Functions Communication and characteristics COM option ... breaker_files...31 Masterpact Schneider...

18
Masterpact Schneider Electric 28 + + + 3 OF SDE PF CH MX XF CE CT CD 5 C C C C C 4 2 1 communication Bus The COM option is required for integration of the circuit breaker or switch-disconnector in a supervision system. Masterpact uses the Digipact or Modbus communications protocol for full compatibility with the SMS PowerLogic electrical-installation management systems. An external gateway is available for communication on other networks: c Profibus c Ethernet… Digipact «device» communication module. Digipact «craddle» communication module 056431 056401 For fixed devices, the COM option is made up of: c a "device" communication module, installed behind the Micrologic control unit and supplied with its set of sensors (OF, SDE ,PF and CH micro-contacts) and its kit for connection to XF and MX communicating voltage releases. For drawout devices, the COM option is made up of: c a "device" communication module, installed behind the Micrologic control unit and supplied with its set of sensors (OF, SDE, PF and CH micro-contacts) and its kit for connection to XF and MX communicating voltage releases c a "craddle" communication module supplied separately with its set of sensors (CE, CD and CT contacts). Status indication by the COM option is independent of the device indication contacts. These contacts remain available for conventional uses. Digipact or Modbus «Device» communication module This module is independent of the control unit. It receives and transmits information on the communication network. An infra-red link transmits data between the control unit and the communication module. Consumption: 30 mA, 24 V. Digipact or Modbus «craddle» communication module This module is independent of the control unit. With Modbus "craddle" communication module, this module makes it possible to address the craddle and to maintain the address when the circuit breaker is in the disconnected position. Consumption: 30 mA, 24 V. XF and MX communicating voltage releases The XF and MX communicating voltage releases are equipped for connection to the "device" communication module. The remote-tripping function (second MX or MN) are independent of the communication option. They are not equipped for connection to the "device" communication module. 1 «Device» communication module 2 «Craddle» communication module 3 OF, SDE, PF and CH «device» sensors 4 CE, CD and CT «craddle» sensors 5 MX and XF release E47073 Modbus «craddle» communication module : hard wire : communication bus Modbus «device» communication module Note: eco COM The eco COM Modbus is intended to fit the circuit breaker with module display (DMB300, DMC300…). Communication COM option in Masterpact Functions and characteristics E45183 056431 BTP207E-20300-auxiliaries.pm6 15/05/01, 15:54 28

Transcript of Functions Communication and characteristics COM option ... breaker_files...31 Masterpact Schneider...

Page 1: Functions Communication and characteristics COM option ... breaker_files...31 Masterpact Schneider Electric Modbus The Modbus RS485 (JBus) system is an open bus on which communicating

Masterpact Schneider Electric28

+

+

CCM modbus

+

CE

CD

CT

3

OFSDEPFCH

MXXF

CECT

CD 5

CCCC

CC

4

2

1

communicationBus

The COM option is required for integrationof the circuit breaker or switch-disconnectorin a supervision system.Masterpact uses the Digipact or Modbuscommunications protocol for fullcompatibility with the SMS PowerLogicelectrical-installation management systems.An external gateway is available forcommunication on other networks:c Profibusc Ethernet…

Digipact «device»communication module.

Digipact «craddle»communication module

0564

3105

6401

For fixed devices, the COM option is made up of:c a "device" communication module, installed behind the Micrologic control unitand supplied with its set of sensors (OF, SDE ,PF and CH micro-contacts) and itskit for connection to XF and MX communicating voltage releases.For drawout devices, the COM option is made up of:c a "device" communication module, installed behind the Micrologic control unitand supplied with its set of sensors (OF, SDE, PF and CH micro-contacts) and itskit for connection to XF and MX communicating voltage releasesc a "craddle" communication module supplied separately with its set of sensors(CE, CD and CT contacts).Status indication by the COM option is independent of the device indicationcontacts. These contacts remain available for conventional uses.Digipact or Modbus «Device» communication moduleThis module is independent of the control unit. It receives and transmits informationon the communication network. An infra-red link transmits data between the controlunit and the communication module.Consumption: 30 mA, 24 V.Digipact or Modbus «craddle» communication moduleThis module is independent of the control unit. With Modbus "craddle"communication module, this module makes it possible to address the craddle andto maintain the address when the circuit breaker is in the disconnected position.Consumption: 30 mA, 24 V.XF and MX communicating voltage releasesThe XF and MX communicating voltage releases are equipped for connection tothe "device" communication module.The remote-tripping function (second MX or MN) are independent of thecommunication option. They are not equipped for connection to the "device"communication module.

1 «Device» communication module2 «Craddle» communication module3 OF, SDE, PF and CH «device» sensors4 CE, CD and CT «craddle» sensors5 MX and XF release

E47

073

Modbus «craddle»communication module : hard wire

: communication bus

Modbus «device»communication module

Note: eco COMThe eco COM Modbus is intended to fit the circuit breaker with module display(DMB300, DMC300…).

CommunicationCOM option in Masterpact

Functionsand characteristics

E45

183

0564

31

BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5428

Page 2: Functions Communication and characteristics COM option ... breaker_files...31 Masterpact Schneider Electric Modbus The Modbus RS485 (JBus) system is an open bus on which communicating

Masterpact Schneider Electric29

The Masterpact switch-disconnectors are compatible only with the Digipact COMoption.

