    SBQ 3314 BUILDING MEASUREMENT III

    DR. SARAJUL FIKRI MOHAMEDDEPARTMENT OF QUANTITY SURVEYING

    FACULTY OF BUILT ENVIRONMENT

    UNIVERSITI TEKNOLOGI MALAYSIA

    FIRE FIGHTINGINSTALLATION

  • 8/2/2019 Fire Fighting Note

    2/125

    Fire Fighting InstallationSystemMeasurement Rules

    SECTION Q

    PLUMBING AND MECHANICALENGINEERING INSTALLATIONS

  • 8/2/2019 Fire Fighting Note

    3/125

    Measurement Rules

    Section Q

    Q.1 Information

    Q.2 Clasification Of Work

    Q.3 Location of works

    Pipeworks

    Q.7 Generally

    Q.8 Pipe and Fittings

    Q.9 Special Connection, etc

    Q.10 Labour

    Q.11 Sundries

    Q.12 Pipework Support

    Q.13 Connection

    Equipment and Ancillaries

    Q.19 Generally

    Q.20 Antivibration and sound insulation

    Q.21. Equipment support

    Q.22. Jointing

    Q.24. Identification plates

    Builders Work

    Q.31 Generally

    Q.32. Particularly

  • 8/2/2019 Fire Fighting Note

    4/125

    FIRE FIGHTING SYSTEMCOMPONENTS

    1. Builders Work

    2. Hose Reel System Swing hose- reel, Water storage tank, Electrical duty pump, Diesel

    duty pump, Piping: incoming pipe -rising pipe, distribution pipe

    3. Fire Alarm panel Manual Break Glass, Fire Alarm Bell, Batteries, Batery Charger

    4. Brasswork Air release valve, Gate valve, Check valve, Strainer valve, Flexible

    joint

    5. Portable Fire Extinguisher6. Equipment and Ancillaries Concrete plinth7. Pipe Support Pipe hanger8. Sundries

    Testing

  • 8/2/2019 Fire Fighting Note

    5/125

    R.2 Clasification of Work

    D.Fire Fighting Installation

    Fire Fighting Installation

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    6/125

    FIRE FIGHTING INSTALLATION

    Standpipe Sprinkler Portable

    DryStandpipe

    WetStandpipe

    Hose Reel

    Wet PipeSystem

    Dry PipeSystem

    Pre-actionSystem

    DelugeSystem

    - Water tank

    - Pump

    - Pipes

    - Sprinkler

    - Alarm

    - Water tank

    - Pump

    - Pipes

    - Sprinkler

    - Fire Detector

    - Alarm

  • 8/2/2019 Fire Fighting Note

    7/125

    GENERALLYQ.1 INFORMATION

    FIRE FIGHTING INSTALLATION

    GenerallyQ.1. Information1 Particulars of the following shall be given :

    a) Regulation, etc.

    b) Kind and quality of material.c) Gauge, thickness or substance of material.d) Any tests, etc.

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    8/125

    THE FIRE PROTECTION SYSTEM INSTALLED ARE INFULL COMPLIANCE AND REGULATIONS

    1. The British Standards Institution 750 For Fire Hydrant

    2. The British Standards Institution 5839 Part 1, 1980For Fire Alarm System

    3. The Requirements Of The Chief Inspectorate Of The

    Fire Services Malaysia.

  • 8/2/2019 Fire Fighting Note

    9/125

    Q.1.2 Assembling and jointing together the componentparts of composite units and providing anynecessary connecting flanges and jointing

    materials shall be deemed to be included withthe items concerned. Where composite units aresupplied by the Employer, particulars shall begiven of the assembly work involved.

    Q.1.3 Patterns, moulds, templets and the like shall bedeemed to be included with the items.

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    10/125

    Q.1.4 Priming and painting off-site and proprietaryfinishes or surface treatment applied as part ofthe production process shall be describedstating whether applied before or after

    fabrication or assembly.

    Q.1.5 Except where otherwise stated the method offixing and the provision of nails, bolts, nuts,

    holes, screws, plugs, shot-fired pins and the likeshall be given in the description of the work.

