FYREHALT FIRE CURTAIN Rev - Smoke Control

9
FILE: SCS-FH.dwg --- PLOTTED ON 04/09/2020 BY ISHTIAQUE ALAM · THIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, AND MUST NOT BE RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OF SMOKE CONTROL SYSTEMS PTY. LTD. · DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY. · ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR. · SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OF MEASUREMENTS PROVIDED BY OTHERS. Rev CHK REASON DATE CLIENT AUSTRALIAN HEADOFFICE PHONE: 1300 665 471 [email protected] NEW ZEALAND PHONE: 09 300 1980 [email protected] WWW.SMOKECONTROL.COM.AU DRAWN BY START DATE DRAWING NUMBER ISSUE STATUS: TITLE PROJECT <<< 594mm 420mm >>> SCALE @A2 SUB SET (CATEGORY) INFORMATION COPY ONLY INFORMATION GIVEN IN SMOKECONTROL.COM.AU AND PUBLICATIONS FOR DOWNLOAD ARE GIVEN TO THE BEST OF OUR KNOWLEDGE AND IN GOOD FAITH. SMOKE CONTROL IS NOT RESPONSIBLE IF RECIPIENTS OF TEST REPORTS, ASSESSMENTS OR LITERATURE MISINTERPRET THE CONTENTS AND WRONGLY USE PRODUCTS BASED ON THOSE MISINTERPRETATIONS. NO LIABILITY IS ACCEPTED FOR ERROR OMISSIONS IN THIS WEB SITE OR OUR DOCUMENTS. IN THE INTERESTS OF IMPROVEMENTS AND CONTINUED DEVELOPMENT SMOKE CONTROL RESERVES THE RIGHT TO CHANGE SPECIFICATION WITHOUT NOTICE. DISCLAIMER WWW.SMOKECONTROL.CO.NZ WWW.SMOKECONTROL.COM REV SCS-FH COVER SHEET SCS-FH-0001 I.A. INFORMATION ONLY 24/08/2020 AS SHOWN FYREHALT FIRE CURTAIN 00 - SPECIFICATIONS - No DESCRIPTION REQUIREMENT RESPONSIBILITY 1 WORKS DONE BY OTHERS ALL DETAILS PERTAINING TO WORK BY OTHERS IS AN ADVISEMENT ONLY AND IT IS THE RESPONSIBILITY OF THE SUPPLIER AND INSTALLER OF THE ITEM/S TO CONFIRM COMPLIANCE TO ITS SUITABILITY FOR THE PURPOSE AND TO CERTIFY ITS COMPLIANCE TO THE REQUIRED FRL TO THE SATISFACTION OF THE FE OR CERTIFIER. BUILDER, ARCHITECT, OTHER TRADES 2 SHOP DRAWINGS APPROVAL OF SHOP DRAWINGS (SIGNITURE AND DATE) IS REQUIRED TO BE RETURNED TO SMOKE CONTROL SYSTEMS BEFORE MANUFACTURE CAN COMMENCE. BUILDER, ARCHITECT 3 DELIVERIES TO SITE IF REQD, FORKLIFT TO BE MADE AVAILABLE. BUILDER 4 VERTICAL MOVEMENT OF PRODUCT IF REQD, CRANE SHALL BE AVAILABLE TO SMOKE CONTROL SYSTEMS AT AGREED TIME OF DELIVERY. IF THIS IS NOT AVAILABLE, THIS MAY INCUR EXTRA CHARGES. BUILDER 5 STORAGE SUFFICIENT CLEAR FLOOR SPACE TO BE MADE AVAILABLE IMMEDIATELY ADJACENT TO EACH INSTALLATION LOCATION. BUILDER 6 ACCESS TO WORKFACE (INSTALLATION) REASONABLY ADEQUATE WORKING AREA REQD., MIN 500mm FROM SYSTEM TO STRUCTURE IS IDEAL. SUBJECT TO SITE CONDITIONS. BUILDER 7 POSSIBLE OBSTRUCTIONS (WHERE PRESENT) THERE MUST NOT BE ANYTHING INTERFERING WITH THE OPERATION OF CURTAIN IN ANY WAY. MIN. 100mm FROM SYSTEM TO ANY POSSIBLE OBSTRUCTION TO DROP LINE OF BOTTOM BAR IS IDEAL. BUILDER 8 ACCESS PANELS (INSTALATION WITHIN CEILING CAVITY) 450X450 NOM. ACCESS PANELS TO BE PROVIDED AT THE NOMINATED LOCATION OF CURTAIN CONTROLLER. MAY NOT BE REQD. WHERE REMOVABLE GRID CEILING ALLOWS FOR CLEAR ACCESS TO CURTAIN CONTROLLERS. BUILDER, CEILING CONTRACTOR 9 POWER REQUIREMENTS 240 VOLT 10 AMP GPO TO BE LOCATED NO MORE THAN 1m AWAY FROM NOMINATED LOCATION OF CURTAIN CONTROLLERS. BUILDER, ELECTRICAL 10 ALARM SIGNAL, ACTIVATION 0 VOLT NORMALLY CLOSED CONTACT (OPEN ON ALARM) TO BE PROVIDED WITHIN 1 METRE OF CURTAIN CONTROLLER. BUILDER, ELECTRICAL, FIRE 11 PRESSURISATION, EXHAUST SYSTEMS IMPORTANT: BALANCING TO CONSIDER AFFECTS OF CURTAINS 23 PA MAX. PRESSURE DIFFERENTIAL STRONGLY RECOMMENDED. BULDER, MECHANICAL SERVICES 12 TUNING ALL SCAFFOLDING & OTHER TRADES TO BE CLEAR 2 DAYS PRIOR TO TUNING & COMMISSIONING. BUILDER 13 COMMISSIONING STAGE 1 PRACTICAL COMPLETION TESTS: PERMANENT POWER & ALARMS CONNECTED FOR DRY RUN PRIOR TO CSC. CURTAINS MUST BE ISOLATED DURING INDIVIDUAL COMMISSIONING OF OTHER ESSENTIAL SERVICES. (PRODUCT LOCKED IN OPEN POSITION AFTER TESTING) SMOKE CONTROL SYSTEMS & BUILDER 14 COMMISSIONING STAGE 2 COORDINATED SERVICES COMMISSIONING (CSC) SMOKE CONTROL SYSTEMS 15 COMMISSIONING STAGE 3 WITNESS TESTING, FINAL COMMISSIONING & HANDOVER SMOKE CONTROL SYSTEMS PRODUCT SPECIFICATIONS SYSTEM COMPONENT MATERIALS FRL COLOUR/FINISH ATTENTION: TECHNICAL REQUIREMENTS FOR THIS PROJECT SCS PROJECT: FYREHALT FIRE CURTAIN FYREHALT FIRE CURTAIN FABRIC 1100°C RATED -/120/- AS1530.4 BOTTOM BAR DULUX DURALLOY COLOUR TBA WILL COME IN RAW FINISH IF COLOUR IS NOT PROVIDED BY CLIENT SIDE GUIDES GALVANISED STEEL SIDE GUIDES HEAD BOX & BOTTOM BAR GALVANISED STEEL HEAD BOX DRAWING INDEX SHEET DESCRIPTION REV 00 - SPECIFICATIONS 0001 COVER SHEET - 01 - FIRE CURTAINS 0101 FYREHALT FIRE CURTAIN - INSTALLED WITHIN OPENING - 0102 FYREHALT FIRE CURTAIN - INSTALLED OVER OPENING - 0103 FYREHALT FIRE CURTAIN - INSTALLED OVER LIFT - 0104 FYREHALT FIRE CURTAIN - FUSIBLE LINK - 0105 FYREHALT FIRE CURTAIN - INSTALLED AT CORNER - 02 - DETAILS 0201 HEAD BOX INSTALLATION TYPES - 0202 SIDE GUIDE INSTALLATION TYPES - 0203 HEAD BOX AND SIDE GUIDE REBATE DETAIL - - AC RELEASED 04/09/2020

