Copyright is vested with FIRELAB cc Reg no: 2005/087037/23 The use of this report is subject to the condition that it will only be published in full or an abridged version approved by FIRELAB FIRELAB cc, Building 28, CSIR Campus, Meiring Naudé Road, Brummeria, Pretoria, SA. (T) +27 12 349 2929, (F) +27 12 349 1519 Kobus Strydom, [email protected], +27 82 892 4565. Peet Strydom, [email protected], +27 82 321 4269 TITLE : Report on the fire propagation properties of the 40 mm IsoLam Ceiling Boards insulation material when tested in accordance with SANS 428 using the SANS 10177 Part 11 Horizontal test protocol REQUESTED BY : Isowall Southern Africa (Pty) Ltd PO Box 912581 SILVERTON Pretoria 0127 CONTRACT No : FTC 18/159 ISSUE No : 2 (17/10/2018) DATE : 10 October 2018

Transcript of FIRELAB cc FIRELAB - Isowall Group

Page 1: FIRELAB cc FIRELAB - Isowall Group

Copyright is vested with FIRELAB cc Reg no: 2005/087037/23

The use of this report is subject to the condition that it will only be published in full or an abridged version approved by FIRELAB

FIRELAB cc, Building 28, CSIR Campus, Meiring Naudé Road, Brummeria, Pretoria, SA. (T) +27 12 349 2929, (F) +27 12 349 1519

Kobus Strydom, [email protected], +27 82 892 4565. Peet Strydom, [email protected], +27 82 321 4269

TITLE : Report on the fire propagation properties of the 40 mm IsoLam Ceiling Boards insulation material when tested in accordance with SANS 428 using the SANS 10177 – Part 11 Horizontal test protocol

REQUESTED BY : Isowall Southern Africa (Pty) Ltd

PO Box 912581 SILVERTON Pretoria 0127

CONTRACT No : FTC 18/159

ISSUE No :

2 (17/10/2018)

DATE : 10 October 2018

Page 2: FIRELAB cc FIRELAB - Isowall Group

SANS 428, SANS 10177 – 11 (H) CONFIDENTIAL 10 October 2018 Isowall Southern Africa (Pty) Ltd Page 1 of 19 40 mm IsoLam Ceiling Boards FTC 18/159 (2)

The Test Report and results only relate to the product(s) and/or sample(s) submitted for testing as identified in Section 2 and Annexures and do not apply to any similar product(s) or sample(s) that has not been tested. This Test Report is only valid for 5 years or until there is a change to the product composition, manufacturing process or previously approved supplier(s). The validity of this report may be extended by a validation certificate issued by FIRELAB upon verification of the product(s) or sample(s). TABLE OF CONTENTS

LIST OF FIGURES AND TABLES ....................................................................................... 1

1. INTRODUCTION ................................................................................................................. 2

2. SAMPLE DESCRIPTION..................................................................................................... 3

3. CLASSIFICATION: SANS 10177 – PART 11:2007 ............................................................. 4

3.1. TEST PROCEDURE ........................................................................................................... 4

3.2. TEST EQUIPMENT ............................................................................................................. 4

4. TEST RESULTS .................................................................................................................. 6

5. DISCUSSION OF RESULTS ............................................................................................. 16

6. CONCLUSION .................................................................................................................. 17

ANNEXURE “A” ................................................................................................................. 18

ANNEXURE “B” ................................................................................................................. 19

LIST OF FIGURES AND TABLES

Figure 3.2.1: SANS 10177 – 11 (H) test facility with specimen frames....................................................... 5

Figure 3.2.2: Typical roof test installation in the SANS 10177 – 11 (H) facility ........................................... 5

Table 4.1: Observations made during the SANS 10177 – 11 (H) test .................................................... 6

Figure 4.1: The test installation prior to ignition of the Fire Source .......................................................... 7

Figure 4.2: Ignition of Fire Source (Crib) ................................................................................................. 7

Figure 4.3: Delamination of the facing ...................................................................................................... 8

Figure 4.4: Facing melting off and board coagulating .............................................................................. 8

Figure 4.5: Hole forming above the Fire Source....................................................................................... 9

