FUNDAMENTAL BEHAVIOR OF CFT BEAM-COLUMNS UNDER FIRE

LOADING

Amit H. Varma, Sandgo Hong

Purdue University

2005 ASCE Structures Congress

New York City, NY

Page 2: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

INTRODUCTION Significant research has been conducted on the fire

resistance of composite CFT columns under standard fire loading.

Researchers at NRC-Canada (Lie, Kodur, Irwin, etc.), China (Lin-Hai Han), and Japan (Sakumoto using FR steel)

Focus on the behavior of columns subjected to constant axial loads, end conditions, and ASTM E119 fire time-temperature loading

The results provide fire resistance rating (FRR) values and have been used to develop standard fire resistant design

They do not provide knowledge of the fundamental force-deformation-temperature behavior of the CFT column or the critical failure segments

Limited research has been conducted on the fundamental force-deformation-temperature behavior of composite CFT beam-columns under combined axial and flexural loads and elevated temperatures from fire loading

Page 3: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

MOTIVATION

Why is it relevant? Four reasons1. The section force-deformation-temperature (P-M--T)

represents the fundamental behavior of CFT beam-columns and it can be used to investigate the effects of various geometric, material, and insulation parameters on fire resistance.

2. These P-M--T responses can be used to calibrate beam-column finite element models used to conduct structural analysis under fire loading

3. The behavior and stability of moment resisting frames under fire loading depends on the strength interaction P-M-T curve for and the fire resistance of the connections

4. The stability of columns under fire loading also depends eventually on the P-M--T response of the critical failure segment at mid-span.

Page 4: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

RESEARCH OBJECTIVES

The objectives of this research project are:

To analytically and experimentally investigate the fundamental force-deformation-temperature (P-M--T) behavior of CFT beam-columns under elevated temperatures from fire loading.

To evaluate the effects of various material (concrete strength, steel yield stress), geometric (column size, width-to-thickness ratio), and insulation (thickness, thermal conductivity) on the fundamental P-M--T behavior of CFT beam-columns.

To develop (or calibrate) fiber-based finite element models for modeling CFT columns and beam-columns while investigating the fire behavior of CFT structures.

Page 5: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

RESEARCH APPROACH

Development and validation of analytical approach for simulating the thermal and structural behavior of CFT members under structural loads and fire loading.

Preliminary analytical investigations of the fundamental P-M--T behavior of CFT beam-columns under elevated temperatures from fire loading. Evaluate the effects of geometric, material, and insulation parameters.

Experimental investigations to measure the fundamental P-M--T behavior of CFT beam-columns under combined axial and flexural loads and elevated temperatures from fire loading.

Analytical model calibration. The experimental results will be used to validate (or calibrate) the preliminary analytical models. The experimental results and calibrated models will be used to develop beam-column finite element models .

Page 6: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

ANALYTICAL APPROACH

The analytical approach was developed and validated using existing experimental data for CFT columns tested under fire loading by researchers at NRC, China, and Japan.

Development and validation of the analytical approach was presented in detail at the 2004 ASCE Structures Congress

The approach consists of three sequentially coupled analysis steps, where the results from each step are required to continue the analysis in the subsequent step:

Step I – Fire dynamics analysis Step II – Nonlinear heat transfer analysis Step III – Nonlinear stress analysis

Step 1

Fire Dynamics Analysis

Step 2

Nonlinear Heat Transfer Analysis

Step 3

Nonlinear Stress

Analysis

Page 7: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

Step 1 - FIRE DYNAMICS ANALYSIS

Fire dynamics analysis is conducted to simulate the convection and radiation heat transfer from the fire source (or furnace walls) to the structural component by solving the simplified Navier-Stokes equations numerically.

It is conducted using the NIST-BFRL developed software FDS, and the results include the heat flux incident upon the surfaces of the component or the surface T-t curves.

Page 8: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

Step 2 - NONLINEAR HEAT TRANSFER ANALYSIS

Nonlinear heat transfer analysis is conducted to simulate the heat transfer through the cross-section of the component and along its length (and the associated convection and radiation losses).

The surface heat flux or T-t curves from the fire dynamics analysis serve as thermal loading for conducting the heat transfer analysis.

The heat transfer analysis can be conducted using the FDM or FEM. It is assumed uncoupled from the stress analysis, which is adequate for structural materials.

