03.11.2011 May 2011 Advanced Training © BOGE KOMPRESSOREN 1 BOGE air. The air to work. Focus Controller

description

focus

Transcript of Focus PPT

Page 1: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 1

BOGE air. The air to work.

Focus Controller

Page 2: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 2

Focus Controller

• Overview of Capabilities

• Focus Hardware

• Focus Interface

• Parameters

• Faults

• Base Load Switching

• Leak Detection

• Software Updates

• Modules

Page 3: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 3

Focus Basics

General Capabilities

All Ratio Capabilities, Plus:

• Control of 1-4 Compressors via Integrated ModBus

• Control of VFD Setpoint in SF Machines

• Efficiency Display

• Leak Detection Mode

• Clock/Sequencer Function

• More User-Friendly Interface

• Two Remote-Switchable Pressure Profiles

• Multiple Add-On Modules to Expand Capabilities Further

Page 4: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 4

Focus Basics

Focus Hardware

Focus TAN

Display Module

Page 5: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 5

Focus Basics

Focus HardwareFocus Base Module

Page 6: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 6

Focus Basics

Focus HardwareAdditional Modules

Page 7: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 7

Focus Controller

Focus Interface

Net/Line Pressure

Compressor Status

Air End

Temperature

Press Right Arrow for Next Screen

Page 8: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 8

Focus Controller

Focus Interface

Net/Line Pressure

Press Right Arrow for Next Screen

Sump/System

Pressure

Compressor Status

Page 9: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 9

Focus Controller

Focus Interface

Press Right Arrow for Next Screen

Hours Until Motor

Servicing Due

Hours Until

Compressor

Servicing Due

Load Cycles Until

Separator

Servicing Due

Battery Voltage

>2.8v is Normal

Page 10: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 10

Focus Controller

Focus Interface

Right Arrow for Next Screen

Total Hours

Idle Hours

Efficiency

Load Cycles

Up Arrow for Leakage Monitor

Page 11: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 11

Focus Controller

Focus Interface

Press Right Arrow for Next Screen

ModBus Status

Key Switch Status

Release Type

Auto Restart

After Power Loss

Delay

Page 12: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 12

Focus Controller

Focus Interface

Press Right Arrow for Next Screen

Pressure Range

Net Pressure Timer Status

Sequencer Status

Page 13: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 13

Focus Controller

Focus Interface

Press Right Arrow for Next Screen

Hold Enter to

Change Date/Time

Page 14: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 14

Focus Controller

Focus Interface

Software Version

Press Right Arrow

for Main Screen

Press Enter for

Code Entry

Page 15: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 15

Focus Controller

Focus Interface

Use Navi Keys to

Enter Access Code

Press Enter

Page 16: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 16

Focus Controller

Focus Interface

Parameter Access

Page 17: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 17

Focus Controller

Focus InterfaceParameter Access

Page 18: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 18

Focus Controller

Focus Parameters

Parameter List in Functional Description

Page 19: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 19

Focus Controller

Focus Faults

Fault Table

Page 20: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 20

FOCUS base load switch (BLS)

FOCUS base load switch

- Integrated BLS for up to 4 machines (via RS485 / optional relay module)

- Modular expendability (max. 5 additional modules)

Page 21: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 21

Focus Controller

Base Load Switching

RS485 RS485 RS485

BLS is Intended to Sequence/Cycle 4 Machines of the Same or Similar Size

Page 22: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 22

Focus Controller

Base Load Switching

51 GND

52 RS485 +

53 RS485 -

120ohm Termination Resistor Jumper

Wiring

Page 23: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 23

Base load switch only by RS 485

FOCUS

Bus address

“0”

MASTER

FOCUS

Bus address

“2”

SLAVE

Bus address

“3”

SLAVE

Bus address

“4”

SLAVE

+ RS485 Interface

RATIO

+ RS485 Interface

RATIO

3 3 3

FOCUS base load switch (BLS)

Page 24: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 24

Contact

Base load switch only by contact (Relay module)

FOCUS

+ 3x Relay module

RATIO BASIC

Relay address

“2”

SLAVE

Relay address

“3”

