First Revision No. 6036-NFPA 5000-2015 [ Global Input ] Throughout the document, change “door electrically controlled egress door assemblies” to “hardware-release of electrically locked egress door assemblies”. Throughout the document, change “delayed-egress locking systems” to “delayed-egress electrically locking systems”. Throughout the document, change "access-controlled egress door(s)" or “access- controlled egress door assemblies” to “sensor-release of electrical locking systems”. Submitter Information Verification Submitter Full Name: Ron Cote Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Tue Aug 04 12:55:13 EDT 2015 Committee Statement Committee Statement: The terms are being renamed in their related provisions in Chapter 11. Correlative updating of terms is needed throughout the document to keep the terminology consistent. Response Message: National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... 1 of 43 10/28/2015 10:41 AM Page 1 of 49

Transcript of First Revision No. 6036-NFPA 5000-2015 [ Global Input ]€¦ · First Revision No. 6036-NFPA...

First Revision No. 6036-NFPA 5000-2015 [ Global Input ]

Throughout the document, change “door electrically controlled egress door assemblies”to “hardware-release of electrically locked egress door assemblies”.

Throughout the document, change “delayed-egress locking systems” to “delayed-egresselectrically locking systems”.

Throughout the document, change "access-controlled egress door(s)" or “access-controlled egress door assemblies” to “sensor-release of electrical locking systems”.

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 04 12:55:13 EDT 2015

Committee Statement

CommitteeStatement:

The terms are being renamed in their related provisions in Chapter 11. Correlativeupdating of terms is needed throughout the document to keep the terminologyconsistent.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 43 10/28/2015 10:41 AM

Page 1 of 49

First Revision No. 6006-NFPA 5000-2015 [ New Section after 3.3.150 ]

3.3.151 Delayed Action Closer.

Self-closing device that incorporates a delay prior to the initiation of closing. Delayed actionclosers are mechanical devices with an adjustable delay. (BLD-MEA)

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 03 15:27:36 EDT 2015

Committee Statement

CommitteeStatement:

Delayed action closers are utilized in buildings. Proposing a definition tocomplement proposed text in new section after 11.2.1.8.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 43 10/28/2015 10:41 AM

Page 2 of 49

First Revision No. 6007-NFPA 5000-2015 [ New Section after 3.3.501 ]

3.3.502 Power Doors.

3.3.502.1* Low Energy Power-Operated Door.

Swinging, sliding, or folding door that opens automatically upon an action by a pedestrian,closes automatically, and operates with decreased forces and decreased speeds.

3.3.502.2 Power-Assisted Door.

Swinging door that opens by reduced pushing or pulling force on the door operatinghardware, closes automatically after the pushing or pulling force is released, and functionswith decreased forces.

3.3.502.3* Power-Operated Door.

Swinging, sliding, or folding door that opens automatically when approached by a pedestrianor opens automatically upon an action by a pedestrian, closes automatically, and includesprovisions to prevent entrapment.

Supplemental Information

File Name Description

5000_FR6007_annex_text.docx

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 03 15:31:41 EDT 2015

Committee Statement

CommitteeStatement:

This revision adds definitions supporting changes to 11.2.9 adding ANSIreferences for the various types of power doors,

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 43 10/28/2015 10:41 AM

Page 3 of 49

Low Energy Power-Operated Door. A pedestrian action might include pressing a

push plate or waving a hand in front of a sensor.

Power-Operated Door. A provision used to prevent entrapment might include sensors.

Page 4 of 49

First Revision No. 6008-NFPA 5000-2015 [ Section No. 11.1.3.2.1.7 ]

11.1.3.2.1.7

Penetrations into and openings through an exit enclosure assembly shall be prohibited, exceptfor the following:

(1) Door assemblies permitted by 11.1.3.2.1.6

(2)

(3) Pathways for devices for security and communication systems serving the exitenclosure, where pathways are installed in metal conduit

(4) Required exit door openings

(5) Ductwork and equipment necessary for independent stair pressurization

(6) Water or steam piping necessary for the heating or cooling of the exit enclosure

(7) Sprinkler piping

(8) Standpipes

(9) Penetrations for fire alarm circuits, where the circuits are installed in metal conduit andpenetrations are protected in accordance with 8.8.7 .

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 03 15:38:36 EDT 2015

Committee Statement

CommitteeStatement:

Relative to new item (3), text is added for security devices such as access systemsand security cameras. This can be done safely if pathways are in metal conduit.

relative to item (9), see new 11.3.2.1.9 where all penetrations must be protected inaccordance with 8.8.7.

ResponseMessage:

* Electrical conduit serving the exit enclosure

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

4 of 43 10/28/2015 10:41 AM

Page 5 of 49

First Revision No. 6009-NFPA 5000-2015 [ New Section after 11.1.3.2.1.8 ]

11.1.3.2.1.9

All penetrations in fire barriers separating the exit from other parts of the building shall beprotected in accordance with 8.8.7 .

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 03 15:45:59 EDT 2015

Committee Statement

Committee Statement: All penetrations need to be protected, so a general requirement is in order.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

5 of 43 10/28/2015 10:41 AM

Page 6 of 49

First Revision No. 6010-NFPA 5000-2015 [ Section No. 11.1.5.4 ]

11.1.5.4

Headroom on stairs and stair landings shall be not less than 6 ft 8 in. (2030 mm) and shall bemeasured vertically above a plane parallel to, and tangent with, the most forward projection ofthe stair tread.

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 03 15:48:51 EDT 2015

Committee Statement

CommitteeStatement:

It is difficult-to-impractical to provide 7’-6” headroom height at an intermediate landing if

the headroom on the stair is designed to take advantage of the 6’-8” headroomallowance. The headroom is there to provide a smoke reservoir to permit smoke to bankdown from the ceiling without immediately affecting the movement of an occupant who isstanding. Within an exit stair enclosure – except for the top floor landing – the smoke willtravel upward along the rake of the stair to a higher level rather than accumulating underthe landing. The basis for the headroom requirement seems not to be served any betterby a 7’-6” headroom than one of 6’-8”.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 43 10/28/2015 10:41 AM

Page 7 of 49

First Revision No. 6011-NFPA 5000-2015 [ New Section after 11.1.6.4 ]

11.1.6.5* Grab Bars for Bathtubs, Bathtub-Shower Combinations, and Showers.

11.1.6.5.1 General.

11.1.6.5.1.1

Where required by Chapters 15 through 31 , new bathtubs, bathtub-showercombinations, and showers, for use by occupants, shall be provided with grab barscomplying with 11.1.6.5.2 through 11.1.6.5.5 , except as otherwise permitted for showersin 11.1.6.5.1.2 , with all dimensions referring to the centerline of the grab bar unlessotherwise stipulated.

11.1.6.5.1.2*

Where a dedicated shower does not expose users to changes in elevation exceeding 0.5 in.(13 mm), as described in 11.1.6.2 , and it provides slip resistance for all surfaces when wet,as a foreseeable condition described in 11.1.6.4 , the requirements of 11.1.6.5.2 through11.1.6.5.5 shall apply only if grab bars are installed.

