Zachary May Building and Safety Standards Branch FPOABC | Kelowna | May 2013 Fire Safety in the 2012 BC Building Code

Transcript of Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in...

Page 1: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Zachary May Building and Safety Standards Branch FPOABC | Kelowna | May 2013

Fire Safety in the 2012 BC Building Code

Page 2: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Fire Safety in the 2012 BC Building Code

• Codes Development • Exit Signs • Limiting Distance & Fire Containment • 10 Minute Response • A2/B3 Occupancies • Lateral Loads

Page 3: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Confederation

Page 4: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

WWII

Page 5: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

National Codes

Page 6: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

• Early codes • Current codes

Page 7: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

National Code Development Process

Page 8: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 9: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

National Code change

Page 10: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Model national Codes adopted as regulation in each province

Page 11: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Fire Safety in the 2012 BC Building Code

• Codes Development • Exit Signs • Limiting Distance & Fire Containment • 10 Minute Response • A2/B3 Occupancies • Lateral Loads

Page 12: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

2012 BC Building Code

Page 13: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Old ‘Exit’ Sign

Page 14: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 15: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

ISO 7010

Page 16: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Designed by Yukio Ota in 1982

Page 17: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

ISO 7010

2010 National Building Code

2012 BC Building Code

Page 18: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Becoming global standard

Hong Kong

Page 19: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Becoming global standard

Stockholm Subway

Page 20: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

2012 BC Building Code

Page 21: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Worth clarifying:

• Internally Illuminated exit signs must have a powered light – photo luminescent does not comply • Photo luminescent signs may be used, but they must have a powered light to illuminate •Applies to renovations as well as new construction

Page 22: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Fire Safety in the 2012 BC Building Code

• Codes Development • Exit Signs • Limiting Distance & Fire Containment • 10 Minute Response • A2/B3 Occupancies • Lateral Loads

Page 23: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Limiting Distance

Page 24: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

St Lawrence Burns

Page 25: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Edmonton, Alberta

Page 26: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

NRC Testing Facility

Page 27: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

New changes in the 2012 BCBC

•Some significant changes for buildings within 2.0m of property line • Requirement for windows and projections • New requirements for containment & egress • Clarification of terms and intent of Code

Page 28: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 29: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Table 3.2.3.1.A. Maximum Concentrated Area of Unprotected Openings

Forming Part of Sentence 3.2.3.1.(5) Limiting Distance, m Max Area of Individual Unprotected Openings, m² 1.2 0.35 1.5 0.78 2.0 1.88

Page 30: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

3.2.3.1.(6) SPACING OF UNPROTECTED OPENINGS WITHIN 2 M The spacing between individual unprotected openings that serve a single room or space shall not be less than: a) 2 m horizontally of another unprotected opening that is on the same exposing building face and serves the single room or space, or b) 2 m vertically of another unprotected opening that serves the single room or space, or another room or space on the same storey.

Page 31: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 32: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

3.2.3.1.(7) SINGLE ROOM OR SPACE "single room or space" shall mean a) two or more adjacent spaces having a full-height separating wall extending less than 1.5 m from the interior face of the exterior wall, or b) two or more stacked spaces that are on the same storey.

Page 33: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

3.2.3.1.(7) SINGLE ROOM OR SPACE 7) For the purpose of Sentence (6), "single room or space" shall mean a) two or more adjacent spaces having a full-height separating wall extending less than 1.5 m from the interior face of the exterior wall, or b) two or more stacked spaces that are on the same storey.

Page 34: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 35: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

3.2.3.6 COMBUSTIBLE PROJECTIONS •3.2.3.6.(2) L.D. < .45 M - no soffits allowed •3.2.3.6.(3) L.D. > .45 M - soffits not allowed to extend within .45 M of P/L. •3.2.3.6.(4) .45M < L.D < 1.2 M – soffits fire blocked •3.2.3.6.(5) where soffits fire blocked for (4) and building is combustible, additional finishes allowed on surface of fire block materials.

Page 36: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 37: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 38: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 39: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 40: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 41: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 42: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Plenum Wires and Cables 3.1.4.3. , 3.1.5.18. and 3.6.4.3. •Plenum - concealed space often used for return air systems •Cables in plenums in combustible buildings must be FT4 •Cables in plenums in noncombustible buildings must be FT6

•Unless in totally enclosed noncombustible raceway

These requirements do not apply to cables used for transmissions of signals for fire alarm, security, radio and television.

BC Fire Code 2.4.1.1.(5) requires removal of abandoned cables.

