FIRESTOP INSPECTION Dr. Selina LIN Technical Manager August 01, 2017 FS Inspection 1

Transcript of Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain...

Page 1: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

FIRESTOP INSPECTION

Dr. Selina LIN

Technical Manager

August 01, 2017

FS Inspection 1

Page 2: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

2

Operations in more than 120 countries

23,385 employees (at the end of 2015)

120 nationalities in the global team

60 new products released (2016)

10,000 products in the entire product

portfolio

HILTI IN FIGURES

FS Inspection

Page 3: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

Drilling and

demolition

Cutting and

grindingEngineering

Measuring

and aligning

Fastening and

installation

Firestop and

insulationServices

• Training and advice

• Quality and testing

• Logistics

• Finance and

administration

• Engineering services

• Tool services

• Direct

fastening

• Screw fastening

technology

• Anchor

technology

• Installation

• Construction

chemicals

• Firestop

• Distance

measuring

• Leveling and

aligning

• Detection

• Design

• Specifications

• Consulting

• Cutting and

grinding

• Diamond

systems

• Drilling and

chiseling

• Diamond

systems

Software

SYSTEM SOLUTIONS FOR THE CONSTRUCTION INDUSTRY

3FS Inspection

Page 4: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

FS Inspection 4

FIRESTOP INSPECTION

Page 5: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

5

AGENDA

• Part 1: Code Requirement

Why: Importance of Firestopping

What: Test Standard V.S. Application Approval

How: Oversea Case Sharing: UAE, Singapore, U.S.A

• Part 2: Inspection Standard

How: ASTM inspection standard

Who: Inspector training

??? Firestopping Inspection in HK

FS Inspection

Page 6: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

FIRE COMPARTMENTATION

to minimize property/life loss and buy time for escape and rescue

FS Inspection 6

Page 7: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

CORRECT FIRESTOP APPLICATIONS

FS Inspection 7

• To Prevent

fire/smoke spread

• To buy time for

escape and rescue

• To minimize

property/life loss

Page 8: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

LONDON GRENFELL TOWER (JUNE 2017)

• the use of the flammable cladding being blamed for

spreading the fire that killed at least 70+ people.

• Barry Turner, director of technical policy at Local Authority

Building Control, which represents council building control

teams in England and Wales, said: “What we need to

know is what was inspected. You can go on site 16

times but not necessarily see everything you need to see.

They may have inspected the fixings, the fire barrier and

the cavity, which are equally important but are useless if

you put a flammable material on the front.”

FS Inspection 8

https://www.theguardian.com/uk-news/2017/jun/21/grenfell-tower-16-council-

inspections-failed-to-stop-use-of-flammable-cladding

Page 9: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

CURTAIN WALL / EXTERNAL FACADE

9

• Curtain wall materials shall be non-combustible, in

accordance to BS-EN 13501-1: 2007 (Class A1);

BS 476 Part 4.

• Perimeter joint shall be sealed up to form smoke

and fire barrier in accordance to BS EN 1364 Part 3

or Part 4 and BS EN 12101-1, respectively.

Non-combustible

FRR and smoke

barrier

FS Inspection

Page 10: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

COMBUSTIBILITY V.S. FIRE RESISTANCE

• Non-combustibility:

– Material characteristic

– Test standard: BS 476 Part 4 Non-combustibility test

for materials

– Limited combustibility : BS 476 Part 7 Method of test

to determine the classification of the surface spread of

flame of products

• Fire resistance:

– System Characteristic : openings + penetrant +

firestop sealing

– Test standard: Linear joint: BS EN 1366-3 or

Penetration seal: BS EN 1366-4; BS 476 Part 20.

FS Inspection 10

Materials of non-combustible DO NOT mean

they are fire resistance within a given

period.

For example, a piece of aluminum foil !

Page 11: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

NON-COMBUSTIBILITY BS 476 – PART 4

• No sudden temperature rise

• Weight loss

• Total flaming time

FS Inspection 11

Page 12: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

BS EN 1364-3 CURTAIN WALLING – FULL CONFIGURATION

FS Inspection 12

Horizontal Joint

Vertical Joint

Page 13: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

BS EN 1364-4 CURTAIN WALLING – PART CONFIGURATION

FS Inspection 13

Horizontal Joint

Page 14: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

BS 476 PART 20

• Linear joint: firestop sealant on top of mineral wool

FS Inspection 14

Page 15: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

FS Inspection 15

FRR SYSTEM

Page 16: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

16FS Inspection

Wrong system and poor installation

NO FRR protection

Wrong Design

Wrong system

Page 17: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

EN V.S. BS TEST STANDARD

FS Inspection 17

Testing standard & Field of application

/ Quality Assurance

Pure Testing standard +

assessment route

Test StandardBS EN 1366-3 Penetration

BS EN 1366-4 Linear Joint BS 476 Part 20 General Principle

Application

Approval/

Classification

Classification Report

European Technical Assessment Test report/Assessment

Quality control Mandatory N/A

EN BS

Page 18: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

BS TEST REPORT

FS Inspection 18

2000 mm * 1200 mm (2.4 m2)

