Furnace Replacement & Installation Checklist
Transcript of Furnace Replacement & Installation Checklist
Gas Furnace Replacement Checklist
INS
PE
CT
ION
& A
DJ
US
TM
EN
TS
Documents: ☐ Warranty and manual in envelope attached to furnace ☐ Agency given copy of sizing calculation
☐ Photos documenting furnace conditions and manufacturer nameplate☐ Installation information sticker (installer name, phone number, date)
☐ Design temperature heat loss calculation: BTU per hour
Electrical: ☐ Service disconnect is present and operational ☐ Dedicated circuit and breaker properly rated☐ Set heat circuit and anticipator (thermostat) PMI ☐ Not applicable
Gas Piping: ☐ Sized for BTUs of all appliances ☐ No leaks ☐ Shut off present☐ Sediment trap present ☐ CSST bonded
Air Filter: ☐ Filter opening covered/sealed ☐ Filter removes easily with no obstructions
Filter Size: x
General:
☐ Furnace elevated off basement floor. Note: If not in basement, can be on floor if approved.☐ Combustion air and exhaust piping properly installed, terminated and supported☐ Distribution plenums sealed and all major duct leaks properly sealed per specifications☐ Condensate properly drained per local code and PMI ☐ Test holes sealed☐ Orphaned water heater has proper draft (see p. 2) ☐ Permit required
Installed and Measured BTUs of New Furnace:
BTUs (high input): Measured Input (2 cu. ft. of gas): Minutes: Seconds:
BTUs (low input): Measured Input (2 cu. ft. of gas): Minutes: Seconds: (if applicable)
Measured Gas Pressure in Inches of Water Column(IWC):
Input (High): Input (Low) – if applicable: Manifold (High):
Manifold (Low):
PE
RF
OR
MA
NC
E T
ES
TIN
G
Steady State Efficiency Test Distribution Static Pressure Adjust to Achieve Typical Ranges for Gas Burning Appliances (see page 2) ☐ IWC or ☐ Pa Total
SSE % O2% CO PPM Intake Air °F Flue °F PMI AFUE% Return Supply Pressure High Input
Low Input
Temperature Rise Variable Speed Furnaces
Heating CFM* Fan Speed Setting Supply °F Return °F (Supply – Return) PMI
Min PMI Max
High Input Low Input (if applicable)
*CFM Measurement Method: ☐ Plate Method ☐ Fan Tables ☐ Other:
I certify the visual inspection and performance tests were completed as indicated.
I certify the heating system was installed to my satisfaction on the date indicated.
Installer Signature: Customer Signature:
Printed Name: Printed Name:
Date: Date:
Customer: Contractor: Brand: Model #:
Date Installed: Serial #:
Page 1 of 2
Acceptable Draft Test Readings for Gas Appliances with Respect to Outdoor
°F <10° 10°-90° >90°Pa. -2.5 (°F Out / 40) - 2.75 -0.5
IWC. -.010 (°F Out / 10,000) - 0.011 -.002
Typical Ranges for Gas Burning Appliances
Performance Indicator SSE 80+ SSE 95+
Carbon monoxide (CO) ppm ≤ 100 ≤ 100 or PMI Stack temperature °F 325°- 450° 90°- 120° Temperature Heat Rise °F 40° - 70° 45° - 70° or PMI
Oxygen (O2) % 4 - 9% 4 - 9% Natural gas pressure output at manifold - Inches of Water Column (IWC) 3.2 - 3.9 IWC 3.2 - 3.9 IWC
Propane pressure output at manifold (IWC) 10-11 IWC 10 – 11 IWC Steady-state efficiency (SSE) 82 - 86% 95 - 97% Supply temperature °F 120° - 140° 95° - 140°
Comments:
Measure supply temperature here or here
Measure supply temperature and use the highest measured temperature
Measure return
temperature here
Measure return
temperature here
Furnace Furnace
Page 2 of 2
Building Inspection Measurement Specification
Is building insulated Y N
Secondary backup heat source Y N
Interior tank capacity
Make up air Y N
Total sq. ft. of space (approx)
Set-up & Assembly Measurement Specification
Furnace to floor distance
Fuel pump to Furnace distance
Fuel tank to Furnace distance
Fuel System Measurement Specification
Fuel Tubing Length (pressure) H= V= Fuel pump to preheater. H=Horizontal/V=Vertical
Fuel Tubing Length (suction) Vertical length of pickup if a non-EnergyLogic tank
Pressure Gauge (fuel pump) 0 to 12 PSI
Vacuum Gauge (fuel pump) 0"-1" Hg - Complete System/3"-5" Hg - Regular System
Fuel Tank level E 1/2 F
Pipe sealant used Y N
Leak check Y N
Pickup Filter used Y N
Fuel Pickup location Y N At least 6" from bottom, for Regular Systems only
Vacuum Test Y N Pump pulls down and holds at 25" Hg
Spin-Up Test Y N Pump spins up to 55 PSI within 1 second
Furnace Installation & Startup Checklist
Page 1 of 2
Customer: Technician:Brand: Model #:
Date Installed: Serial #:
Electrical Components Measurement Specification
Wall Thermostat location Wall Do not mount on furnace or supports
Fan Shipping Bracket removed Y N
20 Amp Circuit Breaker Y N Dedicated power supply - 25 Amp Max per UL Standard
Fan & Limit Control Reading (cold) Arrow on room temperature
Flue Set-up Measurement Specification
Max. 45 degree elbow Y N No more than 45 degress from vertical
4' above roof - recommended Y N Extend 4' above roof within 20' of structures
Rain/Wind Cap present on Flue Y N
Double walled Y N Double walled at point through ceiling
Barometric Dampener open Y N Should be open slightly
Combustion Measurement Specification
CO2 Between 9% and 11%
Air Shutter setting Model 140: 5 Model 200: 7 Model 340: 4
Draft Gauge zero Remove probe from stack to zero gauge
Draft in flue stack + 0.05" Water Column
Smoke Spot Zero to Two
Ohm Reading 250 to 500 ohms at cad cell
Duct Static DP Max. 0.28" (N/A for systems without ducts)
Stack Temperature Record for monitoring only
Overfire Pressure Less than +0.02" Water Column
Ten & Ten Light-Off Test Was Light-Off instantaneous each time?
Customer Sign-off
Received Manual Y N
Maintenance overview Y N
Warranty overview Y N
Customer Name: __________________________________________
Customer Signature: ___________________________________
Date: _______________