We used FEM because it links more easily with step 3. The results from the heat transfer analysis include the T-t curves for the nodes of the FEM mesh and thermal contours.

Page 9: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

Step 3 – NONLINEAR STRESS ANALYSIS

Nonlinear stress analysis is conducted to determine the structural response of the component under applied structural and thermal loads.

The nodal time-temperature (T-t) curves obtained from the heat transfer analysis of step 2 define the thermal loads for the nonlinear stress analysis

The stress analysis can be conducted using the finite element method while using identical meshes for both steps 2 and 3.

The results from the analysis include the complete structural response: deflections, strains, stresses, load-displacement-temperature relationships.

Page 10: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

Step 3 – NONLINEAR STRESS ANALYSIS

For example, the behavior of CFT columns tested according to the ASTM E119 was investigated using the 3-step approach

The sequentially coupled heat transfer and structural analysis were conducted using the FEM and option in ABAQUS.

The analytical approach was validated for an assortment of CFT columns with different material, geometric, insulation parameters tested independently by researchers in Canada, China, and Japan

0

200

400

600

800

1000

1200

0 30 60 90 120 150 180

Time (min)

Te

mp

era

ture

(C

)

C1, surface, calculatedC1, surface, measuredC1, d=71mm, calculatedC1, d=71mm, measured

200 mm CFT

0

200

400

600

800

1000

1200

0 30 60 90 120 150Time (min)

Te

mpe

ratu

re (

C)

C2, surface, calculatedC2, surface, measuredC2, d=60mm, calculatedC2, d=60mm, measured

250 mm CFT

0

200

400

600

800

1000

1200

0 30 60 90 120 150 180 210 240

Time (min)

Tem

pera

ture

(C)

C3, surface, calculated

C3, surface, measured

C3, d=37mm, calculated

C3, d=37mm, measured

300 mm CFT

-40

-30

-20

-10

0

10

20

30

0 50 100 150 200

Time (min)

Axi

al D

ispl

acem

ent (

mm

)

C1, calculatedC1, measured

200x 200x 6.35mm CFT

Fy=350; f’c=47 MPaL=3.8 m; P/Po=15% -30

-20

-10

0

10

20

30

0 40 80 120 160 200Time (min)

Axi

al D

ispl

acem

ent (

mm

)

C5, calculatedC5, measured

300x 300x 9mm CFT

Fy=360; f’c=37 MPa

L=3.5 m; P/Po=20%

FR steel, Ceramic

-50

-40

-30

-20

-10

0

10

0 50 100 150 200

Time (min)

Axi

al D

ispl

acem

ent (

mm

)

C9, calculatedC9, measured

350x 350x 7.7mm CFTFy=285; f’c=19 MPaL=3.8 m; P/Po=50%

SFRM Insulation

Page 11: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

GENERAL FINDINGS

The analytical approach was developed and validated, but the behavior of CFT columns under fire loading were found to be very sensitive with respect to:

Temperature dependent steel and concrete material structural properties, which are not measured or reported explicitly for most CFT specimens.

Column end conditions (rotational and axial restraint). End conditions obtained in the experiment may vary from those assumed in the analysis.

Variations in axial load level (P/Po). Axial load level can vary due to changes in axial load P due to restraint, or due to Po which depends on steel and concrete strength variation.

Relative motion (slip) between steel tube and concrete infill at ends. This slip occurs for some columns that were tested individually and the slip was allowed to occur. This may not be realistic.

Page 12: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

PRELIMINARY ANALYTICAL INVESTIGATIONS

Preliminary investigations were conducted using the (developed and validated) analytical approach to determine the more fundamental force-deformation (P-M-) behavior of CFT sections under elevated temperatures from fire loading.

These P-M--T responses and the effects of various material, geometric, and insulations parameters are the focus of the research for reasons explained earlier.

CFT parameters: Width b = 200 or 300 mm. Width-to-thickness ratio = 32 or 48 Steel tube A500 Gr. B (300 MPa) Concrete strength (f’c=35 MPa) Axial load levels (P=0, 20%, 40%) Thermal insulation thickness (0, 7.5, 13 mm thick)

Page 13: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

PRELIMINARY ANALYTICAL INVESTIGATIONS

The analytical investigations were conducted on a segment of the CFT beam-columns. The length of the segment was equal to the cross-section width b.

It represents the critical segment of CFT column or beam-column subjected to axial and flexural loads and elevated temperatures from fire loading.

