Flow Meter Discharge Coefficient Estimation · Conclusion...
Transcript of Flow Meter Discharge Coefficient Estimation · Conclusion...
Flow Meter Discharge Coefficient Estimation Thomas Zhang
ABSTRCT. Flow meters are the useful and common devices that could measure the mass or volumetric flow rate of fluid. Understanding how to estimate coefficient of the flow meter discharges is fundamental for a huge variety of applications in fluid transportation. This experiment was designed as an introduction to this process using an Edibon flow meter module to estimate discharge coefficient during a fluid flowing process. This simple experiment gives a glimpse into many different methods that can be utilized to determine the coefficient of flow meter discharges. In this experiment, two valves were used to control the flow of water through the system. Flow rates could be indicated by a metal cone and were changed for 6 times. The volumetric flow rates and the manometer pressures corresponding to taps 1-‐7 could be measured and recorded for each time. The result showed that with the volumetric flow rate increased, the energy loss of fluid flowing would increase across Venturi and Orifice flow meter while it would keep constant in Rotameter. Fluid will loss more energy when flowing through Orifice flow meter than through Venturi flow meter. The discharge coefficient of Venturi and Orifice flow meter were estimated to be 1.97 and 0.76 respectively. However, the relative errors of them to the theoretical values were 100% and 21% respectively, which showed a bad accuracy of the measurement.
Introduction According to Bernoulli equation, the pressures of a flow through a pipe at different points with the same section area and height should be the same. However, one of assumptions of Bernoulli equation is that the friction is negligible, which could seldom be set up in real life. So there are always energy losses when fluid flows through a pipe. These energy losses are inevitable and could have a significant impact on fluid flowing process. The estimation of discharge coefficient is of great importance to fluid transportation since the power of pump needed to keep the fluid flows through a distance depends on it. Mannan and Frank (2005) described that in a nozzle or other constriction, the discharge coefficient (also known as coefficient of discharge) is the ratio of the actual discharge to the theoretical discharge. The ratio of the mass flow rate at the discharge end of the nozzle to that of an ideal nozzle which expands an identical working fluid from the same initial conditions to the same exit pressures. Flow meters are important and indispensable devices for fluid measurement, which are widely used in fluid mechanics field. So it is really necessary to measure the discharge coefficient of flow meter in order to obtain the actual flow
ratio. Cengel and Cimbala (2013) also stated that in reality, some pressure losses due to frictional effects are inevitable, and thus the velocity will be less. Also, the fluid stream will continue to contract past the obstruction, and the vena contracta area is less than the flow area of the obstruction. Both losses can be accounted for by incorporating a correction factor called the discharge coefficient Cd whose value (which is less than 1) is determined experimentally. Of the numerous types of obstruction meters available, those most widely used are orifice meters, flow nozzles, and Venturi meters.
Objectives The purposes of this study were: (1) To learn how to estimate the discharge coefficients for venturi and orifice flow meters. (2) To quantify energy losses due to flow through flow meters. (3) To be more familiar with the Bernoulli equation and energy equation.
Materials and Methods Flow Meter Module A flow meter is an instrument used to measure linear, nonlinear, mass or volumetric flow rate of a liquid or a gas. The flow meter module which was used in this experiment consists of three kinds of flow meters: Venture, Orifice and Rotameter flow meters.
Figure 1. FNE18 Flow Meter Module From Edibon (by taking photo)
Venturi meter Herschel (1898) mentioned that a Venturi meter constricts the flow in some fashion, and pressure sensors measure the differential pressure before and within the constriction. This method is widely used to measure flow rate in the transmission of gas through pipelines, and has been used since Roman Empire times. The coefficient of discharge of Venturi meter ranges from 0.93 to 0.97. The first large-‐scale Venturi meters to measure liquid flows were developed by Clemens Herschel who used them to measure small and large flows of water and wastewater beginning at the end of the 19th century.
Figure 2. The working principal of Venturi meter
(http://commons.wikimedia.org/wiki/File: Venturifixed2.PNG) Orifice meter Lipták (1993) discussed that an orifice plate is a plate with a hole through it, placed in the flow; it constricts the flow, and measuring the pressure differential across the constriction gives the flow rate. It is basically a crude form of Venturi meter, but with higher energy losses. There are three type of orifice: concentric, eccentric, and segmental.
