FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop... · 2009. 5. 11. ·...

21
Hilti, Inc., 5400 South 122 nd East Avenue, Tulsa, OK 74121, (800) 879-8000 FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and Installation Data UL Certificate of Compliance LEED information MSDS UL Details Wood Floor Assemblies FC 7013c - Max. 4” (28 Ga) diameter sheet metal duct w/o damper FC 7025b - Max. 10” (28Ga) or 4” (30 Ga) diameter sheet metal duct w/o damper FC 7042a - Steel strut, steel cable, steel rod, steel angle FC 8014d - Single HVAC Line Set Gypsum Wall Assemblies WL 7040g - Max. 48” x 24” sheet metal duct w/o damper WL 7042d - Max. 20” spiral wound duct w/o damper, or 12” sheet metal duct WL 7096a - Max. 13” x 12” sheet metal duct w/o damper WL 7059a - Max. 24” x 12”sheet metal duct with glass fiber duct insulation WL 7143b - Max. 24” x 24” sheet metal duct w/o damper WL 8047c - HVAC Line Set

Transcript of FIRESTOP SUBMITTAL PACKAGEhiltiman.com/xsuxxxxittxx_xackxxgxs/HVAC_Firestop... · 2009. 5. 11. ·...

  • Hilti, Inc., 5400 South 122nd East Avenue, Tulsa, OK 74121, (800) 879-8000

    FIRESTOP SUBMITTAL PACKAGE

    HVAC

    Materials

    FS-ONE Intumesent CaulkCP 606 Acrylic

    Includes:Technical and Installation DataUL Certificate of Compliance

    LEED informationMSDS

    UL Details

    Wood Floor AssembliesFC 7013c - Max. 4” (28 Ga) diameter sheet metal duct w/o damperFC 7025b - Max. 10” (28Ga) or 4” (30 Ga) diameter sheet metal duct w/o damperFC 7042a - Steel strut, steel cable, steel rod, steel angleFC 8014d - Single HVAC Line Set

    Gypsum Wall AssembliesWL 7040g - Max. 48” x 24” sheet metal duct w/o damperWL 7042d - Max. 20” spiral wound duct w/o damper, or 12” sheet metal ductWL 7096a - Max. 13” x 12” sheet metal duct w/o damperWL 7059a - Max. 24” x 12”sheet metal duct with glass fiber duct insulationWL 7143b - Max. 24” x 24” sheet metal duct w/o damperWL 8047c - HVAC Line Set

  • Product Information

    Chap

    ter

    Tab

    sC

    hap

    ter

    Tab

    sC

    hap

    ter

    Tab

    sC

    hap

    ter

    Tab

    sC

    hap

    ter

    Tab

    s

    Hilti, Inc. (U.S.) 1-800-879-8000 • www.us.hilti.com • en español 1-800-879-5000 • Hilti Firestop Systems Guide 2007

    Hilti. Outperform. Outlast.

    sodfm,ev iJdjfiwhriuh. NöoWE

    Z8Z23awöp3i4eß0288u27 uze

    4i5kirdwiloi4jtf-öx-.vbvbvh, ireiv

    u9+ß12oeoo

    tlke0´9^)&(/R 84tc )v 6453

    FS-ONEHigh Performance Intumescent Firestop Sealant

    FS-ONE Technical DataChemical basis Water-based intumescent acrylic

    dispersionColor RedApplication temperature 40°F to 104°F (5°C to 40°C) Skin forming time Approx. 20-30 min.Curing time Approx. 2 mm / 3 daysMovement capability Approx. 5%Expansion rate Up to 3-5 times (unrestricted): original volumeTemperature resistance (cured) –40°F to 212°F (–40°C to 100°C)Surface burning characteristics Flame Spread: 0(ASTM E 84-96) Smoke Development: 5Sound transmission classification 56 (Relates to specific construction)(ASTM E 90-99) ApprovalsCalifornia State Fire Marshal Listing No. 4485-1200:108City of New York MEA 326-96-M Vol. IVTested in accordance with • UL 1479

    • ASTM E 814• ASTM E 84

    At 73°F (23°C) and 50% relative humidity

    FILL, VOID OR CAVITY MATERIALFOR USE IN THROUGH-PENETRATION

    FIRESTOP SYSTEMSSEE UL FIRE RESISTANCE DIRECTORY

    66Y7

    FMAPPROVED

    For Penetration Fire Stops.Consult the Factory Mutual Research Corporation Approval Guide.

