Furse ESP Protectors Equipment - ABB · PDF fileNever work on ESP Protectors, earthing or...
Transcript of Furse ESP Protectors Equipment - ABB · PDF fileNever work on ESP Protectors, earthing or...
Introduction
Series connection
The ESP Protector is connected in-line(or series) with the supply to be protected(see Figure 2a & 2b).
It can be mounted in any orientation.
3.2
2. Before installation
Check that the supply is fused for theapplication, at or below the ESP Protector’scurrent rating.
Fixing methods
The ESP Protector can be clipped onto a‘top hat’ DIN rail.
It includes an innovative DIN foot forconnection to 35 mm DIN rails.
This DIN foot, comprising spring loadedsteel DIN mounts, enables rapid positioningon to the rail (see Figure 3a & 3b).
Pull the spring loaded steel DIN mount down and out to lock into place ready for siting the ESP Protector.
3.4
2.1
Fusedmainspowersupply
Equipment
NL
NL
L
!
GREEN
FULL PROTECTIONGREEN & REDGREEN
REDUCEDPROTECTION(replace unit)
RED NO PROTECTIONWARNING: If lit / flashing disconnectunit & check Neutralto Earth voltage
STATUS INDICATIONESP 240DS-32A
Current Rating
10 Amps or less
32 Amps or less
1. Safety Note
ESP Protector installation should beconducted by a qualified competent personand comply with all relevant Regulationsand Legislation (including BS 7671 WiringRegulations and Building Regulations).
1.1
Incorrect installation will impair theeffectiveness of the ESP Protector.
Always handle cables by their insulation.
Never work on ESP Protectors, earthing ortheir cables during a storm.
1.2
1.4
1.3
Figure 1: Installation within the system on a powersupply fused at 10 A or less (ESP 120D-10A,ESP 240D-10A, ESP 277D-10A, ESP 120DS-10A,ESP 240DS-10A or ESP 277DS-10A) or 32 A or less(ESP 120D-32A, ESP 240D-32A, ESP 277D-32A,ESP 120DS-32A, ESP 240DS-32A or ESP 277DS-32A).
If the supply current exceeds the ESPProtector’s current rating, do not usethis Protector.
If the supply is not fused, a fuse equalto or less than the ESP Protector’s ratingshould be added.
Further advice is available from Furse.
Make sure that the supply voltage is withinthe working voltage of the unit.
Position the ESP Protector at the preferredlocation on the DIN rail and press theprotector back to release the springs. Theprotector locks into place.
Connection to live, neutral and earth
Connections are made to each supply conductor including earth. Terminals marked L, N, E (or ) must be connected to live, neutral and earth respectively.
The screw terminals will accommodateconductor of up to 4 mm2.
We recommend that these are terminatedwith a boot lace ferrule.
Hand tighten connections - do not use power driven screwdrivers. (See 8.4)
Earthing
If the ESP Protector is being installed on a supply without an earth conductor (eg double insulated) the Protector must be connected to the local power earth.
2.2
3. InstallationLocation
The ESP Protector should be installed closeto the equipment it is protecting, either:
(a) within the system (see Figure 1) or
(b) on the fused connection (or spur unit)to the equipment.
Except where it is installed on a supplywhich leaves the building (to protectequipment inside the building fromincoming transients).
In this case the ESP Protector should beinstalled as close as possible to where thecable leaves the building.
Enclose unboxed ESP Protectors
ESP In-Line Mains Protectors for 10 A and 32 A have exposed terminals and should be installed within a panel or enclosure, for reasons of electrical safety.
Often this will be the housing, or panel of the equipment being supplied (See Figure1 and Figure 5a), or in a separate enclosure such as the Furse WBX D4 (See Figure 5b).
3.1
3.3 3.5 Keep clean cables away from dirty cables
Clean outgoing cables should never be routed next to dirty incoming cables or dirty earth leads.
This applies to lines within or external tothe equipment panel.
3.6
3.7
Figure 3a & 3b: Innovative spring loaded DIN foot shownopen and locked in place.
Figure 2a & 2b: Installation of ‘D’ and ‘DS’ variants.
4. Status indication
The ESP Protector gives a continuous visualdisplay of its status.
It has a two colour LED indicator light:
Green only = Full protection, power on.
Green + Red = WARNING. Reducedprotection, replace assoon as possible.
Red only = NO PROTECTION. Replaceimmediately.
No lights = No power connection orsystem fault. Checkexternal fuses andconnections.
4.1
ESP 120D-10AESP 120DS-10A
ESP 240D-10AESP 240DS-10A
ESP 277D-10AESP 277DS-10A
ESP 120D-32AESP 120DS-32A
ESP 240D-32AESP 240DS-32A
ESP 277D-32AESP 277DS-32A
This document explains how to install Furse ESP Protectors for in-line mains power supplies:
ESP 120D-10A | ESP 120DS-10A
ESP 240D-10A | ESP 240DS-10A
ESP 277D-10A | ESP 277DS-10A
ESP 120D-32A | ESP 120DS-32A
ESP 240D-32A | ESP 240DS-32A
ESP 277D-32A | ESP 277DS-32A
ESP 120D-10A | ESP 120DS-10A | ESP 240D-10A | ESP 240DS-10A | ESP 277D-10A | ESP 277DS-10A
ESP 120D-32A | ESP 120DS-32A | ESP 240D-32A | ESP 240DS-32A | ESP 277D-32A | ESP 277DS-32A
It is essential that the ESP Protector is earthed.