The Masterpact circuit breakers are compatible with the Digipact or Modbus COMoption.The COM option may be used with all types of control units to:c identify the devicec indicate status conditionsc control the device.Depending on the different types of Micrologic (A, P, H) control units, the COMoption also offers:c setting of the protection and alarms functionsc analysis of the AC-power parameters for operating-assistance and maintenancepurposes

E47

071

ModuleEventTime

POWERLOGIC System Manager Demo

Ready

File Edit View Setup ToolsControl Display Reports Window Help

ONLINE: DEMO 9:30No working system

5 secondsSampling Mode : MANUAL

0,00

0,20

0,40

0,60

0,80

1,00

1,20

H2 H3 H4 H5 H6 H7 H8 H9 H10 H11 H12

% F

unda

men

tal

Harmonics

Phase A-N Voltage - Harmonics Analysis

Phase 1-N

Harmonics(RMS)

H2: 0.01H3: 0.45H4: 0.03H5: 0.45H6: 0.04H7: 1.27H8: 0.05H9: 0.42H10: 0.01H11: 1.03H12: 0.07

H1: 118.09

OK

Fundamental:

RMS:

RMS-H:

Peak:

CF:

THD:

Overview of functions

switch-disconnector with circuit breaker withcommunication bus communication busDigipact Modbus Digipact Modbus

device identificationaddress c - A P H A P H

calibre - - A P H A P H

type of device - - P H

type of control unit - - A P H A P H

type of long-time rating plug - - A P H A P H

status indicationsON/OFF OF c - A P H A P H

spring charged CH c - A P H A P H

ready to close PF c - A P H A P H

fault-trip SDE - - A P H A P H

connected/disconnected/test c - A P H A P Hposition CE/CD/CT

commandesopening / closing MX/XF c - A P H A P H

spring charging - -reset of the mechanical - -indicator

protections and alarms settingsreading of protections settings A P H A P H

writing of fine settings in the range P Himposed by the adjustment dialsreading/writing of alarms (délestage, relestage, M2C… ) P H

reading/writing of alarms personnalisables H

operating and maintenance aidsmeasurement

current A P H A P H

voltages, frequency, power, etc. P H P H

power quality: fundamental, harmonics H

programming of demand metering P H

fault readingstype of fault A P H

interrupted current P H

waveform captureon faults H

on demand or programmed H

histories and logstrip history P H

alarm history P H

event logs P H

indicatorscounter operation A P H A P H

contact wear P H

maintenance register P H

Note.See the description of the Micrologic control units for further details on protection andalarms, measurements, waveform capture, histories, logs and maintenance indicators.

BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5429

Page 3: Functions Communication and characteristics COM option ... breaker_files...31 Masterpact Schneider Electric Modbus The Modbus RS485 (JBus) system is an open bus on which communicating

Masterpact Schneider Electric30

CommunicationMasterpact in a communicationnetwork

Functionsand characteristics

E67

968

MasterpactMasterpact

pulsar SV

� � � � � � �� � � �

N°1N°1

1 3

OK

error

com

24V

com

error

JBus

BBus

resetAp

IgI ∆nIsd

I iIr

Micrologic 70

Reset

O OFF

discharged

0 1 2 5 3

push OFF

push ON

Ics = 100% Icu

220/440

525

690

100

100

85

Icw 85kA/1s

NX 32 H 2

cat.B

IEC 947-2

UTE VDE BS CEI UNE AS NEMA

EN 60947-2

50/60Hz

UeIcu

(V)

(kA)

volets

shutters

Test

CD3 CD2 CD1

CE6 CE5 CE4

Com UC1 UC2 UC3 UC4 M2C UC2 SDE2 CE3 CE2 CE1MN MX1 XF PF MCH

OF24 OF23 OF22 OF21 OF14 OF13 OF12 OF11

OC24 OC23 OC22 OC21 OC14 OC13 OC12

OF24244

242241

OF23234

232231

OF22224

222221

OF21214

212211

OF14144

142141

OF13134

132131

OF12124

122121

OF11114

112111

OF444

4241

3231

OF334

OF224

2221

OF114

1211

CT3934

932931

CT2924

922921

CT1914

912911

MN/MX2D2/ C12

/ C13D1/ C11

MX1C2

C3C1

XFA2

A3A1

PF254

252251

MCHB2

B3B1

334 324 314CE3

332331

CE2

322321

CE1

312311

Com UC1 UC2 UC3 UC4SDE1

E5E3

E1

E6E4

E2

Z5Z3

Z1

M1Z4

Z2

M2T3

T1

M3T4

T2

F2 +VN

F1 -

V3V2

V1

484/ Q3474/ Q2

471/ Q1

184/ K2182

181/ K1

8482

81M2C/M6C

CD3834

832831

CD2824

822821

CD1814

812811

resetAp

IgI ∆nIsd

I iIr

Micrologic 70

Reset

O OFF

discharged

0 1 2 5 3

push OFF

push ON

Ics = 100% Icu

220/440

525

690

100

100

85

Icw 85kA/1s

NX 32 H 2

cat.B

IEC 947-2

UTE VDE BS CEI UNE AS NEMA

EN 60947-2

50/60Hz

UeIcu

(V)

