  • FRL700

    LCD Repeater Panel

    Installation and Commissioning Manual Revision 1E: Dec 2003

  • TRADEMARK ACKNOWLEDGEMENT

    The following are trademarks of Echelon Corporation, registered in the United States of America and other countries:

    Echelon; Lon; LonWorks; LonTalk; Neuron

    SAFETY

    To ensure safe operation and to keep the product safe, the information, cautions and warnings in this manual must be heeded. Failure to comply with the precautions or with specific warnings elsewhere in this manual violates the safety standard of design, manufacture and intended use of this product. The manufacturer assumes no liability for the customers failure to comply with these requirements

    Aritech is a GE Interlogix brand.

    www.aritech.com

    COPYRIGHT 2003 GE Interlogix B.V.. All rights reserved. GE Interlogix B.V. grants the right to reprint this manual for internal use only. GEInterlogix B.V. reserves the right to change information without notice.

  • CONTENTS

    1. Introduction ...................................................................................................................................................................2 2. General information .....................................................................................................................................................2 3. Technical specifications ..............................................................................................................................................2

    3.1. LCD Screen, indicators, control keys........................................................................................................................................2 3.2. Communication ports .....................................................................................................................................................................2 3.3. Power supply characteristics ......................................................................................................................................................2 3.4. Environmental ....................................................................................................................................................................................2 3.5. Physical Dimensions........................................................................................................................................................................2

    4. Mounting the fire brigade panel ................................................................................................................................3 4.1. Mounting instruction .......................................................................................................................................................................3 4.2. Internal layout ....................................................................................................................................................................................4

    5. Connecting to the fire panel .......................................................................................................................................5 5.1. Connecting to a FP2000-series fire panel .............................................................................................................................5 5.2. Connecting to a FP1100/1200-series fire panel.................................................................................................................6 5.3. Suitable types of cable ...................................................................................................................................................................6

    6. Functional description .................................................................................................................................................7 7. Settings and selections................................................................................................................................................8

    7.1. Language selection..........................................................................................................................................................................8 7.2. Language inserts...............................................................................................................................................................................8

    8. Commissioning a FRL700.............................................................................................................................................8 8.1. Before switching on .........................................................................................................................................................................8 8.2. Procedure for switching on ..........................................................................................................................................................8

    LIST OF FIGURES

    Figure 1: Mounting instruction .......................................................................................................................................................................3 Figure 2: Dimensions ..........................................................................................................................................................................................4 Figure 3: Internal layout ....................................................................................................................................................................................4 Figure 4: Connecting to a FP2000.................................................................................................................................................................5 Figure 5: Connecting to a FP1100/1200....................................................................................................................................................6 Figure 6: Panel layout.........................................................................................................................................................................................7

    1

  • 1. INTRODUCTION

    This manual explains how to carry out the installation and commissioning of the FRL700 LCD repeater panel.

    Please note that the manual is intended as a guide only and is not to be used to replace any local building and/or wiring codes.

    2. GENERAL INFORMATION

    The FRL700 LCD repeater panel is meant to repeat part of the FP2000/FP1200-series fire panels information. Some controls can be carried out from the FRL700 as well.

    The information and controls are those required by the Swedish standard SS3654 (see panel layout for further detail).

    ! WARNING! This is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.

    3. TECHNICAL SPECIFICATIONS

    3.1. LCD Screen, indicators, control keys See panel layout.

    3.2. Communication ports 1 x LonWorks port for connection to the FP2000/FP1200 panel (1.5 km maximum).

    3.3. Power supply characteristics Input: 10-30 VDC

    Max. current consumption: 100 mA @ 10V

    3.4. Environmental Enclosure protection: IP54

    Temperature:

    Operation: (-5 to +40) C

    Storage: (-20 to +60) C

    3.5. Physical Dimensions The overall dimensions are: Width: 320mm

    Height: 240mm

    Depth: 60 mm

    The total panel weight is 1.5 kg

    2

  • 4. MOUNTING THE FIRE BRIGADE PANEL

    4.1. Mounting instruction Figure 1: Mounting ins uction tr

    # Description 1 4mm diameter Mounting screws (3 off) 2 20 mm diameter cable entry (4 off) 3 Earth stud 4 Cable fastening hook / Cable tie (3 off) 5 7 mm diameter mounting holes (3 off) 6 Front cover mounting screws (2 off) 7 Front panel 8 Front cover 9 Base of cabinet

    The cables must be fastened to the cabinet by the means of the cable ties supplied. Use appropriate cable glands on all cable entries.

