www.Fisher.com Fisher r FIELDVUE DVC6200p Digital Valve Controller Device Setup and Accessing Communication and Calibration using Siemens SIMATIC Manager/PDM Contents Related Documents 1 ........................... Connecting the Digital Valve Controller using Enhanced Device Description (EDD) 膕for Siemens SIMATIC PDM 2 .................... Setting PG/PC Interface 3 ....................... Loading the DVC6200p EDD to the SIMATIC 膕Manager/PDM Catalog 8 ....................... Device Setup using Siemens PDM Software 10 ..... Changing Node Address to the Default Address 23 .. Performing One-Step Local Quick Setup to Calibrate and Tune the DVC6200p 25 ........ Refer to the DVC6200p quick start guide or instruction manual for all other information regarding the DVC6200p digital valve controller, including safety cautions and warnings. Related Documents D Fisher FIELDVUE DVC6200p Digital Valve Controller quick start guide (D103562X012) D Fisher FIELDVUE DVC6200p Digital Valve Controller instruction manual (D103563X012) All documents are available from your Emerson Process Management sales office. Also visit our website at www.FIELDVUE.com. Instruction Manual Supplement D103560X012 DVC6200p Digital Valve Controller October 2011

Transcript of Fisher FIELDVUE DVC6200p Digital Valve Controller …/media/resources/fisher/u/490... · Launch the...

www.Fisher.com

Fisher� FIELDVUE™ DVC6200p Digital ValveController Device Setup and AccessingCommunication and Calibration using SiemensSIMATIC Manager/PDM

ContentsRelated Documents 1. . . . . . . . . . . . . . . . . . . . . . . . . . .Connecting the Digital Valve Controller usingEnhanced Device Description (EDD)�for Siemens SIMATIC PDM 2. . . . . . . . . . . . . . . . . . . .

Setting PG/PC Interface 3. . . . . . . . . . . . . . . . . . . . . . .Loading the DVC6200p EDD to the SIMATIC�Manager/PDM Catalog 8. . . . . . . . . . . . . . . . . . . . . . .

Device Setup using Siemens PDM Software 10. . . . .Changing Node Address to the Default Address 23. .Performing One-Step Local Quick Setup

to Calibrate and Tune the DVC6200p 25. . . . . . . .

Refer to the DVC6200p quick start guide or instruction manual for all other information regarding the DVC6200pdigital valve controller, including safety cautions and warnings.

Related Documents� Fisher FIELDVUE DVC6200p Digital Valve Controller quick start guide (D103562X012)

� Fisher FIELDVUE DVC6200p Digital Valve Controller instruction manual (D103563X012)

All documents are available from your Emerson Process Management sales office. Also visit our website atwww.FIELDVUE.com.

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

2

Connecting the DVC6200p using Enhanced Device Description(EDD) for Siemens SIMATIC PDMRefer to figure 1

Figure 1. Connecting the FIELDVUE DVC6200p using EDD for Siemens SIMATIC PDM

BACK-RAIL

PROFIBUS PA

POWERSUPPLY DP/PA COUPLER

24 VDC SUPPLY VOLTAGEFOR DP/PA COUPLER

230V/120V AC

DP 9-PINCABLE CONNECTORS

DP CABLE (PURPLE)

PROFIBUS CARDPCMCIA TYPE

PROFIBUS DPMASTER SYSTEM

(CLASS-2MASTER)

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

3

Setting PG/PC Interface

Note

Setting the PG/PC interface or PC card (CP 5611 or similar PROFIBUS card) is done only once, after the first hardware installation ofthe PC card inside the computer.

1. Set PG/PC Interface is available under the PC ‘Control Panel’ once Siemens Step-7 or Simatic Manager/PDMsoftware is installed.

a. Go to Set PG/PC Interface as shown in figure 2.

b. Under the Interface, click on Select... to add the PCI/PCMCIA/USB type PROFIBUS card installed on the PC.

c. Once the card appears as shown in figure 2 (e.g. CP5611 (PROFIBUS), select CP5611(PROFIBUS) <Active> andclick on Properties..

For further support on Setting PG/PC Interface visit the following Siemens website for detailed setup procedures:

http://support.automation.siemens.com/WW/view/en/25471997

Figure 2. Set PG/PC Interface

SELECT ASPER PROFIBUSCARD USED

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

4

2. If the PROFIBUS card is the only master on the bus select PG/PC is the only master on the bus, as shown in figure 3. Ifthere are other Class 1 or Class 2 masters on the bus, then DO NOT select PG/PC is the only master on the bus.Following that select the Check and select the appropriate transmission rate of the bus.

Figure 3. PROFIBUS Card Parameter Setting

PARAMETER SETTINGS

SET BUS PARAMETERSACCORDING TOCOUPLER USED

Note

The parameter setting above applies only if the PG/PC card is the only master on the bus.