(kA)

volets

shutters

Test

CD3 CD2 CD1

CE6 CE5 CE4

Com UC1 UC2 UC3 UC4 M2C UC2 SDE2 CE3 CE2 CE1MN MX1 XF PF MCH

OF24 OF23 OF22 OF21 OF14 OF13 OF12 OF11

OC24 OC23 OC22 OC21 OC14 OC13 OC12

OF24244

242241

OF23234

232231

OF22224

222221

OF21214

212211

OF14144

142141

OF13134

132131

OF12124

122121

OF11114

112111

OF444

4241

3231

OF334

OF224

2221

OF114

1211

CT3934

932931

CT2924

922921

CT1914

912911

MN/MX2D2/ C12

/ C13D1/ C11

MX1C2

C3C1

XFA2

A3A1

PF254

252251

MCHB2

B3B1

334 324 314CE3

332331

CE2

322321

CE1

312311

Com UC1 UC2 UC3 UC4SDE1

E5E3

E1

E6E4

E2

Z5Z3

Z1

M1Z4

Z2

M2T3

T1

M3T4

T2

F2 +VN

F1 -

V3V2

V1

484/ Q3474/ Q2

471/ Q1

184/ K2182

181/ K1

8482

81M2C/M6C

CD3834

832831

CD2824

822821

CD1814

812811

RS 485

RS 232C,Ethernet

Data concentratorDC150

Digipact Bus ModBUS Bus

Device

CommunicationBus

Communicationinterface

Software

DevicesCircuit breakers equipped with Micrologic control units may be connected to eithera Digipact or Modbus communication bus. The information made availabledepends on the type of Micrologic control unit (A, P or H) and on the type ofcommunication bus (Digipact or Modbus).Switch-disconnectors may be connected exclusively to the Digipact communicationbus.

Communication bus

DigipactThe Digipact bus is the internal bus of the low-voltage switchboard in which theDigipact communicating devices are installed (Masterpact with Digipact COM,PM150, SC150, UA150, etc.). This bus must be equipped with a DC150 dataconcentrator (see the Powerlogic System catalogue).AddressesAddressing is carried out by the DC150 data concentrator.Number of devicesThe maximum number of devices that may be connected to the Digipact bus iscalculated in terms of “communication points”. These points correspond to theamount of traffic the bus can handle. The total number of points for the variousdevices connected to a single bus must not exceed 100.If the required devices represent more than 100 points, add a second Digipactinternal bus.

Communicating device Number of pointsDC150 data concentrator 4Micrologic + Digipact COM 4PM150 4SC150 4UA150 4

Length of busThe maximum recommended length for the Digipact internal bus is 200 meters.Bus power sourcePower is supplied by the DC150 data concentrator (24 V)..

BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5430

Page 4: Functions Communication and characteristics COM option ... breaker_files...31 Masterpact Schneider Electric Modbus The Modbus RS485 (JBus) system is an open bus on which communicating

Masterpact Schneider Electric31

ModbusThe Modbus RS485 (JBus) system is an open bus on which communicatingModbus devices (Masterpact with Modbus COM, PM300, Sepam, Vigilohm, etc.)are installed. All types of PLCs and microcomputers may be connected to the bus.AddressesThe software layer of the Modbus protocol can manage up to 255 addresses (1 to 255).The “device” communication module comprises three addresses linked to:b circuit-breaker manager;b measurement manager;b protection manager.The “craddle” communication module comprises one address linked to:b the craddle manager.The division of the system into four managers secures data exchange with thesupervision system and the circuit-breaker actuators.The manager addresses are automatically derived from the circuit-breaker address@xx entered via the Micrologic control unit (the default address is 47).

logic addresses@xx Circuit-breaker manager (1 to 47)@xx + 50 Craddle manager (51 to 97)@xx + 200 Measurement managers (201 to 247)@xx + 100 Protection manager (101 to 147)

Number of devicesThe maximum number of devices that may be connected to the Modbus busdepends on the type of device (Masterpact with Modbus COM, PM300, Sepam,Vigilohm, etc.), the baud rate (19200 is recommended), the volume of dataexchanged and the desired response time. The RS485 physical layer offers up to32 connection points on the bus (1 master, 31 slaves).A fixed device requires only one connection point (communication module on thedevice).A drawout device uses two connection points (communication modules on thedevice and on the craddle).The number must never exceed 31 fixed devices or 15 drawout devices.Length of busThe maximum recommended length for the Modbus bus is 1200 meters.Bus power sourceA 24 V DC power supply is required (less than 20% ripple, insulation class II).

Communication interfaceThe Modbus bus may be connected to the central processing device in any ofthree manners:b direct link to a PLC. The communication interface is not required if the PLC isequipped with a Modbus port;b direct link to a computer. The Modbus (RS485) / Serial port (RS232)communication interface is required;b connection to a TCP/IP (Ethernet) network. The Modbus (RS485) / TCP/IP(Ethernet) communication interface is required.

SoftwareTo make use of the information provided by the communicating devices, softwarewith a Modbus driver must be used.

Micrologic utilitiesThis is a set of Modbus drivers that may be used with a PC to:b display the variables (I, U, P, E, etc.) with the DDS (Data Display Software)application;b read/write the settings with the RSS (Remote Setting Software) application;b remotely control (ON / OFF) the device with the CSS (Control CommandSoftware) application.These softwares are available upon request.

