connect the positive (red in many systems) wire from the Rail A primary power source to the primary positive connector (A-RTN) on the power terminal block.
Figure 22. Power Connectors on the SCM-CI Panel
Detail of primary (A) power connection
Preliminary Beta Release—Subject to Change 45
Connect the G6 Shelf to the Power Source
3 Connect the negative wire from the Rail B secondary power source to the secondary negative connector (B) on the power terminal block.
4 Connect the positive wire from the Rail B secondary power source to the secondary positive connector (B-RTN) on the power terminal block.
5 If appropriate for your installation, bundle the power cables together. Use an appropriate tie-wrap to tie down the power cable bundle to the chassis. Label the cables as primary and secondary.
Figure 23 shows the G6 shelf connections to a –48VDC power source through an in-rack fuse and alarm panel.
46 Hardware Installation Guide
Grounding, Cabling, and Applying Power
Figure 23. Power Through an In-Rack Fuse and Alarm Panel
Figure 24 shows the power connected to a remote power source.
Preliminary Beta Release—Subject to Change 47
Power Up the Shelf
Figure 24. Power Connection To a Remote Source
Power Up the Shelf
Apply power to the shelf.
48 Hardware Installation Guide
Grounding, Cabling, and Applying Power
Start Up the System
When a G6 Voice Gateway is shipped, the G6 system software is already installed on the SCM, ANM, and TPM cards. Access to this software is through a command line interface (CLI) provided on the SCM. Refer to the Software Installation & System StartUp Guide for information about starting up a G6 shelf. Refer to the CLI Operation Guide & Commands Reference for a list of the commands available and detailed information about using them.
Run Diagnostics
Use the General Bandwidth System Diagnostics to troubleshoot the G6 shelf installation.
Cable the Telephony Ports
The final physical step in installing a G6 Voice Gateway hardware is to connect the gateway into the network. The physical connections into the network are dependent on the equipment in a particular environment. In general, these physical connections consist of cabling G6 Voice Gateway to the network side (typically a Class 5 switch) and, ultimately, to the customer premises equipment.
Connect to the Network Side
Connecting to the network side typically consists of connecting the DS1/T1 ports to a Class 5 switch. The 50-pin connector on the TPM DS1/T1 CIM provides connections for 10 DS1/T1 ports. The bottom 4 pins (wires) provide T1 #10, the second, T1 #9, and so forth. The top 10 pins are not used.
Preliminary Beta Release—Subject to Change 49
Cable the Telephony Ports
Figure 25. Network-Side Connection to a Class 5 Switch
1 Connect a standard DS1/T1 cable to the 50-pin connector header on a TPM DS1/T1 card.
37
36
12
1136
11
37
12
Class 5 Switch G6 Gateway
Detail of wire-wrap cabling for a single T1 connection (T1 #5) to a Class 5 switch
Detail of 50-pin cabling to a TPM card for 10 DS1/ T1 connections
50 Hardware Installation Guide
Grounding, Cabling, and Applying Power
2 If appropriate for your installation, use an appropriate tie-wrap to tie down the DS1/T1 cable to the chassis. Label the cable.
3 Following the color-coding scheme shown in the Color Coding Wire Scheme section, connect the first set of 4 wires for a T1 (usually T1 #1 or T1 #10) to the Class 5 switch. This connection may be a punchdown box, wire-wrap pins, DSX panel, multiplexer, channel bank, or other connection panel.
4 Follow the color-coding scheme to connect the appropriate four wires for each of the other 9 T1 ports. Connecting all 10 ports uses 40 of the wires in the DS1/T1 cable.
Color Coding Wire Scheme
The wiring illustrations in this section are based on the AT&T uniform color-coding scheme telephony wires. To simplify color coding large numbers of wires, each wire pair uses a two-color code with colors selected from two groups of five. The colors for a group are white, red, black, yellow, and violet. The colors for pair (within a group) are blue, orange, green, brown, and slate.
Caution!
The recommended bend radius for thin-type 735A coaxial cable or equivalent is not less than one-quarter of an inch. A sharper bend can result in the cable not working properly. Do not bend the DS3 cables at a sharper radius than one-quarter of an inch.
Preliminary Beta Release—Subject to Change 51
Cable the Telephony Ports
Each pair includes one wire with a solid background of its group color and stripes of its pair color. The second wire in the pair reverses the colors. Note that red-brown and red-orange wires are very similar.