11.1.6.5.2 Vertical Grab Bar.

A vertical grab bar shall be provided either installed on the control end wall of the bathtub,bathtub-shower combination, and shower, as specified in 11.1.6.5.2.1 , or as a freestanding, external pole as specified in 11.1.6.5.2.2 .

11.1.6.5.2.1* Vertical Grab Bar on Control End Wall.

(A)

A vertical grab bar, with a minimum length of 24 in. (610 mm), and its lower end between 36and 39 in. (915 and 990 mm) above the finished floor, shall be installed on the entry/egressside of the control end wall of the bathtub, bathtub-shower combination, and shower unit.

(B)

The grab bar shall be located at least 6 in. (150 mm), measured horizontally, from anyshower curtain rod fixing point on the wall.

11.1.6.5.2.2* Vertical Grab Bar as Free Standing, Vertical Pole.

A vertical, pole-type grab bar fixed to the floor and either the room ceiling or an adjacent wallshall be installed outside of the bathtub, bathtub-shower combination, or shower unit within 6in. (150 mm), measured horizontally, outside of the outer edge of the bathtub, bathtub-shower combination, or shower and within 30 in. (760 mm), measured horizontally, of thevertical plane of the control end wall if there is such a wall.

11.1.6.5.3 Back Wall Grab Bar.

For bathtubs and bathtub-shower combinations bounded on three sides by walls, a grab barshall be provided on the back wall either as a diagonal grab bar as specified in 11.1.6.5.3.1or as a horizontal grab bar as specified in 11.1.6.5.3.2 .

11.1.6.5.3.1* Diagonal Grab Bar on Back Wall.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 43 10/28/2015 10:41 AM

Page 8 of 49

(A)

A diagonal grab bar shall be installed on the back wall with a minimum length of 24 in. (600mm) with its higher end placed closer to the control end wall and located a maximum of 12in. (305 mm) from the control end wall, with a height of 25 in. to 27 in. (635 mm to 685 mm)above the rim of the bathtub.

(B)

The lower end of the diagonal grab bar shall be located at a height of 8 in. to 10 in. (205 mmto 255 mm) above the rim of the bathtub and 28 in. to 30 in. (710 mm to 760 mm) from thecontrol end wall.

11.1.6.5.3.2 Horizontal Grab Bar on Back Wall.

A horizontal grab bar shall be installed on the back wall at a height of 8 in. to 10 in. (205 mmto 255 mm) above the bathtub rim with one end located a maximum of 12 in. (305 mm) fromthe control end wall and the other end located a maximum of 24 in. (610 mm) from theopposite, or head, end of the bathtub.

11.1.6.5.4* Grab Bar Details.

11.1.6.5.4.1

Grab bars shall be circular in cross section with a minimum diameter of 1 1 ⁄4 in. (32 mm)and a maximum diameter of 2 in. (51 mm).

11.1.6.5.4.2

If attached to a wall, the grab bar shall provide a minimum clearance for hand grasp of 1 1 ⁄2in. (38 mm).

11.1.6.5.4.3

The size and clearance dimensions required by 11.1.6.5.4.1 and 11.1.6.5.4.2 shall beprovided, as a minimum, within the height requirements range and the minimum lengthrequirements range of the other provisions of 11.1.6.5 .

11.1.6.5.5 Grab Bar Structural Loading.

Grab bars shall be designed and constructed to the structural loading conditions accordancewith other provisions of this Code .

Supplemental Information

File Name Description

5000_FR6011_annex_text.docx

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 03 15:52:10 EDT 2015

Committee Statement

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 43 10/28/2015 10:41 AM

Page 9 of 49

CommitteeStatement:

The MEA Egress Committee reviewed the detailed justification submitted with theassociated NFPA 101 PI on which an FR is making similar changes to NFPA 101. Theinjury and death problem with bathtub/shower falls demands attention, as well, inNFPA 5000.

The committee positioned the new material as 7.1.6.5 as it is tied to the other items in7.1.6 related to walking surfaces. MEA is not mandating that grab bars be provided.Rather, it is creating a menu that can be mandatorily referenced by other provisions ofthe Code.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 43 10/28/2015 10:41 AM

Page 10 of 49

A.11.1.6.5 The grab bars required by 11.1.6.5 are designed to improve safety of showering and

bathing by ambulatory users, typically entering and exiting a bath, bathtub-shower combination

or shower facility for showering while standing or for other forms of bathing which can entail

transition to/from a crouching or sitting position.

For grab bar requirements appropriate for other uses and users, especially users with disabilities,

refer to requirements in ICC/ANSI A117.1, Standard for Accessible and Usable Buildings and

Facilities. Generally, the grab bars specified for this Code will not interfere with other grab bars

installed in accordance with requirements of ICC/ANSI A117.1 and they can contribute to

meeting the requirements of ICC/ANSI A117.1 and vice versa. For example, combination

vertical and horizontal grab bars (in an L configuration), as addressed by ICC/ANSI A117.1, can

meet the requirements of this Code for a vertical grab bar. Similarly requirements for a

horizontal grab bar on the back wall are compatible.

Dimensions for height of grab bars are based on typical, mass-produced bathtubs with a wall

height, above the finished floor of about 15 in. (380 mm) and the bottom of the bathtub within 1

to 2 in. (2.5 to 5 mm) of the finished floor elevation. Adjustments to stipulated grab bar height

limits and ranges, referenced to the bath tub rim, should be considered for bath tubs having

higher walls and, thus, rim heights, above the bottom of the tub and, possibly, also the wall

height above the finished floor. ICC/ANSI A117.1 references grab bar height dimensions to the

bathtub rim and, for consistency with this widely used ANSI standard, that convention is

maintained in this Code.

A.11.1.6.5.1.2 The provision of 11.1.6.5.1.2 is intended to ensure that grab bars, if provided

voluntarily—i.e., as non-required—for dedicated showers, meet the requirements of the

section—so that something appearing to be a grab bar can effectively perform as one. However

such grab bars would only be considered non-required in the case of dedicated showers not

involving misstep and fall dangers addressed by 11.1.6.2 and 11.1.6.4. This means that walking

surfaces must be at least as safe, in terms of underfoot conditions, as any other portion of the

means of egress (where, for example, handrails are not required) for users not having mobility

disabilities. This would require exceptionally careful choice, and maintenance, of underfoot

materials as well as very effective control of water within and adjacent to the dedicated shower

facility.

A.11.1.6.5.2.1 Grab bars located where they interfere with sealing, with a shower curtain against

escape of water—especially to the floor surface outside the shower facility—might introduce

safety problems in the form of greatly reduced slip resistance of the walking surface (which

could violate this Code). This is avoided with a 6-in. (150-mm), horizontal separation between

the shower curtain rod and the grab bar. It is assumed that other forms of water control, such as

an installed enclosure, will not interfere with the use of grab bars.