SLAVE

Relay address

“4”

SLAVE

Output release Output release Output release

2 22

FOCUS base load switch (BLS)

Other

brand

Page 25: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 25

2 23

Base load switch with combination of contact and RS 485

Contact

Bus address

“0”

MASTER

FOCUS

+ 2x Relay module

FOCUS

RS 485

Bus address

“2”

SLAVE

Relay address

“3”

SLAVE

Relay address

“4”

SLAVE

FOCUS base load switch (BLS)

Autotronic

Output release

Other

brand

Output release

Page 26: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 26

- A differential pressure between pressure transducers of machines and BLS must be

- considered during adjustment of machine pressure settings

9.0 bar

8.0 bar

- The cut in and cut off pressures of the compressors must be above the values of the BLS

Pressure switch points

compressors

Pressure switch points

BLS

8.3 bar

9.5 bar

C 3

C 3

8.5 bar

9.6 bar

C 2

C 2

8.7 bar

9.7 bar

C 1

C 1

- The machine switching points of the machines should be cascaded

Example parameters for base load switch

Page 27: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 27

8.0 bar

9.0 bar

Cut in and cut off characteristic of the BLS

•Priority 1

•Priority 2

•Priority 3

•Priority 4

Priority 1•

Priority 4•

Priority 2•Priority 3•

Example parameters for base load switch

Page 28: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 28

FOCUS FOCUS

+ RS485 Interface

RATIO

+ RS485 Interface

RATIO

- The RATIO controller must be equipped with the RS 485 BUS Interface

RS485

- The machines need to be connected from controller to controller

- Connection sequence in any direction is possible - the Bus address defines the Compressor

- At great cable length a resistor (120 Ω) must be set on both ends of the line

Example with only bus-compatible controllers3 3 3

Example parameters for base load switch

- The pressure control must be active on all „Slave-Machines“ (Bridge on X2:18/19)

Page 29: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 29

BLS(Priority change based on hours)

by only RS485 connection with FOCUS

Requirements:

- 4 Machines connected (2x FOCUS and 2x RATIO)