Common Wiring Scheme for Telephony
Wire Pair
Wire Number
Solid Color
Stripe Color
Pin Number
GB T1 Line
11 White Blue 26
T1 #102 Blue White 1
21 White Orange 27
2 Orange White 2
31 White Green 28
T1 #92 Green White 3
41 White Brown 29
2 Brown White 4
51 White Slate 30
T1 #82 Slate White 5
61 Red Blue 31
2 Blue Red 6
71 Red Orange 32
T1 #72 Orange Red 7
81 Red Green 33
2 Green Red 8
91 Red Brown 34
T1 #62 Brown Red 9
101 Red Slate 35
2 Slate Red 10
111 Black Blue 36
T1 #52 Blue Black 11
121 Black Orange 37
2 Orange Black 12
52 Hardware Installation Guide
Grounding, Cabling, and Applying Power
Connect to the CPE Side
The steps to connect to the CPE side depends on the CPE environment. In general, it involves connecting the ANM card DS3 ports through an ATM switch or another access
131 Black Green 38
T1 #42 Green Black 13
14 1 Black Brown 39
2 Brown Black 14
151 Black Slate 40
T1 #32 Slate Black 15
161 Yellow Blue 41
2 Blue Yellow 16
171 Yellow Orange 42
T1 #22 Orange Yellow 17
181 Yellow Green 43
2 Green Yellow 18
191 Yellow Brown 44
T1 #12 Brown Yellow 19
201 Yellow Slate 45
2 Slate Yellow 20
21 1 Violet Blue 46 not used
2 Blue Violet 21 not used
22 1 Violet Orange 47 not used
2 Orange Violet 22 not used
23 1 Violet Green 48 not used
2 Green Violet 23 not used
24 1 Violet Brown 49 not used
2 Brown Violet 24 not used
25 1 Violet Slate 50 not used
2 Slate Violet 25 not used
Common Wiring Scheme for Telephony
Wire Pair
Wire Number
Solid Color
Stripe Color
Pin Number
GB T1 Line
Preliminary Beta Release—Subject to Change 53
Cable the Telephony Ports
point to the customer premises equipment. The 4-port ANM DS3 card includes 8 BNC connectors for the 4 DS3 ports; the 8-port card includes 16.
Figure 26. CPE-Side Connection to an ATM Switch
1 Connect the first DS3 transmit cable to the first Tx BNC connector header on the primary ANM DS3 card.
2 Connect the first DS3 receive cable to the first Rx BNC connector header on the primary ANM DS3 card.
3 Repeat steps 1 and 2 for each of the other DS3 ports.
4 If appropriate for your installation, bundle the DS3 cables together. Use an appropriate tie-wrap to tie
G6ATM
Detail of BNC cabling to an ANM card for DS3 port 1
G6 Gateway ATM Switch
54 Hardware Installation Guide
Grounding, Cabling, and Applying Power
down the DS3 cable bundle to the chassis. Label the cables to identify them.
5 Connect the other ends of the DS3 cables to the appropriate transmit and receive BNC connectors on the ATM switch or DSLAM.
Read the CPE Side Environments section for more information about connecting to different CPE environments.
CPE Side Environments
The physical connections of the DS3 lines are dependent on the environment. The following diagrams show a few possible connection points.
DSLAM Connection
Figure 27 shows the connection in a DSLAM environment. In this case, the G6 connects directly to a DSLAM, which connects to IADs at the customer premises. The drawing is simplified to show only a simplex connection. A redundant connection would connect the 4 DS3 ports on the standby ANM DS3 card to a second DSLAM.
Caution!
The recommended bend radius for thin-type 735A coaxial cable or equivalent is not less than one-quarter of an inch. A sharper bend can result in the cable not working properly. Do not bend the DS3 cables at a sharper radius than one-quarter of an inch.
Preliminary Beta Release—Subject to Change 55
Cable the Telephony Ports
Figure 27. CPE-Side Connection through a DSLAM
The drawing is simplified to show only a simplex connection. A redundant connection would connect the 4 DS3 ports on the standby ANM DS3 card to a second DSLAM.
ATM Switch Connection
Figure 28 shows the connection in an ATM to DSLAM environment. In this case, the G6 connects to an ATM switch, which connects to a DSLAM and then to IADs at the customer premises.