    R

    C

    LASSIFIED

    FILL, VOID OR CAVITY MATERIALS CLASSIFIED BY

    UNDERWRITERS LABORATORIES, INC.FOR USE IN TROUGH-PENETRATION

    FIRESTOP SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY

    66Y7

    Product description• Intumescent (expands when exposed to fire) firestop sealant that

    helps protect combustible and non-combustible penetrations forup to 4 hours fire rating

    Product features• Smoke, gas and water resistant after material has cured

    • Contains no halogen, solvents or asbestos

    • High fire rating properties

    • Water based, easy to clean

    • Protects most typical firestop penetration applications

    • Can be painted

    • Single component systems available

    • Meets LEED™ requirements for indoor environmental quality credit4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paintsand Coatings

    Areas of application• Steel, copper and EMT pipes

    • Insulated steel and copper pipes

    • Cable bundles

    • Closed or vented plastic pipes

    • HVAC penetrations

    For use with• Concrete, masonry, drywall and wood floor assemblies

    • Wall and floor assemblies rated up to 4 hours

    Examples• Sealing around plastic pipe penetrations in fire rated construction

    • Sealing around combustible and non-combustible penetrations infire rated construction

    1. Clean opening. 2. Pack mineral wool.(If required)

    3. Apply FS-ONE. 4. Smooth FS-ONE.

    5. Leave completedseal undisturbed for 48hours.

    6. Fasten identificationplate (if required).

    1. Clean opening. 2. Pack mineral wool.(If required)

    3. Apply FS-ONE. 4. Smooth FS-ONE.

    5. Leave completedseal undisturbed for 48hours.

    6. Fastenidentification plate (ifrequired).

    FirestopSystem

    Notice • Before handling, read Material Safety DataSheet and

    product label for safe usage and health information.

    • Instructions below are general guidelines — alwaysrefer to the applicable drawing in the UL FireResistance Directory or Hilti Firestop Systems Guidefor complete installation information

    Opening 1. Clean the opening. Surfaces to which FS-ONE will be

    applied should be cleaned of loose debris, dirt, oil,moisture, frost and wax. Structures supportingpenetrating items must be installed in compliancewith local building and electrical standards.

    Application of firestop sealant 2. Install the prescribed backfilling material type and

    depth to obtain the desired rating (if required). Leavesufficient depth for applying FS-ONE.

    3. Application of firestop sealant: Apply FS-ONE to therequired depth in order to obtain the desired fire rating.Make sure FS-ONE contacts all surfaces to providemaximum adhesion. For application of FS-ONE use astandard caulking gun, foil pack gun, bulk loader andbulk gun. With FS-ONE buckets, Graco type sealantpumps may be used. (Contact pump manufacturer forproper selection).

    4. Smoothing of firestop sealant: To complete the seal,tool immediately to give a smooth appearance.Excess sealant, prior to curing, can be cleanedaway from adjacent surfaces and tools with water.

    5. Leave completed seal undisturbed for 48 hours.

    6. For maintenance reasons, a penetration seal couldbe permanently marked with an identification plate.In such a case, mark the identification plate andfasten it in a visible position next to the seal.

    Not for use • High movement expansion joints

    • Underwater

    • On materials where oil, plasticizers or solvents maybleed i.e. impregnated wood, oil based seals, greenor partially vulcanized rubber

    • In any penetration other than those specificallydescribed in this manual or the test reports

    Storage • Store only in the original packaging in a location

    protected from moisture at temperatures between 40°F (5°C) and 86°F (30°C)

    • Observe expiration date on the packaging

    Installation instructions for FS-ONE

    FirestopSystem

    FirestopSystem

    CA

    BLE

    PIP

    E

  • Hilti, Inc. 5400 South 122nd East Avenue

    Tulsa, OK 74146

    1-800-879-8000 www.hilti.com

    February 24, 2009 To Whom It May Concern: Re: Hilti FS-ONE Intumescent Firestop – LEED Info. The Hilti FS-ONE Intumescent Firestop is manufactured in Kaufering, Germany. The FS-ONE pail is made of polyethylene and can be completely recycled. There is no post-consumer or post-industrial content in FS-ONE and it cannot be recycled. The VOC content for FS-ONE is 75 grams/liter. FS-ONE is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non-regulated industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and state regulatory agencies for direction on disposal. Please feel free to contact me at (918) 872-3704 if you have questions. Sincerely, Jerry Metcalf MPH, CHMM Safety/Environmental Manager Hilti Inc (918) 872 3704 [email protected] Rev. Date: 2/24/09