Figure 4.6: Draping ................................................................................................................................... 9

Figure 4.7: Draping continues................................................................................................................. 10

Figure 4.8: Material draping over sprinkler pipe – approx. 8 minutes into the test ................................. 10

Figure 4.9: Back panel softening ............................................................................................................ 11

Figure 4.10: Joint opening on the back panel ........................................................................................... 11

Figure 4.11: Draping of the back panel edge ........................................................................................... 12

Figure 4.12: Crib collapsing & entire front panel draping ......................................................................... 12

Figure 4.13: Test specimen at conclusion of the SANS 10177 – 11 (H) test ........................................... 13

Figure 4.14: Front panel temperatures recorded during SANS 10177 – 11 (H) test ................................ 14

Figure 4.15: Rear panel temperatures recorded during SANS 10177 – 11 (H) test ................................ 15

Page 3: FIRELAB cc FIRELAB - Isowall Group

SANS 428, SANS 10177 – 11 (H) CONFIDENTIAL 10 October 2018 Isowall Southern Africa (Pty) Ltd Page 2 of 19 40 mm IsoLam Ceiling Boards FTC 18/159 (2)

The Test Report and results only relate to the product(s) and/or sample(s) submitted for testing as identified in Section 2 and Annexures and do not apply to any similar product(s) or sample(s) that has not been tested. This Test Report is only valid for 5 years or until there is a change to the product composition, manufacturing process or previously approved supplier(s). The validity of this report may be extended by a validation certificate issued by FIRELAB upon verification of the product(s) or sample(s). 1. INTRODUCTION

This report evaluates the fire propagation properties of the 40 mm IsoLam Ceiling Boards insulation material supplied by Isowall Southern Africa to obtain a classification in accordance with SANS 428, using the SANS 10177 – Part 11 Horizontal (H) test protocol. Intended use of product: Ceiling Panels

Page 4: FIRELAB cc FIRELAB - Isowall Group

SANS 428, SANS 10177 – 11 (H) CONFIDENTIAL 10 October 2018 Isowall Southern Africa (Pty) Ltd Page 3 of 19 40 mm IsoLam Ceiling Boards FTC 18/159 (2)

The Test Report and results only relate to the product(s) and/or sample(s) submitted for testing as identified in Section 2 and Annexures and do not apply to any similar product(s) or sample(s) that has not been tested. This Test Report is only valid for 5 years or until there is a change to the product composition, manufacturing process or previously approved supplier(s). The validity of this report may be extended by a validation certificate issued by FIRELAB upon verification of the product(s) or sample(s). 2. SAMPLE DESCRIPTION

40 mm IsoLam Ceiling Boards has the following characteristics:

Product information:

Product code: Stuc40 Manufacturer: Isowall Southern Africa (Pty) Ltd Manufacturing date: 27-07-2018 Batch number: N/A

Generic Identification:

Insulation

Physical Properties:

Actual mass: ± 15.0 kg/m3 Thickness: 40 mm Width: 1 200 mm Length: 4 800 m

Product Composition:

Layer 1: EPS 15 DV Layer 2: 125 micron PVC foil

Installation details:

Installation Type: Over Purlin Joint Type: Butt joint supported on a T-bar Joint Overlap: N/A Suspension: Over Purlin Facing direction: Downward

Annexure “A”: Company information Annexure “B”: Product information and installation details

The installation in the SANS 10177 – Part 11 (H) test facility prior to ignition of the Fire Source is shown in Figure 4.1, the panels at the conclusion of the test is shown in Figure 4.13.

Page 5: FIRELAB cc FIRELAB - Isowall Group

SANS 428, SANS 10177 – 11 (H) CONFIDENTIAL 10 October 2018 Isowall Southern Africa (Pty) Ltd Page 4 of 19 40 mm IsoLam Ceiling Boards FTC 18/159 (2)

The Test Report and results only relate to the product(s) and/or sample(s) submitted for testing as identified in Section 2 and Annexures and do not apply to any similar product(s) or sample(s) that has not been tested. This Test Report is only valid for 5 years or until there is a change to the product composition, manufacturing process or previously approved supplier(s). The validity of this report may be extended by a validation certificate issued by FIRELAB upon verification of the product(s) or sample(s). 3. CLASSIFICATION: SANS 10177 – PART 11:2007 (H)

