  • 8/10/2019 Flamgard+

    1/2

    1.3 Status Indication

    Flamgard Plus includes a local dis

    the junction box window. This is s

    The display shows the c

    the range 0100%LEL and curre

    ZERO or CAL. The LED shows th

    This is summarised in Table 1.

    Operational LED 4-20

    state indication outp

    Normal S te ad y g re en 4 to 7

    operation

    Normal S te ad y r ed 7 .2 to

    operation

    (Alarm 1)

    Normal F la sh in g r ed 1 0. 4 t

    operation

    (Alarm 2)

    Over-range F la sh in g r ed 2 4m A

    Zero/calibration Flash ing green Config

    mode d ep en

    (see s

    Detector Steady amber 0mA

    fault

    *As standard, AL1 = 20%LEL and

    = RELAY VERSION ONLY

    1.1 Product overview

    Flamgard Plus is a flameproof flammable gas detector

    suitable for use in zone 1 or 2 hazardous areas. It is designed

    to detect flammable gas, present in ambient air, at

    concentrations not exceeding the Lower Explosive Limit

    (LEL) of the target gas for which it is calibrated. A local

    display and magnetically operated switches allow non

    intrusive oneman calibration without a hot work permit.

    Powered by 24 V dc (nominally) FlamgardPlus provides a 4

    20 mA signal (sink or source) proportional to the gas

    concentration and can also be fitted with optional alarm and

    fault relays. For a list of flammable gases that can be

    detected, please contact Crowcon.

    1.2 Product description

    Flamgard Plus comprises four parts; 96HD sensor housing, junction box, amplifier

    and terminal board. Diagram 1 details Flamgard Plus. The overall assembly is

    certified EEx d IIC T6 in Europe and Class 1, Zones 1&2 AEx d IIC T6 in the USA.The 96HD sensor housing is a modular stainless steel assembly that

    dismantles to allow plug in pellistor sensors to be replaced easily (see Diagram

    4). The assembly screws into an M20 entry on the junction box.

    The junction box is manufactured from marine grade alloy and is

    supplied with 2 x M20 (1/2 NPT for USA) cable entries for customer use.

    Alternative cable entries are available from Crowcon.

    The amplifier plugs into the terminal board, and is held in place by two

    captive screws. The amplifier provides power to the pellistor sensor, local

    display and controls, and a 420 mA signal proportional to the gas

    concentration for connection to a control panel. To remove, turn screws anti

    clockwise and use them to pull amplifier out of the enclosure.

    All electrical connections are made via the terminal board mounted

    in the base of the junction box (see Diagram 2). Optional alarm relays (AL1 &

    AL2) and one fault relay (FAULT) are mounted on the terminal board which

    may be used to drive local warning devices or connect FlamgardPlus to a

    control panel.

    FlamgardPlus

    Flameproof

    Flammable Gas

    Detectorwith Nonintrusive Oneman

    Calibration

    instructions

    Installation, operating and maintenance

    instructions, MO7192, Issue 6 02/2011

    Plus

    21 3

    5

    Diagram 1: Flamgard Plus general arrangement

    7 6

    UKOfficeCrowconDetectionInstrumentsLtd2BlacklandsWayAbingdonBusinessParkAbingdonOxfordshireOX141DY,UKTel:+44(0)1235557700Fax:+440)1235557749Email:[email protected]:www.crowcon.com

    RotterdamOfficeCrowconDetectionInstrumentsLtdVlambloem1293068JG,RotterdamNetherlandsTel:+31104211232Fax:+31104210542Email:[email protected]:www.crowcon.com

    USAOfficeCrowconDetectionInstrumentsLtd21KentonLandsRoad,Erlanger,Kentucky410181845USATel:+18005276926or

    18005CROWCON+18599571039

    Fax:+18599571044Email:[email protected]:www.crowcon.com

    SingaporeOfficeCrowconDetectionInstrumentsLtdBlock194PandanLoop#0620PantechIndustrialComplexSingapore128383Tel:+6567452936Fax:+6567450467Email:[email protected]:www.crowcon.com Consider the process conditions. Butane, for instance is normally

    heavier than air, but if released from a process line which is at an elevated

    temperature and/or under pressure, the gas may rise rather than fall.