Transcript of FYREHALT FIRE CURTAIN Rev - Smoke Control

Page 1: FYREHALT FIRE CURTAIN Rev - Smoke Control

FILE: SCS-FH.dwg --- PLOTTED ON 04/09/2020 BY ISHTIAQUE ALAM· THIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, AND MUST NOT BE

RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OF SMOKE CONTROL SYSTEMSPTY. LTD.

· DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY.· ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR.· SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OF MEASUREMENTS

PROVIDED BY OTHERS.

Rev CHK REASON DATE

CLIENT

AUSTRALIAN HEADOFFICEPHONE: 1300 665 [email protected]

NEW ZEALANDPHONE: 09 300 [email protected]

WWW.SMOKECONTROL.COM.AU

DRAWN BY

START DATE

DRAWING NUMBER

ISSUE STATUS:

TITLE

PROJECT

<<< 594mm

420m

m >>

>

SCALE@A2

SUB SET (CATEGORY)

INFORMATIONC O P Y O N L Y

INFORMATION GIVEN IN SMOKECONTROL.COM.AU AND PUBLICATIONS FORDOWNLOAD ARE GIVEN TO THE BEST OF OUR KNOWLEDGE AND IN GOODFAITH. SMOKE CONTROL IS NOT RESPONSIBLE IF RECIPIENTS OF TESTREPORTS, ASSESSMENTS OR LITERATURE MISINTERPRET THE CONTENTSAND WRONGLY USE PRODUCTS BASED ON THOSE MISINTERPRETATIONS. NOLIABILITY IS ACCEPTED FOR ERROR OMISSIONS IN THIS WEB SITE OR OURDOCUMENTS. IN THE INTERESTS OF IMPROVEMENTS AND CONTINUEDDEVELOPMENT SMOKE CONTROL RESERVES THE RIGHT TO CHANGESPECIFICATION WITHOUT NOTICE.

DISCLAIMER

WWW.SMOKECONTROL.CO.NZWWW.SMOKECONTROL.COM

REV

SCS-FH

COVER SHEET

SCS-FH-0001I.A. INFORMATION ONLY

24/08/2020 AS SHOWN

FYREHALT FIRE CURTAIN

00 - SPECIFICATIONS

-

No DESCRIPTION REQUIREMENT RESPONSIBILITY1 WORKS DONE

BY OTHERSALL DETAILS PERTAINING TO WORK BY OTHERS IS AN ADVISEMENT ONLY AND IT IS THERESPONSIBILITY OF THE SUPPLIER AND INSTALLER OF THE ITEM/S TO CONFIRM COMPLIANCE TOITS SUITABILITY FOR THE PURPOSE AND TO CERTIFY ITS COMPLIANCE TO THE REQUIRED FRLTO THE SATISFACTION OF THE FE OR CERTIFIER.

BUILDER, ARCHITECT,OTHER TRADES

2 SHOP DRAWINGS APPROVAL OF SHOP DRAWINGS (SIGNITURE AND DATE) IS REQUIRED TO BE RETURNED TOSMOKE CONTROL SYSTEMS BEFORE MANUFACTURE CAN COMMENCE.

BUILDER, ARCHITECT

3 DELIVERIES TO SITE IF REQD, FORKLIFT TO BE MADE AVAILABLE. BUILDER4 VERTICAL MOVEMENT

OF PRODUCTIF REQD, CRANE SHALL BE AVAILABLE TO SMOKE CONTROL SYSTEMS AT AGREED TIME OFDELIVERY. IF THIS IS NOT AVAILABLE, THIS MAY INCUR EXTRA CHARGES.

BUILDER

5 STORAGE SUFFICIENT CLEAR FLOOR SPACE TO BE MADE AVAILABLE IMMEDIATELY ADJACENT TO EACHINSTALLATION LOCATION.

BUILDER

6 ACCESS TO WORKFACE(INSTALLATION)

REASONABLY ADEQUATE WORKING AREA REQD., MIN 500mm FROM SYSTEM TO STRUCTURE ISIDEAL. SUBJECT TO SITE CONDITIONS.

BUILDER

7 POSSIBLE OBSTRUCTIONS(WHERE PRESENT)

THERE MUST NOT BE ANYTHING INTERFERING WITH THE OPERATION OF CURTAIN IN ANY WAY.MIN. 100mm FROM SYSTEM TO ANY POSSIBLE OBSTRUCTION TO DROP LINE OF BOTTOM BAR ISIDEAL.