    The panel must be connected to earth using the earth stud (3).

    3

  • Figure 2: Dimensions

    4.2. Internal layout Figure 3: Internal layout

    # Item Name Description 1 Slots For the language inserts 2 Connector P7 From top to bottom:

    P7.1: Earth P7.2: Not used P7.3: Ground input P7.4: 24V input P7.5: Data (polarity insensitive) P7.6: Data (polarity insensitive)

    3a Switch Configuration Press once for installation (see fire panels installation manual) Press twice to display the general information screen Press 3 times to display the keyboard-test screen

    3b LED Service This LED flashes in case of installation fault: 1 second ON 1 second OFF: the item is in the unconfigured state. 2 seconds ON 2 seconds OFF: the FRL cannot establish

    communication with the Fire Panel

    4

  • 5. CONNECTING TO THE FIRE PANEL

    5.1. Connecting to a FP2000-series fire panel Figure 4: Connecting to a FP2000

    P7.4 (24V) AUX24+

    P7.3 (GND) AUX24-

    P7.5 DATA*

    P7.6 DATA*

    # Description 1 Connect to DOL supply (AUX24) 2 Connect to LON interface (data)

    * The data lines are polarity insensitive.

    Termination resistors must be mounted on both ends of the communication line.

    On the FRL700: Set jumper J2 in ON position.

    On the FP2000: For detail regarding termination on the FP2000 / FP1200 refer to the LON2000 Installation Manual.

    5

  • 5.2. Connecting to a FP1100/1200-series fire panel Figure 5: Connecting to a FP1100/1200

    P7.4 (24V) AUX+

    P7.3 (GND) AUX-

    P7.5 DATA*

    P7.6 DATA*

    # Description 1 Connect to Charger board (AUX) 2 Connect to LON interface (data)

    * The data lines are polarity insensitive.

    Termination resistors must be mounted on both ends of the communication line.

    On the FRL700: Set jumper J2 in ON position.

    On the FP1100/1200: For detail regarding termination on the FP2000 / FP1200 refer to the LON2000 Installation Manual.

    5.3. Suitable types of cable CAT5 or CAT6 FTP cable is recommended for the data bus. Belden 9841 (RS485) is also suitable.

    Where the system contains only the master and one slave device most types of twisted pair cable can be used, provided the total return-resistance doesnt exceed 100 ohms. If the system may be expanded in the future then the cables specified in the paragraph above should be used.

    For the power cable, care must be taken that the voltage on the devices connector is still within specification. The cables may not exceed 900m.

    Example:

    Length Recommended cable type 300m 0.4 mm diameter (AWG 26) 500m 0.5 mm diameter (AWG 24)- 800m 0.6 mm diameter (AWG 24) 900m 0.7 mm diameter (AWG 22)

    6

  • 6. FUNCTIONAL DESCRIPTION

    Figure 6: Panel layout

    # Item Name Description 1 LCD screen & insert at top

    of LCD screen Detail information Show details on the fire alarms. In case of several alarms (LEDs (6) turns

    on), scrolling to next alarm is possible by the means of (7). 2 Red LED x 3 General Alarm The LEDs turn ON-flashing each time a fire-alarm occurs on the fire

    panel. Turning the key (8) enables the FRL700 controls and the flashing turns to steady. The LEDs flash again when a new alarm occurs. The LEDs turn OFF when the fire panel is reset.

    3 Amber LED Fault The LED is ON when there is a fault on the fire panel. The buzzer (11) will be activated intermittently. If the buzzer was silenced by pressing (10) and the fault is still present on the system, subsequent faults will not reactivate the buzzer. Any fire-alarm will override the fault.

    4 Amber LED Functions disabled The LED is ON when a least one function of the fire panel is disabled 5 Green LED Power The LED is ON when the device is powered. 6 Red LED x 2 Several alarms The LED is ON when there are several fire alarms. 7 Blue push-button Next alarm The screen (1) will display the next alarm when the user presses this

    button. If the button is pressed while the last alarm is shown, the screen will show the first alarm again. If this button is not pressed during 15 seconds, the screen also switches back to the first alarm.

