FIRESTOP INSPECTION
Dr. Selina LIN
Technical Manager
August 01, 2017
FS Inspection 1
2
Operations in more than 120 countries
23,385 employees (at the end of 2015)
120 nationalities in the global team
60 new products released (2016)
10,000 products in the entire product
portfolio
HILTI IN FIGURES
FS Inspection
Drilling and
demolition
Cutting and
grindingEngineering
Measuring
and aligning
Fastening and
installation
Firestop and
insulationServices
Training and advice
Quality and testing
Logistics
Finance and
administration
Engineering services
Tool services
Direct
fastening
Screw fastening
technology
Anchor
technology
Installation
Construction
chemicals
Firestop
Distance
measuring
Leveling and
aligning
Detection
Design
Specifications
Consulting
Cutting and
grinding
Diamond
systems
Drilling and
chiseling
Diamond
systems
Software
SYSTEM SOLUTIONS FOR THE CONSTRUCTION INDUSTRY
3FS Inspection
FS Inspection 4
FIRESTOP INSPECTION
5
AGENDA
Part 1: Code Requirement
Why: Importance of Firestopping
What: Test Standard V.S. Application Approval
How: Oversea Case Sharing: UAE, Singapore, U.S.A
Part 2: Inspection Standard
How: ASTM inspection standard
Who: Inspector training
??? Firestopping Inspection in HK
FS Inspection
FIRE COMPARTMENTATION
to minimize property/life loss and buy time for escape and rescue
FS Inspection 6
CORRECT FIRESTOP APPLICATIONS
FS Inspection 7
To Prevent
fire/smoke spread
To buy time for
escape and rescue
To minimize
property/life loss
LONDON GRENFELL TOWER (JUNE 2017)
the use of the flammable cladding being blamed for
spreading the fire that killed at least 70+ people.
Barry Turner, director of technical policy at Local Authority
Building Control, which represents council building control
teams in England and Wales, said: What we need to
know is what was inspected. You can go on site 16
times but not necessarily see everything you need to see.
They may have inspected the fixings, the fire barrier and
the cavity, which are equally important but are useless if
you put a flammable material on the front.
FS Inspection 8
https://www.theguardian.com/uk-news/2017/jun/21/grenfell-tower-16-council-
inspections-failed-to-stop-use-of-flammable-cladding
https://www.theguardian.com/uk-news/2017/jun/19/grenfell-tower-fire-death-toll-rises-to-79-police-say
CURTAIN WALL / EXTERNAL FACADE
9
Curtain wall materials shall be non-combustible, in
accordance to BS-EN 13501-1: 2007 (Class A1);
BS 476 Part 4.
Perimeter joint shall be sealed up to form smoke
and fire barrier in accordance to BS EN 1364 Part 3
or Part 4 and BS EN 12101-1, respectively.
Non-combustible
FRR and smoke
barrier
FS Inspection
COMBUSTIBILITY V.S. FIRE RESISTANCE
Non-combustibility:
Material characteristic
Test standard: BS 476 Part 4 Non-combustibility test
for materials
Limited combustibility : BS 476 Part 7 Method of test
to determine the classification of the surface spread of
flame of products
Fire resistance:
System Characteristic : openings + penetrant +
firestop sealing
Test standard: Linear joint: BS EN 1366-3 or
Penetration seal: BS EN 1366-4; BS 476 Part 20.
FS Inspection 10
Materials of non-combustible DO NOT mean
they are fire resistance within a given
period.
For example, a piece of aluminum foil !