SMS (System Manager Software)SMS is a software to monitor LV and/or MV electrical energy.The SMS family includes a software range depending on the application andfunction, from single product monitoring to the management of a multiple building:cPower Meter and Circuit Monitor unitscLV devicescSepam units.

BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5431

Page 5: Functions Communication and characteristics COM option ... breaker_files...31 Masterpact Schneider Electric Modbus The Modbus RS485 (JBus) system is an open bus on which communicating

Masterpact Schneider Electric32

Rear connectionhorizontal vertical

Simply turn a horizontal rear connector 90° to make it a vertical connector.

Front connection

Mixed connection

Note.Masterpact circuit breakers can be connected indifferently with bare-copper, tinned-copper and tinned-aluminium conductors, requiring no particular treatment.

Three types of connection are available:c vertical or horizontal rear connectionc front connectionc mixed connection.The solutions presented are similar inprinciple for all Masterpact NT and NWfixed and drawout devices..

ConnectionsOverview of solutions

Functionsand characteristics

0564

32

0564

33

0564

3405

6435

0564

36

0564

37

BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5532

Page 6: Functions Communication and characteristics COM option ... breaker_files...31 Masterpact Schneider Electric Modbus The Modbus RS485 (JBus) system is an open bus on which communicating

Masterpact Schneider Electric33

Type of accessory Masterpact NT06 to NT16 Masterpact NW08 to NW63

fixed drawout fixed drawoutfront rear front rear front rear front rearconnection connection connection connection connection connection connection connection

Optional accessories

E47

064

E46

889

E46

431

E46

431

E46

428

E46

426

E79

058

E46

428

E46

428

Cable lugadapters

Vertical connectionadapters

Bare-cable connectorsand connector shield

E47

067

E47

068

E47

066

Safety shutterswith padlocking

Spreaders

Disconnectablefront-connectionadapter

Shutter positionindication and locking

Masterpact M replacement kitA set of connection parts is available to allow replacement of a Masterpact M08 toM32 circuit breaker by a Masterpact NW without modifying the busbars (pleaseconsult us).

Mounting on a switchboard backplate using special bracketsMasterpact NT and NW fixed front-connected circuit breakers can be installedon a backplate without any additional accessories.Masterpact NW circuit breakers require a set of special brackets.

E46

426

E46

427

E46

427

E70

745Arc chute screen

max. 4000 A

Interphasebarriers

BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5633

Page 7: Functions Communication and characteristics COM option ... breaker_files...31 Masterpact Schneider Electric Modbus The Modbus RS485 (JBus) system is an open bus on which communicating

Masterpact Schneider Electric34

ConnectionsOptional accessories

Functionsand characteristics

Bare-cable connectors and connector shieldThe connectors can be mounted on fixed front-connected devices to allowconnection using bare cables. They are supplied with a connector shield.They are designed to connect four 240 mm2 cables each.

Vertical-connection adaptersMounted on front-connected devices or craddle, the adapters facilitate connectionto a set of vertical busbars.

Cable-lug adaptersCable-lug adapters are used in conjunction with vertical rear connectors or withvertical-connection adapters.They can be used to connect a number of cables fitted with lugs.To ensure adequate mechanical strength, the connectors must be secured togethervia spacers.

Interphase barriersThese barriers are flexible insulated partitions used to reinforce isolation ofconnection points in installations with busbars, whether insulated or not.For Masterpact NT/NW devices, they are installed vertically between rearconnection terminals.

SpreadersMounted on the front or rear connectors, spreaders are used to increase thedistance between bars in certain installation configurations.

Arc chute screenFor Masterpact NT fixed, front connected and using vertical-connection adaptersfront oriented, it is mandatory to install arc chute screen in order to comply with thesafety perimeter.

0564

3805

6440

0564

4105

6415

0564

42

Ipush ON

O OFF

discharged

Opush OFF

E70

746

BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5634

Page 8: Functions Communication and characteristics COM option ... breaker_files...31 Masterpact Schneider Electric Modbus The Modbus RS485 (JBus) system is an open bus on which communicating

Masterpact Schneider Electric35

0564

43 Disconnectable front-connection adapterMounted on a fixed front-connected device, the adapter simplifies replacement of afixed device by enabling fast disconnection from the front.

Safety shuttersMounted on the craddle, the safety shutters automatically block access to thedisconnecting contact cluster when the device is in the disconnected or testpositions (degree of protection IP 20) When the device is removed from its craddle,no live parts are accessible.The shutter-locking system is made up of a moving block that can be padlocked(padlock not supplied). The block:* prevents connection of the device* locks the shutters in the closed positionFor Masterpact NW08 to NW63A support at the back of the craddle is used to store the blocks when they are notused.* 2 blocks for NW08 to NW40* 4 blocks for NW40b to NW63.

Shutter position indication and locking on front faceThis option located on the craddle front plate indicates that the shutters are closed.It is possible to independently or separately padlock the two shutters using one tothree padlocks (not supplied).