Page 43: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 44: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

3.1.9.3. 3) Single conductor metal sheathed cables with combustible jacketting that are more than 25 mm in overall diameter are permitted to penetrate a fire separation required to have a fire-resistance rating without being incorporated in the assembly at the time of testing as required by Article 3.1.9.2., provided the cables are not grouped and are spaced a minimum of 300 mm apart.

Page 45: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

New definition for “Fire Block” and “Fire Stop” Block is to resist fire spread between concealed spaces. Fire block means a material, component or system that restricts the spread of fire within a concealed space or from a concealed space to an adjacent space.

Stop is used for filling gaps around penetrations in fire separations. Fire stop means a system consisting of a material, component and means of support used to fill gaps between fire separations or between fire separations and other assemblies, or used around items that wholly or partially penetrate a fire separation.

Fire Stops and Fire Blocks

Page 46: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 47: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

3.1.9.1. 3) Penetrations of a fire separation in conformance with Sentence 3.6.4.2.(2) shall be sealed by a fire stop that, when subjected to the fire test method in CAN/ULC-S115, “Fire Tests of Firestop Systems,” has an FT rating not less than the fire-resistance rating for the fire separation of the assembly.

Page 48: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 49: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 50: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 51: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

4) Sprinklers are permitted to penetrate a fire separation or a membrane forming part of an assembly required to have a fire-resistance rating without having to meet the fire stop requirements of Sentences (1) to (3), provided the annular space created by the penetration of a fire sprinkler is covered by a metal escutcheon plate in accordance with NFPA 13, “Installation of Sprinkler Systems.” 5) Unless specifically designed with a fire stop, fire dampers are permitted to penetrate a fire separation or a membrane forming part of an assembly required to have a fire-resistance rating without having to meet the fire stop requirements of Sentences (1) to (3), provided the fire damper is installed in conformance with NFPA 80, “Fire Doors and Other Opening Protectives.”

Page 52: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 53: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

3.3.1.5. 1) [described non-residential buildings that require two

egress doors, in case one becomes blocked.]

2) Where 2 egress doorways are required by Sentence (1), they shall be placed at a distance from one another equal to or greater than one third of the maximum overall diagonal dimension of the area to be served, measured as the shortest distance that smoke would have to travel between the nearest required egress doors.

Page 54: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 55: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 56: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Fire Safety in the 2012 BC Building Code

• Codes Development • Exit Signs • Limiting Distance & Fire Containment • 10 Minute Response • A2/B3 Occupancies • Lateral Loads

Page 57: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Limiting Distance and 10 Minute Response Time

Page 58: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Changes to measurement of limiting distance and 10 minute response time

• Meant to clarify intent of previous Code • Always existed in Part 3 • Now included in Part 9 • Construction requirement only • Only requires information from fire departments

Page 59: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

3.2.3.1. [2006 BCBC]

3.2.3.1. [2012 BCBC]

Page 60: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Changes to measurement of limiting distance and 10 minute response time

• Meant to clarify intent of previous Code • Always existed in Part 3 • Now included in Part 9 • Construction requirement only • Only requires information from fire departments

Page 61: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

2006 BCBC

Page 62: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

2012 BCBC

Page 63: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

2012 BCBC

Page 64: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Changes to measurement of limiting distance and 10 minute response time

• Meant to clarify intent of previous Code • Always existed in Part 3 • Now included in Part 9 • Construction requirement only • Only requires information from fire departments

Page 65: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Changes to measurement of limiting distance and 10 minute response time

• Inform building based on actual conditions • Similar to climate tables • Provides a clarity • Delayed implementation • Exists in other jurisdictions • Regulates construction, does not halt construction

Page 66: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Changes to measurement of limiting distance and 10 minute response time

• Meant to clarify intent of previous Code • Always existed in Part 3 • Now included in Part 9 • Construction requirement only • Only requires information from fire departments

Page 67: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Where does this requirement come from?

Page 68: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

NRC Testing Facility

Page 69: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

NRC Fire Research

• St. Lawrence Burns • High-Intensity Residential Fires Working Group • Testing • Fire Modeling • Based on time required for fire to reach flashover

Page 70: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

How do we determine “10 minute” response?

Page 71: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

A-3.2.3.1.(8) Intervention Time and Limiting Distance The total time from the start of a fire until fire suppression by the fire department depends on the time taken for a series of actions. Sentence 3.2.3.1.(8) is only concerned with the time from receipt of notification of a fire by the fire department until the arrival of the first fire department vehicle at the building. It specifies a 10-min time limit which must be met in more than 90% of the calls to the building served by the fire department. This reliability level and provision for flexibility is essentially consistent with NFPA 1710, “Organization and Deployment of Fire Suppression Operations, Emergency Medical Operations, and Special Operations to the Public by Career Fire Departments.”