BUILDER

8 ACCESS PANELS(INSTALATION WITHIN CEILING

CAVITY)

450X450 NOM. ACCESS PANELS TO BE PROVIDED AT THE NOMINATED LOCATION OF CURTAINCONTROLLER.MAY NOT BE REQD. WHERE REMOVABLE GRID CEILING ALLOWS FOR CLEAR ACCESS TOCURTAIN CONTROLLERS.

BUILDER, CEILINGCONTRACTOR

9 POWER REQUIREMENTS 240 VOLT 10 AMP GPO TO BE LOCATED NO MORE THAN 1m AWAY FROM NOMINATED LOCATIONOF CURTAIN CONTROLLERS.

BUILDER, ELECTRICAL

10 ALARM SIGNAL,ACTIVATION

0 VOLT NORMALLY CLOSED CONTACT (OPEN ON ALARM) TO BE PROVIDED WITHIN 1 METRE OFCURTAIN CONTROLLER.

BUILDER, ELECTRICAL,FIRE

11 PRESSURISATION,EXHAUST SYSTEMS

IMPORTANT: BALANCING TO CONSIDER AFFECTS OF CURTAINS 23 PA MAX. PRESSUREDIFFERENTIAL STRONGLY RECOMMENDED.

BULDER,MECHANICAL SERVICES

12 TUNING ALL SCAFFOLDING & OTHER TRADES TO BE CLEAR 2 DAYS PRIOR TO TUNING & COMMISSIONING. BUILDER13 COMMISSIONING

STAGE 1PRACTICAL COMPLETION TESTS: PERMANENT POWER & ALARMS CONNECTED FOR DRY RUNPRIOR TO CSC. CURTAINS MUST BE ISOLATED DURING INDIVIDUAL COMMISSIONING OF OTHERESSENTIAL SERVICES.(PRODUCT LOCKED IN OPEN POSITION AFTER TESTING)

SMOKE CONTROLSYSTEMS & BUILDER

14 COMMISSIONINGSTAGE 2

COORDINATED SERVICES COMMISSIONING (CSC) SMOKE CONTROLSYSTEMS

15 COMMISSIONINGSTAGE 3

WITNESS TESTING, FINAL COMMISSIONING & HANDOVER SMOKE CONTROLSYSTEMS

PRODUCT SPECIFICATIONSSYSTEM COMPONENT MATERIALS FRL COLOUR/FINISH

ATTENTION: TECHNICAL REQUIREMENTS FOR THIS PROJECT

SCS PROJECT:FYREHALT FIRE CURTAIN

FYREHALTFIRE CURTAIN

FABRIC 1100°C RATED

-/120/-AS1530.4

BOTTOM BAR

DULUX DURALLOY COLOUR TBAWILL COME IN RAW FINISH IF COLOUR IS NOT PROVIDED BY CLIENT

SIDE GUIDES GALVANISED STEEL SIDE GUIDESHEAD BOX & BOTTOM BAR GALVANISED STEEL HEAD BOX

DRAWING INDEXSHEET DESCRIPTION REV00 - SPECIFICATIONS0001 COVER SHEET -01 - FIRE CURTAINS0101 FYREHALT FIRE CURTAIN - INSTALLED WITHIN OPENING -0102 FYREHALT FIRE CURTAIN - INSTALLED OVER OPENING -0103 FYREHALT FIRE CURTAIN - INSTALLED OVER LIFT -0104 FYREHALT FIRE CURTAIN - FUSIBLE LINK -0105 FYREHALT FIRE CURTAIN - INSTALLED AT CORNER -02 - DETAILS0201 HEAD BOX INSTALLATION TYPES -0202 SIDE GUIDE INSTALLATION TYPES -0203 HEAD BOX AND SIDE GUIDE REBATE DETAIL -

- AC RELEASED 04/09/2020

Page 2: FYREHALT FIRE CURTAIN Rev - Smoke Control

290x240x110www.smokecontrol.com.auwww.smokecontrol.co.nz

T: 1300 665 471T: +64 9 300 1980

Model: 2129 - Trigger Unit

Project:

Tested By:

Date:

This is an electronic control unit for a fire or smoke curtainsystem. It is a critical building safety system and should notbe deenergised or isolated without permission.

DANGER

DANGER 240 VOLTSISOLATE ELSEWHERE BEFIRE

REMOVING COVERS

290x240x110www.smokecontrol.com.auwww.smokecontrol.co.nz

T: 1300 665 471T: +64 9 300 1980

Model: 2129 - Trigger Unit

Project:

Tested By:

Date:

This is an electronic control unit for a fire or smoke curtainsystem. It is a critical building safety system and should notbe deenergised or isolated without permission.

DANGER

DANGER 240 VOLTSISOLATE ELSEWHERE BEFIRE

REMOVING COVERS

290x240x110

FILE: SCS-FH.dwg --- PLOTTED ON 04/09/2020 BY ISHTIAQUE ALAM· THIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, AND MUST NOT BE

RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OF SMOKE CONTROL SYSTEMSPTY. LTD.

· DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY.· ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR.· SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OF MEASUREMENTS

PROVIDED BY OTHERS.

Rev CHK REASON DATE

CLIENT

AUSTRALIAN HEADOFFICEPHONE: 1300 665 [email protected]

NEW ZEALANDPHONE: 09 300 [email protected]

WWW.SMOKECONTROL.COM.AU

DRAWN BY

START DATE

DRAWING NUMBER

ISSUE STATUS:

TITLE

PROJECT

<<< 594mm

420m

m >>

>

SCALE@A2

SUB SET (CATEGORY)

INFORMATIONC O P Y O N L Y

INFORMATION GIVEN IN SMOKECONTROL.COM.AU AND PUBLICATIONS FORDOWNLOAD ARE GIVEN TO THE BEST OF OUR KNOWLEDGE AND IN GOODFAITH. SMOKE CONTROL IS NOT RESPONSIBLE IF RECIPIENTS OF TESTREPORTS, ASSESSMENTS OR LITERATURE MISINTERPRET THE CONTENTSAND WRONGLY USE PRODUCTS BASED ON THOSE MISINTERPRETATIONS. NOLIABILITY IS ACCEPTED FOR ERROR OMISSIONS IN THIS WEB SITE OR OURDOCUMENTS. IN THE INTERESTS OF IMPROVEMENTS AND CONTINUEDDEVELOPMENT SMOKE CONTROL RESERVES THE RIGHT TO CHANGESPECIFICATION WITHOUT NOTICE.