L N
L N
NL
NL
L N
L N
NL
NL
11C
OM
14N
/ O
12N
/C
L
!
GREEN FULL PROTECTIONGREEN & RED REDUCED
PROTECTION(replace unit)
RED NO PROTECTIONWARNING: If lit / flashing disconnectunit & check Neutralto Earth voltage
STATUS INDICATIONESP 240DS-32A
LINE
CLEAN
LINE
CLEAN
To:BMSPLCBuzzer
The dirty, or line side of the ESP Protector should be connected to the cable carrying the incoming transient voltages - this is usually the cable from the power supply. The output, or clean side ensures a transient free supply to the equipment being protected.If the ESP Protector is connected to a supply leaving the building (to prevent transients being injected back into the building) its line end will be connected to the supply leaving the building.
Working Voltage
90 - 150 VRMS
200 - 280 VRMS
ESP 120D-10AESP 120DS-10A
ESP 120D-32AESP 120DS-32A
ESP 240D-10AESP 240DS-10AESP 240D-32AESP 240DS-32A
ESP 277D-10AESP 277DS-10AESP 277D-32AESP 277DS-32A
232 - 350 VRMS
Insulation tests (flash testing)
The ESP Protector should be fullydisconnected from the circuit beforetesting. Otherwise the ESP Protector willtreat the insulation test as a transientovervoltage and control the voltage to alow level - thereby defeating the object ofthe test.
Use of powered screwdrivers
The use of powered screwdrivers is not recommended. Hand tighten connections only (maximum torque value is 0.8 Nm for these terminals. The recommended values are 50-75% of this maximum).
Copyright Thomas & Betts 2014.
Installationinstructionsforin-linemainsprotectors
Dinmountprotectorsfor120,240&277Volts
uptoeither10or32Amps
Technical Helpis available from:
Thomas & Betts LimitedFurseWilford RoadNottinghamNG2 1EBUnited Kingdom
Tel: +44 (0)115 964 3700Fax: +44 (0)115 986 0538
www.furse.com
ILMii-0914
6. Maintenance
Maintenance should be conducted at leastonce a year and also following lightningactivity. Visually check:
Visual status indication lights (see 4. Status indication for interpretation)
Condition of connecting leads andterminations
6.1
The ESP units remote indication is rated at1 A, 250 Vac. A minimum load of 10 mA,5 V DC is required to ensure reliable contactoperation.
Unit HealthyReduced orNo protection
PowerPresent
PowerAbsent
OPEN
CLOSED
CLOSED
OPEN
CLOSED
CLOSED
OPEN
NO NC NO NC
OPEN
Figure 4: Operation of normally closed (NC) andnormally open (NO) volt free contact.
5.2
Always ensure ESP Protectors are usedon the same installation to ensurecoordination.
Mixing ESP Protectors with alternativemanufacturers’ units could result indamage to both protectors and connectedequipment through poor coordination.
RCD units
ESP Protectors should ideally be installedbefore (or upstream of) residual currentdevices (RCDs) and not on the load side.
ESP Protectors should only be installed onthe load side of the RCDs if the load inquestion is external to the building.
This should help to reduce any spurioustripping of such devices due to transientovervoltages.
Special transient hardened RCDs (type ‘S’)can be obtained from a number ofmanufacturers.
7.2
8.3
8.4
5. Remote indication(DS variants only)
A remote indication of the reduced protection state is provided for linking the protector to a building management system, remote telemetry or PLC to an indication light or buzzer, powered from an external source.
The ESP Protector has both a normally openand a normally closed volt free contact.
The terminal for the volt free contact accepts 1.5 mm2 cable (solid or stranded conductor) and is located on the bottom of the ESP Protector.
It has three terminals, marked:
NO = Normally OpenNC = Normally ClosedC = Common
The normally open (NO) contact is openwhen the ESP Protector is healthy andpower is present. The normally closed (NC)contact is closed when the unit is healthyand power is present.
5.1
7. Application notes
ESP coordination
The ESP Protector is designed to fullycoordinate with upstream/downstream ESPProtectors of equivalent system voltage.
For example an ESP 240D-10A locatedat a sub-distribution board wouldcoordinate effectively with an ESP 240 D1Protector located at a main distributionboard. No additional decoupling elementssuch as inductors are needed to ensureESP Protectors achieve coordination.
7.1
As well as providing warning of the reduced protection state, the normally closed volt free contact can also be used to signal power loss, eliminating the need for special relays. The operation of NC and NO volt free contact is shown below:
Figure 5a: Installation into a fused mains distribution board.
Figure 5b: Installation using a Furse WBX D4 external to power supply.
ESP 120D-10A | ESP 120DS-10A | ESP 240D-10A | ESP 240DS-10A | ESP 277D-10A | ESP 277DS-10A
ESP 120D-32A | ESP 120DS-32A | ESP 240D-32A | ESP 240DS-32A | ESP 277D-32A | ESP 277DS-32A