    The placement of detectors should be determined following

    advice of experts having specialist knowledge of gas dispersion, the

    plant processing equipment as well as safety and engineering issues.

    The agreement reached on the locations of sensors should be

    recorded. Crowcon would be pleased to assist in the selection and

    siting of gas detectors.

    3.2 Mounting

    The mounting detail of Flamgard Plus is given in Diagram 1. Flamgard

    Plus should be installed at the designated location with the detector

    pointing down. This ensures that dust or water will not collect on the

    sinter and stop gas entering the detector.

    3.3 Cabling requirement

    Cabling to Flamgard Plus must be in accordance with the recognised

    standards of the appropriate authority in the country concerned and

    meet the electrical requirements of the detector. Crowcon recommend

    the use of steel wire armoured (SWA) cable and suitable explosion proof

    glands must be used. Alternative cabling techniques, such as steel

    conduit, may be acceptable provided appropriate standards are met.Flamgard Plus requires a dc supply of 1230 V at up to

    210 mA. Ensure the minimum dc supply of 12 V is observed at

    the detector, taking into account the voltage drop due to

    cable resistance.

    For example, a nominal dc supply at the control panel of 24 V

    has a guaranteed minimum supply of 20 V. The maximum voltage drop

    allowed is therefore 8 V. Flamgard Plus can demand up to 210 mA and

    so the maximum loop resistance allowed is 38 Ohms. A 1.5 mm2 cable

    will typically allow cable runs up to 1500m.

    115 (4 ")1

    2/

    135(5

    ")

    5

    1 6

    /

    200

    (8")

    83 (3 )"

    M20 ( NTP)

    CABLE

    ENTRY

    1/ "2

    UNITS

    EXTERNALEARTH POINT

    STEADY ONINDICATESZERO/CALMODE

    ACTIVATED

    "UP"

    HEIGHT= 115 (4 / ")1 2

    4 OFFFIXING HOLES6mm (")

    "DOWN"

    FLASHINGINDICATES4-20mA/RELAYSINHIBITED

    ALARM 1 & 2ADJUSTMENTPOTS

    M20 (" NTP)CABLE ENTRY

    STATUSLED

    LOCALDISPLAY

    TESTPOINTS A

    TESTPOINTS B

    SET BALANCEPOT B

    SET BRIDGEVOLTS POT A

    Flamgard-Plus

    SN:

    ZERO

    STATUS

    Menu

    INHIBIT

    CAL

    LEL

    All dimmensions in mm unless otherwise stated

    TAMPER PROOFGRUB SCREW(1.5mm ALLEN KEY)

    2. DETECTOR CONFIGURATION

    2.1 Standard configuration

    As standard, FlamgardPlus is factory set as follows:

    Current source with 0 mA = Fault

    2 mA = Inhibit ie. Zero/Cal mode

    420 mA = Normal operation

    24 mA = Overrange clamp

    AL1 relay Alarm level 1 set to 20%LEL

    Normally deenergised, energising on alarm

    Contact normally open (NO), closing on alarm

    AL2 relay Alarm level 2 set to 40%LEL

    Normally deenergised, energising on alarm

    Contact normally open (NO), closing on alarm

    FAULT relay Normally energised, deenergised on fault

    Contact normally closed (NC), opening on fault

    Alarm/fault relays automatically reset when alarm or fault has cleared.

    INHIBIT Normally selected, ie. when CAL/ZERO selected

    current output is forced to 2mA and relays are

    held in normal/no alarm state.

    Location of links are shown in Diagram 2.

    2.2 4-20mA options

    To change current source output to sink, set switch to SK position. To

    change Inhibit from 2 mA to 4 mA, fit link to 4 position.

    2.3 Relay options

    To change AL1 or AL2 relay from NO to NC, fit link in the NC position.

    To change FAULT relay from NC to NO, fit link in the NO position.

    2.4 Inhibit options

    To not inhibit 420 mA signal and relays, fit link to N and link to 4.