    8 Key-switch Enable The user has to activate this switch by the means of a firemans key to enable the push-buttons (9) and (10). The enable position is entered when the key is turned clockwise. The key cant be removed in the enable position.

    9 Grey push-button Reset Resets the fire panel (fire alarm and fault conditions). If one or more alarms remain after the reset, the buzzer will resound and the device will re-enter the fire alarm condition. This function can only be carried out when the key-switch (8) is in the enable position.

    9 Grey push-button LED test When the key-switch (8) is in the disabled position, pushing of the grey push-button will perform an LED test.

    10 Grey push-button Silence alarm device(s) Stops the fire brigade panels buzzer and the fire panels alarm devices. This function can only be carried out when the key-switch (8) is in the enable position.

    10 Grey push-button Silence buzzer When the key-switch (8) is in the disabled position, pressing of the grey push-button will stop the Fire Brigade panels buzzer.

    11 Buzzer Alarm The buzzer turns ON each time there is a new alarm or intermittently during the first fault, and turns OFF when (10) is pressed or (8) is turned.

    12 Spare field Alarm code The installer may indicate here the alarm receivers alarm code, by writing on the internal paper insert.

    7

  • 7. SETTINGS AND SELECTIONS

    7.1. Language selection Language has to be Software-Selected in the FP2000 / FP1200.

    Please refer to the FP2000 / FP1200 Installation and commissioning Manuals.

    7.2. Language inserts Inserts are available in several languages. Carefully slip the selected language inserts into the appropriated slots on the panels front plate.

    8. COMMISSIONING A FRL700

    8.1. Before switching on 1. Visually check the fire brigade panel for any damage that might have occurred during

    installation. In particular, check for loose pieces that could have fallen into the unit.

    2. Check that all harnesses are securely plugged into the correct plug positions on the printed circuit boards.

    3. Ensure that there is NO loose bare wiring in the fire brigade panel cabinet. This can damage the unit.

    8.2. Procedure for switching on 4. Switch the mains power on at the fire panels power supply. The green Operation or

    Power LED on the FRL700 turns ON.

    5. Follow the procedure for installation of LON devices for the Fire Panel to which you are connecting the FRL700. This will be in the Fire Panels (e.g. FP2000) manuals.

    6. If the device is already installed, the message TOTAL ALARMS : 000 will appear. If the device is not installed, the following message will be displayed:

    FBP700 Ver.: xx.xx

    No communication

    Press any key

    For SERVICE

    Where xx.xx is the revision of firmware in the panel.

    7. Press the configuration switch. All front buttons react like the configuration switch if there is no communication with the main panel.

    8. The Service LED, situated on the back of the front panel, will turn OFF if communication is established. If no communication is established to the main panel the Service LED will continue to blink slowly.

    9. If communication to the FRL700 can still not be established, ensure that the LON- bus is correctly terminated and that no tree-topology or T-offs are used. (Refer to section 5). Measure the resistance of the communication lines; if both ends of the bus are terminated a value of 60 ohm should be measured. If only one side is terminated a value of 120 ohm will be measured

    8

  • 10. If communication to the FRL700 can still not be established and another FRL700 panel already installed correctly is available, the following can be done to determine if the communication line is working properly:

    Disconnect the installed FRL700 from its position. Connect the communication wire of the new position to the previously installed

    FRL700.

    If the panel starts up correctly and establishes communication the communication line is working properly and the FRL700 is faulty. The faulty unit must then be returned to the supplier.

    9

  • 10

    IntroductionGeneral informationTechnical specificationsLCD Screen, indicators, control keysCommunication portsPower supply characteristicsEnvironmentalPhysical Dimensions

    Mounting the fire brigade panelMounting instructionInternal layout

    Connecting to the fire panelConnecting to a FP2000-series fire panelConnecting to a FP1100/1200-series fire panelSuitable types of cable

    Functional descriptionSettings and selectionsLanguage selectionLanguage inserts

    Commissioning a FRL700Before switching onProcedure for switching on