A.11.1.6.5.2.2 A free-standing pole, satisfying requirements for a grab bar, can offer much

flexibility in placement, for example, within the close quarters of a small bathroom where there

is a water closet adjacent to the bathing facility and a single grab bar can serve both facilities.

Where the bathing facility is free standing, without walls, especially with large soaking tubs,

Page 11 of 49

including those on pedestals, the vertical pole-type grab bar is especially useful. The pole also

can solve attachment problems where walls that are nonexistent or difficult to use for installing

conventional, wall-mounted grab bars.

A.11.1.6.5.3.1 Using the mid points of the distance ranges and the minimum distance from the

control end wall results in a 45-degree angle for the diagonal grab bar. Such a diagonal grab bar

(or alternatively, a horizontal grab bar fairly similar to the option provided by 11.1.6.5.3.1 which

meets requirements of ICC/ANSI A117.1) was found suitable in tests performed of several grab

bar options with 103 independent-living seniors with average age of 70. (“Evaluation of Optimal

Bath Grab Bar Placement for Seniors,” by H. Sveistrup, D. Lockett, N. Edwards and F.

Aminzadeh, University of Ottawa with funding by Canada Mortgage and Housing Corporation,

2003.)

A.11.1.6.5.4 The best performing grab bars are in the middle third of the permitted range for

circular diameter. For some grab bar designs, with undulations and other surface geometry

features to improve slip resistance for users’ hands, these dimensions will be nominal with small

variations depending on where measurements are taken. Children and others with smaller hands

will be able to use best the diameters within the lower part of the permitted range. When using a

free-standing pole for a grab bar, structural considerations, especially for stiffness, might dictate

using diameters in the upper part of the permitted range.

Note that a minimum clearance between the grab bar and an adjacent surface is specified. With

grab bars, especially horizontal ones, on which large, downward loads are imposed by the arms

of users, there is some concern about people’s hands slipping into the clear space; however this

can occur even with an absolute 1.5 in. (38 mm) clearance, as some standards specify and most

grab bar designs provide. Thus the main difference in the end result is where, along its length,

the arm gets wedged behind the grab bar, not the complete prevention of this happening at all.

Page 12 of 49

First Revision No. 6012-NFPA 5000-2015 [ Section No. 11.1.9 ]

11.1.9 Impediments to Egress.

Any device or alarm installed to restrict the improper use of a means of egress, and anydevice or system installed to monitor or record use of a means of egress, shall be designedand installed so that it cannot, even in case of failure, impede or prevent emergency use ofsuch means of egress, unless otherwise provided in 11.2.1.6 and Chapters 19 and 21.

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 03 16:11:38 EDT 2015

Committee Statement

CommitteeStatement:

Adding requirement to help ensure that means of egress is not compromised bymonitoring systems.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 43 10/28/2015 10:41 AM

Page 13 of 49

First Revision No. 6001-NFPA 5000-2015 [ Section No. 11.2.1.3.2 ]

11.2.1.3.2

The elevation of the floor surfaces required by 11.2.1.3.1 shall be maintained on both sides ofthe door openings for a distance not less than the width of the widest leaf and not less than 36in. (915 mm) .

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 28 11:32:40 EDT 2015

Committee Statement

CommitteeStatement:

For smaller door leafs the minimum of 36 inches on both sides of the dooraccommodates an adult gait.

ResponseMessage:

Public Input No. 131-NFPA 5000-2015 [Section No. 11.2.1.3.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 43 10/28/2015 10:41 AM

Page 14 of 49

First Revision No. 6003-NFPA 5000-2015 [ Section No. 11.2.1.4.2 ]

11.2.1.4.2* Door Leaf Swing Direction.

Side-hinged or pivoted-swinging door leaves in the required means of egress shall swing inthe direction of egress travel where any of the following conditions exist:

(1) The door assemblies shall serve an area with an occupant load of 50 or more.

(2) The door assemblies shall be used in an exit enclosure.

(3) The requirement of 11.2.1.4.2(2) shall not apply to door assemblies from individualdwelling units that open directly into an exit enclosure.

(4) The door assemblies shall serve a high hazard contents area.

Supplemental Information

File Name Description

5000_FR6003_annex_text.docx

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 03 14:38:31 EDT 2015

Committee Statement

CommitteeStatement:

The annex text serves as an advisory pointer to the new provisions in 11.4.2.1.2and 11.4.2.2.2.

Response Message:

Public Input No. 26-NFPA 5000-2015 [Section No. 11.2.1.4.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 43 10/28/2015 10:41 AM

Page 15 of 49

A.11.2.1.4.2 See 11.4.2.1.2 and 11.4.2.2.2 for door swing direction requirements for working space about electrical equipment.

Page 16 of 49

First Revision No. 6017-NFPA 5000-2015 [ Section No. 11.2.1.5.6 ]

11.2.1.5.6 Electrically Controlled Door Hardware-Release of Electrically Locked Egress DoorAssemblies.

Door assemblies in the means of egress shall be permitted to be electrically locked ifequipped with approved hardware, listed in accordance with ANSI/UL 294, Standard forAccess Control System Units, electrical locking systems released by the operation of doorhardware provided that all of the following criteria are met:

(1) The hardware for egress side occupant release of the electrical lock is affixed to thedoor leaf.

(2) The hardware has an obvious method of operation that is readily operated in the directionof egress under all lighting conditions .

(3) The hardware is capable of being operated with one hand in the direction of egress.

(4) Operation of the hardware directly interrupts the power supply to the electric lock andunlocks the door assembly in the direction of egress.

(5)

(6) Hardware is listed in accordance with UL 294, Standard for Access Control SystemUnits .

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 04 08:37:25 EDT 2015

Committee Statement

CommitteeStatement:

Revising the title and description of this electrical locking arrangement to moreclosely describe the system and to reduce variability of interpretations.

ResponseMessage:

* Loss of power to the hardware automatically electrically unlocks the door assembly inthe direction of egress.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 43 10/28/2015 10:41 AM

Page 17 of 49

First Revision No. 6018-NFPA 5000-2015 [ Section No. 11.2.1.5.11 ]

11.2.1.5.11

Where pairs of door leaves are required in a means of egress, one of the following criteriashall be met:

(1) Each leaf of the pair shall be provided with a releasing device that does not depend onthe release of one door before the other.

(2) Approved automatic flush bolts shall be used and arranged such that both of thefollowing criteria are met:

(a) The door leaf equipped with the automatic flush bolts shall have no doorknob orsurface-mounted hardware.

(b) Unlatching of any leaf shall not require more than one operation.

(3) The door leaf equipped with the automatic flush bolts shall have no doorknob or surface-mounted hardware on the egress side of the door.

(4) Unlatching of any leaf shall not require more than one operation.