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    11/125

    FIRE FIGHTING INSTALLATIONS

  • 8/2/2019 Fire Fighting Note

    12/125

    Q.1.6 The nature of the background to which work is tobe fixed shall be given in the description. Anynecessary drilling of the backgrounds shall bedeemed to be included. Backgrounds shall beclassified as follows :

    a) Building-board which shall be deemed toinclude hardboard, compressed cement sheet,plasterboard, fibreboard and similar materialswhich do not grip woodscrews.

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    13/125

    Q.1.6 The nature of the background.

    b) Timber which shall be deemed to includesoftwood, hardwood, blockboard, plywood and

    similar materials which will grip wood-screws whena lead-hole has been drilled.

    c) brickwork, concrete or stone work

    d) plain metal

    e) glass

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    14/125

    Q.1.7. Temporary work shall be so described.Removing temporary work and making goodafter shall be deemed to be included with the

    item.

    1.8. Connecting to existing services shall bedescribed

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    15/125

    GENERALLY

    Q.2. CLASSIFICATION OF WORK

    Q.2.1 Work together with its metalwork, supports andthe like (unless associated with more than oneinstallation) shall be classified as follows andgiven under an appropriate heading :

    d) Fire Fighting Installation

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    16/125

    Q.3. LOCATION OF WORK

    Location of works :

    a. Internallyb. Externally

    c. In plant rooms

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    17/125

    PIPE WORKSQ.7 GENERALLY1. Purpose-made pipes and purpose-made pipe

    fittings shall be described.2. Pipes and pipe fittings which are wrapped, coatedor lined by the manufacturer shall be so describedstating the type of treatment.

    3. Pipework required to be temporarily fixed in

    position, dismantled for chromium-plating or otherspecial finishing and subsequently refixed shall beso described.

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    18/125

    Q.8 PIPE AND FITTING1. Pipes (measured over all pipe fittings, short

    running lengths and branches) shall be given inmetres stating the type and the normal size.

    Purpose-made pipe shall be so described andgiven separately. Curved pipes shall be sodescribed stating the mean radius.

    Joints in the running length shall be given in thedescription stating the method of jointing.

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    19/125

  • 8/2/2019 Fire Fighting Note

    20/125

    SETS OF FIRE FIGHTING EQUIPMENT

    Hose Reel

    Portable FE

  • 8/2/2019 Fire Fighting Note

    21/125

    Q.8 PIPE AND FITTING3. Flexible pipes and extensible pipes (measured as

    fully extended) shall each be so described.

    4. Pipes laid or fixed in ducts, trenches and chases orembedded in in-situ concrete or screeds shall eachbe so described.

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    22/125

    Pipe fittingsPIPE FITTINGS

    Piping inside

    switch room

    Heat detector

    Hose reel pipe

    Conduit

  • 8/2/2019 Fire Fighting Note

    23/125

    Q.9. SPECIAL CONNECTIONS, ETC.1. Special connections and special joints in pipes shall

    each be enumerated separately (except wheregiven in the description of another enumerated item)stating the nominal size and kind of pipe concernedand the method of jointing. Classification shall be asfollows :

    a) Connections between pipes of differing materialsand differing grades of the same material.

    b) Connections between pipes and appliances or

    equipment.

    c) Connections to existing pipes.

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    24/125

    Q.10.LABOURS

    Labours on pipes (e.g. made bends, made springs,made offsets, beaded ends, ornamental ends, etc.)shall be deemed to be included with the pipes on which

    they occur.

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    25/125

    Q.11 SUNDRIES

    6. Pipe-sleeves through walls, floors ceilings shall beenumerated stating the type, lengths, the nominalsize and kind of pipe passing through and the type

    of packing required, and if to be supplied for fixingby other trades, this shall be so described.

    7. Wall, floor or ceiling plates shall be groupedtogether as plates and enumerated stating the

    type and size.