  • Product Information

    Chap

    ter

    Tab

    sC

    hap

    ter

    Tab

    sC

    hap

    ter

    Tab

    sC

    hap

    ter

    Tab

    sC

    hap

    ter

    Tab

    s

    Hilti, Inc. (U.S.) 1-800-879-8000 • www.us.hilti.com • en español 1-800-879-5000 • Hilti Firestop Systems Guide 2007

    Hilti. Outperform. Outlast.

    Hilti FirestopSaving Livesthrough innovationand education

    CP 606Flexible Firestop Sealant

    CP 606 Technical DataChemical basis Acrylic based firestop sealantColor Available in red or whiteApplication temperature 40°F to 104°F (5°C to 40°C)Skin-forming time Approx. 15 minCuring time Approx. 3 mm / 3 daysVolume shrinkage Less than 20%Movement capability Approx. 10%Temperature resistance –22°F to 176°F (–30°C to 80°C)Surface burning characteristics Flame Spread: 0(ASTM E 84-96) Smoke Development: 5Sound transmission classification 56 (Relates to specific construction)(ASTM E 90-99) ApprovalsCalifornia State Fire Marshal Listing No. 1452-1200:112

    Listing No. 1451-1200:121Listing No. 4485-1200:132

    City of New York MEA 100-99-M, Vol. IVTested in accordance with • UL 2079 • ASTM E 814

    • ASTM E 1966 • ASTM E 84• UL 1479

    At 73°F (23°C) and 50% relative humidity

    FMAPPROVED

    For Penetration Fire Stops.Consult the Factory Mutual Research Corporation Approval Guide.

    R

    C

    LASSIFIED

    FILL, VOID OR CAVITY MATERIALS CLASSIFIED BY

    UNDERWRITERS LABORATORIES, INC.FOR USE IN TROUGH-PENETRATION

    FIRESTOP SYSTEMS SEE UL FIRE RESISTANCE DIRECTORY

    66Y7

    FILL, VOID OR CAVITY MATERIALFOR USE IN THROUGH-PENETRATION

    FIRESTOP SYSTEMS AND JOINT SYSTEMS

    SEE UL FIRE RESISTANCE DIRECTORY 66Y7

    Product description• An acrylic based firestop sealant that provides movement

    capability in fire rated joints and seals through penetrationsapplications

    Product features• Silicone free

    • Halogen, asbestos and solvent free

    • UV-resistant

    • Paintable

    • Meets 500 cycle requirements (ASTM E 1966 & UL 2079)

    • Smoke, fume and water resistant

    • Easy clean up with water

    • Single component systems available

    • Meets LEED™ requirements for indoor environmental quality credit4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paintsand Coatings

    Areas of application• Sealing construction/expansion joints

    • Top-of-wall joints

    • Metal pipes

    • Cable bundles

    • HVAC penetrations

    For use with• Various base materials such as masonry, concrete, metal, etc.

    • Wall and floor assemblies rated up to 3 hours

    Examples• Where a gypsum wall assembly meets the underside of

    a metal or concrete deck

    • Sealing expansion joints to impede the passage of fire, smoke andtoxic fumes

    • Sealing around HVAC penetrations through fire-rated assemblies

    Notice • Before handling, read Material Safety DataSheet and

    product label for safe usage and health information.

    • Instructions below are general guidelines — alwaysrefer to the applicable drawing in the UL FireResistance Directory or Hilti Firestop Systems Guidefor complete installation information

    Opening1. Clean the opening. Surfaces to which CP 606 will

    be applied should be cleaned of loose debris, dirt,oil, wax and grease. The surface should bemoisture and frost free.

    Application of firestop2. Insert fill of mineral wool or backer (as required).

    3. Apply firestop over backer.

    4. Smooth firestop sealant with a trowel before theskin forms. Once cured, CP 606 can only beremoved mechanically.

    5. For maintenance reasons, a penetration seal can bepermanently marked with an identification plate andfastened in a visible position next to the seal.