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 04 08:47:00 EDT 2015

Committee Statement

CommitteeStatement:

The requirement for no doorknob or surface mounted hardware in (2) (a) is importanton the egress side of the door. While this requirement may or may not be important onthe ingress side of the door, that is outside the scope of 5000.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

14 of 43 10/28/2015 10:41 AM

Page 18 of 49

First Revision No. 6019-NFPA 5000-2015 [ Section No. 11.2.1.6.1 ]

11.2.1.6.1 Delayed-Egress Electrically Locking Systems.

Approved, listed, delayed-egress electrically locking systems shall be permitted to beinstalled on door assemblies serving low and ordinary hazard contents in buildings protectedthroughout by an approved, supervised automatic fire detection system in accordance withSection 55.2, or an approved, electrically supervised automatic sprinkler system inaccordance with Section 55.3, and where permitted in Chapters 15 through 31 and 33through 34 , provided that the criteria of 11.2.1.6.1.1 through 11.2.1.6.1.7 11.2.1.6.1.8 aremet.

Global FR-6036

11.2.1.6.1.1

The provisions of 11.2.1.6.2 for access-controlled egress door assemblies sensor-release ofelectrical locking systems shall not apply to door assemblies with delayed-egress electricallylocking systems.

11.2.1.6.1.2

The door leaves shall unlock in the direction of egress delay of the delayed-egress electricallylocking system shall deactivate allowing unobstructed egress upon actuation of an approved,electrically supervised automatic sprinkler system installed in accordance with Section 55.3,or upon the actuation of any heat detector or not more than two smoke detectors of anapproved, supervised automatic fire detection system installed in accordance with Section55.2.

11.2.1.6.1.3

The door leaves shall unlock in the direction of egress delay of the delayed-egress electricallylocking system shall deactivate allowing unobstructed egress upon loss of power controllingthe lock or locking mechanism.

11.2.1.6.1.4

An irreversible process shall release the electrical lock in the direction of egress within 15seconds upon application of a force to the release device required in 11.2.1.5.11 that shall notbe required to exceed 15 lbf (67 N) nor be required to be continuously applied for more than 3seconds. The initiation of the release process shall activate an audible signal in the vicinity ofthe door opening. Once the lock has been released by the application of force to the releasingdevice, relocking rearming the delay electronics shall be by manual means only.

11.2.1.6.1.5

Where approved by the authority having jurisdiction, a delay not exceeding 30 seconds shallbe permitted.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

15 of 43 10/28/2015 10:41 AM

Page 19 of 49

11.2.1.6.1.6*

On the door leaf adjacent to the release device in the direction of egress, there shall be aspecial sign in letters at least 1 in. (25 mm) high that complies with 11.10.8.1 and 11.10.8.2and reads as follows:

(1) PUSH UNTIL ALARM SOUNDS, DOOR CAN BE OPENED IN 15 SECONDS for doorsthat swing in the direction of egress travel

(2) PULL UNTIL ALARM SOUNDS, DOOR CAN BE OPENED IN 15 SECONDS for doorsthat swing against the direction of egress travel

11.2.1.6.1.7

Emergency lighting The egress side of doors equipped with a delayed-egress electricallylocking system shall be provided in the area of the door assembly with emergency lighting inaccordance with Section 11.9 .

11.2.1.6.1.8

Hardware shall be listed in accordance with UL 294, Standard for Access Control SystemUnits .

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 04 08:49:30 EDT 2015

Committee Statement

CommitteeStatement:

The revisions clarify the requirements of this section, and add a neededrequirement for electrical locking hardware to be listed to UL 294.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

16 of 43 10/28/2015 10:41 AM

Page 20 of 49

First Revision No. 6020-NFPA 5000-2015 [ Section No. 11.2.1.6.2 ]

11.2.1.6.2* Access-Controlled Egress Door Assemblies. Sensor-Release of ElectricalLocking Systems.

Where permitted in Chapters 15 through 31 and 33, door assemblies in the means of egressshall be permitted to be equipped with sensor-release electrical lock locking system hardwarethat prevents egress provided that all of the following criteria are met:

(1) A sensor shall be provided on the egress side, arranged to unlock electrically the doorleaf in the direction of egress upon detection of an approaching occupant.

(2) Door leaves shall automatically electrically unlock in the direction of egress upon loss ofpower to the sensor or to the part of the access control locking system that electricallylocks the door leaves.

(3) Door locks shall be arranged to electrically unlock in the direction of egress from amanual release device complying with all of the following criteria:

(a) The manual release device shall be located on the egress side, 40 in. to 48 in.(1015 mm to 1220 mm) vertically above the floor, and within 60 in. (1525 mm) of thesecured door openings.

(b) The manual release device shall be readily accessible and clearly identified by asign that reads as follows: PUSH TO EXIT.

(c) When operated, the manual release device shall result in direct interruption ofpower to the lock — independent of the locking system electronics — and the lockshall remain unlocked for not less than 30 seconds.

(4) Activation of the building fire-protective signaling system, if provided, shall automaticallyelectrically unlock the door leaves in the direction of egress, and the door leaves shallremain electrically unlocked until the fire-protective signaling system has been manuallyreset.

(5) The activation of manual fire alarm boxes that activate the building fire-protectivesignaling system specified in 11.2.1.6.2(4) shall not be required to unlock the doorleaves.

(6) Activation of the building automatic sprinkler or fire detection system, if provided, shallautomatically electrically unlock the door leaves in the direction of egress, and the doorleaves shall remain electrically unlocked until the fire-protective signaling system hasbeen manually reset.

(7) The egress side of access-controlled sensor-released electrically locked egress doors,other than existing access controlled sensor-released electrically locked egress doors,shall be provided with emergency lighting in accordance with Section 11.9.

(8) Hardware shall be listed in accordance with UL 294, Standard for Access Control Units .

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

17 of 43 10/28/2015 10:41 AM

Page 21 of 49

City:

State:

Zip:

Submittal Date: Tue Aug 04 09:15:44 EDT 2015

Committee Statement

CommitteeStatement:

The title and description of these special locking arrangements are renamed to moreclosely describe the permitted special locking arrangement. This will help to reducevariability in interpretations. Also, the revision adds a requirement for the hardware fornew systems to comply with UL 294.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

18 of 43 10/28/2015 10:41 AM

Page 22 of 49

First Revision No. 6021-NFPA 5000-2015 [ Section No. 11.2.1.6.3 ]

11.2.1.6.3 Elevator Lobby Exit Access Door Assemblies Locking.

Where permitted in Chapters 16 through 31, door assemblies separating the elevator lobbyfrom the exit access required by 11.4.1.6.1 shall be permitted to be electrically locked,provided that all the following criteria are met:

(1) The lock electrical locking hardware is listed in accordance with ANSI/ UL 294.

(2) The building is protected throughout by a fire alarm system in accordance with Section55.2.

(3) The building is protected throughout by an approved, electrically supervised automaticsprinkler system in accordance with Section 55.3.

(4) Waterflow in the sprinkler system required by 11.2.1.6.3(3) is arranged to initiate thebuilding fire alarm system.

(5) The elevator lobby is protected by an approved, supervised smoke detection system inaccordance with Section 55.2.

(6) Detection of smoke by the detection system required by 11.2.1.6.3(5) is arranged toinitiate the building fire alarm system and notify building occupants.