- all machines on the same or similar size

- 7 hours changeover

Example parameters for base load switch

- Pressure range of installation 8bar - 9bar

Page 30: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 30

Number of connected machines

base-change cycle in hours

P070 4

P071 7hrs

RS485

P050 0

P051 9600

P052 8E1

FOCUS

Cut off pressure Operating range of

Cut in pressure base load switch

Parameter settings of FOCUS “Master” machine

MASTER SLAVE SLAVE SLAVE

RATIO

+Interface

RATIO

+InterfaceFOCUS

3 33

Example parameters for base load switch

P012 9.0bar

P013 8.0bar

Modbus address MASTER = „ 0 „

Modbus baud rate MASTER = SLAVE

Modbus communication parameter MASTER = SLAVE

Page 31: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 31

RS485

FOCUS

P063 2

P050 2

P051 9600

P052 8E1

P012 9.3bar

P013 8.3bar

Cut off pressure Operating range for

Cut in pressure failure of BLS

Modbus address SLAVE = „ 2 „

Modbus baud rate MASTER = SLAVE

Modbus communication parameter MASTER = SLAVE

External release via Bus MASTER controls SLAVE

Parameter settings of FOCUS “Slave” machine

SLAVE

RATIO

+Interface

RATIO

+InterfaceFOCUS

3 3

3

Example parameters for base load switch

Page 32: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 32

CODE 2

210

CODE 3

830 96

8E1

Cut off pressure Operating range for

Cut in pressure failure of BLS

Parameter settings of RATIO “Slave” machine

Modbus address SLAVE = „ 3 „

Modbus baud rate MASTER = SLAVE

Modbus communication parameter MASTER = SLAVE

External release via Bus MASTER controls SLAVE

SLAVE

RS485

FOCUS FOCUS RATIO

+InterfaceRATIO

+ RS485 Interface

RATIO

3

33

Example parameters for base load switch

CODE 9.5bar

360 8.5bar

Page 33: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 33

CODE 2

210

CODE 4

830 96

8E1

Cut off pressure Operating range for

Cut in pressure failure of BLS

SLAVE

Parameter settings of RATIO “Slave” machine

RS485

RATIO

+Interface

FOCUS FOCUS

RATIO

+ RS485 Interface

RATIO

Modbus address SLAVE = „ 4 „

Modbus baud rate MASTER = SLAVE

Modbus communication parameter MASTER = SLAVE

External release via Bus MASTER controls SLAVE3

3

3

Example parameters for base load switch

CODE 9.7bar

360 8.7bar

Page 34: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 34

Code 360

9.5bar / 8.5bar

Code 830

3 / 96 / 8E1

Code 210

2

P012 9.3bar

P013 8.3bar

P050 2

P051 9600

P052 8E1

P063 2

P012 9.0bar

P013 8.0bar

P050 0

P051 9600

P052 8E1

P070 4

P071 7hrs

FOCUS FOCUS

+ RS485 Interface

RATIO

+ RS485 Interface

RATIO

Code 360

9.7bar / 8.7bar

Code 830

4 / 96 / 8E1

Code 210

2

RS485

3 33

Example parameters for base load switch

Page 35: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 35

- all machines on the same or similar size

- 23 hours changeover

- Pressure range of installation 8bar - 9bar

- 4 machines connected (1x FOCUS, 1x RATIO, 1x BASIC

and 1x Other brand controller)

Example parameters for base load switch

BLS(Priority change based on hours)

by only relay module connection with FOCUS

Requirements:

Page 36: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 36

Contact

FOCUS

+ 3x Relay module

RATIO BASIC Other

brand

Output release Output release

- The FOCUS Master machine must be equipped with the relay modules for the

- connected compressors

Output release

Signal line

- Every single relay module has to be connected to the output release of the machines

- Every single relay module must be configured with it’s own rotary switch

- The cable length should not be longer then 50m

2 22

Example parameters for base load switch

Page 37: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 37

MASTER

Parameter settings of FOCUS “Master” machine

FOCUS

RATIO Other

brandBASIC

2 22

Contact

Example parameters for base load switch

P012 9.0bar

P013 8.0bar

Cut off pressure Operating range of

Cut in pressure base load switch

P070 4

P071 23hrs

Number of connected machines

base-change cycle in hours

Page 38: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 38

FOCUS

SLAVE

Parameter settings of RATIO “Slave” machine

RATIO

BASIC

The Relay module in the switch cabinet of the “master machine”, has to be configured to „2“.

CODE 9.3bar

360 8.3bar

Cut off pressure Operating range for

Cut in pressure failure of BLS

CODE 1

210

External release via contact MASTER controls SLAVE

2 2

2Contact

Example parameters for base load switch

Other

brand

Page 39: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 39

The Relay module in the switch cabinet of the “master machine”, has to be configured to „3“.

Parameter settings of BASIC “Slave” machine

SLAVE

RATIOFOCUS

BASIC

2

22

Contact

Example parameters for base load switch

CODE 1

210

External release via contact MASTER controls SLAVE

CODE 9.5bar

360 8.5bar

Cut off pressure Operating range for

Cut in pressure failure of BLS

Other

brand

Page 40: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 40

The Relay module in the switch cabinet of the “master machine”, has to be configured to „4“.

9.7bar

8.7bar

Cut off pressure Operating range for

Cut in pressure failure of BLS

External release via contact MASTER controls SLAVE

SLAVE

Parameter settings of other brand “Slave” machine

RATIOFOCUS BASIC

Other

brand

2

2

2

Contact

Example parameters for base load switch

Page 41: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 41

FOCUS

+ 3x Relay module

RATIO BASIC Other

brand

Signal line

Code 360:

9.5bar / 8.5bar

Code 210:

1

Code 360:

9.3bar / 8.3bar

Code 210:

1

P012 9.0bar

P013 8.0bar

P070 4

P071 23hrs

Pressure settings:

9.7bar / 8.7bar

Output release:

active2 22

Contact

Example parameters for base load switch

Output release Output release Output release

Page 42: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 42

FOCUS

+ 3x Relay module

RATIO BASIC Other

brand

2 22

Contact

Example parameters for base load switch

Output releaseOutput release Output release

Settings of rotary

switches of relay

modules

Page 43: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 43

BLS(Clock switch based priority change)

by combination of contact and RS485

with FOCUS

Requirements:

- 4 machines connected ( 1x FOCUS 55 kW, 1x FOCUS 37 kW,

- 1x Autotronic 22 kW und 1x “other brand” 37 kW

- Working time: 6.00Uhr to 19.30Uhr

Example parameters for base load switch

Page 44: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 44

- Pressure range of installation 10.5bar - 11.5bar

- The 55 kW machine is frequency controlled

- The 55 kW compressor is base load machine

- Both 37 kW compressors are peak load machines

- The 22 kW compressor is a reserve machine

Example parameters for base load switch

BLS(Clock switch based priority change)

by combination of contact and RS485

with FOCUS

Page 45: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 45

RS485

- The FOCUS must be equipped with two relay modules

FOCUS

+ 2x Relay module

FOCUS

- The FOCUS machines are connected from controller to controller

- On great cable length resistor terminator (120 Ω) has to be set on the end of the bus

- Every single relay module must be configured with it’s own rotary switch

- Every single relay module has to be connected to the output release of the machines

- The cable length should not be longer then 50m from relay module to machine controller2 23

Contact

Example parameters for base load switch

Autotronic

Output release

Other

brand

Output release

- The pressure control must be active on all „Slave-Machines“ (Bridge on X2:18/19)

Page 46: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 46

RS485

MASTER

FOCUS

Parameter settings of FOCUS “Master” machine

BASICAuto-

tronic

Other

brandFOCUS

FOCUS

2 23

Contact

Example parameters for base load switch

Number of connected machines

base-change cycle = “0” deactivates BLS based on hours

P070 4

P071 0hrs

P050 0

P051 9600

P052 8E1

Cut off pressure Operating range of

Cut in pressure base load switch

P012 11.5bar

P013 10,5bar

Modbus address MASTER = „ 0 „

Modbus baud rate MASTER = SLAVE

Modbus communication parameter MASTER = SLAVE

Page 47: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 47

• • •

Canal A

MO 6:00

1243

Canal B

MO 19:30

3241

Channel A

MO 6:00

1243

Channel B

MO 19:30

3241

Canal D

DI 19:30

3421

Canal C

DI 6:00

1423

Channel C

TU 6:00

1423

Channel D

TU 19:30

3421

Canal I

FR 6:00

1423

Channel I

FR 6:00

1423

Canal J

FR 11:00

1243

Channel J

FR 11:00

1243

Clock switch settings of FOCUS “Master” machine

RS485

MASTER

FOCUS BASICAuto-

tronic

Other

brandFOCUS

FOCUS

2 23

Contact

Example parameters for base load switch

Canal K

FR 16:00

3241

Channel K

FR 16:00

3241

Canal K

FR 16:00

0000

Channel K

FR 16:00

0000

Page 48: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 48

SLAVE

Parameter settings of FOCUS “Slave” machine

FOCUS BASICAuto-

tronic

Other

brand

RS485FOCUS

2 2

3Contact

Example parameters for base load switch

External release via bus MASTER controls SLAVEP063 2

P050 2

P051 9600

P052 8E1

Modbus address MASTER = „ 2 „

Modbus baud rate MASTER = SLAVE

Modbus communication parameter MASTER = SLAVE

P012 11.5bar

P013 10,5bar

Cut off pressure Operating range for

Cut in pressure failure of BLS

Page 49: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 49

Contact to

pressure switch

External release via Contact MASTER controls SLAVE

SLAVE

Parameter settings of Autotronic “Slave” machine

FOCUSFOCUS Other

brand

RS485Auto-

tronic

2

23

Contact

Example parameters for base load switch

The Relay module in the switch cabinet of the “master machine”, has to be configured to „3“.