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    26/125

    PIPE-SLEEVES

  • 8/2/2019 Fire Fighting Note

    27/125

    Q.12 PIPEWORK SUPPORTS

    12.1 Standard pipe supports shall be given in thedescription of the pipes stating the type and

    spacing of the supports.

    12.2. Non-standard pipe supports shall be describedand enumerated (no).

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    28/125

    Q.12 PIPEWORK SUPPORTS

    4. Components or assemblies of components (e.g.clips, saddles, pipe-hooks, holderbats, brackets,rollers, chairs and hangers or black-plates and

    girder-lugs) used to fix supports for more thanone pipe shall be enumerated separately statingthe type and size of components. Springcompensated components shall be so described

    stating the loading and movement to beaccommodated.

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    29/125

    PIPEWORK SUPPORTS

  • 8/2/2019 Fire Fighting Note

    30/125

    PIPE SUPPORT

  • 8/2/2019 Fire Fighting Note

    31/125

    Q.13 CONNECTIONS

    Connections to public mains, making good publichighway and any other work which may only be

    carried out by a Public Undertaking or LocalAuthority shall be given as a provisional sum.

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    32/125

    EQUIPMENT AND ANCILLARIESQ.19 Generally

    1. Unless otherwise stated, equipment such as boilers,generators, heaters, water treatment plant, tankscylinders, calorifiers, pumps, coolers, air-handlingunit, fans, refrigerator equipment, meters, sanitaryfittings, etc. and ancillaries such as soot doors toboilers, valves and cocks, gauges, automaticcontrols etc. shall be enumerated and related to thespecification referred to in clause Q.1.1.

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    33/125

    EQUIPMENT AND ANCILLLARIESQ.19 Generally

    2. Shall be described in conjunction with amanufacturers detailed specification (Q.19.2)

    3. Any limiting dimensions on the size shall begiven. (Q.19.3)

    4. Electrical connection shall be given in

    accordance with section R . (Q.19.4)

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    34/125

    DIESEL PUMP

    Pengganti apabila pam operasi elektrik tidak dapat berfungsi. Stanby pump. 135 main flow, 40 m tekanan dan 2900 rpm Equipments and ancillaries, Q.19.kecuali dinyatakan peralatan

    seperti tangki, silinder pam serta injap dan pili perlu di nyatakan.

    Unit NO

  • 8/2/2019 Fire Fighting Note

    35/125

    Carbon dioxide fire extinguishing systems are usedbecause of the most efficient extinguishing agents

    It is situated at the switch room

    It removes the oxygen and covers the surroundingatmosphere and literally strangles the fires to death.

    Advantages:

    a) odorless and non-toxic

    b) dry, inert gas, it will not conduct electricityc) cannot damage clothes or equipment nor

    contaminate liquids or food

    CO2 Fire Extinguishing Systems

  • 8/2/2019 Fire Fighting Note

    36/125

    HOSE REEL SYSTEM:

    WET PIPE

  • 8/2/2019 Fire Fighting Note

    37/125

    HOSE REEL SYSTEM

    Pressurised using 1 unit of electrical pumpset as duty pump& 1 unit diesel engine pumpset as standby

    Designed to operate an automatic mode (Pressure switch)& manual mode (manual starting from the pumpsets control

    panel)

    Standard coil length 30m, 36m or 100m.

    Specification :-Working Pressure : 220Psi (15 Bar)

    Minimum Burst Pressure : 696Psi (48 Bar)Test Pressure : 250Psi

  • 8/2/2019 Fire Fighting Note

    38/125

    Nozzles

    Hose Guides

    Fire Hose

    Reel

    Pressure

    Reducing Valve

    Fire Hose

    Reel

    Hose reel

  • 8/2/2019 Fire Fighting Note

    39/125

    TYPICAL HOSE REEL

    WET RISER

  • 8/2/2019 Fire Fighting Note

    40/125

    WET RISERIs constantly filled with water and thesupply should be capable ofmaintaining a running pressure of410kPa at the highest landing valve

    and give a flow rate of 23litres persecond. The maximum runningpressure permitted with one outletopen should be 510kPa.