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

5

3. Click on Diagnostics... as shown in figure 4.

Figure 4. Diagnostics...

SELECT ASPER PROFIBUSCARD USED

4. The diagnostics window will be shown as indicated in figure 5. Click on Test to check the status of the PROFIBUScard and network.

Figure 5. Status/Network Diagnostics—Test

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

6

5. The status will be shown in the box next to Test as shown in figure 6. If the status is Failed, changes as per step 2may be required.

Figure 6. Status/Network Diagnostics—Status

Note

If “Test” fails, check the DP/PA coupler type used and the parameter setting, as recommended by the coupler manufacturer.

6. To test the address of the host and any connected device select Read as shown in figure 7.

Figure 7. Status/Network Diagnostics—Read

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

7

7. Any master or slave (devices) that is connected will be reflected (in the example shown in figure 8, the PROFIBUScard is connected to address 4). Station Active refers to Masters on the bus. Station Passive refers to the slave(devices) on the bus. An active ready PLC (Master Class 1) will be denoted as Station Active Ready.

Figure 8. Status/Network Diagnostics—Station Address

STATION ADDRESS

Note

The default address of the DVC6200p is set by the factory to 126.

8. Select OK to close the Set PG/PC interface.

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

8

Loading the DVC6200p EDD to the SIMATIC Manager/PDMCatalogSelect Options > SIMATIC PDM > Manage Device Catalog..., as shown in figure 9.

Figure 9. Manage Device Catalog...

Click on Browse to find the source of the DD file, select all attributes, then OK.

Figure 10. Browse CLICK “BROWSE” TOSELECT THE DD FOLDER

Note

Loading the EDD on the SIMATIC PDM on a station is only needed once, unless a new or updated EDD is required.

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

9

Expand the selection for PROFIBUS PA and choose 'PA Standalone' as shown in figure 11. (This is for Standalone PDMstatus only. For a PDM snap-on to STEP 7 SIMATIC Manager select 'PA Step7'). This will load the DD file catalog. SelectOK.

Figure 11. SIMATIC PDM Device Selection

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

10

Device Setup using Siemens SIMATIC PDM SoftwareBefore beginning Device Setup, be sure the instrument is correctly mounted. Refer to the installation instructionssupplied with the mounting kit.

WARNING

Changes to the instrument setup may cause changes in the output pressure or valve travel. Depending on the application,these changes may upset process control, which may result in personal injury or property damage.

1. Launch the SIMATIC Manager application through the shortcut in the Windows desktop or from the Windows StartUp Menu. Select File > New, as shown in figure 12 to create the new project. Enter the project name, such asDVC6200p, as shown in the example in figure 12, or open an existing user project.

Figure 12. Create New Project

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

11

2. Right click on Net on the left hand pane, select Insert New Object > PROFIBUS DP net (if it does not alreadyavailable).

Figure 13. Adding PROFIBUS DP Network

3. Right click on the PROFIBUS DP net icon on the left pane, select SIMATIC PDM > Start LifeList, as shown in figure 14.

Figure 14. Access Start LifeList

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

12

Select Scan immediately after Start, as shown in figure 15, to scan all possible addresses for the devices. Click OK. Thedefault address range is from 0 to 126.

Figure 15. LifeList Options

All scanned addresses will be returned, as shown in figure 16.

Figure 16. SIMATIC PDM LifeList

NEW DEVICESCANNED

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

13

To change the device address, right­click on current device addresses and select Assign Address. Once done exit thePDM LifeList

Figure 17. Assign/Change Device Address

4. Right click on PROFIBUS DP net, select Insert New Object > PROFIBUS PA device. Type in the Device Name/Tag anddefine the Device Address.

Figure 18. Adding PROFIBUS PA Device

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

14

5. Under Device type click Assign, select Fisher Controls PA Standalone for standalone station PDM or select FisherControls PA Step7 for a STEP 7 PDM. Click OK.

Note

The DVC6200p EDD needs to be loaded in the SIMATIC Manager/PDM Device Catalog as per STEP 7 SIMATIC Manager.

Figure 19. Assign Device Type

ASSIGNDEVICEADDRESSAS PERLIFELIST

ENTER TAGNAME HERE

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

15

6. Right click on DVC6200p (device) and select Open Object, as shown in figure 20.

Figure 20. Open Device in SIMATIC PDM

You will be required to sign in accordingly. See figure 21.

Figure 21. User Class Selection

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

16

7. This will open the offline parameters of the DVC6200p EDD, as shown in figure 22.

Figure 22. Device Offline Parameters (Default)

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

17

8. On the menu tab, select Online to open the DVC6200p EDD. Then select Overview, as shown in figure 23.

Figure 23. Going Online

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

18

Refer to figure 24 to view the Overview screen interface. Overview shows the Primary Variables (PV's) and the DeviceStatus and Mode.