(7) Initiation of the building fire alarm system by other than manual fire alarm boxes unlocksthe electrical locks on elevator lobby doors.

(8) Loss of power to the elevator lobby electronic electrical lock system unlocks theelectrical locks on the elevator lobby door assemblies.

(9) Once unlocked, the elevator lobby doors remain electrically unlocked until the buildingfire alarm system has been manually reset.

(10) Where the elevator lobby doors remain mechanically latched after being electricallyunlocked, latch releasing hardware in accordance with 11.2.1.5.5 is affixed to the doors.

(11) A two-way communication system is provided for communication between the elevatorlobby and a central control point that is constantly staffed.

(12) The central control point staff required by 11.2.1.6.3(11) is capable, trained, andauthorized to provide emergency assistance.

(13) The provisions of 11.2.1.6.1 for delayed-egress electrically locking systems are notapplied to the elevator lobby doors.

(14)

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

* The provisions of 11.2.1.6.2 for access-controlled egress door assemblies sensor-release of electrically locking systems are not applied to the elevator lobby doors.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

19 of 43 10/28/2015 10:41 AM

Page 23 of 49

Zip:

Submittal Date: Tue Aug 04 09:28:04 EDT 2015

Committee Statement

Committee Statement: Recommended revisions are intended to clarify requirements.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

20 of 43 10/28/2015 10:41 AM

Page 24 of 49

First Revision No. 6004-NFPA 5000-2015 [ Section No. 11.2.1.7 ]

11.2.1.7* Panic Hardware and Fire Exit Hardware.

11.2.1.7.1

Where a door assembly is required to be equipped with panic hardware or fire exit hardware,such hardware shall meet all of the following criteria:

(1) It shall consist of a cross bar or push pad, the actuating portion of which extends acrossnot less than one-half of the width of the door leaf.

(2) It shall be mounted not less than 34 in. (865 mm), and not more than 48 in. (1220 mm),above the floor.

(3) It shall be constructed so that a horizontal force not to exceed 15 lbf (67 N) actuates thecross bar or push pad and latches.

11.2.1.7.2*

Only approved fire exit hardware shall be used on fire protection–rated door assemblies.

11.2.1.7.2.1

Panic hardware and fire exit hardware shall comply with ANSI/ UL 305, Standard for SafetyPanic Hardware, and ANSI/BHMA A156.3, Exit Devices.

11.2.1.7.3

Required panic hardware and fire exit hardware in other than detention and correctionaloccupancies, as otherwise provided in 21.2.11, shall not be equipped with any locking device,set screw, or other arrangement that prevents the release of the latch when pressure isapplied to the releasing device.

11.2.1.7.4

Devices that hold the latch in the retracted position shall be prohibited on fire exit hardware,unless listed and approved for that purpose.

Supplemental Information

File Name Description

5000_FR6004-annex_text.docx

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 03 14:52:00 EDT 2015

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

21 of 43 10/28/2015 10:41 AM

Page 25 of 49

Committee Statement

CommitteeStatement:

The annex serves as an advisory pointer to the new provisions of 11.4.2.1.2and 11.4.2.2.2.

Response Message:

Public Input No. 27-NFPA 5000-2015 [Section No. 11.2.1.7]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

22 of 43 10/28/2015 10:41 AM

Page 26 of 49

A.11.2.1.7 See 11.4.2.1.2 and 11.4.2.2.2 for door unlatching requirements for working space about electrical equipment.

Page 27 of 49

First Revision No. 6022-NFPA 5000-2015 [ New Section after 11.2.1.8.3 ]

11.2.1.8.4 Delayed Action Closers.

Doors required to be self-closing and not required to be automatic closing shall be permittedto be equipped with delayed action closers.

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 04 09:44:47 EDT 2015

Committee Statement

CommitteeStatement:

Delayed action closers will be of help to individuals needing extra time to movethrough the door opening. Currently the Code does not address where they can andcan't be used. See FR-6006 in Chapter 3 for definition of 'delayed action closer'.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

23 of 43 10/28/2015 10:41 AM

Page 28 of 49

First Revision No. 6023-NFPA 5000-2015 [ Section No. 11.2.1.9.1 ]

11.2.1.9.1* General.

Where means of egress door leaves are operated by power upon the approach of a person, orare provided with power-assisted manual operation, the design shall be such that, in the eventof power failure, the door leaves open manually to allow egress travel or close whennecessary to safeguard the means of egress.

11.2.1.9.1.1

Power-operated swinging doors, power-operated sliding doors, and power-operated foldingdoors shall comply with ANSI/BHMA A156.10, Power Operated Pedestrian Doors .

11.2.1.9.1.2

Power-assisted swinging doors and low-energy power-operated swinging doors shall complywith ANSI/BHMA A156.19, Power Assist and Low Energy Power Operated Doors .

11.2.1.9.1.3

Low-energy power-operated sliding doors and low-energy power-operated folding doorsshall comply with ANSI/BHMA A156.38, Low Energy Power Operated Sliding and FoldingDoors .

11.2.1.9.1.4

The forces required to manually open the door leaves specified in 11.2.1.9.1 shall not exceedthose required in 11.2.1.4.5, except that the force required to set the door leaf in motion shallnot exceed 50 lbf (222 N).

11.2.1.9.1.5

The door assembly shall be designed and installed so that, when a force is applied to the doorleaf on the side from which egress is made, it shall be capable of swinging from any position toprovide full use of the required width of the opening in which it is installed. (See 11.2.1.4.)

11.2.1.9.1.6

On the egress side of each door opening, there shall be a special sign that complies with11.10.8.1 and 11.10.8.2 and reads as follows:

IN EMERGENCY, PUSH TO OPEN

11.2.1.9.1.7

The sign required by 11.2.1.9.1.611.2.1.9.1.611.2.1.9.1.3 shall be in letters not less than 1 in.(25 mm) high on a contrasting background.

11.2.1.9.1.8

Sliding power-operated door assemblies in exit access serving an occupant load of fewer than50 that manually open in the direction of door leaf travel, with forces not exceeding thoserequired in 11.2.1.4.5, shall not be required to have a swing-out feature required by11.2.1.9.1.511.2.1.9.1.511.2.1.9.1.2 . The required sign shall read as follows:

IN EMERGENCY, SLIDE TO OPEN

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

24 of 43 10/28/2015 10:41 AM

Page 29 of 49

11.2.1.9.1.9

In the emergency breakout mode, a door leaf located within a two-leaf opening shall beexempt from the minimum 32 in. (810 mm) single-leaf requirement of 11.2.1.2.3, provided thatthe clear width of the single leaf is not less than 30 in. (760 mm).

11.2.1.9.1.10

For a biparting sliding door assembly in the emergency breakout mode, a door leaf locatedwithin a multiple-leaf opening shall be exempt from the minimum 32 in. (810 mm) single-leafrequirement of 11.2.1.2.3.2(1) if a clear opening of not less than 32 in. (810 mm) is providedby all leafs leaves broken out.