0564

45E

4747

6

BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5635

Page 9: Functions Communication and characteristics COM option ... breaker_files...31 Masterpact Schneider Electric Modbus The Modbus RS485 (JBus) system is an open bus on which communicating

Masterpact Schneider Electric36

resetAp

IgI ∆nIsd

I iIr

Micrologic 70

Opush OFF

Ipush ON

O OFF

discharged

0 1 2 5 3

Ics = 100% Icu

IEC 947-2� � � � � � � � � � �

NW 1250 H1

Ui 1000V Uimp 12kV

Ue(V)220/240

480/690

Icu(kA)

10085

Uimp 8kV1

2

9

8

7

654

3

LockingOn the device

Functionsand characteristics

1 reset button for mechanicaltrip indication

2 OFF pushbutton3 OFF position lock4 electrical closing

pushbutton5 ON pushbutton6 springs charged indication7 pushbutton locking8 contact position indication9 operation counter

E47

062

Pushbutton lockingThe transparent cover blocks access to the pushbuttons used to open and closethe device.It is possible to independently lock the opening button and the closing button. Thelocking device is often combined with a remote operating mechanism.The pushbuttons may be locked using either:c three padlocks (not supplied)c lead sealc two screws.

Device locking in the OFF positionThe circuit breaker is locked in the OFF position by physically maintaining theopening pushbutton pressed down:c using padlocks (one to three padlocks, not supplied)c using keylocks (one or two different keylocks, supplied).Keys may be removed only when locking is effective (Profalux or Ronis type locks).The keylocks are available in any of the following configurations:c one keylockc one keylock mounted on the device + one identical keylock supplied separatelyfor interlocking with another devicec two different key locks for double locking.Profalux and Ronis keylocks are compatible with each other.A locking kit (without locks) is available for installation of one or two keylocks(Ronis, Profalux, Kirk or Castell).Accessory-compatibilityFor Masterpact NT: 3 padlocks or 1 keylockFor Masterpact NW: 3 padlocks and/or 2 keylocks

Cable-type door interlockThis option prevents door opening when the circuit breaker is closed and preventscircuit breaker closing when the door is open.For this, a special plate associated with a lock and a cable is mounted on the rightside of the circuit breaker.With this interlock installed, the source changeover function cannot beimplemented.

Pushbutton locking using apadlock

Access to pushbuttonsprotected by transparentcover

OFF position locking using apadlock

OFF position locking using akeylock

0564

4605

6447

0564

4805

6449

BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5636

Page 10: Functions Communication and characteristics COM option ... breaker_files...31 Masterpact Schneider Electric Modbus The Modbus RS485 (JBus) system is an open bus on which communicating

Masterpact Schneider Electric37

1

2

8

10

9

7

5

6

4

305

6451

1 mismatch protection2 door interlock3 racking interlock4 keylock locking5 padlock locking6 position indicator7 craddle front plate

(accessible with cubicledoor closed)

8 racking-handle entry9 reset button10 racking-handle storage

On the craddle

E47

063

« Disconnected» positionlocking by padlocks

« Disconnected» positionlocking by keylocks

Door interlock

Racking interlock

0564

5005

6417

0564

5205

6453 Mismatch protection

« Disconnected» position lockingMounted on the craddle and accessible with the door closed, these devices lockthe circuit breaker in the « disconnected» position in two manners:c using padlocks (standard), up to three padlocks (not supplied)c using keylocks (optional), one or two different keylocks are available.Profalux and Ronis keylocks are available in different options:c one keylockc two different keylocks for double lockingc one (or two) keylocks mounted on the device + one (or two) identical keylockssupplied separately for interlocking with another device.A locking kit (without locks) is available for installation of one or two keylocks(Ronis, Profalux, Kirk or Castell).

« Connected» , « disconnected» and « test» position lockingThe « connected» , « disconnected» and « test» positions are shown by an indicator.The exact position is obtained when the racking handle blocks. A release button isused to free it.On request, the « disconnected» position locking system may be modified to lockthe circuit breaker in any of the three positions, « connected» , « disconnected» and« test» .

Door interlock catchMounted on the right or left-hand side of the craddle, this device inhibits opening ofthe cubicle door when the circuit breaker is in « connected» or « test» position. It thebreaker is put in the « connected» position with the door open, the door may beclosed without having to disconnect the circuit breaker.

Racking interlockThis device prevents insertion of the racking handle when the cubicle door is open.

Cable-type door interlockThis option is identical for fixed and drawout versions.

Racking interlock between crank and OFF pushbuttonThis option makes it necessary to press the OFF pushbutton in order to insert theracking handle and holds the device open until the handle is removed.

Automatic spring discharge before breaker removalThis option discharges the springs before the breaker is removed from the craddle.

Mismatch protectionMismatch protection ensures that a circuit breaker is installed only in a craddle withcompatible characteristics. It is made up of two parts (one on the craddle and oneon the circuit breaker) offering twenty different combinations that the user mayselect.

BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5737

Page 11: Functions Communication and characteristics COM option ... breaker_files...31 Masterpact Schneider Electric Modbus The Modbus RS485 (JBus) system is an open bus on which communicating

Masterpact Schneider Electric38

Indication contacts

Indication contacts are available:c in the standard version for relayapplicationsc in a low-level version for control of PLCsand electronic circuits.M2C and M6C contacts may beprogrammed via the Micrologic P and Hcontrol units.