DISCLAIMER

WWW.SMOKECONTROL.CO.NZWWW.SMOKECONTROL.COM

REV

SCS-FH

FYREHALT FIRE CURTAININSTALLED WITHIN OPENING

SCS-FH-0101I.A. INFORMATION ONLY

24/08/2020 AS SHOWN

FYREHALT FIRE CURTAIN

01 - FIRE CURTAINS

-

STRUCTURAL OPENING10

SYSTEM WIDTH10

100BETWEEN GUIDES

100

STRU

CTUR

AL O

PENI

NG

SYST

EM H

EIGH

T

165

CURT

AIND

ROP

CURTAIN CONTROLLER2129-TRIGGER UNITSIZE: 290x240x110REQS. 240V 10A GPO & 0 VOLT N.C. CONTACTTO FIP TO BE PROVIDE BY OTHERS. LOCATEDNO MORE THAN 1m AWAY FROM MOTOR

U/S SLAB

FCL

FFL

450x450 ACCESS PANEL BY OTHERSLOCATED AT THE NOMINATE LOCATION OF CURTAIN CONTROLLER

OPERATION SWITCHLOCATION TBA ON SITE

OPTIONAL STROBE AND/OR SOUNDER

FRL -/120/120 FIRE RATEDBULKHEAD BY OTHERS

450x450 ACCESS PANEL SUPPLIED &INSTALLED BY OTHERSLOCATED AT THE NOMINATE LOCATION OFCURTAIN CONTROLLER

165

50

OPTIONAL STROBEAND/OR SOUNDERBOTH SIDES IF NEEDED

OPERATION SWITCHLOCATION TBA ON SITE

CURTAIN CONTROLLER2129-TRIGGER UNITSIZE: 290x240x110REQS. 240V 10A GPO & 0 VOLT N.C. CONTACTTO FIP TO BE PROVIDE BY OTHERS. LOCATEDNO MORE THAN 1m AWAY FROM MOTOR

450x450 ACCESS PANEL BY OTHERSLOCATED AT THE NOMINATE LOCATION OF CURTAIN CONTROLLER

A

A

B B

2 COR

E CA

BLE

1FRONT ELEVATIONFYREHALT FIRE CURTAIN - INSTALLED WITHIN OPENINGSCALE 1:20 @ A2

165

50

B SECTIONSCALE 1:20 @ A2

A SECTIONSCALE 1:20 @ A2

2 CONTROLLERREQUIRED FORSYSTEM WIDTHMORE THAN 5.5m

- AC RELEASED 04/09/2020

Page 3: FYREHALT FIRE CURTAIN Rev - Smoke Control

290x240x110www.smokecontrol.com.auwww.smokecontrol.co.nz

T: 1300 665 471T: +64 9 300 1980

Model: 2129 - Trigger Unit

Project:

Tested By:

Date:

This is an electronic control unit for a fire or smoke curtainsystem. It is a critical building safety system and should notbe deenergised or isolated without permission.

DANGER

DANGER 240 VOLTSISOLATE ELSEWHERE BEFIRE

REMOVING COVERS

290x240x110www.smokecontrol.com.auwww.smokecontrol.co.nz

T: 1300 665 471T: +64 9 300 1980

Model: 2129 - Trigger Unit

Project:

Tested By:

Date:

This is an electronic control unit for a fire or smoke curtainsystem. It is a critical building safety system and should notbe deenergised or isolated without permission.

DANGER

DANGER 240 VOLTSISOLATE ELSEWHERE BEFIRE

REMOVING COVERS

290x240x110

FILE: SCS-FH.dwg --- PLOTTED ON 04/09/2020 BY ISHTIAQUE ALAM· THIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, AND MUST NOT BE

RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OF SMOKE CONTROL SYSTEMSPTY. LTD.

· DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY.· ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR.· SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OF MEASUREMENTS

PROVIDED BY OTHERS.

Rev CHK REASON DATE

CLIENT

AUSTRALIAN HEADOFFICEPHONE: 1300 665 [email protected]

NEW ZEALANDPHONE: 09 300 [email protected]

WWW.SMOKECONTROL.COM.AU

DRAWN BY

START DATE

DRAWING NUMBER

ISSUE STATUS:

TITLE

PROJECT

<<< 594mm

420m

m >>

>

SCALE@A2

SUB SET (CATEGORY)

INFORMATIONC O P Y O N L Y

INFORMATION GIVEN IN SMOKECONTROL.COM.AU AND PUBLICATIONS FORDOWNLOAD ARE GIVEN TO THE BEST OF OUR KNOWLEDGE AND IN GOODFAITH. SMOKE CONTROL IS NOT RESPONSIBLE IF RECIPIENTS OF TESTREPORTS, ASSESSMENTS OR LITERATURE MISINTERPRET THE CONTENTSAND WRONGLY USE PRODUCTS BASED ON THOSE MISINTERPRETATIONS. NOLIABILITY IS ACCEPTED FOR ERROR OMISSIONS IN THIS WEB SITE OR OURDOCUMENTS. IN THE INTERESTS OF IMPROVEMENTS AND CONTINUEDDEVELOPMENT SMOKE CONTROL RESERVES THE RIGHT TO CHANGESPECIFICATION WITHOUT NOTICE.

DISCLAIMER

WWW.SMOKECONTROL.CO.NZWWW.SMOKECONTROL.COM

REV

SCS-FH

FYREHALT FIRE CURTAININSTALLED OVER OPENING

SCS-FH-0102I.A. INFORMATION ONLY

24/08/2020 AS SHOWN

FYREHALT FIRE CURTAIN

01 - FIRE CURTAINS

-

STRUCTURAL OPENING

SYSTEM WIDTH100

BETWEEN GUIDES100

STRU

CTUR

AL O

PENI

NG

SYST

EM H

EIGH

T

165

CURT

AIND

ROP

CURTAIN CONTROLLER2129-TRIGGER UNITSIZE: 290x240x110REQS. 240V 10A GPO & 0 VOLT N.C. CONTACTTO FIP TO BE PROVIDE BY OTHERS. LOCATEDNO MORE THAN 1m AWAY FROM MOTOR

U/S SLAB

FCL

FFL

450x450 ACCESS PANEL BY OTHERSLOCATED AT THE NOMINATE LOCATION OF CURTAIN CONTROLLER

OPTIONAL RETRACT BUTTON.LOCATION TBA ONSITE.