    Not for use• On areas immersed in water

    Storage• Store only in the original packaging in a location

    protected from moisture at a temperature of 40°F to77°F (5°C to 25°C)

    • Observe expiration date on package

    Installation instructions for CP 606

    1. Clean opening 2. Insert backingmaterial compressedper UL System

    3. Apply CP 606 4. Smooth CP 606 5. Fasten identificationplate (if required)

    1. Clean opening 2. Insert backingmaterial

    3. Apply CP 606 4. Smooth CP 606 5. Fasten identificationplate (if required)

    FirestopSystem

    FirestopSystem

    JO

    INT

    DU

    CT

  • Hilti, Inc. 5400 South 122nd East Avenue

    Tulsa, OK 74146

    1-800-879-8000 www.hilti.com

    February 24, 2009 To Whom It May Concern: Re: Hilti CP 606 Flexible Firestop – LEEDs Info. The Hilti CP 606 Flexible Firestop Sealant is manufactured in Kaufering, Germany. The CP 606 pail is made of polyethylene and can be completely recycled. There is no post-consumer or post-industrial content in CP 606 and it cannot be recycled. The CP 606 does not contain any Rapidly Renewable Materials. The VOC content for CP 606 is 71.0 grams/liter. CP 606 is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non-regulated industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and state regulatory agencies for direction on disposal. Please feel free to contact me at (918) 872-3704 if you have questions. Sincerely, Jerry Metcalf MPH, CHMM Safety/Environmental Manager Hilti Inc. 918 872 3704 [email protected] Rev. Date: 2/24/09

  • Sheet Drawing No.HILTI, Inc.

    Tulsa, Oklahoma USA (918) 252-6000Date

    Scale

    FRONT VIEW

    A

    A

    SECTION A-A

    NOTES : 1. MAXIMUM AREA OF OPENING = 1300 SQ. IN. WITH A MAXIMUM DIMENSION OF 50 IN. 2. ANNULAR SPACE = MINIMUM 0", MAXIMUM 2". 3. AFTER SEALING SPACE BETWEEN DUCT AND GYPSUM WALL ASSEMBLY WITH HILTI

    FIRESTOP SEALANT, FASTEN STEEL ANGLE (MIN. 18 GA.) TO DUCT WITH MINIMUM NO. 8 x 3/4" LONG SHEET METAL SCREWS. STEEL ANGLE TO OVERLAP DUCT BY MINIMUM 2" AND GYPSUM WALL ASSEMBLY BY MINIMUM 1". ANGLE DOES NOT HAVE TO BE FASTENED TO GYPSUM WALL ASSEMBLY.

    1. GYPSUM WALL ASSEMBLY (UL/ULC CLASSIFIED U300 OR U400 SERIES WALL) (1-HR. OR 2-HR. FIRE-RATING) (2-HR. SHOWN).

    2. (NOT SHOWN). WOOD STUDS TO CONSIST OF NOMINAL 2" x 4" LUMBER. STEEL STUDS TO BE MINIMUM 2-1/2" WIDE.

    3. RECTANGULAR SHEET METAL DUCT (MAXIMUM SIZE : 24" x 48", MINIMUM 24 GA. THICKNESS). (NOTE : NOT FOR USE IN DUCT SYSTEMS CONTAINING A FIRE DAMPER).

    4. OPENING TO BE "FRAMED OUT" WITH LIGHTGAGE METAL FRAMING STUDS. 5. MINIMUM 5/8" DEPTH HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT, HILTI CP 601S ELASTO- MERIC

    FIRESTOP SEALANT, OR HILTI CP 606 FLEXIBLE FIRESTOP SEALANT. 6. (NOT SHOWN). APPLY MINIMUM 1/2" BEAD HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT, HILTI CP

    601S ELASTOMERIC FIRESTOP SEALANT, OR HILTI CP 606 FLEXIBLE FIRESTOP SEALANT AT POINT OF CONTACT PRIOR TO ATTACHING STEEL ANGLE.

    WL7040g

    1 of 1

    5/64" = 1"

    Sept. 11, 2001

    UL/cUL SYSTEM NO. W-L-7040

    F-RATING = 1-HR. OR 2-HR.T-RATING = 0-HR.

    WL7

    040g

    .0911

    01

    12

    3

    4 5

    6

    MAXIMUM 6" C/C SPACING(SEE NOTE NO. 3 BELOW)

  • Sheet Drawing No.