PS- 12bar

set. 11bar

Cut off pressure Operating range for

Cut in pressure failure of BLS

Page 50: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 50

FOCUS

External release via Contact MASTER controls SLAVE

SLAVE

Parameter settings of other brand “Slave” machine

BASICAuto-

tronicFOCUS

RS485Other

brand

2

2

3

Contact

Example parameters for base load switch

The Relay module in the switch cabinet of the “master machine”, has to be configured to „4“.

12.2bar

11.2bar

Cut off pressure Operating range for

Cut in pressure failure of BLS

Page 51: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 51

Autotronic

Output release

Pressure settings:

12.2bar / 11.2bar

Output release:

active

Pressure switch

12bar / 11bar

Contact to

pressure switch

P012 11.8bar

P013 10.8bar

P050 2

P051 9600

P052 8E1

P063 2

P012 11.5bar

P013 10.5bar

P050 0

P051 9600

P052 8E1

P070 4

P071 0hrs

Contact

RS485

FOCUS

+ 2x Relay module

FOCUS

2 23

Example parameters for base load switch

Other

brand

Output release

Page 52: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 52

Example parameters for base load switch

Contact

RS485

FOCUS

+ 2x Relay module

FOCUS Autotronic

Output release

Settings of rotary

switches of relay

modules

2 23

Other

brand

Output release

Page 53: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 53

Focus Controller

Leak Detection (>v1.15 Only)

Single Measurement

Continuous

Measurement

Hours of Run Time

Used Only for Leaks

Page 54: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 54

Focus Controller

Leak Detection (v1.15 Only)

Conditions:

• All Plant Usage Must be Off

• Compressors Must be Enabled / Green

• These conditions must remain for 6 hours

Page 55: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 55

Focus Controller

Leak Detection (v1.15 Only)

Starting a Test:

1. Navigate to the Leak Detection Screen

2. Hold Enter for 2 secs, until “Le” starts flashing, then release Enter

3. Hold Enter for another 2 secs to initiate a 6hr test

4. After 6 hours, values will appear showing calculated wasted run

hours

5. The system will monitor in 6hr intervals, and will update the values if

a lower load period is detected

Page 56: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 56

Focus Controller

Leak Detection (v1.15 Only)

Faults:

• 9999 = Power Failure

• 9990 = Loss of “Ready” Status

Page 57: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 57

Focus Controller

Software Updates

Potential Damage to Focus Controller and PC

Follow Directions Exactly

NEVER Disconnect Flashing Cables With the Focus Energized

Page 58: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 58

Focus Controller

Software Updates

• Focus Flashing Device

and Serial Cable

Boge P/Ns:

659003101 & 681004805

• CS Manager +

• Laptop w/ Serial Port

Page 59: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 59

Focus Controller

Software Updates

Remove Power from the Focus –

the Screen Must Turn Off

Breaker 4F is Sufficient

Main Panel Disconnect is Safest

The E-Stop Will Not Power Down

the Focus

Page 60: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 60

Focus Controller

Software Updates

Connect Flash Device

Ground to Term 32

Connect the Flash Device

Cable to the Software

Update Port and the

Serial Cable to your PC

Disconnect the Digital

Outputs

Page 61: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 61

Focus Controller

Software Updates

Disconnect the

Transformer Ground

Power On the Focus

Controller

Page 62: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 62

Focus Controller

12

3

4 51. Restrict Selection

2. Identify

3. Ensure “Type” Turns

Green – Indicates Comm

4. Select Correct Program

and Version

5. Write to Flash

Page 63: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 63

Focus Controller

Red Indicates a Comm

Problem

Check Cables, Port

Settings, and Power

Page 64: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 64

Focus Controller

Software UpdatesWait for Flashing to Finish

Ignore Any Faults

De-energize the Focus

Wait 10 Seconds

Page 65: Focus PPT

03.11.2011May 2011 Advanced Training © BOGE KOMPRESSOREN 65

Focus Controller

Software UpdatesAfter Waiting 10 Seconds:

1. Disconnect the Flash

Cable from the Focus Base

2. Connect the Flash Cable to

the Focus TAN

3. Energize the Focus and

Repeat the CSM+ Process

4. De-Energize

5. Wait 10 Seconds

6. Disconnect All Flash

Cables, Reconnect

Transformer Ground