OPTIONAL STROBE AND/OR SOUNDER

FRL -/120/120 FIRE RATEDBULKHEAD BY OTHERS

450x450 ACCESS PANEL SUPPLIED &INSTALLED BY OTHERSLOCATED AT THE NOMINATE LOCATION OFCURTAIN CONTROLLER

165

50

OPTIONAL STROBEAND/OR SOUNDERBOTH SIDES IF NEEDED

OPTIONAL RETRACT BUTTON.LOCATION TBA ONSITE.

CURTAIN CONTROLLER2129-TRIGGER UNITSIZE: 290x240x110REQS. 240V 10A GPO & 0 VOLT N.C. CONTACTTO FIP TO BE PROVIDE BY OTHERS. LOCATEDNO MORE THAN 1m AWAY FROM MOTOR

450x450 ACCESS PANEL BY OTHERSLOCATED AT THE NOMINATE LOCATION OF CURTAIN CONTROLLER

A

A

B B

2 COR

E CA

BLE

165

50

B SECTIONSCALE 1:20 @ A2

A SECTIONSCALE 1:20 @ A2

2 CONTROLLERREQUIRED FORSYSTEM WIDTHMORE THAN 5.5m

20 20

MUST HAVE SUFFICIENTSTRUCTURE TO SUPPORT25 Kg/ LINEAR METRE OFCURTAIN WIDTH

1FRONT ELEVATIONFYREHALT FIRE CURTAIN - INSTALLED OVER OPENINGSCALE 1:20 @ A2

- AC RELEASED 04/09/2020

Page 4: FYREHALT FIRE CURTAIN Rev - Smoke Control

290x240x110www.smokecontrol.com.auwww.smokecontrol.co.nz

T: 1300 665 471T: +64 9 300 1980

Model: 2129 - Trigger Unit

Project:

Tested By:

Date:

This is an electronic control unit for a fire or smoke curtainsystem. It is a critical building safety system and should notbe deenergised or isolated without permission.

DANGER

DANGER 240 VOLTSISOLATE ELSEWHERE BEFIRE

REMOVING COVERS

290x240x110

FILE: SCS-FH.dwg --- PLOTTED ON 04/09/2020 BY ISHTIAQUE ALAM· THIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, AND MUST NOT BE

RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OF SMOKE CONTROL SYSTEMSPTY. LTD.

· DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY.· ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR.· SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OF MEASUREMENTS

PROVIDED BY OTHERS.

Rev CHK REASON DATE

CLIENT

AUSTRALIAN HEADOFFICEPHONE: 1300 665 [email protected]

NEW ZEALANDPHONE: 09 300 [email protected]

WWW.SMOKECONTROL.COM.AU

DRAWN BY

START DATE

DRAWING NUMBER

ISSUE STATUS:

TITLE

PROJECT

<<< 594mm

420m

m >>

>

SCALE@A2

SUB SET (CATEGORY)

INFORMATIONC O P Y O N L Y

INFORMATION GIVEN IN SMOKECONTROL.COM.AU AND PUBLICATIONS FORDOWNLOAD ARE GIVEN TO THE BEST OF OUR KNOWLEDGE AND IN GOODFAITH. SMOKE CONTROL IS NOT RESPONSIBLE IF RECIPIENTS OF TESTREPORTS, ASSESSMENTS OR LITERATURE MISINTERPRET THE CONTENTSAND WRONGLY USE PRODUCTS BASED ON THOSE MISINTERPRETATIONS. NOLIABILITY IS ACCEPTED FOR ERROR OMISSIONS IN THIS WEB SITE OR OURDOCUMENTS. IN THE INTERESTS OF IMPROVEMENTS AND CONTINUEDDEVELOPMENT SMOKE CONTROL RESERVES THE RIGHT TO CHANGESPECIFICATION WITHOUT NOTICE.

DISCLAIMER

WWW.SMOKECONTROL.CO.NZWWW.SMOKECONTROL.COM

REV

SCS-FH

FYREHALT FIRE CURTAININSTALLED OVER LIFT

SCS-FH-0103I.A. INFORMATION ONLY

24/08/2020 AS SHOWN

FYREHALT FIRE CURTAIN

01 - FIRE CURTAINS

-

STRUCTURAL OPENING

SYSTEM WIDTH100

BETWEEN GUIDES100

STRU

CTUR

AL O

PENI

NG

SYST

EM H

EIGH

T

165

CURT

AIND

ROP

CURTAIN CONTROLLER2129-TRIGGER UNITSIZE: 290x240x110REQS. 240V 10A GPO & 0 VOLT N.C. CONTACTTO FIP TO BE PROVIDE BY OTHERS. LOCATEDNO MORE THAN 1m AWAY FROM MOTOR

U/S SLAB

FFL

OPTIONAL RETRACT BUTTON.LOCATION TBA ONSITE.

165

50

OPTIONAL RETRACT BUTTON.LOCATION TBA ONSITE.

CURTAIN CONTROLLER2129-TRIGGER UNITSIZE: 290x240x110REQS. 240V 10A GPO & 0 VOLT N.C. CONTACTTO FIP TO BE PROVIDE BY OTHERS. LOCATEDNO MORE THAN 1m AWAY FROM MOTOR

A

A

B B

2 COR

E CA

BLE

165

50

B SECTIONSCALE 1:20 @ A2

A SECTIONSCALE 1:20 @ A2

20 20

20

2 CORE CABLE

1FRONT ELEVATIONFYREHALT FIRE CURTAIN - INSTALLED OVER LIFTSCALE 1:20 @ A2

- AC RELEASED 04/09/2020

Page 5: FYREHALT FIRE CURTAIN Rev - Smoke Control

290x240x110www.smokecontrol.com.auwww.smokecontrol.co.nz

T: 1300 665 471T: +64 9 300 1980

Model: 2129 - Trigger Unit

Project:

Tested By:

Date:

This is an electronic control unit for a fire or smoke curtainsystem. It is a critical building safety system and should notbe deenergised or isolated without permission.