11.2.1.9.1.11

Door assemblies complying with 11.2.1.14 shall be permitted to be used.

11.2.1.9.1.12

The requirements of 11.2.1.9.1 through 11.2.1.9.1.1111.2.1.9.1.1111.2.1.9.1.8 shall not applyin detention and correctional occupancies where otherwise provided in 21.2.11.

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 04 10:09:20 EDT 2015

Committee Statement

CommitteeStatement:

This revision adds requirements for new doors to comply with the set ofANSI/BHMA expert standards on power doors. This is reasonable for new doorinstallations.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

25 of 43 10/28/2015 10:41 AM

Page 30 of 49

First Revision No. 6024-NFPA 5000-2015 [ Section No. 11.2.1.10.1 ]

11.2.1.10.1

Revolving door assemblies shall comply with all of the following:

(1) Revolving door assemblies shall comply with ANSI/BHMA A156.27, Power and ManualOperated Revolving Doors , and shall be installed in accordance with the manufacturer'sinstallation instruction.

(2) Revolving door wings shall be capable of being collapsed into a book-fold position orbreakout for egress in accordance with ANSI/BHMA A156.27 .

(3) When revolving door wings are collapsed into the book-fold position or breakout position ,the parallel egress paths formed shall provide an aggregate width of 36 in. (915 mm).

(4) Revolving door assemblies shall not be used within 10 ft (3050 mm) of the foot or the topof stairs or escalators.

(5) Under all conditions, there shall be a dispersal area acceptable to the authority havingjurisdiction between the stairs or escalators and revolving door assemblies.

(6) The revolutions per minute (rpm) of revolving door wings shall not exceed the values inTable 11.2.1.10.1 ANSI/BHMA A156.27 .

(7) Each revolving door assembly shall have a conforming side-hinged swinging doorassembly in the same wall as the revolving door and within 10 ft (3050 mm) of therevolving door.

(8) Revolving door assemblies shall be permitted without the adjacent swinging doorassemblies required by 11.2.1.10.1(6) for street floor elevator lobbies, provided that nostairways or door openings from other parts of the building discharge through the lobby,and the lobby has no occupancy other than as a means of travel between the elevatorsand street.

Table 11.2.1.10.1 Revolving Door Maximum Speed

InsideDiameter

Power Driven–Type Speed Control(rpm)

Manual-Type Speed Control(rpm)

ft/in. mm

6 ft 6 in. 1980 11 12

7 ft 2135 10 11

7 ft 6 in. 2285 9 11

8 ft 2440 9 10

8 ft 6 in. 2590 8 9

9 ft 2745 8 9

9 ft 6 in. 2895 7 8

10 ft 3050 7 8

Submitter Information Verification

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

26 of 43 10/28/2015 10:41 AM

Page 31 of 49

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 04 10:13:11 EDT 2015

Committee Statement

CommitteeStatement:

The revisions introduce the reference standard requirements from ANSI/BHMA A156.27for Revolving Doors. BHMA A156.27 includes provisions for acceptable door speeds(max. RPM), egress / breakout requirements for the various types and configurations ofrevolving doors, glazing (consistent with Federal and IBC requirements for safetyglazing), kinetic energy, and safety requirements such as emergency stop switches,sensors, and speed controls. These provisions enhance current NFPA requirements fornew revolving doors.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

27 of 43 10/28/2015 10:41 AM

Page 32 of 49

First Revision No. 6002-NFPA 5000-2015 [ Section No. 11.2.1.10.4 ]

11.2.1.10.4

The requirement of 11.2.1.10.3 shall not apply to revolving door wings, provided that thecollapsing force is reduced to a force not to exceed 130 lbf (580 N) under the all of thefollowing conditions:

(1) Power failure, or removal of power to the device holding the wings in position

(2) Actuation of the automatic sprinkler system, where such a system is provided

(3) Actuation of a smoke detection system that is installed to provide coverage in all areaswithin the building that are within 75 ft (23 m) of the revolving door assemblies

(4) Actuation of a clearly identified manual control switch in an approved location thatreduces the holding force to a force not to exceed 130 lbf (580 N)

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jul 28 11:42:06 EDT 2015

Committee Statement

Committee Statement: This revision corrects a grammatical error.

Response Message:

Public Input No. 133-NFPA 5000-2015 [Section No. 11.2.1.10.4]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

28 of 43 10/28/2015 10:41 AM

Page 33 of 49

First Revision No. 6016-NFPA 5000-2015 [ Section No. 11.2.2.6.1.8 ]

11.2.2.6.1.8

The signage shall be in a position that is visible from within the stair enclosure when the doorleaf is in the open or closed position.

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 04 08:31:16 EDT 2015

Committee Statement

CommitteeStatement:

The sign is for providing persons who are within the stair enclosure with usefulinformation. There is no need to see the sign before entering the enclosure. There isno intent to require a vision panel for viewing the sign before entering the enclosure.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

29 of 43 10/28/2015 10:41 AM

Page 34 of 49

First Revision No. 6014-NFPA 5000-2015 [ Section No. 11.2.2.6.5.10 ]

11.2.2.6.5.10 Materials.

Exit stair path markings shall be made of any material, including paint, provided that anelectrical charge is not required to maintain the required luminescence. Such materials shallinclude, but shall not be limited to, self-luminous materials and photoluminescent materials.Materials shall comply with one of the following either (1) or (2) that follows :

(1) ASTM E 2072 E2072 , Standard Specification for Photoluminescent (Phosphorescent)Safety Markings, with the following exceptions: and ASTM E2073, Standard TestMethod for Photopic Luminance of Photoluminescent (Phosphorescent) Markings

The charging source shall be 1 ft-candle (10.8 lux) of fluorescent illumination for60 minutes.

The minimum luminance shall be 5 millicandelas/m 2 after 90 minutes.

(2) ANSI/ UL 1994, Standard for Luminous Egress Path Marking Systems

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 04 08:19:03 EDT 2015

Committee Statement

CommitteeStatement:

Both ASTM E2072 and ASTM E2073 need to be referenced to cover the subjectadequately. The previous exceptions can be deleted as ASTM E2072-14 calls forluminance of not less than 30 mcd/m2 at 10 minutes and 5 mcd/m2 at 90 minutes.ASTM E2073-10 addresses how the luminance is measured. The formatting of theintroduction is changed to use the words “shall comply with either (1) or (2) that follows”as both of the standards in part (1) must be followed; the previous wording of “shallcomply with ONE of the following” could confuse the issue.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

30 of 43 10/28/2015 10:41 AM

Page 35 of 49

First Revision No. 6025-NFPA 5000-2015 [ Section No. 11.2.3.9 ]

11.2.3.9 Enclosure Pressurization.

11.2.3.9.1*

Smokeproof enclosures using pressurization shall use an approved engineered system with adesign pressure difference across the barrier of not less than 0.05 in. water column (12.5 Pa)in sprinklered buildings, or 0.10 in. water column (25 Pa) in nonsprinklered buildings, and shallbe capable of maintaining these pressure differences under likely conditions of stack effect orwind. The pressure difference across doors shall not exceed that which allows the door tobegin to be opened by a force of 30 lbf (133 N) in accordance with 11.2.1.4.5. Smokeproofenclosures using pressurization shall be in accordance with NFPA 92 .