Functionsand characteristics

ON/OFF indication contacts (OF)Two types of contacts indicate the ON or OFF position of the circuit breaker:c microswitch type changeover contacts for Masterpact NTc rotary type changeover contacts directly driven by the mechanism for MasterpactNW. These contacts trip when the minimum isolation distance between the maincircuit-breaker contacts is reached.OF NT NW

supplied as standard 4 4maximum number 4 12breaking capacity (A) standard minimum load: 100mA/24Vp.f.: 0.3 V AC 240/380 6 10/6*AC12/DC12 480 6 10/6*

690 6 6V DC 24/48 2.5 10/6*

125 0.5 10/6*250 0.3 3

low-level minimum load: 2mA/15V DCV AC 24/48 5 6

240 5 6380 5 3

V DC 24/48 5/2.5 6125 0.5 6250 0.3 3

* standard contacts: 10 A; optional contacts: 6 A.

« Fault-trip» indication contacts (SDE)Circuit-breaker tripping due to a fault is signalled by:c a red mechanical fault indicator (reset)c one changeover contact (SDE).Following tripping, the mechanical indicator must be reset before the circuit breakermay be closed.SDE NT/NW

supplied as standard 1maximum number 2breaking capacity (A) standard minimum load: 100mA/24Vp.f.: 0.3 V AC 240/380 5AC12/DC12 480 5

690 3V DC 24/48 3

125 0.3250 0.15

low-level minimum load: 2mA/15V DCV AC 24/48 3

240 3380 3

V DC 24/48 3125 0.3250 0.15

Combined « connected/closed» contacts (EF)The contact combines the « device connected» and the « device closed»information to produce the « circuit closed» information.Supplied as an option for Masterpact NW, it is mounted in place of the connector ofan additional OF contact.EF NW

maximum number 8breaking capacity (A) standard minimum load: 100mA/24Vp.f.: 0.3 V AC 240/380 6AC12/DC12 480 6

690 6V DC 24/48 2.5

125 0.8250 0.3

low-level minimum load: 2mA/15V DCV AC 24/48 5

240 5380 5

V DC 24/48 2.5125 0.8250 0.3

ON/OFF indication contacts(OF) (microswitch type)

ON/OFF indication contacts(OF) (rotary type)

Combined contacts

Additional « fault-trip»indication contacts (SDE)

0564

1805

6419

0564

6205

6455

BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5838

Page 12: Functions Communication and characteristics COM option ... breaker_files...31 Masterpact Schneider Electric Modbus The Modbus RS485 (JBus) system is an open bus on which communicating

Masterpact Schneider Electric39

CE, CD and CT « connected/disconnected/test» positioncarriage switches

M2C programmablecontacts: circuit-breakerinternal relay with twocontacts

M6C programmablecontacts: circuit-breakerexternal relay with sixindependent changeovercontacts controlled from thecircuit breaker via a three-wire connection.

0564

5605

6413

0564

30

« Connected» , « disconnected» and « test» position carriageswitchesThree series of optional auxiliary contacts are available for the craddle:c changeover contacts to indicate the « connected» position (CE)c changeover contacts to indicate the « disconnected» position (CD). This positionis indicated when the required clearance for isolation of the power and auxiliarycircuits is reached.c changeover contacts to indicate the « test» position (CT). In this position, thepower circuits are disconnected and the auxiliary circuits are connected.Additional actuatorsA set of additional actuators may be installed on the craddle to change thefunctions of the carriage switches.

NT NWcontacts CE/CD/CT CE/CD/CT

maximum number standard 3 2 1 3 3 3with additional actuators 9 0 0

6 3 06 0 3

breaking capacity (A) standard minimum load: 100mA/24Vp.f.: 0.3 V AC 240 8 8AC12/DC12 380 8 8

480 8 8690 6 6

V DC 24/48 2.5 2.5125 0.8 0.8250 0.3 0.3

low-level minimum load: 2mA/15V DCV AC 24/48 5 5

240 5 5380 5 5

V DC 24/48 2.5 2.5125 0.8 0.8250 0.3 0.3

M2C / M6C programmable contactsThese contacts, used with the Micrologic P and H control units, may beprogrammed via the control unit keypad or via a supervisory station with the COMcommunication option. They require an external power supply module.They indicate:c the type of faultc instantaneous or delayed threshold overruns.They may be programmed:c with instantaneous return to the initial statec without return to the initial statec with return to the initial state following a delay.characteristics M2C/M6C

minimum load 100mA/24Vbreaking V AC 240 5capacity (A) 380 3p.f.: 0.7 V DC 24 1.8

48 1.5125 0.4250 0.15

471

S1

474

484

S2

20

S6

24 22

5

S1

1 3

11

S2

7 9

2

S3

6 4

8

S4

12 10

14

S5

18 16

M2C: 24 V DCpower suppliedby control unit(consumption100 mA).

M6C: external 24 V DC power supply required (consumption100 mA).

E59

469

E59

470

BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5839

Page 13: Functions Communication and characteristics COM option ... breaker_files...31 Masterpact Schneider Electric Modbus The Modbus RS485 (JBus) system is an open bus on which communicating

Masterpact Schneider Electric40

The remote ON / OFF function is used to remotely open and close the circuitbreaker. It is made up of:c an electric motor (MCH) equipped with a « springs charged» limit switch contact(CH)c two voltage releases:v a closing release (XF)v an opening release (MX).Optionally, other functions may be added:c a « ready to close» contact (PF)c an electrical closing pushbutton (BPFE)c remote reset following a fault.A remote-operation function is generally combined with:c device ON / OFF indication (OF)c « fault-trip» indication (SDE).