3.1. TEST PROCEDURE

The large-scale fire propagation properties of the system were evaluated by performing a test in the FIRELAB’s large-scale SANS 10177 – 11 roof insulation test facility. A schematic diagram of the test facility with the specimen frames is shown in Figure 3.2.1. The facility was equipped with a typical water sprinkler system to observe any obstructions during the event of testing; however, no water has been applied. The use of water during a test is dependent upon the client’s request. The ignition source for the under-roof evaluation was constructed from 60 kg dry 38 mm x 38 mm SA Pine sticks stacked in an open-crib configuration to form a 1 000 mm x 750 mm x 480 mm high crib. The pack was ignited with commercial firelighters at each corner, in order to simulate a fire with slow heat build-up. The maximum heat output of the fire source (approximately 2.5 MW based on previous research) occurred after approximately 12 minutes. The fire source was located at one end of the facility, approximately 1.5 m from the front end, 1.5 m from the side and 1.5 m from the center line of the specimen frame. The position of the crib is indicated in Figure 3.2.1. Only the first two panels were used for the test. No mass loss measurements were taken during the evaluations. This test was performed simulating an over-purlin suspended wire insulation system. This evaluation investigated the fire propagation properties of the roof insulation with the purlins positioned across the width of the test facility. A schematic side view of a typical roof test installation is shown in Figure 3.2.2. For this evaluation, the specimen frames were aligned in such a way that the roof slope was equal to 3 degrees. The distance between the top of the fire source and the roof directly above it was 2.7 meters. Note: The third 6 m by 6 m panel (end) was not used during this evaluation. 3.2. TEST EQUIPMENT

Data logging equipment c/w controller Stopwatch Type K thermocouple SANS 10177 – 11 Test Facility

Page 6: FIRELAB cc FIRELAB - Isowall Group

SANS 428, SANS 10177 – 11 (H) CONFIDENTIAL 10 October 2018 Isowall Southern Africa (Pty) Ltd Page 5 of 19 40 mm IsoLam Ceiling Boards FTC 18/159 (2)

The Test Report and results only relate to the product(s) and/or sample(s) submitted for testing as identified in Section 2 and Annexures and do not apply to any similar product(s) or sample(s) that has not been tested. This Test Report is only valid for 5 years or until there is a change to the product composition, manufacturing process or previously approved supplier(s). The validity of this report may be extended by a validation certificate issued by FIRELAB upon verification of the product(s) or sample(s).

Figure 3.2.1: SANS 10177 – 11 (H) test facility with specimen frames

Figure 3.2.2: Typical roof test installation in the SANS 10177 – 11 (H) facility

Page 7: FIRELAB cc FIRELAB - Isowall Group

SANS 428, SANS 10177 – 11 (H) CONFIDENTIAL 10 October 2018 Isowall Southern Africa (Pty) Ltd Page 6 of 19 40 mm IsoLam Ceiling Boards FTC 18/159 (2)

The Test Report and results only relate to the product(s) and/or sample(s) submitted for testing as identified in Section 2 and Annexures and do not apply to any similar product(s) or sample(s) that has not been tested. This Test Report is only valid for 5 years or until there is a change to the product composition, manufacturing process or previously approved supplier(s). The validity of this report may be extended by a validation certificate issued by FIRELAB upon verification of the product(s) or sample(s). 4. TEST RESULTS

Observations made during the SANS 10177 – 11 test conducted on 18 September 2018 are shown in Table 4.1, temperatures recorded are depicted graphically in Figures 4.14 and 4.15:

Isowall – 40 mm IsoLam Ceiling Boards

OBSERVATIONS DURING THE SANS 10177 – PART 11 (H) TEST

TIME (mm:ss) OBSERVATIONS

00:00 – Test Started –

01:10 Joint loosening

01:40 PVC stiffening

02:05 Boards start sagging

02:20 Bubbles forming

02:55 Molten droplets above the fire source

03:15 Hole forming above the fire source

04:10 Material draping

05:20 Entire panel skin coagulated

07:00 Aluminium section dropped down

07:45 First panel entirely draping & molten debris dropping around fire source

08:35 Back panel EPS sagging and panel on left side draping over sprinkler pipe

12:00 Material draping on back panel edge

15:30 Crib collapsed

21:00 Crib consumed

22:00 – Test Terminated –

Notes: Average Ambient Temperature during test = 29.7 °C

Debris only observed under the first bay (0 – 4 m)