Page 72: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Clause 4.1.2.1 of NFPA 1710 establishes “time objectives” for fire incidents as follows: 1 min (60 s) for turn-out of responders after receipt of notification of a fire, and 4 min (240 s) or less for arrival of the first arriving engine company at a fire suppression incident and/or 8 min (480 s) or less for the deployment of a full first alarm assignment at a fire suppression incident. The standard requires that the fire department establish a “performance objective” of not less than 90% for each response time objective. This reliability level is referred to in NFPA 1710 as a “performance objective.” Note: Appendix is for commentary only, and is not an enforceable part of the Building Code.

Page 73: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Still confused? Ask the Building and Safety Standards Branch:

Page 74: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

“Response time” is measured from the fire department’s receipt of the emergency call until a properly manned fire truck arrives at the building. The response time should be “turn out” time plus travel time to the site of the proposed building.

Page 75: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

The Building & Safety Standards Branch plays no role in determining fire department response times. Calculations/judgments can only be based on what the present circumstances are, or perhaps those that are known to occur in the near future.

Page 76: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

The Code does not require the application of any NFPA standard for fire department performance objectives. NFPA 1710 is referenced in the Building Code’s appendix to provide context to the 90% reliability objective identified in the Code. We recommend actual times be used in calculation of response times and not performance objectives identified in NFPA standards. As mentioned above, response times will be unique from community to community dependent upon real life circumstances.

Page 77: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

What happens if we do not have 10 minute response in our community?

Page 78: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

11 Minute fire department response means:

• Greater limiting distance • Fewer windows on exposing building face • More likely to have sprinklers • Generally safer construction to mitigate the risk

Page 79: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Changes to measurement of limiting distance and 10 minute response time

• Meant to clarify intent of previous Code • Always existed in Part 3 • Now included in Part 9 • Construction requirement only • Only requires information from fire departments

Page 80: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Fire Safety in the 2012 BC Building Code

• Codes Development • Exit Signs • Limiting Distance & Fire Containment • 10 Minute Response • A2/B3 Occupancies • Lateral Loads

Page 81: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 82: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 83: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 84: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 85: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 86: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 87: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 88: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Fire Safety in the 2012 BC Building Code

• Codes Development • Exit Signs • Limiting Distance & Fire Containment • 10 Minute Response • A2/B3 Occupancies • Lateral Loads

Page 89: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Why? Where? When? What? How?

Page 90: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Why the new requirements?

1. clarify application of code

before: seismic was considered implicitly

Page 91: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Why the new requirements?

1. clarify application of code

2. reduce risks

Page 92: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

http://www.earthquakesafety.com/_photo/earthquake-damaged-house.jpg

Page 93: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 94: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 95: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

now explicit and detailed requirements

Page 96: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Where are the new requirements?

Subsection 9.23.13.

… and several in existing subsections in Section 9.23.

Page 97: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

structural design requirements in Part 9

Part 9 Part 4

9.4.1.1.

good engineering practice

Canadian Wood Council “Engineering Guide for Wood

Frame Construction”

seismic

Part 4 good engineering practice

Part 9

9.23.13.

9.23.13.4. to 9.23.13.7. + other cross-referenced

provisions

gravity

Page 98: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

traditional constructi

on Part 4

good engineering practice

optional

optional optional

optional optional optional

Extreme

High

Low -Moderate

Forces

Sa(0.2) = 0.7

Sa(0.2) = 1.2

q50 = 0.8

q50 = 1.2

* different limits for heavy construction

9.23.13.3.

9.23.13.2.

9.23.13.1.

*

*

*

9.23.13.4. to

9.23.13.7.

Wind

Earthquake

Page 99: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Victoria , Langford, Sidney, Tofino, Ucluelet Cloverdale, Langley, Ladner, White Rock Ladysmith, Duncan, Crofton, Bamfield Sooke, Youbou, Surrey, Richmond

New Westminster, Nanaimo, Port Renfrew Abbotsford, Jordan River, Haney Vancouver, Burnaby, Mission City West Vancouver, North Vancouver Sechelt, Tahsis, Parksville Qualicum Beach, Gold River

Port Alberni, Chilliwack, Alberni, Squamish

Kelowna

Agassiz, Whistler, Powell River

Sa(0.2)

Kent

q50

Courtney, Sandspit Sandspit

1.2

0.7 0.8

Sa(0.2) values can be found in Div. B Appendix C.

Wind Earthquake

Page 100: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 101: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

What are the new requirements?