Step 1 – FDS analysis to simulate heat transfer to the surface of the segment

Step 2 – Nonlinear heat transfer analysis to simulate transfer through section and along length

Step 3 – Nonlinear stress analysis for constant axial load, monotonic flexural loading moment), and nodal thermal loading (T-t) from step 2

Steps 2 and 3 conducted using the finite element method and ABAQUS

Page 14: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

MATERIAL PROPERTIES – T Dependent

Temperature dependent thermal and structural material properties were used along with the 3D finite element models of the CFT failure segment.

These material properties were based on values generally reported in the literature (Lie and Irwin 1995 etc.).

T-Thermal properties are given in a table in the paper

900oC

700oC

500oC

300oC

100oC

0

100

200

300

400

0 0.002 0.004 0.006 0.008 0.01

Strain (mm/mm)

Str

ess

(MP

a)

Steel --T

0

10

20

30

40

0.000 0.010 0.020 0.030 0.040

Strain (mm/mm)

Str

ess,

MP

A

500o

C600o

C

700o

C

800o

C

400o

C

Concrete --T

T=100oC

T=300oC

T=500oC

T=700oC

T=900oC

Page 15: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

Thermal response- CFT without insulation

0

200

400

600

800

1000

1200

0 30 60 90 120 150 180Time (minutes)

Tem

per

atu

re

ASTM E119 T-t No Insulation

Step 1 – Results from FDS Analysis for ASTM E119 T-t curveStep 2 – Results from heat transfer

analysis

Surface Temperature =300oCTime = 5.6 mts.

Surface Temperature =600oCTime = 14.2 mts.

Page 16: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

Structural Response – CFT without ins.

0.00

30,000.00

60,000.00

90,000.00

120,000.00

150,000.00

0 0.005 0.01 0.015 0.02 0.025

Curvature (1/mm)

Mom

ent (N

-m)

2.5E-5 5.0E-5 7.5E-5 10.0E-5 12.5E-5

P/Po=20%, T=20oC

P/Po=20%, T=300oC

P/Po=20%, T=600oC

P/Po=20%, T=900oC

P/Po=0%, T=20oC

P/Po=0%, T=300oC

P/Po=0%, T=600oC

P/Po=0%, T=900oC

Step 3 – P-M--T curves for CFT without insulation

0.0

0.3

0.6

0.9

1.2

0 200 400 600 800 1000 1200Temperature (T)

Mom

ent/

Mom

ent

@ 2

0o C

(M/M

20)

P=20%, No Insul

P=0, No Insul

Page 17: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

Findings for CFTs Without Insulation

For CFTs without insulation: Fire loading results in quick heating of the steel tube

(broiling) while the concrete infill remains relatively cooler. Significant portions remain at T< 100oC till much later

This relative heating causes rapid reduction in flexural stiffness and strength of the CFT section under fire loading effects

This reduction depends primarily on the rise in steel temperature, and is independent of axial load level, width, and other parameters

This by itself, may not be a cause of concern unless the demands placed on the CFT without insulation exceed the reduced stiffness and strength at elevated temperatures

Page 18: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

Thermal response of CFT with insulation

Consider similar CFTs with some insulation. Assume commonly used insulation materials with properties given in the paper.

The presence of thermal insulation results in a slow increase in the steel surface temperature.

0

200

400

600

800

1000

1200

0 30 60 90 120 150 180Time (minutes)

Te

mpe

ratu

re

ASTM E119 T-t No InsulationInsulation = 13 mm Insulation=6.5 mm

Steel surface w/o insulation

Steel surface with insulation

Insulation thick = 6.5 mmTime=180 mts

Insulation thick = 13.0 mmTime=180 mts

The heating of the composite CFT section becomes more uniform (not broiling)

Page 19: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

Structural Response of CFT with Insulation

0

30,000

60,000

90,000

120,000

150,000

0 0.005 0.01 0.015 0.02 0.025

Rotation (rad.)

Mo

me

nt

(N-m

)

P-M--T curves for CFT with b/t=32

Ins. Thick = 13 mm

Ins. Thick = 6.5 mm

Ambient T=20oCP/Po=0

P/Po=20%

P/Po=40%

P/Po=0P/Po=20%

P/Po=40%

P/Po=0

P/Po=20%

P/Po=40%

2.5E-5 5.0E-5 7.5E-5 10.0E-5 12.5E-5

Curvature (1/mm)

0

30,000

60,000

90,000

120,000

150,000

0.000 0.005 0.010 0.015 0.020 0.025

Rotation (Rad.)