1800 mm * 1300 mm (2.34 m2)

5000 mm * 400 mm (2.0 m2)

Page 19: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

FS Inspection 19

EUROPEAN TECHNICAL APPROVAL/ASSESSMENT

Page 20: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

EUROPEAN TECHNICAL ASSESSMENT

FS Inspection 20

Page 21: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

QUALITY ASSURANCE ON MANUFACTURER

ETAG 026 Guideline for European technical approvals for firestopping and fire sealing products Part 1

3. Evaluation and attestation of conformity and CE marking

FS Inspection 21

Page 22: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

FS Inspection 22

INSPECTION PRACTICE

• Code requirement

• How to conduct

• Who to conduct

• How to be qualified as inspectors

• Who sign off / liable

• Who pay for inspectors

Page 23: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

FS Inspection 23

UNITED ARAB EMIRATES

Page 24: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

FS Inspection 24

Certify and Sign

off Inspection

report, submitted

to civil defense

CIVIL DEFENSE CONSULTANT

FIRESTOP SPECIALIST /

HOUSE OF EXPERTS

Firestop

inspection report

at successive

stage

New UAE Code

3.3.6. Work shall not be certified as

completed unless approved by the

consultant’s, Firestopping specialist or

civil defense approved house of

expertise.

Page 25: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

INSPECTOR QUALIFICATION

FS Inspection 25

FIRESTOP SPECIALIST /

HOUSE OF EXPERTS

Consultant/expertise for

Inspections (3.6.7)

Accreditation to ISO/IEC 17020

or IAS AC 291 criteria or

equivalent

2 Engineers, qualified in

accordance with Section 3.6.8.

Training and certification by

system manufactures

3 years experience in

Firestopping inspections.

Specialist for Design,

consultancy or Inspections (3.6.8)

Bachelor’s degree in engineering

Certification from any of FM,

UL/ULC, or IFC exams

certification.

Training and certification by

system manufactures

5 years experience in

Firestopping system’s design and

inspections.

Shall be certified and licensed by

Civil Defense, based on their

qualification and written

examination.

Page 26: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

INSPECTION STANDARD

FS Inspection 26

FIRESTOP SPECIALIST /

HOUSE OF EXPERTS

Page 27: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

SINGAPORE

FS Inspection 27

Page 28: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

Installation by Hilti FSC

+DoC

submission

to PSB

Installation by contractor/

sub-contractor

Inspection by FSC

Option 1: By Firestop Specialist Contractor Option 2: By Trade Subcontractor

Currently there is a difficulty in execution of inspection as the FSC are empowered

to inspect their own work

PE

endorsement+

+DoC

submission

to PSB

PE

endorsement+

FIRESTOP INSTALLATION OPTIONS

FS Inspection 28

CoC DoC Form 2Form 2DoCCoC

Page 29: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

PSB TUV SUD LISTING SCHEME

Step 2:

Declaration of Compliance

Step 3:

FSSD Form 2Step 1:

Certificate of Conformity

By Manufacturer or

Manufacturer’s FSCBy professional engineer

(PE)

By Manufacturer and

TUV Sud PSB

FS Inspection 29

This declaration is issued by the PLS listed company

named below, who is responsible for the installation

process as shown in the table below.

Page 30: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

FS Inspection 30

U.S.A.

INTERNATIONAL BUILDING CODE

Page 31: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

IBC CHAPTER 17 SPECIAL INSPECTIONS ON FS

FS Inspection 31

BUILDING OWNER

REGISTERED DESIGN

PROFESSIONAL

APPROVED AGENCY

1705.16 : . In high-rise buildings or in buildings assigned to Risk Category III or IV in

accordance with Section 1604.5, special inspections for through-penetrations, membrane

penetration firestops, fire- resistant joint systems, and perimeter fire barrier systems.

1704.2 Special inspections. Owner…. shall employ one or

more approved agencies to perform inspections……..

Page 32: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

INSPECTION QUALIFICATION

FS Inspection 32

Chapter 17: Special inspections and tests

1703.1.1 Independence.

An approved agency shall be objective, competent and independent from the contractor

responsible for the work being inspected. The agency shall also disclose possible conflicts of interest so that

objectivity can be confirmed.

1704.2.1 Special inspector qualifications.

The special inspector shall provide written documentation to the building official demonstrating his

or her competence and relevant experience or training. …….

The registered design professional in responsible charge and engineers of record involved in the

design of the project are permitted to act as the approved agency and their personnel are permitted to act as the

special inspector for the work designed by them, provided they qualify as special inspectors.