    To maintain the required water

    pressure it is usually necessary toinstall pumping equipment. Directpumping from the main is notpermitted and a suction tank with aminimum actual volume of water of45.5 m2 must be installed.

  • 8/2/2019 Fire Fighting Note

    41/125

    COMPONENTS

    Hose reelPiping

    Brasswork

    Pump:

    Duty pump

    Standby pump

    Water Tank

  • 8/2/2019 Fire Fighting Note

    42/125

    WATER STORAGE TANK

    Equipments and ancillaries

    Clause Q.19.

    Unless otherwise stated, equipment such as tankshall be enumerated (no).

  • 8/2/2019 Fire Fighting Note

    43/125

  • 8/2/2019 Fire Fighting Note

    44/125

    HOSE REEL

    Hose reel wall

    mounted

  • 8/2/2019 Fire Fighting Note

    45/125

    VALVE

    BIBHorizontal

  • 8/2/2019 Fire Fighting Note

    46/125

    HOSE

    General purpose syntheticdelivery hose. Suitable forindustrial and rural firebrigades as well as staticbuilding protection.

    General industrial, commercialand civil engineeringapplications including waterauthorities where a high burstperformance hose is not

    necessary

    Lightweight and flexibleHeat and cold resistantAnti rot and anti-twist

  • 8/2/2019 Fire Fighting Note

    47/125

    BRANCH PIPE AND NOZZLE

    Branch pipes provide an adjustablenozzle to allow the curtain of water tobe altered from a narrow spray to awide spray.

    Nozzles provide a fixed jet of water.The basic branch pipe according toBS336 has an 21/2" inlet maleinstantaneous and outlet threaded11/3" BSP male for either a plain jetor a branchpipe adjustable nozzle.

    The branch pipe is controlled fromSHUT-OFF through JET and SPRAYto wide angle CURTAIN by rotatingthe annular sleeve.

  • 8/2/2019 Fire Fighting Note

    48/125

    HOSE REEL SYSTEM:

    DRY PIPE

  • 8/2/2019 Fire Fighting Note

    49/125

    System for dry riser

    This range includes:

    inlet breechings inlet and outlet

    cabinets outlet valves

    standpipes, bars andkeys.

  • 8/2/2019 Fire Fighting Note

    50/125

    DRY RISER COMPONENT

    DRY RISER

    Designed to house inletbreechings and landing

    valves Georgian wired glass panel

    and spring cylinder lock withkey

    Manufactured from zintec,

    epoxy polyester powdercoated - Red

  • 8/2/2019 Fire Fighting Note

    51/125

    FIRE EXTINGUSHER

  • 8/2/2019 Fire Fighting Note

    52/125

    FIRE EXTINGUSHER

  • 8/2/2019 Fire Fighting Note

    53/125

    Type of Fire

    Extinguisher

    Dry powderWater

    Gas

    Carbon

    dioxide

    (CO2)

    Foam

    Portable Fire Extinguisher

  • 8/2/2019 Fire Fighting Note

    54/125

    PORTABLE FIRE EXTINGUISHER

    1. Dry powder-No2. Testing-item.

    CARBON DIOXIDE SYSTEM

    1. CO2 cylinder-No

    2. Testing-item.

    Portable Fire Extinguisher

  • 8/2/2019 Fire Fighting Note

    55/125

    POWDER EXTINGUISHERS

    http://www.fire-protection-services.co.uk/products/http://www.fire-protection-services.co.uk/products/http://www.fire-protection-services.co.uk/products/
  • 8/2/2019 Fire Fighting Note

    56/125

    WATER EXTINGUISHERS

    http://www.fire-protection-services.co.uk/products/http://www.fire-protection-services.co.uk/products/http://www.fire-protection-services.co.uk/products/http://www.fire-protection-services.co.uk/products/http://www.fire-protection-services.co.uk/products/http://www.fire-protection-services.co.uk/products/
  • 8/2/2019 Fire Fighting Note

    57/125

    Foam extinguishers

    http://www.fire-protection-services.co.uk/products/http://www.fire-protection-services.co.uk/products/http://www.fire-protection-services.co.uk/products/http://www.fire-protection-services.co.uk/products/
  • 8/2/2019 Fire Fighting Note

    58/125

    Portable Fire Extinguisher.

