Siemens Building Technologies Fire Products DivisionCompany Confidential
FireFinder XLSSystem Basics
![Page 2: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/2.jpg)
Siemens Building Technologies Fire Products DivisionCompany Confidential
Fire Alarm System Basics
System & Processor
Inputs Outputs
An
nu
nc
iatio
n
& C
on
trol
![Page 3: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/3.jpg)
Siemens Building Technologies Fire Products DivisionCompany Confidential
Inputs
Manual pull stations• HMS-S, HMS-D, HMS-SA, HMS-M, HMS-2S
Monitor points (Transmit-Receive Interface, or TRI)• HTRI-S, HTRI-D, HTRI-R, HTRI-M• Used for waterflow, tamper, security, damper• Relay output available
Conventional Zone Module – HZM Short circuit isolator – HLIM Intelligent LEDs
• ILED-HC, ILED-HW Detectors
• Bases – DB-11, DB-HR, ADBH-11, AD-11P, AD-HR• Detectors – HFP-11, HFPT-11
– FirePrint!
Inputs
![Page 4: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/4.jpg)
Siemens Building Technologies Fire Products DivisionCompany Confidential
What is FirePrint?
A revolutionary fire detection method that distinguishes between a fire’s unique “fingerprint” and deceptive phenomena, and reports only real fires.
11 different selectable applications FirePrint is NOT a fancy form of “alarm
verification/confirmation”• Makes decisions based on obscuration/temperature/time
Siemens offers the No False Alarm Guarantee• If the system is designed and maintained properly, Siemens
will pay any fines associated with false alarms from FirePrint detectors
• No other manufacturer offers this guarantee
• Since 1997, total fines paid out equals $0!
Inputs
![Page 5: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/5.jpg)
Siemens Building Technologies Fire Products DivisionCompany Confidential
DPU Device Programming Unit
Tests/addresses both MXL and FireFinder XLS devices• Not used for XL3 devices
Built in loop tester!• Have contractor test all loop wiring & devices before panel
gets there!• Indicates # & type of devices, and what device is at what
address• Finds multiple response addresses• Ground faults, activations indicated
Connection to label printer• Prints loop # & address• Multiple copies available
Inputs
![Page 6: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/6.jpg)
Siemens Building Technologies Fire Products DivisionCompany Confidential
DLC – Device Loop Card
Plug-in card 252 devices on a loop! 1 or 2 loops per card
• T-tapped inside card• Total 252 total devices in any combination
50 cards/100 loops per system 2500 devices per system Non-twisted, non-shielded wire
• Great for retrofits! Wire is POLARITY INSENSITIVE (SureWire) Smart Degrade capability
• Loop accessories/outputs operate in Degrade
Inputs
![Page 7: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/7.jpg)
Siemens Building Technologies Fire Products DivisionCompany Confidential
CDC-4 Conventional Detector Card
Plug-in card 4 conventional detection circuits Optional Alarm Verification Supports Siemens conventional detectors & circuit
closure devices Supports select COMPETITIVE conventional detectors
• Check the installation instruction in the Tech Support area of the website
Inputs
![Page 8: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/8.jpg)
Siemens Building Technologies Fire Products DivisionCompany Confidential
PMI – Person/Machine Interface
Main operator interface & central processor Large graphics screen for events, details, icons &
bitmaps System event LEDs Large lighted buttons – prompts users through system
operation “More Info” button – users get to detail & map screens Touch screen for reports and maintenance
System Processor
An
nu
nc
iatio
n
& C
on
trol
![Page 9: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/9.jpg)
Siemens Building Technologies Fire Products DivisionCompany Confidential
Lighted buttons to prompt user
Partial System Disable
Audible Status
-Large 6” display with touch screen
System Status LED’s
Menu Access
Navigation Controls
HELP
![Page 10: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/10.jpg)
Siemens Building Technologies Fire Products DivisionCompany Confidential
ALARM SUPERVISORY SECURITY TROUBLE
POWER
ON
AUDIBLES
SILENCED
PARTIAL SYS
DISABLED
MORE
INFO
![Page 11: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/11.jpg)
Siemens Building Technologies Fire Products DivisionCompany Confidential
ALARM SUPERVISORY SECURITY TROUBLE
POWER
ON
AUDIBLES
SILENCED
PARTIAL SYS
DISABLED
![Page 12: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/12.jpg)
Siemens Building Technologies Fire Products DivisionCompany Confidential
ALARM SUPERVISORY SECURITY TROUBLE
POWER
ON
AUDIBLES
SILENCED
PARTIAL SYS
DISABLED
![Page 13: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/13.jpg)
Siemens Building Technologies Fire Products DivisionCompany Confidential
Enclosures
CAB1• Supports 1 row (4 module spaces) with PTB & batteries
CAB2• Supports 2 rows (8 module spaces) with PTB & batteries
CAB3• Supports 3 rows (12 module spaces) with PTB & batteries
Transponder enclosures• Same as CAB enclosures w/ grill outer doors
REMBOX2• Supports 2 inner door rows• No card cages
REMBOX4• Supports 4 inner door rows• No card cages
CAB-BATT Battery Box• For 55 AH, 100 AH batteries
System Processor
![Page 14: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/14.jpg)
CAB1Small enclosure (one row) Ships complete:
• back box• inner door• outer door• module mounting plate
(CAB-MP)• door lens (OD-LP)
Options:• CAB1R (red version)• Tamper switch (HTSW-1)• Semi-flush trim kit (CAB1-TK)
![Page 15: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/15.jpg)
CAB2 Medium
Enclosure (2 row)
CAB2 Ships complete:
• CAB2-BB• CAB2-BD• (2) CAB-MP’s• (1) OD-LP
Requires either (1):• OD-LP (lens)• OD-BP (blank)• OD-GP (grill)
Options:CAB2R (red version)CAB-2TK (semi-flush trim kit)
![Page 16: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/16.jpg)
CAB-3 Large Enclosure
(3 row) CAB3 Ship Complete
• CAB3-BB • CAB3-BD• (3) CAB-MP’s• (1) OD-LP
Requires either (2):• OD-LP (lens)• OD-BP (blank)
• OD-GP (grill)
Options:CAB3R (red version)CAB-3TK (semi-flush trim kit)
![Page 17: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/17.jpg)
Siemens Building Technologies Fire Products DivisionCompany Confidential
Remote “Lobby” EnclosuresREMBOX2 and REMBOX4
REMBOX2• Space for (2) inner door
modules. • Typically LVM and up to
(4) SCM-8’s • Optional plate to mount
(4) OCM-16 or SIM-16• Local tamper switch
option (HTSW-1)• Semi-flush or surface
mounting. No trim kit needed.