Figure 28. CPE-Side Connection through an ATM Switch
The drawing is simplified to show only a simplex connection. A redundant connection would connect the 4 DS3 ports on the standby ANM DS3 card to a second ATM switch.
DSLAMG6 IAD Phone
G6 DSLAM IAD PhoneATM
56 Hardware Installation Guide
Grounding, Cabling, and Applying Power
CMTS Connection
Figure 28 shows the connection in an ATM to CMTS cable environment. In this scenario, the G6 connects to an ATM switch, which connects to a CMTS and then to MTAs at the customer premises.
Figure 29. CPE-Side Connection through an ATM Switch
The drawing is simplified to show only a simplex connection. A redundant connection would connect the 4 DS3 ports on the standby ANM DS3 card to a second ATM switch. Future ANM cards will provide for G6 to CMTS direct connections.
G6 ATM CTMS MTA Phone
Preliminary Beta Release—Subject to Change 57
Cable the Telephony Ports
58 Hardware Installation Guide
5C H A P T E R
Adding ModuleCards
This chapter provides instructions on how to install additional module cards when you are upgrading a G6 shelf. Cards can be installed and removed while the G6 shelf is running (hot-swappable).
Tools and Supplies Required
Installing the G6 chassis into a rack requires only standard tools and supplies.
A flat-blade screwdriver and a #1 Phillips screwdriver
Wire cutters
Wire strippers
An antistatic ESD wrist grounding strap
A digital voltmeter
Cable bundling material, such as cable ties or waxed twine (depending on the location cabling requirements)
Cable identification tags or equivalent markers
Safety Guidelines
Follow these guidelines for a safe installation.
Review the safety information in General Safety Precautions in the Preface of this guide.
Preliminary Beta Release—Subject to Change 59
Installing G6 Module Cards
Pay close attention to any notes and comply with cautions and warnings throughout the installation procedures.
Comply with all applicable safety requirements, practices, and standards cited in NEBS.
Comply with your organization’s safety guidelines.
Installing G6 Module Cards
After setting up the rack, chassis, ground, and power, install the G6 module cards that provide telephony and control features and the cable interface cards. Figures 30 through 33 show the card installations. When installing more than one type of card, install them in the following order to ensure that auto-discovery works properly.
SCM cards
ANM cards
TPM cards
CIM cards
Prepare the Slot Before installing a card, remove the faceplate or cover that covers the slot.
Install the SCM Cards
The SCM card is installed into the chassis as part of a typical factory installation. Follow this procedure to install an SCM card only if you are adding a new SCM
Caution! Electrical Hazard
Use proper ESD precautions at all times when handling the G6 cards. Static volt-ages as low as 30V can damage circuitry. Observe all standard antistatic procedures when you handle the G6 Voice Gateway and components.
60 Hardware Installation Guide
Adding Module Cards
card to an empty chassis, adding a standby SCM card for redundancy, or replacing a primary (active) SCM card. Otherwise, skip this procedure and continue the section with the next procedure, Install the ANM Cards. Refer to Figure 30 to perform the steps to install a primary SCM card into card slot 9.
Preliminary Beta Release—Subject to Change 61
Install the SCM Cards
Figure 30. SCM Installation (Chassis Front View)
1 Using a #1 Phillips screwdriver, open the two latches on the card. Remove the screws and fully extend the latches.
2 Align the card with the card guide and, with the
1. Open and extend the latches.
3. Close and secure the latches.
2. Install the card.
Slots 9, 10
SCM
62 Hardware Installation Guide
Adding Module Cards
latches fully extended, slide the card into the slot.
3 Snap down the card latches, ensuring that the screws are out of the way. Use the screwdriver to tighten the card latch screws and secure the card into the chassis.
If you are using redundant cards, repeat this procedure to install the secondary SCM card into card slot 10.
The cable interface for the SCM cards is already installed and is not field replaceable.
NoteInstall a card only into an SCM slot. Install the primary SCM card slot first in slot 9 and then the standby card in slot 10.
Safety ComplianceIn order to comply with the UL-1950 safety standard, you must secure the cards to the chassis. Standard TR-78 for customer ser-viceable modules states that modules must be removable without tools. Ensure that the cards are installed and secured according to the standards in use by your organization.
Preliminary Beta Release—Subject to Change 63
Install an ANM Card
Install an ANM Card
Refer to Figure 31 to perform the steps to install a primary (active) ANM card into one of the card slots that currently support the high-speed ANM cards.