The material draped over the sprinkler pipe

Table 4.1: Observations made during the SANS 10177 – 11 (H) test

Page 8: FIRELAB cc FIRELAB - Isowall Group

SANS 428, SANS 10177 – 11 (H) CONFIDENTIAL 10 October 2018 Isowall Southern Africa (Pty) Ltd Page 7 of 19 40 mm IsoLam Ceiling Boards FTC 18/159 (2)

The Test Report and results only relate to the product(s) and/or sample(s) submitted for testing as identified in Section 2 and Annexures and do not apply to any similar product(s) or sample(s) that has not been tested. This Test Report is only valid for 5 years or until there is a change to the product composition, manufacturing process or previously approved supplier(s). The validity of this report may be extended by a validation certificate issued by FIRELAB upon verification of the product(s) or sample(s).

Figure 4.1: The test installation prior to ignition of the Fire Source

Figure 4.2: Ignition of Fire Source (Crib)

Page 9: FIRELAB cc FIRELAB - Isowall Group

SANS 428, SANS 10177 – 11 (H) CONFIDENTIAL 10 October 2018 Isowall Southern Africa (Pty) Ltd Page 8 of 19 40 mm IsoLam Ceiling Boards FTC 18/159 (2)

The Test Report and results only relate to the product(s) and/or sample(s) submitted for testing as identified in Section 2 and Annexures and do not apply to any similar product(s) or sample(s) that has not been tested. This Test Report is only valid for 5 years or until there is a change to the product composition, manufacturing process or previously approved supplier(s). The validity of this report may be extended by a validation certificate issued by FIRELAB upon verification of the product(s) or sample(s).

Figure 4.3: Delamination of the facing

Figure 4.4: Facing melting off and board coagulating

Page 10: FIRELAB cc FIRELAB - Isowall Group

SANS 428, SANS 10177 – 11 (H) CONFIDENTIAL 10 October 2018 Isowall Southern Africa (Pty) Ltd Page 9 of 19 40 mm IsoLam Ceiling Boards FTC 18/159 (2)

The Test Report and results only relate to the product(s) and/or sample(s) submitted for testing as identified in Section 2 and Annexures and do not apply to any similar product(s) or sample(s) that has not been tested. This Test Report is only valid for 5 years or until there is a change to the product composition, manufacturing process or previously approved supplier(s). The validity of this report may be extended by a validation certificate issued by FIRELAB upon verification of the product(s) or sample(s).

Figure 4.5: Hole forming above the Fire Source

Figure 4.6: Draping

Page 11: FIRELAB cc FIRELAB - Isowall Group

SANS 428, SANS 10177 – 11 (H) CONFIDENTIAL 10 October 2018 Isowall Southern Africa (Pty) Ltd Page 10 of 19 40 mm IsoLam Ceiling Boards FTC 18/159 (2)

The Test Report and results only relate to the product(s) and/or sample(s) submitted for testing as identified in Section 2 and Annexures and do not apply to any similar product(s) or sample(s) that has not been tested. This Test Report is only valid for 5 years or until there is a change to the product composition, manufacturing process or previously approved supplier(s). The validity of this report may be extended by a validation certificate issued by FIRELAB upon verification of the product(s) or sample(s).

Figure 4.7: Draping continues

Figure 4.8: Material draping over sprinkler pipe – approx. 8 minutes into the test

Page 12: FIRELAB cc FIRELAB - Isowall Group

SANS 428, SANS 10177 – 11 (H) CONFIDENTIAL 10 October 2018 Isowall Southern Africa (Pty) Ltd Page 11 of 19 40 mm IsoLam Ceiling Boards FTC 18/159 (2)

The Test Report and results only relate to the product(s) and/or sample(s) submitted for testing as identified in Section 2 and Annexures and do not apply to any similar product(s) or sample(s) that has not been tested. This Test Report is only valid for 5 years or until there is a change to the product composition, manufacturing process or previously approved supplier(s). The validity of this report may be extended by a validation certificate issued by FIRELAB upon verification of the product(s) or sample(s).