APPROVED AGENCY

Page 33: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

33

BREAK (15 MINS)

FS Inspection

Page 34: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

34

AGENDA

• Part 1: Code Requirement

Why: Importance of Firestopping

What: Test Standard V.S. Application Approval

How: Oversea Case Sharing: UAE, Singapore, U.S.A

• Part 2: Inspection Standard

How: ASTM inspection standard

Who: Inspector training

??? Firestopping Inspection in HK

FS Inspection

Page 35: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

FS Inspection 35

ASTM INSPECTION STANDARD

Page 36: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

2012 IBC (1705.16.1) Penetration firestops. Inspections of

penetration firestop system. Conducted by approved agency

in accordance with ASTM E 2741

2012 IBC (1705.16.2) Fire-resistant joint system. Conducted

by approved agency in accordance with ASTM E 2393.

FIRESTOP INSPECTION STANDARD

FS Inspection 36

Page 37: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

THE INSPECTION PROCESS

Review design documents : Method Statement

Verify materials prior to installation: Delivery Note

Verify against listed systems and/or EJ : ETA or EN test reports

Verify that ALL firestops installed : on-site FRR system installation

ASTM E2741: Standard Practice for On-Site Inspection of Installed Fire Stops

For each “type” of firestop being installed:

Witness 10% of Installations, or Destructive Testing on 2% of Installations

ASTM E2393, Standard Practice for On-Site Inspection of Installed Fire Resistive Joint Systems and Perimeter

Fire Barriers

For each “type” of fire resistive joint system being installed:

Witness 5% of linear feet being installed, or Destructive (or disassembly) testing on 1 ft. per every

500 ft.

FS Inspection 37

Page 38: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

IF NON-COMPLIANCE IDENTIFIED

One non-compliant:

one full additional inspection of that type

10% non-compliance of one type:

inspection halted, installer re-inspects own work

Non-compliant firestop must be repaired/replaced

E2174/E2393: no guidance on what is an acceptable non-compliance percentage

FS Inspection 38

Page 39: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

EXAMPLE OF INSPECTION FORM FROM ASTM2393

FS Inspection 39

At the end of the project the Inspector shall

submit a final inspection report (cover page

summary of deficiency + all inspection form)

Page 40: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

CHECK LIST BY MANUFACTURE

FS Inspection 40

Page 41: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

TRAINING FOR INSPECTOR

FS Inspection 41

Page 42: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

FIRESTOP INSPECTION TRAINING CAN BE FOUND AT

WWW.FIRESTOP.ORG/INSPECTION

FS Inspection 42

About the IFC:

The International Firestop Council (IFC) is a nonprofit association of manufacturers, distributors, installers, inspectors and other

key stakeholders interested in passive fire protection materials and systems in North America and abroad.

What IFC do:

The IFC provides impartial and broad-based education, information, resources, affiliation, and procedures regarding firestop

system selection, performance, installation and inspection to the construction and code-enforcement communities.

Page 43: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

ONLINE TRAINING COURSE

• Basic self-learning modules

• (via PowerPoint presentations)

To scroll through each of the PowerPoint slide files, click on the down arrow to advance the slide show and

the up arrow to backtrack.

Firestop Overview – Just the Basics

Construction Joints

Flexible Fire Resistive Duct Enclosures

Perimeter Curtain Walls

Firestop System Selection

Comprehensive Firestop Tutorial (96 slides)

FS Inspection 43

Page 44: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

IFC CERTIFICATE

FS Inspection 44

Exam certificate can be used to present qualifications to AHJ

A Premier Certificate (as required by OSHPD) requires the exam plus hands-

on product training from at least four firestop product manufacturers

Optional 1-day hands-on how-to-inspect training seminars are offered 4-6

times per year around the US.

Page 45: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

VERIFYING WHETHER SOMEONE HAS PASSED THE IFC INSPECTOR EXAM

• www.firestop.org/certificate-holders

– Premier certificate holders:

additional hands-on product training

FS Inspection 45

Page 46: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

FS Inspection 46

INSPECTION IN HK

Page 47: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

HK PROJECT FLOW

47

Architect/Consultant’s Spec

Material submission by

contractor

Site inspection by COW/BSI if any

Test report submission via

BA-13/14

Materials submission folder FRR sealant/grouting/materials

FS Inspection

Page 48: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

APP-13 & CDB

FS Inspection 48

FRR material test report

submitted upon OP applications

Materials selected from Center

Data Bank

Page 49: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

APP-158 : INSTALLATION OF CHECKING ON FRR MATERIALS

49FS Inspection

The format of inspection

report/record?

Checklist, photo records, or

w/ designed drawings?

Page 50: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

FIRESTOP DOCUMENTATION

FS Inspection 50

Page 51: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

CFS-DM CLOUD BASED SYSTEM

FS Inspection 51

Page 52: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials

FS Inspection 54

FROM GOOD TO GREAT

• WHY: Fire Safety of Building is important to human life and

Property AND It is Challenging

• WHAT:

– FRR system and approval

• HOW:

– Oversea code and practice on inspection

– Firestopping Inspection in HK

• WHO:

– Architect / MEP consultant

– Contractor / installer

– Inspector (COW/BSI) or third party agency

Page 53: Firestop inspection - hkicw.org Inspection HKICW... · CURTAIN WALL / EXTERNAL FACADE 9 •Curtain wall materials shall be non-combustible, in ... Method Statement Verify materials