    HILTI, Inc.Tulsa, Oklahoma USA (918) 252-6000

    Date

    Scale

    FRONT VIEW

    A

    A

    SECTION A-A

    NOTES : 1. MAXIMUM DIAMETER OF OPENING FOR STEEL STUD WALLS = 21-3/4" 2. MAXIMUM DIAMETER OF OPENING FOR WOOD STUD WALLS = 14-1/2". 3. ANNULAR SPACE = MINIMUM 0", MAXIMUM 1-1/2".

    1. GYPSUM WALL ASSEMBLY (UL/ULC U300 OR U400 SERIES WALL SERIES) (1-HR. OR 2-HR. FIRE-RATING) (2-HR. SHOWN).

    2. (NOT SHOWN). WOOD STUDS TO CONSIST OF NOMINAL 2" x 4" LUMBER. STEEL STUDS TO BE MINIMUM 2-1/2" WIDE.

    3. PENETRATING ITEM TO BE ONE OF THE FOLLOWING : A. MAXIMUM 20" NOMINAL DIAMETER SPIRAL WOUND SHEET METAL DUCT (MIN. 24 GA.). B. MAXIMUM 12" NOMINAL DIAMETER SHEET METAL DUCT (MIN. 28 GAUGE).

    4. HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT, HILTI CP 601S ELASTOMERIC FIRESTOP SEALANT, OR HILTI CP 606 FLEXIBLE FIRESTOP SEALANT :

    A. MINIMUM 5/8" DEPTH, FOR A 1-HR. FIRE RATING. B. MINIMUM 1-1/4" DEPTH, FOR A 2-HR. FIRE RATING.

    5. MINIMUM 1/2" BEAD HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT OR CP 601S ELASTOMERIC FIRESTOP SEALANT, OR HILTI CP 606 FLEXIBLE FIRESTOP SEALANT AT POINT OF CONTACT.

    WL7042d

    1 of 1

    3/32" = 1"

    Jan. 15, 2001

    UL/cUL SYSTEM NO. W-L-7042

    F-RATING = 1-HR. OR 2-HR.T-RATING = 0-HR.

    WL7

    042d

    .0115

    01

    12

    3

    4

    5

  • Sheet Drawing No.HILTI, Inc.

    Tulsa, Oklahoma USA (918) 252-6000Date

    Scale

    FRONT VIEW

    A

    A

    SECTION A-A

    NOTES : 1. MAX. AREA OF OPENING = 395 SQ. IN. WITH A MAX. DIM. OF 26-3/4". 2. INSULATION SHOULD BE COMPRESSED 50% SUCH THAT THE

    ANNULAR SPACE = MIN. 1/4", MAX. 1".

    1. GYPSUM WALL ASSEMBLY (UL/ULC CLASSIFIED U400 SERIES WALL) (1-HR. OR 2-HR. FIRE-RATING) (2-HR. SHOWN).

    2. (NOT SHOWN). STEEL STUDS TO BE MINIMUM 2-1/2" WIDE. OPENING TO BE "FRAMED OUT" ON ALL SIDES OF OPENING WITH LIGHTGAGE METAL STUD MATERIAL.

    3. MAXIMUM 24" x 12" RECTANGULAR SHEET METAL DUCT (MINIMUM 24 GA.). (NOTE : NOT FOR USE IN DUCT SYSTEMS CONTAINING A FIRE DAMPER).

    4. MAXIMUM 1-1/2" THICKNESS GLASS FIBER DUCT INSULATION (MIN. 3/4 PCF DENSITY) WITH FOIL-SCRIM-KRAFT FACING. (SEE NOTE NO. 2 BELOW).

    5. HILTI FS-ONE INTUMESCENT FIRESTOP SEALANT : A. MINIMUM 5/8" DEPTH OF SEALANT FOR A 1-HR. FIRE-RATING. B. MINIMUM 1-1/4" DEPTH OF SEALANT FOR A 2-HR. FIRE-RATING.

    WL7059a

    1 of 1

    3/32" = 1"

    Feb. 1, 2001

    UL/cUL SYSTEM NO. W-L-7059

    F-RATING = 1-HR. OR 2-HR.T-RATING = 1/2-HR. OR 3/4-HR.

    WJ7

    059a

    .0201

    01

    12

    3

    4 5