Mo

men

t (N

-m)

P-M--T curves for CFT with b/t=48

Ins. Thick = 13 mm

Ins. Thick = 6.5 mm

Ambient T=20oCP/Po=0

P/Po=20%

P/Po=40%P/Po=0P/Po=20%

P/Po=40%

P/Po=0

P/Po=20%

P/Po=40%

2.5E-5 5.0E-5 7.5E-5 10.0E-5 12.5E-5

Curvature (1/mm)

0

10

20

30

40

50

0 0.2 0.4 0.6 0.8 1 1.2

Moment /Moment @ P=0

Ax

ial L

oad

Lev

el P

/Po %

Ins=13 mm

Ins=6.5 mm

T=20oC

b=200 mm, b/t=32

b=200 mm, b/t=48

b=300 mm, b/t=32

Normalized Strength P-M Interaction

Page 20: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

Findings for CFTs with Insulation

The insulation thickness becomes the most important parameter influencing P-M--T behavior and strength (P-M) under elevated temperatures from fire loading.

As expected, CFTs with b/t =48 have greater increase in moment capacity with increase in axial load (below the balance point). This continues to be true at elevated temperatures also.

The tube width (b) and width-to-thickness (b/t) ratio do not have significant influence on the P-M--T behavior of CFTs at elevated temperatures from fire loading

Page 21: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

EXPERIMENTAL INVESTIGATIONS

Experimental investigations will focus on measuring the P-M--T response of CFT segments. Parameters included in the experimental studies are:

Tube width (b) and b/t ratio Concrete strength f’c

Axial load level Heating (surface temperature) Insulation thickness and type

Experimental test matrix is currently being finalized using results of preliminary investigations

Page 22: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

TEST SETUP

The test-setup will be similar to those used for measuring P-M- response of beam-column specimens at ambient temperature

It will be a cantilever column with axial force and lateral load applied at the top (free) end and the bottom end clamped.

H o l l o w C o r e J a c k

A x i a l L o a d i n g B e a m

A x i a l T e n s i o n R o d

H y d r a u l i c R a m D i r e c t i o n

C l e v i s

S t e e l B a s e P l a t e

C o n c r e t e B l o c k

CFT

A custom-built portable furnace will be placed to surround the plastic hinge region. It will subject the surface to the selected T-t curve.

Thus, the specimen plastic hinge region will be subjected to P, M, and T.

The deformations of the plastic hinge region will be measured using close-range photogrammetry and digital image processing techniques.

Page 23: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

FURNACE DESCRIPTION

The portable furnace consists of ceramic fiber radiant heaters. Four such panel heaters are assembled to form a box around the hinge region.

Heaters have wattage density of 2.5 kW/ft2. Can provide surface temperature approaching 1200oC. They use radiant heating which is efficient and economic

Page 24: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

FURNACE T-t CONTROL

Radiant heaters are fully controllable. Specify control surface T-t curve and the heater will provide it.

For example, in the experiment below, we are controlling steel surface T-t curve under the insulation.

The insulation surface T-t curve can also be directly controlled. This experiment is in progress.

0

100

200

300

400

500

0 50 100 150 200Time (min)

Te

mp

era

ture

(C

)

Input tempmeasured 1measured 2measured 3measured 4

Page 25: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

FURNACE T-t CONTROL

In this experiment we are directly controlling the steel surface T-t curve without insulation to follow the ASTM E119 gas T-t curve.

0

200

400

600

800

1000

1200

0 20 40 60 80 100 120 140 160 180 200

Time (min)

Te

mp

era

ture

(C

)

ASTM E119

FDS1

steel 1

steel 2

steel 3

steel 4

Measured surface T-t curves

Specified surface T-t curve

ASTM E119 T-t curve

Page 26: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

DEFORMATION MEASUREMENTS The deformation (or movement) of any point on the

specimen surface can be measured using close-range photogrammetry and digital image processing fundamentals.

For example, the thermal expansion was measured as shown below.