    Diagram 2: Terminal and amplifier layouts Table 1: LED status indicator s

    TEST

    OUTPUT

    40-200mV

    POINT

    4mA

    SK

    -

    +

    SR

    OUTPUTOPTIONS

    INHIBIT

    17 4

    N

    2

    Y

    ALARM

    RANGE

    GAS

    NOTUSED ONFLAMGARD PLUS

    ALARM1

    10

    SENSOR

    6

    5

    4

    3

    1

    2

    ISOLATE

    GND

    OTHER

    NO

    NC

    0V NC

    NO

    RL3

    RL2

    0V

    ALARM 2

    4-20mA

    10-30V

    FAULT

    7

    8

    9

    ALARM1

    NCN

    O

    R

    L1

    ALARM

    11

    12

    OXYGEN

    CONTROLEQUIPMENT

    GNDISOLA

    TE

    LINK

    INTERNALTERMINAL LAYOUT

    ALARMSET POTS

    CONTACTREVERSINGLINKS

    ALARM 1

    FAULT

    TO96HDSENSOR

    ALARM 2

    REAR VIEW OFAMPLIFIER

    RELAYCONTACT

    =ALARM RELAY VERSION ONLY

    Gas Detection You Can Trust

    1180

    3. INSTALLATION

    WARNING

    Flamgard Plus is designed for use in Zone 1 and 2 hazardous

    areas and is certified EEx d IIC T6 (AEx d IIC T6 in USA).

    Installation must be in accordance with the recognised

    standards of the appropriate authority in the country concerned.

    For more information contact Crowcon. Prior to carrying out any

    work ensure local regulations and site procedures are followed.

    3.1 Location

    There are no rules which dictate the siting and location of detectors,

    however, considerable guidance is available from BS EN 50073:1999

    British Standard Code of Practice for the Selection, Installation, Use and

    Maintenance of Apparatus for the Detection and Measurement of

    Combustible Gases or Oxygen. In the USA refer to the National

    Electrical Code (NEC 1999). Similar international codes of practice may

    be used where applicable. In addition certain regulatory bodies publish

    specifications giving minimum gas detection requirements for specific

    applications.

    The detector should be mounted where the gas is most likely

    to be present. The following points should be noted when locating

    flammable gas detectors:

    To detect gases which are lighter than air (eg methane), detectors

    should be mounted at high level and Crowcon recommend the useof a collector cone (Part No. C01051).

    To detect heavier than air gases (eg butane), detectors should be

    mounted at low level.

    When locating detectors consider the possible damage caused by natural

    events e.g. rain or flooding. For detectors mounted outdoors Crowcon

    recommend the use of a Weatherproof Cap (Part No. C01442).

    Consider ease of access for functional testing and servicing.

    Consider how the escaping gas may behave due to natural or forced

    air currents. Mount detectors in ventilation ducts if appropriate.

    1. INTRODUCTION

    Table 2 shows maximum cable dis

    C SA R es is ta nc e ( Oh

    mm2 (awg) Cable

    1.0 (17) 18.1

    1.5 (15) 12.1

    Table 2: Maximum cable dista

    Acceptable cross sectional area

    provides guidance only, actual c

    should be used to calculate maxi

    3.4 Electrical connections

    All connections are made via the

    of the junction box (see Diagram

    colour coded and should be ter

    coded terminal (terminals 4, 5 &

    and 3 (420mA signal) are con

    Flamgard Plus is factory set as

    specified otherwise when ord

    configuration). Diagram 3 summa

    Note: The junction box and cabdetector or control panel to l

    interference and to ma intain ele

    Note: The junction box for the F

    marine-grade alloy, and has a po

    taken during installation to prote

    environments could result in pai

    boxes. This in no way compromi

    as the marine-grade alloy junctio

    environments.

  • 8/10/2019 Flamgard+

    2/2

    10 1213

    4.3Sensorreplacement/servicingofdetectors

    WARNING

    ThisworkshouldbecarriedoutbyCrowconoranapproved

    servicecentreunlesssuitabletraininghasbeenreceived.