1 Using a #1 Phillips screwdriver, open the two latches on the card. Remove the screws and fully extend the latches.
2 Align the card with the card guide and, with the latches fully extended, slide the card into the slot.
3 Snap down the card latches, ensuring that the screws are out of the way. Use the screwdriver to tighten the
NoteInstall a card only into an ANM slot. Slots 1-6 support the high-speed ANM cards. For ANM redundancy, install the cards in pairs.
first primary ANM card in slot 1 and its standby (secondary) card in slot 2
next primary ANM card in slot 3 and its standby card in slot 4
third primary ANM card in slot 5 and its standby card in slot 6
64 Hardware Installation Guide
Adding Module Cards
card latch screws and secure the card into the chassis.
If you are installing additional ANM cards, repeat this procedure to install the additional cards into the appropriate slots.
Safety Compliance
In order to comply with the UL-1950 safety standard, you must secure the cards to the chassis. Standard TR-78 for customer ser-viceable modules states that modules must be removable without tools. Ensure that the cards are installed and secured according to the standards in use by your organization.
Preliminary Beta Release—Subject to Change 65
Install an ANM Card
Figure 31. ANM Installation (Chassis Front View)
After installing the ANM cards, install a cable interface module (CIM-DS1) for each primary ANM card and a sparing CIM for each standby ANM card. Read Install CIM Cards for instructions. Read CIM Cards for more information about the types of CIMs available.
Slots 1-6ANM
. Open and extend the latches.
3. Close and secure the latches.
2. Install the card.
66 Hardware Installation Guide
Adding Module Cards
Install a TPM Card
Refer to Figure 32 to perform the steps to install a primary (active) TPM card into one of the card slots that support TPM cards.
1 Using a #1 Phillips screwdriver, open the two latches on the card. Remove the screws and fully extend the latches.
2 Align the card with the card guide and, with the latches fully extended, slide the card into the slot.
3 Snap down the card latches, ensuring that the screws are out of the way. Use the screwdriver to tighten the card latch screws and secure the card into the chassis.
If you are installing additional TPM cards, repeat this procedure to install the additional cards into the appropriate slots.
NoteInstall a card only into a TPM slot. Slots 3–8 and 11–18 support TPM cards. For TPM redundancy, install a sparing TPM card for the others (N+1 sparing). A typical config-uration is to install the TPM standby card (and a sparing CIM) in slot 18 of each G6 shelf.
Safety Compliance
In order to comply with the UL-1950 safety standard, you must secure the cards to the chassis. Standard TR-78 for customer ser-viceable modules states that modules must be removable without tools. Ensure that the cards are installed and secured according to the standards in use by your organization.
Preliminary Beta Release—Subject to Change 67
Install a TPM Card
After installing the TPM cards, install a CIM for each TPM card. Read Install CIM Cards for instructions. Read CIM Cards for more information about the types of CIMs available.
68 Hardware Installation Guide
Adding Module Cards
Figure 32. TPM Installation (Chassis Front View)
Slots 3-8, 11-18
TPM
1. Open and extend the latches.
3. Close and secure the latches.
2. Install the card.
Preliminary Beta Release—Subject to Change 69
CIM Cards
After installing the TPM cards, install a CIM-T1/DS1 for each primary TPM card and a sparing CIM for the standby TPM card. Read the section, Install CIM Cards, for instructions. Read the section, CIM Cards, for more information about the types of CIMs available.
CIM Cards The cable interface module (CIM) cards provide the backside electrical interfaces and cabling connections for SCM, ANM, and TPM cards. There are four types of CIMS.
SCM-CIThe SCM-CI card provides a power and cable interface to the chassis for both the active SCM card and the standby SCM card if one is installed.
CIM-DS3The CIM-DS3 card provides a primary DS3 interface (four or eight DS3 connectors). The CIM-DS3 card provides the cable interface for a primary ANM card. Each set of two 75-ohm BNC connectors on the CIM-DS1 card provides a single DS3 port.
CIM-DS1/T1The CIM-DS1/T1 card provides a primary DS1 interface (10 TPM T1/DS1 ports). The CIM-DS1/T1 card provides the cable interface for a primary TPM card. The CHAMP connector on the CIM-DS1 card provides the 10 T1/DS1 ports.
Caution
The SCM-CI is mounted in the chassis during factory assembly. The SCM-CI can-not be removed from the chassis without taking the entire G6 Voice Gateway out of service. The SCM-CI is not field replace-able.
