Location:
Engineer:Study Case: LF
12.5.0E
Page: 1
SN: ESPELTGAEC
Filename: practica1
Project: ETAP
Contract:
Date: 04-21-2014
Revision: Base
Config.: Normal
NoneLoad Diversity Factor:
DesignGeneration Category (1):
DesignLoading Category (1):
Load Flow Analysis
Electrical Transient Analyzer Program
Number of Buses:
Number of Branches:
1 0 2 3
1 0 0 1 0 0 2
TotalLoadV-Control
XFMR2 TotalTie PDImpedanceLine/CableReactor XFMR3
Swing
Maximum No. of Iteration:
System Frequency:
Unit System:
Project Filename:
Output Filename:
Precision of Solution:
Method of Solution: Adaptive Newton-Raphson Method
99
0.0001000
60.00 Hz
English
practica1
C:\Users\labctr\Desktop\flacal\practica1\flujo1.lfr
![Page 2: flujo1 - Complete.pdf](https://reader030.fdocuments.net/reader030/viewer/2022021219/55cf978b550346d033923cd7/html5/thumbnails/2.jpg)
7/18/2019 flujo1 - Complete.pdf
http://slidepdf.com/reader/full/flujo1-completepdf 2/12
Location:
Engineer:Study Case: LF
12.5.0E
Page: 2
SN: ESPELTGAEC
Filename: practica1
Project: ETAP
Contract:
Date: 04-21-2014
Revision: Base
Config.: Normal
Adjustments
Transformer Impedance:
Reactor Impedance:
Tolerance
Overload Heater Resistance:
Transmission Line Length:
Cable Length:
Temperature Correction
Transmission Line Resistance:
Cable Resistance:
Apply
Adjustments /Global
Individual
Percent
Apply
Adjustments
Individual
/Global Degree C
Individual
Individual
Individual
Individual
Yes
Yes
No
No
No
Yes
Yes
![Page 3: flujo1 - Complete.pdf](https://reader030.fdocuments.net/reader030/viewer/2022021219/55cf978b550346d033923cd7/html5/thumbnails/3.jpg)
7/18/2019 flujo1 - Complete.pdf
http://slidepdf.com/reader/full/flujo1-completepdf 3/12
Location:
Engineer:Study Case: LF
12.5.0E
Page: 3
SN: ESPELTGAEC
Filename: practica1
Project: ETAP
Contract:
Date: 04-21-2014
Revision: Base
Config.: Normal
Bus Input Data
Sub-sys
GenericConstant IConstant ZConstant kVAInitial VoltageBus
Mvar MWMvarMWMvar MWMvar MWAng.% Mag.kVID
Load
Bus1 1 0.0115.000 100.0
Bus2 1 0.013.200 100.0
Bus3 1 0.013.200 100.0 9.000 0.000
0.0000.000 9.000Total Number of Buses: 3 0.000 0.000 0.000 0.000 0.000
ID kV
Generation Bus
Sub-sysType
Voltage
% Mag. Angle MW Mvar Max Min
Generation Mvar Limits
% PF
Bus1 1Swing 0.0115.000 100.0
0.000 0.000
![Page 4: flujo1 - Complete.pdf](https://reader030.fdocuments.net/reader030/viewer/2022021219/55cf978b550346d033923cd7/html5/thumbnails/4.jpg)
7/18/2019 flujo1 - Complete.pdf
http://slidepdf.com/reader/full/flujo1-completepdf 4/12
Location:
Engineer:Study Case: LF
12.5.0E
Page: 4
SN: ESPELTGAEC
Filename: practica1
Project: ETAP
Contract:
Date: 04-21-2014
Revision: Base
Config.: Normal
Line/Cable Input Data
ID Library Size T (°C)
Line/Cable
Ohms or Siemens/1000 ft per Conductor (Cable) or per Phase (Line)
Adj. (ft) #/Phase% Tol.
Length
YR X
Cable1 15NCUS3 3/0 328.1 1 0.089655 0.036000750.0
Line / Cable resistances are listed at the specified temperatures.