    Alat pemadammudahalih (Portable FireExtinguisher) digunakanmelindungi bangunan

    dari bahaya kebakarankecil.

  • 8/2/2019 Fire Fighting Note

    59/125

    Carbon

    Dioxide fire

    extinguisher

    Portable foam &

    water Extinguisher

    Portable Dry

    Chemical Powder

    Fire Extinguisher

  • 8/2/2019 Fire Fighting Note

    60/125

    ALARM SYSTEM

  • 8/2/2019 Fire Fighting Note

    61/125

  • 8/2/2019 Fire Fighting Note

    62/125

    MANUAL ALARM

    COMPONENTS

    Fire alarm panel

    Manual break glass

    Alarm bell

  • 8/2/2019 Fire Fighting Note

    63/125

    MANUAL BREAK GLASS

    SMOKE DETECTOR

  • 8/2/2019 Fire Fighting Note

    64/125

    SMOKE DETECTOR

  • 8/2/2019 Fire Fighting Note

    65/125

    SMOKE DETECTOR

    SMOKE DETECTOR

    Fire alarm system isfunctioning as a

    components which givewarning sign to occupants ina building if it is burning.

    It normally, installed withdetector.

    There is 2 type of detector,passive (Manual breakglass) and active (Smokedetector, heat detector, lightdetector).

  • 8/2/2019 Fire Fighting Note

    66/125

    LIGHT FITINGSLIGHT FITTINGS

    Keluar Sign

    Flashing lights

    Emergency light

    SPRINKLER SYSTEM

  • 8/2/2019 Fire Fighting Note

    67/125

    SPRINKLER SYSTEM

    Sprinkler system adalah sebuah sistem gabungan antara paip-paipyang dipasang di dalam bangunan dan sprinkler (overhead piping) bagimembolehkan ianya digunakan sebagai alat pemadam api.

    Alat-alat di dalam sistem :

    Tangki Air (gravity Tank).Fire Pump.

    Tangki Simpanan (Reservoir/Pressure Tank).

    Penyambungan kepada Bekalan Utama (Connection to Main/CityService).

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    68/125

    EQUIPMENT AND ANCILLLARIES

    Q.20 Anti-vibration and sound insulation

    Anti-vibration mountings for plant shall be enumeratedstating the type and the size. Anti-vibration materialand sound-insulating material in plant bases shall begiven in square metres stating the nature of thematerial and the thickness.

    MEASUREMENT RULES

    ANTI VIBRATION

  • 8/2/2019 Fire Fighting Note

    69/125

    ANTI VIBRATION

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    70/125

    EQUIPMENT AND ANCILLLARIES

    Q.21 Equipment supports

    1. Equipment supports shall be enumerated and

    described.2. Particulars of the method of fixing shall be given in

    the description in accordance with clauses Q.1.5-6.

    MEASUREMENT RULES

    FIRE HYDRANT

  • 8/2/2019 Fire Fighting Note

    71/125

    FIRE HYDRANT

    & HOSE REEL

    PORTABLE FIRE

    EXTINGUISHER

    (DRY POWDER)

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    72/125

    EQUIPMENT AND ANCILLLARIES

    Q.22 Jointing

    Particulars of the method of jointing shall be given inthe description of the equipment.

    MEASUREMENT RULES

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    73/125

    EQUIPMENT AND ANCILLLARIES

    Q.24 Identification Plates

    Identification plates shall be deemed to be included.

    MEASUREMENT RULES

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    74/125

    SUNDRIES

    Q.30 Generally

    1. Draining and refilling existing system shall be given

    as a provisional or prime cost sum.

    2. Disconnecting, setting aside and refixing equipmentfor the convenience of other trades shall be given

    as an item stating the relevant particulars.