11.2.3.9.2

Equipment, control wiring, power wiring, and ductwork for pressurization shall be located inaccordance with one of the following specifications:

(1) Exterior to the building and directly connected to the enclosure by ductwork enclosed innoncombustible or limited-combustible construction

(2) Within the enclosure with intake and exhaust air vented directly to the outside or throughductwork enclosed by a 2-hour fire resistance–rated separation

(3) Within the building, under the following conditions:

(a) Where the equipment and ductwork are separated from the remainder of thebuilding, including other mechanical equipment, by a 2-hour fire resistance–ratedseparation

(b) Where the building, including the enclosure, is protected throughout by anapproved, electrically supervised automatic sprinkler system installed in accordancewith Section 55.3, and the equipment and ductwork are separated from theremainder of the building, including other mechanical equipment, by not less than a1-hour fire resistance–rated separation.

11.2.3.9.3

In all cases specified by 11.2.3.9.2(1) through (3), openings into the required fireresistance–rated separations shall be limited to those needed for maintenance and operationand shall be protected by self-closing fire protection–rated devices.

11.2.3.9.4

The requirement of 11.2.3.9.2 shall not apply to any of the following:

(1) Control wiring and power wiring utilizing a 2-hour rated cable or cable system

(2) Where encased with not less than 2 in. (51 mm) of concrete

(3) Control wiring and power wiring protected by a listed electrical circuit protectivesystem with not less than a 2-hour fire resistive rating

Submitter Information Verification

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

31 of 43 10/28/2015 10:41 AM

Page 36 of 49

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 04 10:25:11 EDT 2015

Committee Statement

CommitteeStatement:

The fire safety criteria applicable to air traffic control towers (ATCTs) are originallybased on an agreement between the operators and controllers utilizing the ATCTs. Thechanges relate to providing extra protection for the controllers and fire service.

ATCTs create a unique hazard. ATCTs typically have a limited number of occupants. Inaddition, occupants must be awake and alert. The hazard associated with ATCTs isaffected by the building’s limited uses, height, and the potential delay in evacuationbecause of the handoff of flights.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

32 of 43 10/28/2015 10:41 AM

Page 37 of 49

First Revision No. 6026-NFPA 5000-2015 [ Section No. 11.2.3.12 ]

11.2.3.12 Emergency Power Supply System (EPSS).

A Type 60, Class 2, Level 2, emergency power supply system (EPSS) for mechanicalventilation equipment and enclosure pressurization systems shall be provided in accordancewith NFPA 110, Standard for Emergency and Standby Power Systems . The generator shallbe located in a room having a minimum 1-hour fire resistance–rated separation from theremainder of the building. The generator shall have a fuel supply not less than that which isadequate to operate the equipment for 2 hours. The transfer switch equipment and thestandby panelboard shall be located in a room having a minimum 1-hour fire resistance–ratedseparation from the remainder of the building and normal electrical equipment.

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 04 10:30:41 EDT 2015

Committee Statement

CommitteeStatement:

The fire safety criteria applicable to air traffic control towers (ATCTs) are originallybased on an agreement between the operators and controllers utilizing the ATCTs. Thechanges relate to providing extra protection for the controllers and fire service.

ATCTs create a unique hazard. ATCTs typically have a limited number of occupants. Inaddition, occupants must be awake and alert. The hazard associated with ATCTs isaffected by the building’s limited uses, height, and the potential delay in evacuationbecause of the handoff of flights.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

33 of 43 10/28/2015 10:41 AM

Page 38 of 49

First Revision No. 6015-NFPA 5000-2015 [ Section No. 11.2.4.1.2 ]

11.2.4.1.2*

Horizontal exits shall be permitted to be substituted for other exits where the total egresscapacity and the total number of the other exits (stairs, ramps, doors leading outside thebuilding) is not less than half that required for the entire area of the building or connectedbuildings, and provided that none of the other exits is a horizontal exit provided that both ofthe following are met , unless otherwise permitted by 11.2.4.1.3.

(1) A minimum of half of the number of exits from any compartment created by horizontalexits is provided by other than horizontal exits

(2) A minimum of half of the egress capacity required for any compartment created byhorizontal exits is provided by other than horizontal exits

Supplemental Information

File Name Description

5000_FR6015_annex_text.docx

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 04 08:25:30 EDT 2015

Committee Statement

CommitteeStatement:

The current text of 11.2.4.1.2 does not explain the “maximum 50 percent” criteriacorrectly. Each compartment created by horizontal exits needs to prove that at leasthalf the number of exits and at least half the capacity is provided by something otherthan horizontal exits.

This First Revision also revises annex text. The current text of A.11.2.4.1.2 is incorrect.Extra door openings in a horizontal exit must either be subject to the horizontal exitmaximum 50 percent criterion or considered as convenience openings that are notcredited with satisfying any means of egress requirements.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

34 of 43 10/28/2015 10:41 AM

Page 39 of 49

A.11.2.4.1.2* Example… Assume that… Another option… It is not the intent of 11.2.1.4.2 to limit the number of doors in the fire barrier forming the horizontal exit. Where doors other than those serving as horizontal exits are provided, such doors are permitted to be considered as part of the exit access and not as exits convenience openings that are not credited with satisfying any means of egress requirements.

Page 40 of 49

First Revision No. 6005-NFPA 5000-2015 [ Section No. 11.4.2 ]

11.4.2 Spaces About Electrical Equipment.

11.4.2.1 600 Volts, Nominal, or Less.

The minimum number of means of egress for working space about electrical equipment shallbe in accordance with NFPA 70, National Electrical Code , Article 110.26(C).

11.4.2.1.1 Number of Means of Egress.

The minimum number of means of egress for working space about electrical equipment shallbe in accordance with NFPA 70 , Article 110.26(C).

11.4.2.1.2 Door Unlatching and Direction of Door Swing.

The method of door unlatching and direction of door swing for working space about electricalequipment shall be in accordance with NFPA 70 , Article 110.26(C)(3).

11.4.2.2 Over 600 Volts, Nominal.

The minimum number of means of egress for working space about electrical equipment shallbe in accordance with NFPA 70, Article 110.33(A).

11.4.2.2.1 Number of Means of Egress.

The minimum number of means of egress for working space about electrical equipment shallbe in accordance with NFPA 70 , Article 110.33(A).

11.4.2.2.2 Door Unlatching and Direction of Door Swing.

The method of door unlatching and direction of door swing for working space about electricalequipment shall be in accordance with NFPA 70 , Article 110.33(A)(3).