-0.2

0

0.2

0.4

0.6

0.8

1

1.2

1.4

0 20 40 60 80 100 120 140 160 180 200

Time (min)

Th

erm

al E

xpan

sio

n (

mm

)

Predicted Thermal Expansion at final 1.7mm

Page 27: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

TEMPERATURE MEASUREMENTS

Thermocouples bonded to steel and embedded in concrete to measure temperatures

0

50

100

150

200

250

300

350

400

0 20 40 60 80 100 120 140 160 180 200

Time (min)

Tem

per

atu

re (

C)

computed measured

measured computed

Page 28: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

EXPERIMENTAL INVESTIGATIONS

Will be conducted this year. Results to be presented at next ASCE Structures Congress.

Acknowledgments National Science Foundation - funding Purdue University Dr. Jim Bethel – photogrammetry Jarupat Srisa-Ard - student

Page 29: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

THE END

Page 30: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

MOTIVATION 2

Researchers around the world have developed finite element method based computer programs to conduct structural analysis under fire loading.

For example, researchers at Liege Univ. (SAFIR), Sheffield Univ. (FEMFAN), Univ. of Manchester, Nat. Univ. of Singapore (SINTEF)

Most of these programs use fiber-based or concentrated hinge based beam-column finite elements for modeling the behavior of columns and beam-columns under fire loading

These finite elements must be validated (or calibrated) using experimental data and realistic P-M--T behavior

Page 31: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

MOTIVATION 3

Consider a 6-story structure with perimeter moment resisting frames for lateral stiffness and stability.

Design for dead, live, wind loads. Satisfy building and interstory drift requirements. Consider state when subjected to D+0.5L+W+Compartment Fire load

No Insulation after 15 mts.0.5 in.

insulation after 180 mts.

0.25 in. insulation after 180 mts.

No insulation after 35 mts.

Section P-M at ambient

0.25

0.50

0.75

1.0 1.25

00

0.2

0.4

0.6

0.8

1.0

Nomalized moment capacity Mn/Mp

Nom

aliz

ed a

xia

l ca

paci

ty P

/PY

Page 32: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

MOTIVATION 4

The behavior and failure of columns under constant axial load and elevated temperatures from fire loading also depends on the section P-M--T response of the failure segment.

-16

-14

-12

-10

-8

-6

-4

-2

0

0 50 100 150Time (min)

Axi

al D

isp

lace

me

nt (

mm

)

0

20

40

60

80

100

120

0 20 40 60 80 100 120Time (min)

Mom

ent (

KN

-m)

P

P

P

M=P

P0

1000

2000

3000

4000

5000

6000

0 100 200 300 400 500Moment (KN-m)

Axi

al F

orce

(KN

)

Page 33: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

Step 1 - FIRE DYNAMICS ANALYSIS

During experiments, the furnace gas temperature was controlled to follow the ASTM E119 T-t curve. The temperatures of the CFT column surfaces were measured using thermocouples.

FDS model of the furnace, and the surface T-t curves for 200, 250, and 300 mm CFT columns that were tested shown below.

(b)

Quarter volum

e of CFT column

(a)

Quarter volum

e of CFT column

Hot air flow direction

(a)

Symmetry plane

Symmetry plane

Heated wall

Heated w

all

Hot air flow direction

Hot air

flow direction

Quarter volume of CFT column

(b)

Figure 1. FDS model of NRC Furnace with CFT column

(a)

Symmetry plane

Symmetry plane

Heated wall

Heated w

all

Hot air flow direction

Hot air flow

direction

Quarter volume of CFT column

0

200

400

600

800

1000

1200

0 30 60 90 120 150

Time (min)

Te

mp

era

ture

(C

)

ASTM E119

FDS

ExperimentFDM

Page 34: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

Step 2 - NONLINEAR HEAT TRANSFER ANALYSIS

For example, nonlinear heat transfer analyses of CFT columns tested by other researchers were conducted.

The surface T-t curves from step 1 were used as thermal loading

3D finite element models were developed to conduct the heat transfer analysis and analyzed using ABAQUS.

The results were compared with experimental results.

Page 35: FUNDAMENTAL BEHAVIOR OF CFT BEAM- COLUMNS UNDER FIRE LOADING Amit H. Varma, Sandgo Hong Purdue University 2005 ASCE Structures Congress New York City,

Stress analysis results for CFT beam-column with b/t=32, P/Po = 20%, and insulation thickness=6.5 mm (Curvature = 12.5 x 10-5 1/mm)

Steel tube longitudinal strain Steel tube longitudinal stress

Concrete longitudinal strain Concrete longitudinal stress

(Pa)

(Pa)