Frankfurt (Germany), 6-9 June 2011 Irina Melnik – the Netherlands – Session S2 – 0665...
-
Upload
aron-homer-johns -
Category
Documents
-
view
217 -
download
0
description
Transcript of Frankfurt (Germany), 6-9 June 2011 Irina Melnik – the Netherlands – Session S2 – 0665...
Frankfurt (Germany), 6-9 June 2011
Irina Melnik – the Netherlands – Session S2 – 0665
Intelligent Distribution Substation improves power quality
Frankfurt (Germany), 6-9 June 2011
Need for new technologies
Monitoring and control New technologies
Changes in power flows Larger voltage variations
Uncertainty for planning Complex grid operation
Fluctuating loads Distributed generation
MV
LV
Load
Power
MV
LV
Load
Power
PowerPowerMV
LVMicroCHP PV
MicroCHP
MicroCHP
Generation
PV
Load
MV
LVMicroCHP
MicroCHP PV
MicroCHP
MicroCHP
MicroCHP
MicroCHP
Generation
PV
Load
Frankfurt (Germany), 6-9 June 2011
Intelligent distribution substation (IntDS)
Additional functions of the IntDS: Monitoring Control Improving Power Quality
Developed by a consortium of Dutch industries
Installed and tested in the grid of DSO Alliander
Frankfurt (Germany), 6-9 June 2011
“Intelligent” components of IntDS
Electricity storage systemwith bidirectional inverter
Measurement system
Smart Transformer
Frankfurt (Germany), 6-9 June 2011
IntDS implementation
District with large amount ofmicro Combined Heat Powerat customers
Frankfurt (Germany), 6-9 June 2011
Test program
Voltage control Reduction of harmonic distortion Reduction of flicker Mitigation of voltage dips
Power Quality improvement by the IntDS:
Frankfurt (Germany), 6-9 June 2011
Voltage control
Performed by Smart Transformer:
Electronic tap changer ensuresa constant voltage level on the LV rail of the IntDS.
The voltage control set-pointhas to be determined to achievethe optimal voltage level on PCC’sof all LV customers.
Smart Transformer
Frankfurt (Germany), 6-9 June 2011
Voltage control – test resultsU avgU maxU min
LV bus-bar
1 2 3
control no control
LV customer
1 2 3
control no control
Frankfurt (Germany), 6-9 June 2011
Harmonic distortion reduction
Performed by ESI(Electricity storage inverter) :
Resistive harmonic damping
Passive harmonic dampingThe filter capacitors of the ESI take part in the filtering of harmonics. Electricity storage system
with bidirectional inverter
Frankfurt (Germany), 6-9 June 2011
Harmonic distortion reduction – test resultsH03 maxH05 maxH07 maxTHD max
LV bus-bar control nono control
LV customer controlno control no
Frankfurt (Germany), 6-9 June 2011
Voltage dips mitigation
Can be performed by:the Smart Transformerthe ESI (Electricity storage inverter)
Voltage dips occur only a few times per yearon an LV bus-bar of Dutch distribution substations.That’s why this functionality is not actively tested.
Frankfurt (Germany), 6-9 June 2011
Flicker reduction (LV side)
Performed by:
The electronic tap changer of the Smart Transformer
The flicker reduction control of the bidirectional inverter (ESI) of the storage system.
Frankfurt (Germany), 6-9 June 2011
Flicker reduction – test resultsPlt avgPst avgPlt maxPst max
LV bus-bar no control
LV customer no control
Frankfurt (Germany), 6-9 June 2011
Conclusions The Intelligent substation has proved to be safe in operation.
The first field test results demonstrate a significant reduction of voltage variations, harmonic and THD levels both at the LV bus-bar of the IntDS and at the LV customers.
Further metering and test programs will be performed to set optimal set-points for control equipments.
The proved principles can be used for area’s with high levels of PQ distortions.
Irina Melnik – the Netherlands – Session S2 – 0665