    FlamgardPlususesthe96HDsensorhousingwhichallowstheuserto

    replacethesensors,gasketsandsinterifnecessary.Anexplodedview

    ofthe96HDsensorhousingisgiveninDiagram4.Thefollowing

    proceduremaybefollowedwhenservicingaFlamgardPlusdetector.

    aSwitchoffandisolatepowertothedetectorrequiringattention.

    bOpenthedetectorJunctionboxbylooseningthetamperproofgrub

    screwandremovingthelidbyrotatingitanticlockwise.

    cRemovetheamplifier.

    dDisconnectthe3sensorwiresfromtheterminalboard(terminals4,

    5&6).

    eUnscrewthecomplete96HDsensorhousingfromthejunctionbox.

    Note:Ifaspare96HDsensorhousingcompletewithnewsensoris

    availableignorestepsftokandreturntheold96HDtoCrowcon

    oranapprovedservicecentreforrepair.

    fOpenthe96HDsensorhousingbyremovingthefourAllenhead

    screwsfromtheTopCapwitha3mmAllenkey.

    gRemovethesensorfromtheTopCapPCB.Flammablesensors

    haveanextrablacksleevewhichmaybeseparatefromthesensor.

    Thisisnormalandthesleevemaybereused.

    hFitthereplacementsensorcheckingthepartnumberiscorrect.This

    partnumberislabelledonthemainbodyofthedetector.

    iInspectthegasketsandreplaceifnecessary.

    jThesinterassemblywillonlyneedtobereplacedifithasbecome

    blockedbydustoroil.Suchblockagecausestheresponsetimeof

    thedetectortobeslowandmayaffectsensitivity.Toremovethe

    11

    jAllowthegasreadingtostabilise.

    kPlacetheendoftheCROMagovertheUPorDOWNarrow

    padstomakethedisplayreadthecorrectconcentration.

    lIfthecontrolequipmentdisplayrequiresadjustmentconsultthe

    operatingmanualfortheequipment.

    Returningtonormaloperation(NORMALMode):

    nPlacetheendofCROMagovertheMENUpad.Alldecimalpoints

    willdisappearandthebacklightwillturnoff.ThegreenstatusLED willbeonsteadily(assumingnogasispresentatthedetector).

    oThedetectorisnowoperational.

    Note:AlwaysreturnthedetectortoNORMALmodetoavoidleaving

    thedetectorinapermanentlyinhibitedstate.

    4.2Routinemaintenance

    Theoperationallifeofthepellistorsensordependsontheapplicationfor

    whichitisbeingused.Suchadeviceshouldworksatisfactorilyforupto

    5yearsinidealconditions.Sitepracticeswilldictatethefrequencywith

    whichdetectorsaretested.Crowconrecommendthatdetectorsbegas

    testedatleastevery6monthsandrecalibratedasnecessary.Tore

    calibrateadetectorfollowstepsgivenin4.1.

    Pellistorscansufferfromlossofsensitivitywhenthereisa

    presenceofpoisonsorinhibitorssuchassilicones,sulphides,chlorine,

    leadorhalogenatedhydrocarbons.FlamgardPlususespoisonresistant

    pellistorstomaximisetheoperationallife.Inapplicationswheresuch

    compoundsarepresentcontinuously,werecommendtheuseof

    XgardIRorIRmax,Crowconsfixedpointinfraredflammablegas

    detectors,whichareimmunetosuchpoisonsandinhibitors.

    5.SPAREPARTSANDACCESSORIES

    DescriptionPartnumber

    M20to1/2inchNPTadaptorM02125

    M20to3/4inchNPTadaptorM02281

    Gasket1M04452

    Gasket2M04128

    SinterremovaltoolM01614

    CollectorConeC01051

    CeilingMountingBracketM01401

    WeatherproofCapC01442

    ReplacementCROMagC01697

    96HDsensorhousingcompletewithsensorS01749*1

    ReplacementsensorS01673*1

    SinterassemblyS01781

    AmplifierS01865

    TerminalboardS01846

    RelayboardS01847

    LoctiteNo.243ContactCrowcon

    CalibrationgasContactCrowcon

    1718

    ued)

    nalrelaysaremadeviathe6way

    nthebaseofthejunctionbox(see

    ed1A@30Vdc.