DANGER

DANGER 240 VOLTSISOLATE ELSEWHERE BEFIRE

REMOVING COVERS

290x240x110

290x240x110

FILE: SCS-FH.dwg --- PLOTTED ON 04/09/2020 BY ISHTIAQUE ALAM· THIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, AND MUST NOT BE

RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OF SMOKE CONTROL SYSTEMSPTY. LTD.

· DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY.· ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR.· SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OF MEASUREMENTS

PROVIDED BY OTHERS.

Rev CHK REASON DATE

CLIENT

AUSTRALIAN HEADOFFICEPHONE: 1300 665 [email protected]

NEW ZEALANDPHONE: 09 300 [email protected]

WWW.SMOKECONTROL.COM.AU

DRAWN BY

START DATE

DRAWING NUMBER

ISSUE STATUS:

TITLE

PROJECT

<<< 594mm

420m

m >>

>

SCALE@A2

SUB SET (CATEGORY)

INFORMATIONC O P Y O N L Y

INFORMATION GIVEN IN SMOKECONTROL.COM.AU AND PUBLICATIONS FORDOWNLOAD ARE GIVEN TO THE BEST OF OUR KNOWLEDGE AND IN GOODFAITH. SMOKE CONTROL IS NOT RESPONSIBLE IF RECIPIENTS OF TESTREPORTS, ASSESSMENTS OR LITERATURE MISINTERPRET THE CONTENTSAND WRONGLY USE PRODUCTS BASED ON THOSE MISINTERPRETATIONS. NOLIABILITY IS ACCEPTED FOR ERROR OMISSIONS IN THIS WEB SITE OR OURDOCUMENTS. IN THE INTERESTS OF IMPROVEMENTS AND CONTINUEDDEVELOPMENT SMOKE CONTROL RESERVES THE RIGHT TO CHANGESPECIFICATION WITHOUT NOTICE.

DISCLAIMER

WWW.SMOKECONTROL.CO.NZWWW.SMOKECONTROL.COM

REV

SCS-FH

FYREHALT FIRE CURTAINFUSIBLE LINK

SCS-FH-0104I.A. INFORMATION ONLY

24/08/2020 AS SHOWN

FYREHALT FIRE CURTAIN

01 - FIRE CURTAINS

-

STRUCTURAL OPENING

SYSTEM WIDTH100

BETWEEN GUIDES100

STRU

CTUR

AL O

PENI

NG

SYST

EM H

EIGH

T

165

CURT

AIND

ROP

CURTAIN CONTROLLER2129-TRIGGER UNITSIZE: 290x240x110REQS. 240V 10A GPO & 0 VOLT N.C. CONTACTTO FIP TO BE PROVIDE BY OTHERS. LOCATEDNO MORE THAN 1m AWAY FROM MOTOR

FFL

OPTIONAL RETRACT BUTTON.LOCATION TBA ONSITE.

165

OPTIONAL RETRACT BUTTON.LOCATION TBA ONSITE.

CURTAIN CONTROLLER2129-TRIGGER UNITSIZE: 290x240x110REQS. 240V 10A GPO & 0 VOLT N.C. CONTACTTO FIP TO BE PROVIDE BY OTHERS. LOCATEDNO MORE THAN 1m AWAY FROM MOTOR

A

A

B B

2 COR

E CA

BLE

165

50

B SECTIONSCALE 1:20 @ A2

A SECTIONSCALE 1:20 @ A2

20 20

20FUSIBLE LINK

2 CORE CABLE

FUSIBLE LINKOPTIONAL INTERNALSCONDERY FUSIBLE LINK.

FUSIBLE L

OPTIONAL INTERNAL FUSIBLELING

1FRONT ELEVATIONFYREHALT FIRE CURTAIN - FUSIBLE LINKSCALE 1:20 @ A2

- AC RELEASED 04/09/2020

Page 6: FYREHALT FIRE CURTAIN Rev - Smoke Control

FILE: SCS-FH.dwg --- PLOTTED ON 04/09/2020 BY ISHTIAQUE ALAM· THIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, AND MUST NOT BE

RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OF SMOKE CONTROL SYSTEMSPTY. LTD.

· DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY.· ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR.· SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OF MEASUREMENTS

PROVIDED BY OTHERS.

Rev CHK REASON DATE

CLIENT

AUSTRALIAN HEADOFFICEPHONE: 1300 665 [email protected]

NEW ZEALANDPHONE: 09 300 [email protected]

WWW.SMOKECONTROL.COM.AU

DRAWN BY

START DATE

DRAWING NUMBER

ISSUE STATUS:

TITLE

PROJECT

<<< 594mm

420m

m >>

>

SCALE@A2

SUB SET (CATEGORY)

INFORMATIONC O P Y O N L Y

INFORMATION GIVEN IN SMOKECONTROL.COM.AU AND PUBLICATIONS FORDOWNLOAD ARE GIVEN TO THE BEST OF OUR KNOWLEDGE AND IN GOODFAITH. SMOKE CONTROL IS NOT RESPONSIBLE IF RECIPIENTS OF TESTREPORTS, ASSESSMENTS OR LITERATURE MISINTERPRET THE CONTENTSAND WRONGLY USE PRODUCTS BASED ON THOSE MISINTERPRETATIONS. NOLIABILITY IS ACCEPTED FOR ERROR OMISSIONS IN THIS WEB SITE OR OURDOCUMENTS. IN THE INTERESTS OF IMPROVEMENTS AND CONTINUEDDEVELOPMENT SMOKE CONTROL RESERVES THE RIGHT TO CHANGESPECIFICATION WITHOUT NOTICE.

DISCLAIMER

WWW.SMOKECONTROL.CO.NZWWW.SMOKECONTROL.COM

REV

SCS-FH

FYREHALT FIRE CURTAININSTALLED AT CORNER

SCS-FH-0105I.A. INFORMATION ONLY

24/08/2020 AS SHOWN

FYREHALT FIRE CURTAIN

01 - FIRE CURTAINS

-

SYSTEM WIDTH100

BETWEEN GUIDES100

SYST

EM H

EIGH

T

165

CURT

AIND

ROP

FFL

A

A

B B

B SECTIONSCALE 1:20 @ A2

A SECTIONSCALE 1:20 @ A2

U/S SLAB

3298 165 SYSTEM WIDTH100

BETWEEN GUIDES100

FRL-/120/120FIRE RATEDBULKHEADBY OTHERS.