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Mon Aug 03 15:00:48 EDT 2015

Committee Statement

CommitteeStatement:

Code users should be forewarned that the NEC includes requirements on the means ofdoor unlatching and direction of door swing for spaces about electrical equipment.Design and installation to the only the requirements in NFPA 5000 will not result in acomplying situation. It is better to know about the requirement and meet it at the time ofdesign/construction than to be denied a Certificate of Occupancy.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

35 of 43 10/28/2015 10:41 AM

Page 41 of 49

Public Input No. 25-NFPA 5000-2015 [Section No. 11.4.2]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

36 of 43 10/28/2015 10:41 AM

Page 42 of 49

First Revision No. 6027-NFPA 5000-2015 [ Section No. 11.7.2 ]

11.7.2 Exit Discharge Through Interior Building Areas.

Exits shall be permitted to discharge through interior building areas, provided that all of thefollowing criteria are met:

(1) Not more than 50 percent of the required number of exit stairs serving normally occupiedareas of each floor, and not more than 50 percent of the exit stair capacity required fornormally occupied areas of each floor, shall discharge through areas on any level ofdischarge, except that 100 percent of the exits shall be permitted to discharge throughareas on any level of discharge in detention and correctional occupancies as otherwiseprovided in 21.2.7.2.

(2) Each level of discharge shall discharge directly outside at the finished ground level, ordischarge directly outside and provide access to the finished ground level by outsidestairs or outside ramps.

(3) The interior exit discharge shall lead to a free and unobstructed way to the exterior of thebuilding, and such way shall be readily visible and identifiable apparent or shall beidentifiable by exit signage from the point of discharge from the exit.

(4) The interior exit discharge shall be protected by one of the following methods:

(a) The level of discharge shall be protected throughout by an approved automaticsprinkler system in accordance with Section 55.3, or the portion of the level ofdischarge used for interior exit discharge shall be protected by an approvedautomatic sprinkler system in accordance with Section 55.3 and shall be separatedfrom the nonsprinklered portion of the floor by fire barriers with a fire resistancerating meeting the requirements for the enclosure of exits. (See 11.1.3.2.1.)

(b) The interior exit discharge area shall be in a vestibule or foyer that meets all of thefollowing criteria:

i. The depth from the exterior of the building shall be not more than 10 ft (3050mm), and the length shall be not more than 30 ft (9.1 m).

ii. The foyer shall be separated from the remainder of the level of discharge byfire barriers with minimum 1-hour 1 hour fire resistance rating.

iii. The foyer shall serve only as a means of egress and shall include an exitdirectly to the outside.

(5) The entire area on the level of discharge shall be separated from areas below byconstruction having a fire resistance rating not less than that required for the exitenclosure, unless otherwise provided in 11.7.2(6).

(6) Levels below the level of discharge in an atrium shall be permitted to be open to the levelof discharge where such level of discharge is protected in accordance with 8.12.3.

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

37 of 43 10/28/2015 10:41 AM

Page 43 of 49

City:

State:

Zip:

Submittal Date: Tue Aug 04 10:36:25 EDT 2015

Committee Statement

CommitteeStatement:

The only change being made is to subitem (3).

The provision of 11.7.2(3) is routinely interpreted that exit signage meets the readilyvisible and identifiable unobstructed way requirement. Adding the exit signage languageto the Code makes the requirement explicitly clear and removes the need to interpretthe provision. This change will ensure design professionals and AHJs are clearly awareof the identifiable free and unobstructed way interior exit discharge requirements.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

38 of 43 10/28/2015 10:41 AM

Page 44 of 49

First Revision No. 6028-NFPA 5000-2015 [ Section No. 11.7.3.3 ]

11.7.3.3*

Stairs and ramps that continue more than one-half story beyond below the level of dischargeshall be provided with an approved means to prevent or dissuade occupants from travelingpast the level of discharge during emergency building evacuation.

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 04 10:40:23 EDT 2015

Committee Statement

CommitteeStatement:

By using the word "Beyond," the requirement, as it is currently written, applies tooccupants traveling in both directions past the level of exit discharge. This means thatwhere a stair has points of entry on levels above and below the level of exit discharge,the requirement to dissuade occupants from passing that level would apply in bothdirections. This would essentially create the need for multiple gates, doors, or othermeans of disrupting egress within the stair; one above and one below the level of exitdischarge.

By replacing the word "Beyond" with the word "Below," the requirement is clarified suchthat it only applies to occupants traveling in a downward direction past the level of exitdischarge.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

39 of 43 10/28/2015 10:41 AM

Page 45 of 49

First Revision No. 6029-NFPA 5000-2015 [ Section No. 11.8.1.1 ]

11.8.1.1*

Illumination of means of egress shall be provided in accordance with Section 11.8 for everybuilding and structure where required in Chapters 15 through 31 and 33 through 34. For thepurposes of this requirement, exit access shall include only designated stairs, aisles, corridors,ramps, escalators, and passageways leading to an exit. For the purposes of this requirement,exit discharge shall include only designated stairs, aisles, corridors, ramps, escalators,walkways, and exit passageways leading to a public way.

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 04 10:42:49 EDT 2015

Committee Statement

Committee Statement: Exit passageways are exits and not part of exit discharge.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

40 of 43 10/28/2015 10:41 AM

Page 46 of 49

First Revision No. 6030-NFPA 5000-2015 [ Section No. 11.9.2.4 ]

11.9.2.4

Emergency generators providing and related transfer switch equipment that provide power toemergency lighting systems shall be installed, tested, and maintained in accordance withNFPA 110. Stored electrical energy systems, where required in this Code, other than batterysystems for emergency luminaires in accordance with 11.9.2.5, shall be installed and tested inaccordance with NFPA 111, Standard on Stored Electrical Energy Emergency and StandbyPower Systems .

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 04 10:49:22 EDT 2015

Committee Statement

Committee Statement: Transfer switches are a fundamental part of the emergency power chain.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

41 of 43 10/28/2015 10:41 AM

Page 47 of 49

First Revision No. 6031-NFPA 5000-2015 [ Section No. 11.12.2 ]

11.12.2

A common path of travel not exceeding 100 ft (30 m) shall be permitted in any of the followinglocations:

(1) In buildings protected throughout by an approved, electrically supervised automaticsprinkler system in accordance with Section 55.3

(2) In mechanical equipment rooms with no fuel-fired equipment

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 04 11:09:27 EDT 2015

Committee Statement

CommitteeStatement:

The current language can be misinterpreted as only permitting a common path oftravel of 100 ft (30 m) if both conditions are met. The proposed change adds languagethat provides clarification and is consistent with the formatting of conditional provisionsin the remainder of the document.

ResponseMessage:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

42 of 43 10/28/2015 10:41 AM

Page 48 of 49

First Revision No. 6013-NFPA 5000-2015 [ Chapter E [Title Only] ]

Supplemental Evacuation Equipment

Submitter Information Verification

Submitter Full Name: Ron Cote

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Tue Aug 04 08:15:42 EDT 2015

Committee Statement

Committee Statement: Correction to use proper term as used elsewhere in Annex E.

Response Message:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

43 of 43 10/28/2015 10:41 AM