    4.OPERATION

    WARNING

    Priortocarryingoutanyworkensurelocal

    regulationsandsiteproceduresarefollowed.Neverattempttoopenthedetectororjunctionboxwhenflammablegasis

    present.Ensurethattheassociatedcontrolpanelisinhibited

    soastopreventfalsealarms.

    4.1CommissioningProcedure

    aOpenthejunctionboxofthedetectorbylooseningthetamperproofgrubscrewandremovingthelidbyrotatingitanticlockwise.

    bRemovetheamplifierandcheckthatallelectricalconnectionshave

    beenmadeandarecorrectasperDiagram3.

    cReplacetheamplifierandclosethejunctionboxensuringthatall

    screwshavebeenrefittedcorrectly.

    dApplypowertothedetector.ThestatusLEDwillshowasteady

    greenindicatingnormaloperation.

    eLeavethedetectortostabilisefor12hours.

    Zeroingthedetector(ZEROMode):

    fPlacetheendofCROMagovertheMENU.GreenStatusLEDwill

    flash.DecimalpointaboveZEROwillilluminate.Displaybacklight

    willilluminate.DecimalpointaboveINHIBITmayflashiftheoption

    hasbeeninternallyselected.

    gWithnoflammablegaspresentatthedetector,placetheendofthe

    CROMagkeyovertheUPorDOWNarrowpadstomakethe

    displayreadzero.

    Calibratingthedetector(CALMode):

    hPlacetheendoftheCROMagovertheMENUpad.Thedecimal

    pointabovethewordCALwillilluminate.Otherindicationsremain

    unchanged.

    iApplycalibrationgastothedetectorataflowrateof0.5litres/min.

    Crowconrecommend50%LELgasforcalibrationpurposes

    (contactCrowconforthesupplyofcalibrationgas.)

    4.4ChangingAlarmLevels(RelayVersionOnly)

    WARNING

    ThisworkshouldbecarriedoutbyCrowconoranapprovedservicecentreunlesssuitabletraininghasbeen

    received.Beforeattemptingtochangealarmlevelsensure

    thedetectorisinfreshairandnoflammablegasispresent.

    AsstandardtheAL1andAL2alarmlevelsarefactorysetat20%LEL

    and40%LELrespectively.Tochangeeitheralarmlevel:

    aSwitchoffandisolatepowertothedetectorrequiringattention.

    bOpenthejunctionboxofthedetectorbylooseningthetamperproof

    grubscrewandremovingthelidbyrotatingitanticlockwise.

    cRemovetheamplifierfromtheterminalboard.

    dEnsurethattheINHIBITlinkissettoN.

    eRefittheamplifiertotheterminalboardensuringthatallscrewshave

    beensecuredcorrectly.

    fApplypowertothedetectorandallowthedetectortostabilise.

    gPlacetheendofCROMagovertheMENUpad.Thedecimal

    pointabovethewordZEROwillilluminate.

    hWithnoflammablegaspresentatthedetector,placetheendofthe

    CROMagkeyovertheUPorDOWNarrowpadstomakethe

    displayreadthedesiredalarmlevel.

    iUsingalonginstrumentscrewdriver,turntherelevantALARMSET

    potmountedontheterminalboard(seeDiagrams1&2)toadjust

    thealarmlevel.TrippingoftheALARM1levelrelayisconfirmedby

    thestatusLEDturningasteadyred.TrippingoftheALARM2level

    relayisconfirmedbytheStatusLEDflashingred.

    jOncethealarmlevelhasbeenset,placeendofCROMagoverthe

    UPorDOWNarrowpadsandresetthedisplaytoreadzero.

    kPlacetheendoftheCROMagovertheMENUpadtoreturnthe

    detectortonormaloperation,ie.Nodecimalpointsdisplayed,

    backlightoffandtheStatusLEDindicatingsteadygreen.

    lCheckthatthedetectoroperatescorrectlybyapplyingtestgasas

    necessary.

    mSwitchoffandisolatepowertothedetector.

    nResetjumperswhichmayhavebeenchangedinstepdabove.

    oReplacetheamplifierandclosethejunctionbox,ensuringthatall

    screwshavebeenrefittedcorrectly.

    pApplypowertothedetectorandallowtostabilisebeforechecking

    correctoperation.

    qRecalibrateifnecessaryaspersection4.1.