• concept

• basic requirements

• exceptions

Page 102: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Concept

Page 103: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

figure from HPO Illustrated Guide for Seismic Design of Houses

Page 104: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 105: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 106: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

New Key Components:

braced wall band

braced wall panel

Page 107: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Braced Wall Band an imaginary continuous straight band extending vertically and horizontally through the building or part of the building, within which braced wall panels are constructed

Braced Wall Panel a portion of a wood-frame wall where bracing, sheathing, cladding or interior finish is designed and installed to provide the required resistance to lateral loads due to wind or earthquake

Page 108: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

figure from HPO Illustrated Guide for S i i D i f H

Page 109: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

figure from HPO Illustrated Guide for S i i D i f H

Page 110: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 111: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 112: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

fundamental requirement: adequate amount of properly constructed walls how to locate and size walls

how to build and fasten walls

main goal: strong stable overall frame

Page 113: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Basic Requirements

Page 114: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Braced Wall Bands shall be full storey height

be ≤ 1.2m wide

lap at both ends with another BWB

be aligned with BWBs on storeys above & below

be spaced, at maximum, 10.6 m 7.6m where 1.0 ≤ Sa(0.2) ≤ 1.2 [Vi i ]

9.23.13.4.

Page 115: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Max 1.2 m Max 1.2 m

Max 1.2 m

Max 10.6 m (7.6 m) Max 10.6 m (7.6 m)

figure from HPO Illustrated Guide for Seismic Design of Houses

Page 116: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Braced Wall Panels shall be located within BWBs

extend from top of supporting footing, slab or subfloor to underside of floor ceiling or roof framing above

conform to limits on max spacing max distance from end of BWB min length min total length

9.23.13.5.

Page 117: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

> 750 > 600 <

2 4

00

< 6

400

< 10 600 (or 7 600)

Page 118: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

25% 25%

25%

Minimum Total Length of Braced Wall Panels in a braced wall band

1 storey 2 storeys 3 storeys

for light construction

40%

25%

25%

75%

Page 119: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance
Page 120: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Compliance

cladding panel-type (plywood, hardboard, OSB)

9.27 Table 9.23.3.4.

sheathing

plywood, OSB,

waferboard, or diagonal lumber

sheathing

9.23.16. Table 9.23.13.6.

fasteners 9.23.3.5

interior finish

panel-type (gypsum board)

9.29. Table 9.23.13.6.

Materials in Braced Wall Panels

9.23.13.6.

OR

OR

Page 121: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Exceptions

Page 122: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

9.23.13.5.(3)

porches &

sun rooms • ≤ 3.5m projection • 1:2 plan dimensions • no floor above • integral with main roof or fastened to wall

BWPs not required

Page 123: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

9.23.13.5.(4) and (5)

attached garages

BWPs not required in front wall

• ≤ 7.6m between front and back • ≥ 50% of back wall is BWPs • ≥ 25% of side walls is BWPs • ≤ 1 floor above

Page 124: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

setbacks

Page 125: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

9.23.13.7.(1), (2), (3)

setbacks additional requirements for adjacent interior braced wall band

additional fastening in perpendicular walls

sheathed floor and roof at setback

figure from HPO Illustrated Guide for S i i i f

Page 126: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

heavy construction

Page 127: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

traditional constructi

on Part 4

good engineering practice

optional

optional optional

optional optional optional

Extreme

High

Low -Moderate

Forces

Sa(0.2) = 0.7

Sa(0.2) = 1.1

9.23.13.3.

9.23.13.2.

9.23.13.1.

9.23.13.4. to 9.23.13.7.

heavy construction

Page 128: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

Victoria , Langford, Sidney, Tofino, Ucluelet Cloverdale, Langley, Ladner, White Rock Ladysmith, Duncan, Crofton, Bamfield Sooke, Youbou, Surrey, Richmond

New Westminster, Nanaimo, Port Renfrew Abbotsford, Jordan River, Haney Vancouver, Burnaby, Mission City West Vancouver, North Vancouver Sechelt, Tahsis, Parksville Qualicum Beach, Gold River

Port Alberni, Chilliwack, Alberni, Squamish

Kelowna

Agassiz, Whistler, Powell River

Sa(0.2)

Kent

q50

Courtney, Sandspit Sandspit

1.1

0.7 0.8

heavy construction

Wind Earthquake

Page 129: Fire Safety in the 2012 BC Building Code - FPOA Seminar/2013/Files/Zachary May... · Fire Safety in the 2012 BC Building Code • Codes Development • Exit Signs • Limiting Distance

25% 25%

25%

Minimum Total Length of Braced Wall Panels in a braced wall band

1 storey 2 storeys 3 storeys

Light Construction

Heavy Construction

40%

25%

25%

25%

75%

40%

25%

75%