Custom made firefighting vehicle body solutions for firefighting excellence
Firefighting 1
-
Upload
hkatniwala -
Category
Documents
-
view
216 -
download
0
Transcript of Firefighting 1
-
7/21/2019 Firefighting 1
1/1
COOLINGTOWER
MAKEUPTANK
DN
9M WIDEROAD
8MWIDESERVICEROAD
MAINROAD
FIRE
FIGHTING
TANK
DOMESTIC
TANK
LIFT ROOM
FIREFIGHTINGTANK
DOMESTICTANK
DN
SIAMESE
CONNECTION
ATRIUM
MUNICIPAL WATER MAIN
MUNICIPAL CONNECTION TO
SITE
GATE VALVE
FERRULE
STOP VALVE
SUPPLY PIPE TO
WATER HYDRANTS
WATER METER
STRAINER
BOOSTER PUMP
FIRE HYDRANTS
COOLING TOWER TO
CONDENSOR
BREECHING LINE
WET RISER CUM DOWN
COMER PIPE
CONNECTION FROM THE
STATIC TANK TO WET RISER
FIRE SAFETY:THE TECHNICAL INTERPRETATION OF FIRESAFETY OF BUILDING IS TO CONVEY THE FIRERESISTANCE IN TERMS OF HOURS WHENSUBJECTED TO FIRE OF KNOWN INTENSITY.
WIDE INTERPRETATION OF FIRE SAFETY COVERTHE FOLLOWING ASPECTS: FIRE PREVENTION & REDUCTION OF NUMBER
OF OUT-BREAKS OF FIRE. SPREAD OF FIRE, BOTH INTERNALLY &
EXTERNALLY. SAFE EXIT OF ALL OCCUPANTS IN THE EVENT
OF AN OUT-BREAK OF FIRE. FIRE EXTINGUISHING APPARATUS.
FIRE HYDRANTS:A FIRE HYDRANT IS AN OUTLET PROVIDED IN WATER PIPE FORTAPPING WATER MAINLY IN CASE OF A FIRE. THE CONNECTION ISMADE WITH FIRE HYDRANT WHEN A FIRE OCCURS IN THE AREAUNDER THE COMMAND OF FIRE HYDRANT AND THE WATER THUSOBTAINED FROM FIRE HYDRANT IS USED FOR FIRE FIGHTING PUPOSE.FIRE HYDRANTS ARE PLACED AT 33 M C/C FROM EACHOTHER IN
INHABITED AREAS & 300 M C/C IN OPEN AREAS.
FIRE HYDRANTS ARE PROVIDED ON A RING MAIN OF 150MM DIA INTHE GROUND AROUND THE BUILDING PRIPHERI. THE RING MAINGETS WATER FROM UNDERGROUND TANK WITH PRESSURE SO THATAVAILABLE PRESSURE AT EACH HYDRANT IS OF THE ORDER OF
6CM.HOSE
CONNECTION
SECTION - POST HYDRANT
DRAIN HOLE
FOOT PIECE
SEAT RING
VALVE
BARREL
G.LVL
WEATHER CAP
BONNET
OPERATINGNUT
STEMNUT
POST HYDRANT:PILLAR OR POST FIRE HYDRANTS: IT REMAINS STANDING ABOVE THEGROUND LIKE A POST BY ABOUT 0.9 M TO 1.20 M AND CONNECTEDTO A WATER MAIN UNDERGROUND.
FERRULE:FERRULE CONNECTION IS USED FOR TAKINGOUT DOMESTIC SERVICE CONNECTIONFROM MUNICIPAL MAINS.
BREECHING LINE:BREECHING LINE IS PROVIDED NEAR THEBOUNDRY, FOR FILLING OF UGT, WHEN IT ISEMPTY DUE TO USE FOR FIRE FIGHTING.
FLUSH HYDRANTS:THESE HYDRAN TS ARE INSTALLEDUNDERGROUND IN A BRICK OR CAST IRONCHAMBER WITH ITS TOP COVER SLIGHTLYABOVE STREET LEVEL. WITH LETTERS 'F.H.'INSCRIBED ON THE TOP COVER FOR
INDENTIFICATION.
SUPPLY PIPE TO
UNDERGROUND
STORAGE TANK
METER BOX WITH
COVER
STOP VALVE
WATER METERCOMPOUND WALL
SERVICE PIPE
GOOSE NECK
FERRULE
MUNICIPAL WATER
SUPPLY LINE
ROAD FOOTHPATH
SECTION OF MUNICIPAL WATER SUPPLY CONNECTION
VALVE SEAT
OUTLET
STEM
LEATHER VALVE
MASONARY WALL
OPERATINGARRANGEMENT
FOR STEM
C.I.COVERG.L.
SECTION THROUGH FLUSH WATER HYDRANT
SITE PLAN SCALE-1:200
FIRE CONTROL ROOM- F.C.R.
THIS ROOM IS PROVIDED ON THE GROUND FLOORWHICH COMPRISE OF PANEL SHOWING WORKING OF ALLTHE SMOKE DETECTORS.IN CASE OF FIRE, THE FIREMEN ASSESS THE SITUATION ANDCAUSE OF FIRE THROUGH THIS ROOM.
DN