    Notes:

    AreaClassifications:-

    Zone0:Anareaclassified,asZone0willhaveignitable

    concentrationsofflammablegases,vapoursorliquidspresentcontinuouslyorforlongperiodsof

    timeundernormaloperatingconditions.

    Zone1:Anareaclassified,asZone1islikelytohave

    ignitableconcentrationsofflammablegases,

    vapoursorliquidspresentundernormaloperating

    conditions.

    Zone2:Anareaclassified,asZone2isnotlikelytohave

    ignitableconcentrationsofflammablegases,

    vapoursorliquidspresentundernormaloperating

    conditions.

    toFlamgardPlusDiagram4:96HDassembly

    1516

    d)

    614)isrequired.LoctiteNo243

    assemblythreadstomaintain

    kingtimetoensurethatthe3mm

    edintoposition.

    hejunctionboxensuringthatthe

    correctly.

    tivescrewsarefastenedsecurely.

    acrossTestPointsAandadjust

    VMreadscorrectly(seeTable3for

    acrossTestPointsBandadjust

    reads0mV. ngtofastenthetamperproofgrub

    uregivenin4.1.

    tAComment

    mV)

    Poisonresistant

    Poisonresistant

    Leadresistant

    Earlymodel

    Lowpower

    ForHalogens

    Ammoniaoraviationfuel

    Earlymodel

    dinthisdetectorshouldbe

    ectedfromexposuretosilicones,

    retothesecompoundswill

    hesensor,andrenderthesensor

    *1

    FlamgardPlusmaybefittedwitharangeofpellistorsensorsdependingon

    thespecificapplication.Thecorrectsparesensorpartnumberisitemised

    onthesensorhousinglabel.

    5.SPECIFICATION

    Dimensions200x115x115mm(8x41/2x4

    1/2)

    Weight2.2kg(4.8lbs)

    Material96HDsensorhousing:316Stainlesssteel

    Junctionbox:Marinegradealloy

    Temperaturerange1055oc(14131

    oF)

    Humidityrange099%RH,noncondensing

    IngressprotectionIP65

    ExplosionprotectionFlameproof

    ApprovalcodesII2GExdIICT6Gb(+55oc)

    ULClass1,Zones1&2,AExdIICT6

    SafetyCertNo.Sira03ATEX1124

    StandardsEN600790,EN600791:2007,UL2279

    ZonesCertifiedforuseinZone1orZone2

    areas.(seeareaclassificationssection)

    GasgroupsIIA,IIB,IIC

    Operatingvoltage1230Vdc

    OperatingcurrentRelayversion:210mA(maximum)

    Nonrelayversion:160mA(maximum)

    Detectoroutput420mAsourceorsinkselectable

    0mA=Fault

    2mA=Inhibit(4mAoption)

    420mA=0100%LEL

    24mA=Overrange

    Relaysoutputs2xAlarmrelaysSPNO(SPNCoption)

    1xFaultrelaySPNC(SPNOoption)

    Contactrating1A@30Vdc

    (PartNoMO4128)

    NEOPRENEGASKET1

    GASKET

    2

    TOPCAP&SENSORPCB

    MAINBODY

    SINTER

    (PartNoSO1781)SINTERASSEMBLY

    (PartNoMO4452)

    SLEEVE

    PELLISTOR

    ALLENHEADSCREWS

    4OFFM4X12MM

    4-20mA

    12-30V

    0V

    FLAMGARD-PLUS

    SINK

    2

    +V

    3

    1

    0V

    CONTROLEQUIPMENTSAFEAREA

    sensorsattestpointA