Figure 24. FIELDVUE DVC6200 EDD Overview

CHANGE MODE HEREDEVICE STATUS—CLICK TOSEE ACTIVE STATUS ALERTS

9. To configure the DVC6200p, select Configure > Guided Setup and go to Device Setup as shown in figure 25. GuidedSetup takes you through Device Setup, Auto Calibration, and Performance Tuner.

Figure 25. Accessing Device Setup

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

19

WARNING

During calibration the valve will move full stroke. To avoid personal injury and property damage caused by the release ofprocess fluid or pressure, isolate the valve from the process and equalize pressure on both sides of the valve or bleed off theprocess fluid.

10. To only perform the auto calibration, select Configure > Calibrate. Select Auto Calibration from the Travel tab, asshown in figure 26.

Figure 26. Accessing Auto Calibration

11. Once calibrated it is advised to run the Performance Tuner. Run the Performance Tuner by selecting Service Tools >Maintenance. Select Performance Tuner from the Tuner tab, as shown in figure 27.

Figure 27. Accessing Performance Tuner

WARNING

During performance tuning the valve may move, causing process fluid or pressure to be released. To avoid personal injuryand property damage caused by the release of process fluid or pressure, isolate the valve from the process and equalizepressure on both sides of the valve or bleed off the process fluid.

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

20

12. Once Performance Tuner is completed – Run the Stroke Valve procedure on the Overview screen to validate AutoCalibration. Click on Stroke Valve as shown in figure 28. Select Yes to accept the Warning message, then OK.

Figure 28. Accessing Stroke Valve

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

21

13. Select the stroke valve options. Enter the Travel Target value and then click the OK button as shown in figure 29.

Figure 29. Stroke Valve—Travel Target

Step 1

Step 2 Step 3

14. Wait until the travel reading stabilizes then select EXIT as shown in figure 30 to stop the valve motion. Select OKaccept the travel value.

Figure 30. Stroke Valve—Accepting Travel Target

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

22

15. Set the Transducer Block in AUTO then select OK as shown in figure 31.

Figure 31. Transducer Block Mode Selection

Select OK to accept the completion of Stroke Valve as shown in figure 32.

Figure 32. Stroke Valve—Complete

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

23

Changing Node Address to the Default AddressThis procedure will change the DVC6200p PROFIBUS PA device to the spare address (126).

1. Select Online > Service Tools > Maintenance > Restart Options. Click on Restart Options as shown in figure 33.

Figure 33. FIELDVUE DVC6200p Maintenance, Restart Options Selection

RESTARTOPTIONS

2. Select Default Bus Address, as shown in figure 34, from the Restart Options.

Figure 34. Restart Options, Default Bus Address

DEFAULT BUSADDRESS

3. This will reset the device address to 126. Select OK to proceed with this change.

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

24

Figure 35. Reset Device Address

4. Once the address has been reset, communication will be disconnected. Select OK to complete.

Figure 36. Communication Disconnected

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

25

Performing One­Step Local Quick Setup to Calibrate and Tune theDVC6200p Digital Valve Controller

Note

This calibration method can be used when there is no Class­2 master (ex. SIMATIC PDM) or other configuration software available.

WARNING

Changes to the instrument setup may cause changes in the output pressure or valve travel. Depending on the application,these changes may upset process control, which may result in personal injury or property damage.

WARNING

During calibration the valve will move full stroke. To avoid personal injury and property damage caused by the release ofprocess fluid or pressure, isolate the valve from the process and equalize pressure on both sides of the valve or bleed off theprocess fluid.

Travel calibration and auto tuning can also be accomplished by shorting the auxiliary terminal connections, shown infigure 37, between 3 to 10 seconds. You can abort the procedure by shorting the auxiliary terminals for 1 second.Pressure range will also be captured during this procedure.

Figure 37. Short the Auxiliary Terminal Connections

Instruction Manual SupplementD103560X012

DVC6200p Digital Valve ControllerOctober 2011

26

Note

If the digital valve controller is connected with SIMATIC PDM, the overview screen of the EDD will indicate calibration in process.

Note

Calibration time varies depending on the type and size of the actuator. For a Fisher 667 size 30 actuator typical calibration time isapproximately 4-5 minutes.

Emerson Process Management Marshalltown, Iowa 50158 USASorocaba, 18087 BrazilChatham, Kent ME4 4QZ UKDubai, United Arab EmiratesSingapore 128461 Singapore

www.Fisher.com

The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are notto be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales aregoverned by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of suchproducts at any time without notice.

�Fisher Controls International LLC 2011; All Rights Reserved

Fisher and FIELDVUE are marks owned by one of the companies in the Emerson Process Management business division of Emerson Electric Co. EmersonProcess Management, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. All other marks are the property of theirrespective owners.