Wiring diagram of a point-to-point remote ON / OFF function

Wiring diagram of a bus-type remote ON / OFF function

A2 A3

A1

XFcom

C1

C2 C3

OF

MXcom

B1

B3 B2

CH

MCH

COM

PF

SDE

CH

closingorder

openingorder

springcharged

supervisor

12 14

11

OF1

82 84

81

SDE

252 254

251

PF

A2

A1

XF

C2

C1

MX

B3 B2

B1

CH

MCH

closedopenfaultreadyto close

closingorder

openingorder

springcharged

Remote operationRemote ON / OFF

Functionsand characteristics

Two solutions are available for remoteoperation of Masterpact devices:c a point-to-point solutionc a bus solution with the COMcommunication option.

0564

07

E46

041

E46

042

Note:An opening order always takes priority over a closingorder.If opening and closing orders occur simultaneously, themechanism discharges without any movement of themain contacts. The circuit breaker remains in the openposition (OFF).In the event of maintained opening and closing orders,the standard mechanism provides an anti-pumpingfunction by blocking the main contacts in open position.Anti-pumping function. After fault tripping or intentionalopening using the manual or electrical controls, theclosing order must first be discontinued, then reactivatedto close the circuit breaker.When the automatic reset after fault trip (RAR) option isinstalled, to avoid pumping following a fault trip, theautomatic control system must take into account theinformation supplied by the circuit breaker before issuinga new closing order or blocking the circuit breaker in theopen position (information on the type of fault, e.g.overload, short-time fault, earth fault, earth leakage,short-circuit, etc.).

BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5840

Page 14: Functions Communication and characteristics COM option ... breaker_files...31 Masterpact Schneider Electric Modbus The Modbus RS485 (JBus) system is an open bus on which communicating

Masterpact Schneider Electric41

Electric motor (MCH) forMasterpact NT

XF and MX voltage releases

“Ready to close” contacts(PF)

0564

20

0564

2105

6457

Electric motor (MCH)The electric motor automatically charges and recharges the spring mechanismwhen the circuit breaker is closed. Instantaneous reclosing of the breaker is thuspossible following opening. The spring-mechanism charging handle is used only asa backup if auxiliary power is absent.The electric motor (MCH) is equipped as standard with a limit switch contact (CH)that signals the “charged” position of the mechanism (springs charged).characteristics

power supplyV AC 50/60 Hz 48/60 - 100/130 - 200/240 - 277- 380/415 - 400/440 - 480V DC 24/30 - 48/60 - 100/125 - 200/250

operating threshold 0.85 to 1.1 Unconsumption (VA or W) 180motor overcurrent 2 to 3 In for 0.1 secondcharging time maximum 3 seconds for Masterpact NT

maximum 4 seconds for Masterpact NWoperating frequency maximum 3 cycles per minuteCH contact 10 A at 240 V

Voltage releases (XF and MX)Closing release (XF)The XF release remotely closes the circuit breaker if the spring mechanism ischarged.Opening release (MX)The MX release instantaneously opens the circuit breaker when energised. Thesupply can be maintained or automatically disconnected.characteristics XF MX

power supplyV AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 277 - 380/480V DC 12 - 24/30 - 48/60 - 100/130 - 200/250

operating threshold 0.85 to 1.1 Un 0.7 to 1.1 Unconsumption (VA or W) hold: 4.5 hold: 4.5

pick-up: 200 pick-up: 200circuit-breaker response 55 ms ± 10 (Masterpact NT) 50 ms ± 10time at Un 70 ms ± 10 (NW i 4000A)

80 ms ± 10 (NW > 4000A)

“Ready to close” contact (PF)The “ready to close” position of the circuit breaker is indicated by a mechanicalindicator and a PF changeover contact. This signal indicates that all the followingare valid:c the circuit breaker is in the OFF positionc the spring mechanism is chargedc a maintained opening order is not present:v MX energisedv fault tripv remote tripping (second MX or MN)v device not completely racked inv device locked in OFF positionv device interlocked with a second device.characteristics NT/NW

maximum number 1breaking capacity standard minimum load: 100mA/24Vp.f.: 0.3 V AC 240/380 5AC12/DC12 480 5

690 3V DC 24/48 3

125 0.3250 0.15

low-level minimum load: 2mA/15V DCV AC 24/48 3

240 3380 3

V DC 24/48 3125 0.3250 0.15

Electric motor (MCH) forMasterpact NW

0564

68

BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5941

Page 15: Functions Communication and characteristics COM option ... breaker_files...31 Masterpact Schneider Electric Modbus The Modbus RS485 (JBus) system is an open bus on which communicating

Masterpact Schneider Electric42

Electrical closing pushbutton (BPFE)Located on the front panel, this pushbutton carries out electrical closing of thecircuit breaker. It is generally associated with the transparent cover that protectsaccess to the closing pushbutton.Electrical closing via the BPFE pushbutton takes into account all the safetyfunctions that are part of the control/monitoring system of the installation.The BPFE connects to the closing release (XF) in place of the COM module.