Figure 4.9: Back panel softening

Figure 4.10: Joint opening on the back panel

Page 13: FIRELAB cc FIRELAB - Isowall Group

SANS 428, SANS 10177 – 11 (H) CONFIDENTIAL 10 October 2018 Isowall Southern Africa (Pty) Ltd Page 12 of 19 40 mm IsoLam Ceiling Boards FTC 18/159 (2)

The Test Report and results only relate to the product(s) and/or sample(s) submitted for testing as identified in Section 2 and Annexures and do not apply to any similar product(s) or sample(s) that has not been tested. This Test Report is only valid for 5 years or until there is a change to the product composition, manufacturing process or previously approved supplier(s). The validity of this report may be extended by a validation certificate issued by FIRELAB upon verification of the product(s) or sample(s).

Figure 4.11: Draping of the back panel edge

Figure 4.12: Crib collapsing & entire front panel draping

Page 14: FIRELAB cc FIRELAB - Isowall Group

SANS 428, SANS 10177 – 11 (H) CONFIDENTIAL 10 October 2018 Isowall Southern Africa (Pty) Ltd Page 13 of 19 40 mm IsoLam Ceiling Boards FTC 18/159 (2)

The Test Report and results only relate to the product(s) and/or sample(s) submitted for testing as identified in Section 2 and Annexures and do not apply to any similar product(s) or sample(s) that has not been tested. This Test Report is only valid for 5 years or until there is a change to the product composition, manufacturing process or previously approved supplier(s). The validity of this report may be extended by a validation certificate issued by FIRELAB upon verification of the product(s) or sample(s).

Figure 4.13: Test specimen at conclusion of the SANS 10177 – 11 (H) test

Page 15: FIRELAB cc FIRELAB - Isowall Group

SANS 428, SANS 10177 – 11 (H) CONFIDENTIAL 10 October 2018 Isowall Southern Africa (Pty) Ltd Page 14 of 19 40 mm IsoLam Ceiling Boards FTC 18/159 (2)

The Test Report and results only relate to the product(s) and/or sample(s) submitted for testing as identified in Section 2 and Annexures and do not apply to any similar product(s) or sample(s) that has not been tested. This Test Report is only valid for 5 years or until there is a change to the product composition, manufacturing process or previously approved supplier(s). The validity of this report may be extended by a validation certificate issued by FIRELAB upon verification of the product(s) or sample(s).

Figure 4.14: Front panel temperatures recorded during the SANS 10177 – 11 (H) test

Page 16: FIRELAB cc FIRELAB - Isowall Group

SANS 428, SANS 10177 – 11 (H) CONFIDENTIAL 10 October 2018 Isowall Southern Africa (Pty) Ltd Page 15 of 19 40 mm IsoLam Ceiling Boards FTC 18/159 (2)

The Test Report and results only relate to the product(s) and/or sample(s) submitted for testing as identified in Section 2 and Annexures and do not apply to any similar product(s) or sample(s) that has not been tested. This Test Report is only valid for 5 years or until there is a change to the product composition, manufacturing process or previously approved supplier(s). The validity of this report may be extended by a validation certificate issued by FIRELAB upon verification of the product(s) or sample(s).

Figure 4.15: Rear panel temperatures recorded during the SANS 10177 – 11 (H) test

Page 17: FIRELAB cc FIRELAB - Isowall Group

SANS 428, SANS 10177 – 11 (H) CONFIDENTIAL 10 October 2018 Isowall Southern Africa (Pty) Ltd Page 16 of 19 40 mm IsoLam Ceiling Boards FTC 18/159 (2)

The Test Report and results only relate to the product(s) and/or sample(s) submitted for testing as identified in Section 2 and Annexures and do not apply to any similar product(s) or sample(s) that has not been tested. This Test Report is only valid for 5 years or until there is a change to the product composition, manufacturing process or previously approved supplier(s). The validity of this report may be extended by a validation certificate issued by FIRELAB upon verification of the product(s) or sample(s). 5. DISCUSSION OF RESULTS