70 Hardware Installation Guide
Adding Module Cards
CIM-SPAREThe CIM-SPARE card provides a standby DS1 interface that enables the SCM to redirect DS1 traffic through the sparing bus to a hot standby, dedicated sparing TPM card in the case of a TPM card failure. The CIM-SPARE card provides the cable interface for a standby TPM card.
Install a CIM Card
Refer to Figure 33 to perform the steps to install a CIM card into the G6 shelf.
Install a primary (active) CIM card for each primary ANM or TPM card you installed previously. Install a sparing CIM-DS3 card for each standby ANM card you installed previously. Install a sparing CIM-SPARE card for the standby TPM card you installed previously.
Preliminary Beta Release—Subject to Change 71
Install a CIM Card
Ensure that the CIM slot numbers match the slot numbers into which you previously installed the cards. The CIM cards are color coded to match their corresponding cards.
1 Align the CIM card with the card guide and slide the card into the slot.
2 Tighten the thumbscrew to secure the card into the chassis.
If you are installing additional CIM cards, repeat this procedure to install the additional cards into the appropriate slots.
NoteInstall a CIM-DS3 or CIM-DS1 for each frontside ANM or TPM card, respectively. Install a CIM-SPARE card for each standby ANM or TPM card.
Install each CIM card into exactly the same slot number in which the card is installed.
Slots 1-6 support ANM cards.
Slots 3-8 and 11-18 support TPM cards.
72 Hardware Installation Guide
Adding Module Cards
Figure 33. CIM Installation (Chassis Rear View)
Cover Empty Slots
Any card slots that are empty must be covered with a blank faceplate. Any CIM slots that do not contain a CIM must be covered with a blank cover panel. Blank faceplates and cover panels provide three important functions.
Slots 1-6
Slots 3-8, 11-18
ANM
TPM
2. Secure the card.
1. Install the card.
Preliminary Beta Release—Subject to Change 73
Connect the Line Cables
Preventing exposure to hazardous voltages and currents inside the chassis
Containing electromagnetic interference (EMI) that might disrupt other equipment
Directing the flow of cooling air throughout the chassis
Do not remove the covers or faceplates from empty card slots. Install a cover or faceplate over any slot from which you remove a card.
Connect the Line Cables
After installing the cards, connect the line cables to the appropriate CIM cards.
Secure the Cables
After connecting the line cables to the appropriate CIM cards, secure and label the cables.
1 Use cable bundling material, such as cable ties or waxed twine to secure the cables to the rack or within a cable tray.
2 Use identification tags or equivalent markers to identify the cables.
WARNING
Do not operate the system unless all cards, face-plates, and covers are in place.
74 Hardware Installation Guide
6C H A P T E R
Removing ModuleCards
This chapter provides instructions on how to remove a module card for replacement or return. The cards can be removed and installed while the G6 shelf is running (hot-swappable).
Tools and Supplies Required
Removing a card from the G6 chassis into a rack requires only standard tools and supplies.
A #1 Phillips screwdriver
An antistatic ESD wrist grounding strap
Safety Guidelines
Follow these guidelines for a safe removal.
Review the safety information in General Safety Precautions in the Preface of this guide.
Pay close attention to any notes and comply with cautions and warnings throughout the installation procedures.
Comply with all applicable safety requirements, practices, and standards cited in NEBS.
Preliminary Beta Release—Subject to Change 75
Remove a Frontside Card
Comply with your organization’s safety guidelines.
Remove a Frontside Card
Follow this procedure to remove an SCM card. If you have a redundant card, you can remove either the primary or secondary card without impacting system performance.
The G6 shelf is not fault tolerant when either of the SCM cards is removed. An ANM primary/standby pair is not fault tolerant when either the standby or the primary card in the pair is removed. None of the TPM cards are fault tolerant when the TPM standby card is removed.
Refer to Figure 34 while performing the steps to remove an SCM card.
Caution! Electrical Hazard
Use proper EDS precautions at all times when handling the G6 cards. Static voltages as low as 30V can cause latent damage to circuitry. Be sure to observe all standard antistatic procedures when you handle this unit, including wearing a grounding strap.