![Page 5: flujo1 - Complete.pdf](https://reader030.fdocuments.net/reader030/viewer/2022021219/55cf978b550346d033923cd7/html5/thumbnails/5.jpg)
7/18/2019 flujo1 - Complete.pdf
http://slidepdf.com/reader/full/flujo1-completepdf 5/12
Location:
Engineer:Study Case: LF
12.5.0E
Page: 5
SN: ESPELTGAEC
Filename: practica1
Project: ETAP
Contract:
Date: 04-21-2014
Revision: Base
Config.: Normal
2-Winding Transformer Input Data
ID MVA Prim. kV Sec. kV % Z1 X1/R1 Prim. Sec.
Transformer % Tap Setting
% Tol.
Rating Z Variation
+ 5% - 5%
Phase Shift
Type Angle% Z
Adjusted
Phase
T1 4.80 23.70 0 000 0 0.0004.80003-Phase Dyn25.000 115.000 13.200
![Page 6: flujo1 - Complete.pdf](https://reader030.fdocuments.net/reader030/viewer/2022021219/55cf978b550346d033923cd7/html5/thumbnails/6.jpg)
7/18/2019 flujo1 - Complete.pdf
http://slidepdf.com/reader/full/flujo1-completepdf 6/12
Location:
Engineer:Study Case: LF
12.5.0E
Page: 6
SN: ESPELTGAEC
Filename: practica1
Project: ETAP
Contract:
Date: 04-21-2014
Revision: Base
Config.: Normal
Branch Connections
ID From Bus To Bus R X ZType
CKT/Branch % Impedance, Pos. Seq., 100 MVA BaseConnected Bus ID
Y
T1 Bus1 0.81 19.18 19.20Bus22W XFMR
Cable1 Bus2 1.69 0.68 1.82Bus3Cable
![Page 7: flujo1 - Complete.pdf](https://reader030.fdocuments.net/reader030/viewer/2022021219/55cf978b550346d033923cd7/html5/thumbnails/7.jpg)
7/18/2019 flujo1 - Complete.pdf
http://slidepdf.com/reader/full/flujo1-completepdf 7/12
Location:
Engineer:Study Case: LF
12.5.0E
Page: 7
SN: ESPELTGAEC
Filename: practica1
Project: ETAP
Contract:
Date: 04-21-2014
Revision: Base
Config.: Normal
LOAD FLOW REPORT
Bus
ID kV
Voltage
Ang.% Mag.
Generation
MW Mvar
Load
MW Mvar
Load Flow
MW Mvar AmpID %PF
XFMR
%Tap
Bus1* 115.000 0.0100.000 0.1608.977 Bus2 8.977 0.160 45.1 100.00 0
Bus2 13.200 -1.099.911 Bus3 8.970 0.005 392.7 100.00 0 0 0
Bus1 -8.970 -0.005 392.7 100.0
Bus3 13.200 -1.099.760 0.0008.957 Bus2 -8.957 0.000 392.7 100.00 0
*
# Indicates a bus with a load mismatch of more than 0.1 MVA
Indicates a voltage regulated bus (voltage controlled or swing type machine connected to it)
![Page 8: flujo1 - Complete.pdf](https://reader030.fdocuments.net/reader030/viewer/2022021219/55cf978b550346d033923cd7/html5/thumbnails/8.jpg)
7/18/2019 flujo1 - Complete.pdf
http://slidepdf.com/reader/full/flujo1-completepdf 8/12
Location:
Engineer:Study Case: LF
12.5.0E
Page: 8
SN: ESPELTGAEC
Filename: practica1
Project: ETAP
Contract:
Date: 04-21-2014
Revision: Base
Config.: Normal
Bus Loading Summary Report
ID
Bus
kV
Directly Connected Load
MW Mvar MVA % PF AmpRated Amp LoadingMW Mvar MW Mvar
Constant kVA Constant Z Constant IPercent
Generic
MW Mvar
Total Bus Load
Bus1 115.000 8.978 45.1100.00 0 0 0 0 0 0 0
Bus2 13.200 8.970 392.7100.00 0 0 0 0 0 0 0
Bus3 13.200 8.957 392.7100.00 0 8.957 0 0 0 0 0
* Indicates operating load of a bus exceeds the bus critical limit ( 100.0% of the Continuous Ampere rating).