The specimen softened, followed by the material sufficiently coagulating and draping, preventing the material from reaching its ignition temperature. Softened debris was observed during the test. No ignition was observed. Most of the debris dropping down occurred inside the Fire Source Area (0 – 4 m). For this evaluation a Fixed Water Suppression (Sprinkler) system, without water, was installed. Some of the material draped over the sprinkler pipes during the test; this may affect the operation of a sprinkler installation. Draping occurred approximately 8 minutes into the start of the test, at which time operational sprinklers might have already activated; therefore it is not clear from the test whether the draping would occur if an active sprinkler system is used. It is recommended that a second test, with an operation sprinkler system, be conducted to determine whether or not the functioning of the sprinklers will be affected.

Page 18: FIRELAB cc FIRELAB - Isowall Group

SANS 428, SANS 10177 – 11 (H) CONFIDENTIAL 10 October 2018 Isowall Southern Africa (Pty) Ltd Page 17 of 19 40 mm IsoLam Ceiling Boards FTC 18/159 (2)

The Test Report and results only relate to the product(s) and/or sample(s) submitted for testing as identified in Section 2 and Annexures and do not apply to any similar product(s) or sample(s) that has not been tested. This Test Report is only valid for 5 years or until there is a change to the product composition, manufacturing process or previously approved supplier(s). The validity of this report may be extended by a validation certificate issued by FIRELAB upon verification of the product(s) or sample(s). 6. CONCLUSION

The 40 mm IsoLam Ceiling Boards supplied by Isowall Southern Africa was classified in accordance with SANS 428 using the SANS 10177 –11 Horizontal test protocol. Classification in accordance with SANS 428:

SANS 10177 – 11 » B/ B1/ 2/ H (USP)*

* Although the panel preformed satisfactory without sprinklers, a test with an operational

sprinkler installation is recommended. Provision for adequate roof ventilation and/or a sprinkler protection system will need to be considered based on the size, slope and configuration of each roof. This should form part of the Fire Safety Design of the building in order to satisfy the requirements as contemplated by SANS 10400 – T. The above does not relate to Fire Resistance. Should Fire Resistance be a requirement, the system needs to be tested using the SANS 10177 – 2 test protocol.

………………………… ……………………………….. Compiled by: J. Vogel Approved by: J.S. Strydom

This copy has been produced from a .pdf format electronic file that has been provided by FIRELAB to the sponsor of the report and may only be reproduced in full. Extracts or abridgements of reports must not be published without permission of FIRELAB. The original signed paper version of this report is the sole authentic version. Only original paper versions of this report bear authentic signatures of the responsible FIRELAB staff.

Page 19: FIRELAB cc FIRELAB - Isowall Group

SANS 428, SANS 10177 – 11 (H) CONFIDENTIAL 10 October 2018 Isowall Southern Africa (Pty) Ltd Page 18 of 19 40 mm IsoLam Ceiling Boards FTC 18/159 (2)

The Test Report and results only relate to the product(s) and/or sample(s) submitted for testing as identified in Section 2 and Annexures and do not apply to any similar product(s) or sample(s) that has not been tested. This Test Report is only valid for 5 years or until there is a change to the product composition, manufacturing process or previously approved supplier(s). The validity of this report may be extended by a validation certificate issued by FIRELAB upon verification of the product(s) or sample(s).

ANNEXURE “A”

Page 20: FIRELAB cc FIRELAB - Isowall Group

SANS 428, SANS 10177 – 11 (H) CONFIDENTIAL 10 October 2018 Isowall Southern Africa (Pty) Ltd Page 19 of 19 40 mm IsoLam Ceiling Boards FTC 18/159 (2)

The Test Report and results only relate to the product(s) and/or sample(s) submitted for testing as identified in Section 2 and Annexures and do not apply to any similar product(s) or sample(s) that has not been tested. This Test Report is only valid for 5 years or until there is a change to the product composition, manufacturing process or previously approved supplier(s). The validity of this report may be extended by a validation certificate issued by FIRELAB upon verification of the product(s) or sample(s).

ANNEXURE “B”