76 Hardware Installation Guide
Removing Module Cards
Figure 34. Frontside Card Removal (Chassis Front View)
1 Using a #1 Phillips screwdriver, open the two latches on the card. Remove the screws and fully extend the latches.
2 With the latches fully extended, slide the card out of the card guide.
1. Open and extend the latches.
3. Close and secure the latches.
2. Remove the card.
Slots 1-6
Slots 3-8, 11-18Slots 9, 10
ANM
SCMTPM
Preliminary Beta Release—Subject to Change 77
Remove a CIM Card
3 Close the card latches and use a #1 Phillips screwdriver to secure the card latch screws before returning the card.
The cable interface for the SCM cards is not field replaceable.
Remove a CIM Card
Refer to Figure 35 to perform the steps to remove a CIM card.
78 Hardware Installation Guide
Removing Module Cards
Figure 35. CIM Card Removal (Chassis Rear View)
1 Loosen the thumbscrew to release the card.
2 Slide the card out of the slot.
Cover Empty Slots
Any card slots that are empty must be covered with a blank faceplate. Any CIM slots that do not contain a CIM must be covered with a blank cover panel. Blank faceplates and cover panels provide three important functions.
Slots 1-6
Slots 2-8, 11-18Slots 9, 10
ANM
SCMTPM
1. Loosen the thumbscrew.
2. Remove the CIM card.
Preliminary Beta Release—Subject to Change 79
Cover Empty Slots
Preventing exposure to hazardous voltages and currents inside the chassis
Containing electromagnetic interference (EMI) that might disrupt other equipment
Directing the flow of cooling air throughout the chassis
Do not remove the covers or faceplates from empty card slots. Install a cover or faceplate over any slot from which you remove a card.
WARNING
Do not operate the system unless all cards, face-plates, and covers are in place.
80 Hardware Installation Guide
Index
Aair filter tray
installation and maintenance 28See also cooling, ventilation
aisle requirements 28
alarmand event pins on the SCM-CI
panel 14connecting alarms on the FAP 38connecting to a fuse 38–39connectors on the FAP 38cut off button on SCM card 38fan failure 2
ANM (Access network module) 8–10CMTS interface 8DSLAM interface 8installing 60, 64–66LED status 10redundancy 64removing 76–78slots 4See also cards, CIM (Cable interface
module), SCM (System control module), TPM (Telephony port module)
Bbattery 33
battery return lines 33
Ccables
interfaces with ANM, SCM, TPM cards 13
securing line cables to CIM 74
cardsANM 8–10
CMTS interface 8
DSLAM interface 8
installing 64–66
LED status 10
redundancy 64
removing 76–78
slots 4
CIM 70–71CIM-DS1 70
CIM-DS1/T1 16–18
CIM-DS3 16–18, 70
ports and connectors 17
CIM-SPARE 71
installing 60, 71–73
protection circuits 34
removing 78–79
SCM-CI 3, 5–6, 13–16, 70
management ports 13
Preliminary Beta Release—Subject to Change Index-81
power connectors 45
securing line cables to 74
slots 4, 72
status LED 18
empty slots 73–74, 79installing 60power requirements 33removing 76–78
safety guidelines 75
tools and supplies 75
SCM 5accessing software with CLI 49
installing 60–63
removing 76–78
serial craft port on 7
slots 4
status LED 7
shipping 21–23slot numbers 4TPM 11–12
installing 60, 67–70
removing 76–78
slots 4
status LED 12
weight 29
CIM (Cable interface module) 70–71CIM-DS1 70CIM-DS1/T1 17CIM-DS3 16–18, 70
ports and connectors 17
CIM-SPARE 71installing 60, 71–73protection circuits 34removing 78–79SCM-CI 3, 5–6, 13–16, 70
management ports 13
securing line cables to 74slots 4, 72status LED 18
See also ANM (Access network module), cards, SCM (System control module), TPM (Telephony port module)
CLI (command line interface)software access 49
CMTSANM interface to 8
complying with standardsNEBS Level 3 27TR-78
ANM installation 65
SCM installation 63
TPM installation 67
UL-1950ANM installation 65
SCM installation 63
TPM installation 67
connectorsalarm 38Ethernet 40
cooling 2–3fan
failure 2
tray installation 28
ventilation 28
Ddamage
returns 24static and removing cards 76unpacking 21
depthG6 shelf 29See also height, rack requirements,
shelves, weight, width
Index-82 Hardware Installation Guide
diagnosticsshelf installation 49
dimensionsG6 shelf 29G6 Voice Gateway 2