Figure 3. Orifice plate
(fpunktz, 6 October 2006, http://www.ilkdresden.de/iso5167/index.html) Rotameter Holman (2001) defined rotameter as a device that measures the flow rate of liquid or gas in a closed tube. It belongs to a class of meters called variable area meters, which measure flow rate by allowing the cross-‐sectional area the fluid travels through, to vary, causing a measurable effect. It consists of a tapered tube, typically made of glass, with a float inside that is pushed up by fluid flow and
pulled down by gravity. As flow rate increases, greater viscous and pressure forces on the float cause it to rise until it becomes stationary at a location in the tube that is wide enough for the forces to balance. Rotameters are available for a wide range of liquids but are most commonly used with water or air. They can be made to reliably measure flow down to 1% accuracy Experimental method Frank (2003) showed that mathematically the discharge coefficient might be related to the mass flow rate of a fluid through a straight tube of constant cross-‐sectional area through the following equation:
(1) Where:
= Discharge Coefficient through the constriction (unit-less).
= Cross-sectional area of flow constriction (unit length squared).
= Mass flow rate of fluid through constriction (unit mass of fluid per unit time).
= Density of fluid (unit mass per unit volume).
= Pressure drop across constriction (unit force per unit area).
In this experiment, two valves were used to control the flow of water through the system. Flow rates could be indicated by the metal cone and were changed for 6 times. The volumetric flow rates of the water flow were measured with timer and the dump valve system. The manometer pressures corresponding to taps 1-‐7 were also recorded for each time. For analysis, the graphs of the energy losses at the various flow rates due to flow through each of the meters were plotted in order to observe the relationship between them with the data collected in the lab. In addition, the graphs of volumetric flow rates (Q) vs. square root of pressure drop across the three flow meters for each time could also be plotted. Thus the equation given above could finally be simplified and transformed into:
(2)
Slope =CdA22
ρ 1− A2A1
"
#$
%
&'
2(
)**
+
,--
Table 1. Cross-‐section areas of Venturi and Orifice Flow Meters The discharge coefficient was obtained from equation (1) using the slopes of the graphs and the cross-‐sectional areas of Venturi and Orifice flow meter.
Results and Discussion The graphs of the energy losses vs. flow rates were plotted for each in order to observe the relationship between them. The energy losses of them are obtained from the pressure drop between the inlet and outlet of each flow meter respectively.
Graph 1. Energy loss vs. volumetric flow rate of Venturi flow meter
With the volumetric flow rate increased, the pressure drop of the fluid flowing through venturi flow meter would increase as well. It means that when the fluid flows faster, it will have more energy loss because of the friction. This result is reasonable since the friction between fluid and surface of pipe is mainly caused by viscosity:
τ =ηdvdy (3)
Where: τ: the shear stress of fluid (unit force per unit area) v: the velocity of fluid (unit length per unit time) y: the distance of the pipe surface to the counting point (unit length) η: the viscosity of fluid (unit pressure times unit time)
0 10 20 30 40 50 60 70 80 90 100
0 0.0001 0.0002 0.0003 0.0004
Pressure drop (pa)
Flow rate (m3 /s)
Venturi energy loss
A1(m2) A2(m2)
Venturi 8.04 10-4 3.14 10-4
Orifice 9.62 10-4 2.83 10-4
× ×× ×
Since viscosity and radius of fluid is constant, with the velocity increases, the shear stress of fluid would increase as well, which will cause energy loss. And through observing the graph 1, in Venturi flow meter, the energy loss will rise almost linearly with the volumetric flow rate increases.
Graph 2. Energy loss vs. volumetric flow rate of Rotameter
However, in Rotameter, the pressure drop would stay nearly the same with the volumetric flow rate increased. This result may has something to do with the variable cross-‐sectional area, which could influence the shear stress and make it constant, as a result, keep the energy loss in a same level.