# Indicates operating load of a bus exceeds the bus marginal limit ( 95.0% of the Continuous Ampere rating).
![Page 9: flujo1 - Complete.pdf](https://reader030.fdocuments.net/reader030/viewer/2022021219/55cf978b550346d033923cd7/html5/thumbnails/9.jpg)
7/18/2019 flujo1 - Complete.pdf
http://slidepdf.com/reader/full/flujo1-completepdf 9/12
Location:
Engineer:Study Case: LF
12.5.0E
Page: 9
SN: ESPELTGAEC
Filename: practica1
Project: ETAP
Contract:
Date: 04-21-2014
Revision: Base
Config.: Normal
Branch Loading Summary Report
ID Type
Loading
Amp %
Capability
(MVA) MVA %
Loading (output)
CKT / Branch Cable & Reactor
Transformer
Loading (input)
%MVA
Ampacity
(Amp)
Cable1 Cable 210.17 392.70 186.85*
T1 Transformer 25.000 8.978 35.9 8.970 35.9
* Indicates a branch with operating load exceeding the branch capability.
![Page 10: flujo1 - Complete.pdf](https://reader030.fdocuments.net/reader030/viewer/2022021219/55cf978b550346d033923cd7/html5/thumbnails/10.jpg)
7/18/2019 flujo1 - Complete.pdf
http://slidepdf.com/reader/full/flujo1-completepdf 10/12
Location:
Engineer:Study Case: LF
12.5.0E
Page: 10
SN: ESPELTGAEC
Filename: practica1
Project: ETAP
Contract:
Date: 04-21-2014
Revision: Base
Config.: Normal
Branch Losses Summary Report
ID MW Mvar MW Mvar kW kvar From To
CKT / Branch From-To Bus Flow To-From Bus Flow Losses % Bus Voltage% Drop
Vd
in Vmag
6.5 154.6 100.0 99.9 0.09T1 8.977 0.160 -8.970 -0.005
13.6 5.5 99.9 99.8 0.15Cable1 8.970 0.005 -8.957 0.000
20.1 160.1
![Page 11: flujo1 - Complete.pdf](https://reader030.fdocuments.net/reader030/viewer/2022021219/55cf978b550346d033923cd7/html5/thumbnails/11.jpg)
7/18/2019 flujo1 - Complete.pdf
http://slidepdf.com/reader/full/flujo1-completepdf 11/12
Location:
Engineer:Study Case: LF
12.5.0E
Page: 11
SN: ESPELTGAEC
Filename: practica1
Project: ETAP
Contract:
Date: 04-21-2014
Revision: Base
Config.: Normal
Alert Summary Report
Cable 95.0100.0
Bus
MarginalCritical
95.0100.0
Loading
% Alert Settings
95.0100.0
95.0100.0
95.0100.0
Line
Transformer
Reactor
Panel
95.0100.0
95.0 98.0
102.0105.0
95.0100.0
95.0100.0
95.0100.0
100.0
Generator Excitation
Bus Voltage
UnderExcited (Q Min.)
OverExcited (Q Max.)
UnderVoltage
OverVoltage
Protective Device
Generator
Inverter/Charger 100.0 95.0
Critical Report
Device ID Type Rating/LimitCondition Unit Operating % Operating Phase Type
186.9 3-PhaseOverloadCable1 Cable Amp210,17 392,70
![Page 12: flujo1 - Complete.pdf](https://reader030.fdocuments.net/reader030/viewer/2022021219/55cf978b550346d033923cd7/html5/thumbnails/12.jpg)
7/18/2019 flujo1 - Complete.pdf
http://slidepdf.com/reader/full/flujo1-completepdf 12/12
Location:
Engineer:Study Case: LF
12.5.0E
Page: 12
SN: ESPELTGAEC
Filename: practica1
Project: ETAP
Contract:
Date: 04-21-2014
Revision: Base
Config.: Normal
0.0000.0000.000
0.0000.0000.000
Lagging100.008.957
Total Generic Load:
Total Constant I Load:
0.0000.000
0.1600.020
Number of Iterations: 3
System Mismatch:
Apparent Losses:
SUMMARY OF TOTAL GENERATION , LOADING & DEMAND
0.000
Lagging
Lagging
0.0008.957
0.0000.000
99.988.9780.1608.977
0.0000.0000.000
99.988.9780.1608.977
% PFMVAMvarMW
Total Static Load:
Total Motor Load:
Total Demand:
Source (Non-Swing Buses):
Source (Swing Buses):