REMBOX4• Space for (4) inner door
modules. Typically LVM and SCM-8’s.
• Optional plate to mount (8) OCM-16 or SIM-16
• Local tamper switch option (HTSW-1)
• Semi-flush or surface mounting. No trim kit needed.
System Processor
![Page 18: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/18.jpg)
Siemens Building Technologies Fire Products DivisionCompany Confidential
CC-5/CC-2 Card cages
All wiring lands on removable terminal blocks All cards fit in the same card cage
• No separate Fire/Voice card cages Efficient card mounting
• 10 cards in 19”w x 14”h row– MXL – 6 cards in 19”w x 17”h row
• Less space required = less/smaller enclosures 60 pin bus between all cardcages
• Connected by 1 cable!
System Processor
![Page 19: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/19.jpg)
Siemens Building Technologies Fire Products DivisionCompany Confidential
All cards same size and plug into CC-5/CC-2 cardcages
Thumb screws for handles & to keep cards in place
![Page 20: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/20.jpg)
Power limited Field wiring (top)
Non-Power limited internal wiring
(bottom)
Power input to cards from PSC-12/PSX-12 or ZAC/ZAM
amplifiers
Out of enclosure to field devices or remote enclosures
60 pin bus - power, data, communications etc.
Removable terminal blocks (with covers)
Card guides removable for easy wiring access in enclosure - mounted with (2) captive screws each.
Labels to identify which card goes in which slot.
![Page 21: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/21.jpg)
![Page 22: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/22.jpg)
Siemens Building Technologies Fire Products DivisionCompany Confidential
PSC-12/PSX-12 Power Supplies
Filtered & Regulated 12 amp 24VDC supply• 5 amp continuous use
120 to 240 volt AC input, 50/60 Hz. PSC-12 – Battery charger for 100AH batteries
• New batteries – BTX-3 PSX-12 – Power only (no charger) to
extend power in cabinet Four 2-amp Form “C” relays built in
• Alarm, trouble, 2 programmable
System Processor
![Page 23: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/23.jpg)
Siemens Building Technologies Fire Products DivisionCompany Confidential
ZIC-4A – Zone Indicating Card
Plug-in card Four Class A or B circuits Used as
• NAC – horn or strobe• Speaker circuit – 1 or 2 channel• Releasing circuit• Municipal Tie/Leased Line• Bell follower (NAC extender)
4 Amp capacity per circuit (96 Watts speaker)
Outputs
![Page 24: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/24.jpg)
Siemens Building Technologies Fire Products DivisionCompany Confidential
CRC-6 Controllable Relay Card
Six independently controlled Form C relays 4 amps 30VDC/120VAC (resistive) 3.5 amps 120VAC (inductive @ 0.6 p.f.) Coils supervised Status and troubleshooting LEDs built in
Outputs
![Page 25: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/25.jpg)
Siemens Building Technologies Fire Products DivisionCompany Confidential
SSD System Status Display
4 x 40 character LCD display Local sounder & scroll buttons Acknowledge/Silence/Reset capabilities on SSD-C
• Keyswitch activates control buttons Can be mounted in a larger enclosure
• Model SSD-C-REM Up to 32 on a system!
SSD-C
An
nu
nc
iatio
n
& C
on
trol
![Page 26: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/26.jpg)
Siemens Building Technologies Fire Products DivisionCompany Confidential
RPM Remote Peripheral Module
Two serial ports & 1 parallel port Mounts in its own enclosure
• Can be mounted under desk Used for
• Printer connection (PAL-1)– No VDT connection available
• FSI connection• Apogee Insight Life Safety system connection
OutputsA
nn
un
cia
tion
& C
on
trol
![Page 27: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/27.jpg)
Siemens Building Technologies Fire Products DivisionCompany Confidential
FireFinder XLS – Module review (vs. MXL)
FireFinder XLS MXL PMI MMB-2, MMB-3, MKB-4 DLC ALD-2I ZIC-4A CSM-4 PSC-12/PSX-12 MPS-6/12 CC-5/CC-2 MOM-4/MOM-2 CAB1, CAB2, CAB3 MSE-2, MME-3, MLE-6 CRC-6 CRM-4 SSD, SSD-C RCC-1, RCC-2 RPM PIM-1, PIM-2
![Page 28: FireFinder XLS System Basics (12!10!04)1](https://reader033.fdocuments.net/reader033/viewer/2022061418/553e7df0550346ad468b49ad/html5/thumbnails/28.jpg)
Siemens Building Technologies Fire Products DivisionCompany Confidential
FireFinder XLSSystems Basics
Thank You!Mark Pavlica
Product Manager
Siemens Fire Safety