distribution panels 33
DSLAMANM interface to 8
Eearth grounding 34
equipment rackspower requirements 33
external timing portsconnecting 41–44
Ffan
failure 2–3LEDs 3tray installation 28
FAP (fuse and alarm panel)connecting alarms 38
fault circuit protection fuserating 44
fault toleranceand card removal 76
frame grounding 34, 36–37
fuse and alarm panel 33connecting alarms to 38
GG6 Voice Gateway
installation 32aisle requirements 28
standards compliance 27
ventilation 28
packaging and shipping 21–23rack requirements 28returns 24shelf dimensions 29
GR-1089cardcage 4surge protection and alarm
connection 38surge protection of BITS and CC 14surge protection on wire-wrap pins on
the SCM-CI 14
GR-1244BITS termination if no SCM cards are
present 14
GR-303interface with PSTN through TPM 11
GR-63aisle requirements and installation 28cardcage 4
groundingchassis 3–4, 36–37earth 34frame 34, 36–37logic 34requirements 34supplies
installing G6 chassis into a rack 34–35
transient 34, 36–37
Preliminary Beta Release—Subject to Change Index-83
Hheight
G6 shelf 29See also depth, rack requirements,
shelves, weight, width
Iinspection 21
installationaisle requirements 28G6 Voice Gateway into a mounting
rack 32G6 Voice Gateway into a rack 30–31rack requirements 28safety guidelines when installing a G6
Voice Gateway into a rack 31
standards compliance 27ventilation 28
inventory 24
LLEDs
ANM status 10CIM status 18fan assembly module status 3SCM status 7TPM status 12
limits, thermal 2
logic grounding 34
Mmanagement ports
connecting 40–41
module cardsSee ANM (Access network module),
cards, SCM (System control module), TPM (Telephony port module)
mountingchassis into rack or cabinet 2installing G6 chassis in rack 32
NNEBS Level 3-compliancy 27
Ppower source 33
connecting the G6 shelf to a 44–48
protection circuitsCIM 34
Rrack requirements 28
See also depth, height, shelves, weight, width
removingANM 76–78CIM 78–79SCM 76–78TPM 76–78
requirements
Index-84 Hardware Installation Guide
aisle 28installing module cards 59power 33rack 28removing a card from G6 chassis 75
returnsreturn material authorization number
(RMA) 24
Ssafety
empty slots 73–74guidelines xvi
installing a G6 chassis into a rack 35–36
installing G6 Voice Gateway into a rack 31
installing module cards 59
mounting and servicing G6 Voice Gateway 32
removing module cards 75
TR-78 63, 65, 67
UL-1950 63, 65, 67
SCM (System control module) 5accessing software with CLI 49installing 60–63removing 76–78serial craft port on 7slots 4status LED 7See also ANM (Access network
module), cards, CIM (Cable interface module), TPM (Telephony port module)
serial craft porton SCM 7
shelf dimensions 29
See also depth, height, rack requirements, shelves, weight, width
shelvesstacking 28See also depth, height, rack
requirements, weight, width
standards, complying withNEBS Level 3 27TR-78
ANM installation 65
SCM installation 63
TPM installation 67
UL-1950ANM installation 65
SCM installation 63
TPM installation 67
storage rackspower requirements 33
suppliesfor installing G6 Voice Gateway into a
rack 30–31for removing a card from G6 chassis 75installing G6 Voice Gateway into a
rack 34–35installing module cards 59
system software 18–19
TTFTP
downloading system software via 18
thermal limits 2
timing pinsconnecting the G6 Voice Gateway to a
BITS 42–43on the SCM-CI panel 14SCM-CI 42
Preliminary Beta Release—Subject to Change Index-85
toolsfor installing G6 Voice Gateway into a
rack 30–31for removing a card from G6 chassis 75installing G6 chassis into a rack 34–35installing module cards 59
TPM (Telephony port module) 11–12installing 60, 67–70removing 76–78slots 4status LED 12See also ANM (Access network
module), cards, CIM (Cable interface module), SCM (System control module)
TR-78ANM installation 65SCM installation 63TPM card installation 67
transient grounding 34, 36–37
UUL-1950
ANM installation 65SCM installation 63TPM installation 67
Vventilation 28
Wweight
G6 chassis lifting hazard 24
G6 shelf 29See also depth, height, rack
requirements, shelves, width
widthG6 shelf 29See also depth, height, rack
requirements, shelves, weight
Index-86 Hardware Installation Guide