POSSIBLE SERVICE PENETRATIONSTO BE PROTECTED BY OTHERS

100 BETWEEN GUIDE 100

SYSTEM WIDTH

100

BETW

EEN

GUID

E10

0

SYST

EM W

IDTH

PROPRIETARY FRL -/120/120 CORNER POST

FRL -/120/120 WALLS BY OTHERS

1FRONT ELEVATIONFYREHALT FIRE CURTAIN - INSTALLED AT CORNERSCALE 1:20 @ A2

- AC RELEASED 04/09/2020

Page 7: FYREHALT FIRE CURTAIN Rev - Smoke Control

FILE: SCS-FH.dwg --- PLOTTED ON 04/09/2020 BY ISHTIAQUE ALAM· THIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, AND MUST NOT BE

RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OF SMOKE CONTROL SYSTEMSPTY. LTD.

· DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY.· ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR.· SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OF MEASUREMENTS

PROVIDED BY OTHERS.

Rev CHK REASON DATE

CLIENT

AUSTRALIAN HEADOFFICEPHONE: 1300 665 [email protected]

NEW ZEALANDPHONE: 09 300 [email protected]

WWW.SMOKECONTROL.COM.AU

DRAWN BY

START DATE

DRAWING NUMBER

ISSUE STATUS:

TITLE

PROJECT

<<< 594mm

420m

m >>

>

SCALE@A2

SUB SET (CATEGORY)

INFORMATIONC O P Y O N L Y

INFORMATION GIVEN IN SMOKECONTROL.COM.AU AND PUBLICATIONS FORDOWNLOAD ARE GIVEN TO THE BEST OF OUR KNOWLEDGE AND IN GOODFAITH. SMOKE CONTROL IS NOT RESPONSIBLE IF RECIPIENTS OF TESTREPORTS, ASSESSMENTS OR LITERATURE MISINTERPRET THE CONTENTSAND WRONGLY USE PRODUCTS BASED ON THOSE MISINTERPRETATIONS. NOLIABILITY IS ACCEPTED FOR ERROR OMISSIONS IN THIS WEB SITE OR OURDOCUMENTS. IN THE INTERESTS OF IMPROVEMENTS AND CONTINUEDDEVELOPMENT SMOKE CONTROL RESERVES THE RIGHT TO CHANGESPECIFICATION WITHOUT NOTICE.

DISCLAIMER

WWW.SMOKECONTROL.CO.NZWWW.SMOKECONTROL.COM

REV

SCS-FH

HEAD BOX INSTALLATION TYPES

SCS-FH-0201I.A. INFORMATION ONLY

24/08/2020 AS SHOWN

FYREHALT FIRE CURTAIN

02 - DETAILS

-

1SIDE ELEVATIONSOFIT FIXING DETAILSCALE 1:5 @ A2

165

48 67 50BU

LKHE

AD16

510

0 MIN

STOPPER BRACKETFIXED TO SIDE GUIDE

FIRE RATEDBULKHEAD BYOTHERS

2/ 10g SCREWS ORM8 DYNABOLTS @1500 MAX. CTS.

450x450 ACCESSPANEL BY OTHERSLOCATED AT THENOMINATE LOCATION OFCURTAIN CONTROLLER

FIXING STRUCTURE REQUIREDAT APPROPRIATE LOCATIONTO SUPPORT 25Kg/LINEALMETRE OF CURTAIN WIDTH

165

BULK

HEAD

5075

40

165

FIRE RATEDBULKHEAD BYOTHERS

FIXING STRUCTURE REQUIREDAT APPROPRIATE LOCATIONTO SUPPORT 25Kg/LINEALMETRE OF CURTAIN WIDTH

2/ 10g SCREWS ORM8 DYNABOLTS @1500 MAX. CTS.

2SIDE ELEVATIONFACE FIXING DETAILSCALE 1:5 @ A2

48 67 50

165

165

2/ Ø8 DYNABOLTS@ 1500 MAX. CTS.

4SIDE ELEVATIONFIXED TO SLABSCALE 1:5 @ A2

STOPPER BRACKETFIXED TO SIDE GUIDE

TRIM ANGLE BY OTHERS

3

25 50 CEILING GAP 25

100

OPTIONAL 100X3 THICK ALUMINIUMBOTTOM BAR COVER FINISHED TOARCHITECTS SPECIFICATIONS

5ELEVATIONOPTIONAL LEVELING BOTTOMBARSCALE 1:2 @ A2

3SIDE ELEVATIONSOFIT FIXING TO BEAM DETAILSCALE 1:5 @ A2

2/ SERIES 500STRUCTURALTEK SCREWS @1500 MAX. CTS.

MAX STEEL THICKNESS 12mmOTHERWISE ADDITIONAL FIXINGSTRUCTURE MUST BE ADDED.

- AC RELEASED 04/09/2020

Page 8: FYREHALT FIRE CURTAIN Rev - Smoke Control

FILE: SCS-FH.dwg --- PLOTTED ON 04/09/2020 BY ISHTIAQUE ALAM· THIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, AND MUST NOT BE

RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OF SMOKE CONTROL SYSTEMSPTY. LTD.

· DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY.· ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR.· SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OF MEASUREMENTS

PROVIDED BY OTHERS.

Rev CHK REASON DATE

CLIENT

AUSTRALIAN HEADOFFICEPHONE: 1300 665 [email protected]

NEW ZEALANDPHONE: 09 300 [email protected]

WWW.SMOKECONTROL.COM.AU

DRAWN BY

START DATE

DRAWING NUMBER

ISSUE STATUS:

TITLE

PROJECT

<<< 594mm

420m

m >>

>

SCALE@A2

SUB SET (CATEGORY)

INFORMATIONC O P Y O N L Y

INFORMATION GIVEN IN SMOKECONTROL.COM.AU AND PUBLICATIONS FORDOWNLOAD ARE GIVEN TO THE BEST OF OUR KNOWLEDGE AND IN GOODFAITH. SMOKE CONTROL IS NOT RESPONSIBLE IF RECIPIENTS OF TESTREPORTS, ASSESSMENTS OR LITERATURE MISINTERPRET THE CONTENTSAND WRONGLY USE PRODUCTS BASED ON THOSE MISINTERPRETATIONS. NOLIABILITY IS ACCEPTED FOR ERROR OMISSIONS IN THIS WEB SITE OR OURDOCUMENTS. IN THE INTERESTS OF IMPROVEMENTS AND CONTINUEDDEVELOPMENT SMOKE CONTROL RESERVES THE RIGHT TO CHANGESPECIFICATION WITHOUT NOTICE.