NON-COMBUSTIBILITY BS 476 PART 4
No sudden temperature rise
Weight loss
Total flaming time
FS Inspection 11
BS EN 1364-3 CURTAIN WALLING FULL CONFIGURATION
FS Inspection 12
Horizontal Joint
Vertical Joint
BS EN 1364-4 CURTAIN WALLING PART CONFIGURATION
FS Inspection 13
Horizontal Joint
BS 476 PART 20
Linear joint: firestop sealant on top of mineral wool
FS Inspection 14
FS Inspection 15
FRR SYSTEM
16FS Inspection
Wrong system and poor installation
NO FRR protection
Wrong Design
Wrong system
EN V.S. BS TEST STANDARD
FS Inspection 17
Testing standard & Field of application
/ Quality Assurance
Pure Testing standard +
assessment route
Test StandardBS EN 1366-3 Penetration
BS EN 1366-4 Linear Joint BS 476 Part 20 General Principle
Application
Approval/
Classification
Classification Report
European Technical Assessment Test report/Assessment
Quality control Mandatory N/A
EN BS
BS TEST REPORT
FS Inspection 18
2000 mm * 1200 mm (2.4 m2)
1800 mm * 1300 mm (2.34 m2)
5000 mm * 400 mm (2.0 m2)
FS Inspection 19
EUROPEAN TECHNICAL APPROVAL/ASSESSMENT
EUROPEAN TECHNICAL ASSESSMENT
FS Inspection 20
QUALITY ASSURANCE ON MANUFACTURER
ETAG 026 Guideline for European technical approvals for firestopping and fire sealing products Part 1
3. Evaluation and attestation of conformity and CE marking
FS Inspection 21
FS Inspection 22
INSPECTION PRACTICE
Code requirement
How to conduct
Who to conduct
How to be qualified as inspectors
Who sign off / liable
Who pay for inspectors
FS Inspection 23
UNITED ARAB EMIRATES
FS Inspection 24
Certify and Sign
off Inspection
report, submitted
to civil defense
CIVIL DEFENSE CONSULTANTFIRESTOP SPECIALIST /
HOUSE OF EXPERTS
Firestop
inspection report
at successive
stage
New UAE Code
3.3.6. Work shall not be certified as
completed unless approved by the
consultants, Firestopping specialist or
civil defense approved house of
expertise.
INSPECTOR QUALIFICATION
FS Inspection 25
FIRESTOP SPECIALIST /
HOUSE OF EXPERTS
Consultant/expertise for
Inspections (3.6.7)
Accreditation to ISO/IEC 17020
or IAS AC 291 criteria or
equivalent
2 Engineers, qualified in
accordance with Section 3.6.8.
Training and certification by
system manufactures
3 years experience in
Firestopping inspections.
Specialist for Design,
consultancy or Inspections (3.6.8)
Bachelors degree in engineering
Certification from any of FM,
UL/ULC, or IFC exams
certification.
Training and certification by
system manufactures
5 years experience in
Firestopping systems design and
inspections.
Shall be certified and licensed by
Civil Defense, based on their
qualification and written
examination.
INSPECTION STANDARD
FS Inspection 26
FIRESTOP SPECIALIST /
HOUSE OF EXPERTS
SINGAPORE
FS Inspection 27
Installation by Hilti FSC
+DoC
submission
to PSB
Installation by contractor/
sub-contractor
Inspection by FSC
Option 1: By Firestop Specialist Contractor Option 2: By Trade Subcontractor
Currently there is a difficulty in execution of inspection as the FSC are empowered
to inspect their own work
PE
endorsement+
+DoC
submission
to PSB
PE
endorsement+
FIRESTOP INSTALLATION OPTIONS
FS Inspection 28
CoC DoC Form 2Form 2DoCCoC
PSB TUV SUD LISTING SCHEME
Step 2:
Declaration of Compliance
Step 3:
FSSD Form 2Step 1:
Certificate of Conformity
By Manufacturer or
Manufacturers FSCBy professional engineer
(PE)
By Manufacturer and
TUV Sud PSB
FS Inspection 29
This declaration is issued by the PLS listed company
named below, who is responsible for the installation
process as shown in the table below.
FS Inspection 30
U.S.A.
INTERNATIONAL BUILDING CODE
IBC CHAPTER 17 SPECIAL INSPECTIONS ON FS
FS Inspection 31
BUILDING OWNER
REGISTERED DESIGN
PROFESSIONAL
APPROVED AGENCY
1705.16 : . In high-rise buildings or in buildings assigned to Risk Category III or IV in
accordance with Section 1604.5, special inspections for through-penetrations, membrane
penetration firestops, fire- resistant joint systems, and perimeter fire barrier systems.
1704.2 Special inspections. Owner. shall employ one or
more approved agencies to perform inspections..
INSPECTION QUALIFICATION
FS Inspection 32
Chapter 17: Special inspections and tests
1703.1.1 Independence.
An approved agency shall be objective, competent and independent from the contractor
responsible for the work being inspected. The agency shall also disclose possible conflicts of interest so that
objectivity can be confirmed.
1704.2.1 Special inspector qualifications.
The special inspector shall provide written documentation