Remote reset after fault tripElectrical reset after fault trip (Res)Following tripping, this function resets the “fault trip” indication contacts (SDE) andthe mechanical indicator and enables circuit breaker closing.Power supply: 110 / 130 V AC and 200 / 240 V AC

Automatic reset after fault trip (RAR)Following tripping, a reset of the mechanical indicator (reset button) is no longerrequired to enable circuit-breaker closing. The mechanical (reset button) andelectrical (SDE) indications remain in fault position until the reset button is pressed.

Remote operationRemote ON / OFF (cont.)

Functionsand characteristics

Electrical closing pushbutton (BPFE).

0564

69

E46

044

SDE2

K2

K1

resetorder

E46

045

A2 A3

A1

BPFE

XF com

remoteclosingorder

BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5942

Page 16: Functions Communication and characteristics COM option ... breaker_files...31 Masterpact Schneider Electric Modbus The Modbus RS485 (JBus) system is an open bus on which communicating

Masterpact Schneider Electric43

This function opens the circuit breaker via an electrical order. It is made up of:c a shunt release (second MX)c or an undervoltage release (MN)c or a delayed undervoltage release (MN + delay unit).The delay unit, installed outside the circuit breaker, may be disabled by anemergency OFF button to obtain instantaneous opening of the circuit breaker.

Wiring diagram for the remote-tripping function

Voltage releases (second MX)When energised, the MX voltage release instantaneously opens the circuit breaker.A continuous supply of power to the second MX locks the circuit breaker in the OFFposition.characteristics

power supplyV AC 50/60Hz 24 - 48 - 100/130 - 200/250 - 277- 380/480V DC 12 - 24/30 - 48/60 - 100/130 - 200/250

operating threshold 0.7 to 1.1 Unpermanent locking function 0.85 to 1.1 Unconsumption (VA or W) pick-up: 200

hold: 4.5circuit-breaker response 50 ms ± 10time at Un

Instantaneous voltage releases (MN)The MN release instantaneously opens the circuit breaker when its supply voltagedrops to a value between 35% and 70% of its rated voltage. If there is no supply onthe release, it is impossible to close the circuit breaker, either manually orelectrically. Any attempt to close the circuit breaker has no effect on the maincontacts. Circuit-breaker closing is enabled again when the supply voltage of therelease returns to 85% of its rated value.characteristics

power supplyV AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 380/480V DC 24/30 - 48/60 - 100/130 - 200/250

operating opening 0.35 to 0.7 Unthreshold closing 0.85 Unconsumption (VA or W) pick-up: 200 hold: 4.5circuit-breaker response 40 ms ± 5 pour NTtime at Un 90 ms ± 5 pour NW

MN delay unitsTo eliminate circuit-breaker nuisance tripping during short voltage dips, operation ofthe MN release can be delayed. This function is achieved by adding an externaldelay unit in the MN voltage-release circuit. Two versions are available, adjustableand non-adjustable.characteristics

power supply non-adjustable 100/130 - 200/250V AC 50-60 Hz /DC adjustable 48/60 - 100/130 - 200/250 - 380/480operating threshold opening 0.35 to 0.7 Un

closing 0.85 Unconsumption (VA or W) pick-up: 200 hold: 4.5circuit-breaker response non-adjustable 0.25 stime at Un adjustable 0.5 s - 0.9 s - 1.5 s - 3 s

openingorder

D2

D1

MN

delayedopeningorder

instantaneousopeningorder

time delayunit

MN

D2

D1

10 12

3 6

openingorder

C12

C11

MX2

E46

043

MX or MN voltage release

0564

58

Remote tripping

E46

553

E46

554

0564

21

BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5943

Page 17: Functions Communication and characteristics COM option ... breaker_files...31 Masterpact Schneider Electric Modbus The Modbus RS485 (JBus) system is an open bus on which communicating

Masterpact Schneider Electric44

0564

6305

6464

E47

535

0168

19

Auxiliary terminal shield (CB)Optional equipment mounted on the craddle, the shield prevents access to theterminal block of the electrical auxiliaries.

Operation counter (CDM)The operation counter sums the number of operating cycles and is visible on thefront panel. It is compatible with manual and electrical control functions.

Escutcheon (CDP)Optional equipment mounted on the door of the cubicle, the escutcheon increasesthe degree of protection to IP 40 (circuit breaker installed free standing: IP30) .It is available in fixed and drawout versions.

Blanking plate (OP) for escutcheonUsed with the escutcheon, this option closes off the door cut-out of a cubicle notyet equipped with a device. It may be used with the escutcheon for both fixed anddrawout devices.

Transparent cover (CP) for escutcheonOptional equipment mounted on the escutcheon, the cover is hinged and securedby a screw. It increases the degree of protection to IP 54, IK10. It adapts to bothfixed and drawout devices.

AccessoriesFunctionsand characteristics

Transparent cover (CP) forEscutcheon

Escutcheon (CDP) with blanking plate

BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5944

Page 18: Functions Communication and characteristics COM option ... breaker_files...31 Masterpact Schneider Electric Modbus The Modbus RS485 (JBus) system is an open bus on which communicating

Masterpact Schneider Electric45

BTP207E-20300-auxiliaries.pm6 15/05/01, 15:5945