Graph 3. Energy loss vs. volumetric flow rate of Orifice flow meter
The energy loss of the fluid flowing through Orifice flow meter would increase with the volumetric flow rate increased, which was similar to Venturi flow meter. The difference between them was that the energy loss had a powerful trend of rising instead of linear trend. As a result, it would lead to a higher energy loss. This was mainly caused by the hole in the center of Orifice meter, which had a
2284
2286
2288
2290
2292
2294
2296
2298
0 0.0001 0.0002 0.0003 0.0004
Pressure drop (pa )
Flow rate (m3 /s)
Rotameter energy loss
0 100 200 300 400 500 600 700 800 900
0 0.0001 0.0002 0.0003 0.0004
Pressure drop (pa)
Flow rate (m3 /s)
Orifice energy loss
much smaller radius compared with Venturi flow meter. Because if the velocity and viscosity of fluid keep constant, a smaller radius could lead to a larger shear stress, which makes the fluid loss more energy.
The graph of volumetric flow rate vs. square root of pressure drop across each flow meter was plotted in order to estimate the discharge coefficient of these three flow meters.
Graph 4. Volumetric flow rate vs. square root of pressure drop across each flow
meter
Through observing the graph 4, the slope of the graph of Venturi flow meter is equal to 0.00003; the slope of Orifice flow meter is equal to 0.00001. Since the energy loss of Rotameter does not change with the volumetric flow rate increases, the slope of it is infinite and the discharge coefficient of it could not be obtained through calculation. Put the slope of the graph of Venturi and Orifice flow meter as well as the cross-‐section areas into the equation (2), Cd = 1.97 for Venturi flow meter and Cd = 0.76 for Orifice flow meter could be obtained. Compared them with the theoretical values which are 0.982 and 0.627 respectively, the discharge coefficient of orifice flow meter are similar, which has a relative error of 21%. However, the discharge coefficient of Venturi flow meter got from lab is far away from the theoretical value, which has a relative error over 100%. So it shows a bad accuracy of the estimation of discharge coefficient in this lab. It may have something to do with the imprecise reading or wrong operation.
Conclusion
The analysis of the collected data from discharge coefficient estimation in this experiment allowed for a sufficient overview of the rules of fluid transportation
y = 3E-‐05x
y = 1E-‐05x
0
0.00005
0.0001
0.00015
0.0002
0.00025
0.0003
0.00035
0 10 20 30 40 50 60
Flow
rate (m
3 /s)
Square root of pressure drop [pa1/2]
Venturi
Rotameter
Orifice
and measurement. The energy loss of fluid flowing across Venturi and Orifice flow meter would increase with the volumetric flow rate increased. While the fluid flowed through Orifice flow meter would have a higher energy loss. However, the energy loss would keep constant with the volumetric flow rate increased in Rotameter. Through calculation, the discharge coefficient of Venturi and Orifice flow meter were 1.97 and 0.76 respectively. However, it showed a bad accuracy since the relative errors of them to the theoretical values were 100% and 21% respectively. The precision of reading and operation need to be improved to reduce errors. Generally speaking, the energy loss of fluid flowing through a pipe must be taken into account when working on fluid transportation during engineering process. And when using a flow meter to measure flow rate of a fluid, it is also necessary to take the discharge coefficient of it into calculation.
Reference Mannan, S. and Frank, P. L. (2005). Lee's Loss Prevention in the Process Industries:
Hazard Identification, Assessment and Control, Volume 1, Elsevier Butterworth Heinemann. ISBN 978-‐0750678575.
Cengel, Y. A. and Cimbala, J. M. (2014). Fluid Mechanics Fundamentals and Applications, 3rd edition. New York: McGraw Hill. 88 p. Herschel, C. (1898). Measuring Water, Providence, RI: Builders Iron Foundry Lipták, B. G. (1993). Flow Measurement, Chilton Book Company, p. 85 Holman, J. A. (2001). Experimental methods for engineers, Boston: McGraw-‐Hill.
ISBN 978-‐0-‐07-‐366055-‐4. Frank M. W. (2003). Fluid Mechanics, 7th Edition, McGraw-‐Hill Series in
Mechanical Engineering. ISBN 0072402172, 9780072402179, p. 886