DISCLAIMER

WWW.SMOKECONTROL.CO.NZWWW.SMOKECONTROL.COM

REV

SCS-FH

SIDE GUIDE INSTALLATION TYPES

SCS-FH-0202I.A. INFORMATION ONLY

24/08/2020 AS SHOWN

FYREHALT FIRE CURTAIN

02 - DETAILS

-

1PLANTOE FIXED SIDE GUIDESCALE 1:2 @ A2

2PLANREBETED SIDE GUIDESCALE 1:2 @ A2

3PLANFACE FIXED SIDE GUIDESCALE 1:5 @ A2

4PLAN90° POST DETAILSCALE 1:5 @ A2

10 100

12g SCREWS ORØ8 DYNABOLTS @1000 MAX. CTS.

SEALANT & PACKING

SIDE GUIDEBOTTOM BAR

165

5036

10 100

12g SCREWS ORØ8 DYNABOLTS@ 1000 MAX CTS.

SEALANT & PACKING

SIDE GUIDE

BOTTOM BAR

WALL MAY NEED TO BEREBATED TO ALLOW FORFITMENT OF HEAD BOX. SEESHEET 0203 FO R DETAILS.

APPROPRIATEFIXING STRUCTURE

12g SCREWS ORØ8 DYNABOLTS @1000 MAX. CTS.

ARCHITECTURALCLADDING BY OTHERS

6733

100

APPROPRIATEFIXING STRUCTURE

165100

FRL -/120/120 FIRE RATEDSTRUCTURAL POST BY OTHERS

POST FIXED TO STRUCTURETOP & BOTTOM

ARCHITECTURALCLADDING BY OTHERS

12g SCREWS @ 1000 MAX. CTS.

50

100

165

50

- AC RELEASED 04/09/2020

Page 9: FYREHALT FIRE CURTAIN Rev - Smoke Control

20203

20203

30203

FILE: SCS-FH.dwg --- PLOTTED ON 04/09/2020 BY ISHTIAQUE ALAM· THIS DRAWING IS COPYRIGHT AND THE PROPERTY OF THE AUTHOR, AND MUST NOT BE

RETAINED, COPIED OR USED WITHOUT THE AUTHORITY OF SMOKE CONTROL SYSTEMSPTY. LTD.

· DO NOT SCALE FROM DRAWING, USE PROVIDED DIMENSIONS ONLY.· ALL DISCREPENCIES MUST BE BROUGHT TO THE ATTENTION OF AUTHOR.· SMOKE CONTROL SYSTEMS DO NOT TAKE RESPONSIBILITY OF MEASUREMENTS

PROVIDED BY OTHERS.

Rev CHK REASON DATE

CLIENT

AUSTRALIAN HEADOFFICEPHONE: 1300 665 [email protected]

NEW ZEALANDPHONE: 09 300 [email protected]

WWW.SMOKECONTROL.COM.AU

DRAWN BY

START DATE

DRAWING NUMBER

ISSUE STATUS:

TITLE

PROJECT

<<< 594mm

420m

m >>

>

SCALE@A2

SUB SET (CATEGORY)

INFORMATIONC O P Y O N L Y

INFORMATION GIVEN IN SMOKECONTROL.COM.AU AND PUBLICATIONS FORDOWNLOAD ARE GIVEN TO THE BEST OF OUR KNOWLEDGE AND IN GOODFAITH. SMOKE CONTROL IS NOT RESPONSIBLE IF RECIPIENTS OF TESTREPORTS, ASSESSMENTS OR LITERATURE MISINTERPRET THE CONTENTSAND WRONGLY USE PRODUCTS BASED ON THOSE MISINTERPRETATIONS. NOLIABILITY IS ACCEPTED FOR ERROR OMISSIONS IN THIS WEB SITE OR OURDOCUMENTS. IN THE INTERESTS OF IMPROVEMENTS AND CONTINUEDDEVELOPMENT SMOKE CONTROL RESERVES THE RIGHT TO CHANGESPECIFICATION WITHOUT NOTICE.

DISCLAIMER

WWW.SMOKECONTROL.CO.NZWWW.SMOKECONTROL.COM

REV

SCS-FH

HEAD BOX AND SIDE GUIDEREBATE DETAIL

SCS-FH-0203I.A. INFORMATION ONLY

24/08/2020 AS SHOWN

FYREHALT FIRE CURTAIN

02 - DETAILS

-

- AC RELEASED 04/09/2020

1FRONT ELEVATIONFIREHALT FIRE CURTAIN - REBATEDSCALE 1:5 @ A2

2PLANREBETED SIDE GUIDESCALE 1:2 @ A2

3ELEVATIONREBETED DETAILSCALE 1:5 @ A2

10 100

12g SCREWS ORØ8 DYNABOLTS@ 1000 MAX CTS.

SEALANT & PACKING

SIDE GUIDE

BOTTOM BAR

WALL MAY NEED TO BEREBATED TO ALLOW FORFITMENT OF HEAD BOX. SEESHEET 0203 FO R DETAILS.

165

BULK

HEAD

5075

40

165

FIRE RATEDBULKHEAD BY OTHERS

FIXING STRUCTURE REQUIREDAT APPROPRIATE LOCATIONTO SUPPORT 25Kg/LINEALMETRE OF CURTAIN WIDTH

2/ 10g SCREWS ORM8 DYNABOLTS @1500 MAX. CTS.

165 200

200

365

APPROPRIATEFIXING STRUCTURE A 365X200X110 REBATE IS REQUIRED FOR

THE HEAD BOX WHERE SIDE GUIDES NEED TOBE REBATED INTO THE WALL ADN THE WALLSPANS FROM SLAB TO SLAB.WORKS MUST BE PERFORMED BY OTHERSPRIOR TO INSTALLATION OF FIRE CURTAIN.