    MEASUREMENT RULES

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    75/125

    SUNDRIESQ.30 Generally

    3. Temporarily operating each installation (except fortesting) shall be given as an item stating any

    required qualifications of the attendant, the durationof the operating period in hours and the purposeand particulars of any special insurance coverrequired by the Employer. Provision of solid fuel,

    liquid fuel, gas and electricity for power and lightingshall be deemed to be included with the item

    MEASUREMENT RULES

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    76/125

    SUNDRIESQ.30 Generally4. Testing each installation shall be given as an itemstating any

    required qualifications of the attendant, the number of stagetests in addition to the final, the purpose of the tests, theinstruments and appliances required to be provided andparticulars of any special insurance cover required by theEmployer. Provision of solid fuel, liquid fuel, gas and electricityfor power and lighting shall be deemed to be included with theitem.

    5. Preparing plans or diagrams of the installations as fitted shallbe given as an item stating the kind of information required tobe shown and the number of copies of each drawing requiredto be provided.

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    77/125

    SCHEMATIC DRAWING

    1.Heat Detector

    2.Smoke Detector

    3.Extinguishing Nozzles

    4.Fire Curtain (for Louver Door /Opening)

    5. CO2 Cylinder c/w Accessories

    6. Alarm Bell

    7. Key Switch

    8. Double Inter-lock ControlPanel c/w Back

    9. Normal / Discharge Light

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    78/125

    BUILDERS WORKQ.31 GENERALLY

    1. Unless otherwise stated, all items of builders shall

    be given in accordance with the appropriatesection.

    2. Builders works in connection with plumbing andmechanical engineering installations shall be

    grouped together under an appropriate heading.

    MEASUREMENT RULES

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    79/125

    BUILDERS WORKQ.32 PARTICULARLY

    1. Excavating trenches for pipes not exceeding 55mmnominal size shall be given in accordance with

    clause D.12.9

    2. For pipe over 55mm shall be given in accordancewith clause V.2

    3. Cutting away for making good after M&E works

    MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    80/125

    SUMMARY OF SMM

    SUMMARY OF MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    81/125

    CLAUSE ELEMENT METHOD UNIT

    Q.1.1 All element Shall be given in regulations, kind and qualityof material, gauge, thickness or substance ofmaterial with any tests.

    Q.1.2 Assembling and

    jointing

    Connecting flanges and jointing shall include

    with the items.

    Q.1.3 Patterns, moulds,templets Shall be include with the items.

    Q.1.4 Priming andpainting

    Described the work whether applied before orafter fabrication or assembly.

    Q.1.5 Nails, bolts, nuts,holes, screws,plugs, shot-firedpins

    In the description of work, stated the method offixing.

    SUMMARY OF MEASUREMENT RULES

    SUMMARY OF MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    82/125

    Q.1.6

    (a-f)

    a) building board

    b) timberc) metal-faced or

    composition-faced timber

    d) brickwork,concrete orstonework

    e) plain metalf) glass

    Shall stated the method of fixing and includingthe necessary drilling of the backgrounds andbe given in the description.

    Q.1.7 Temporary work Shall be include with the items ( removingtemporary work and making good )

    Q.1.8 Connections Shall be given in the description the nature of

    work, turning off supplies of any restrictionwhen breaking into existing pipes.

    Q.2.1 d) fire fightinginstallation

    Given under an appropriate heading with itsmetalwork and supports.

    SUMMARY OF MEASUREMENT RULES

    SUMMARY OF MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    83/125

    Q.3.1 All element The location for the work that must be

    identified :i) internallyii) externallyiii) in plant rooms

    Q.8.1 Pipes Measured all over the pipe fittings, shortrunning lengths and branches stating the type

    and nominal size. Separate it if it is purpose-made pipe. Curved pipe stating the radius.Joints shall be given in the description statingthe method of jointing.

    M

    Q.8.2 Joints of a specialcharacters and extrademountablecouplers

    Shall be described as extra over Nos.

    Q.8.3 Flexible pipes andextensible pipes

    Measured as fully extended and shall each beso described.

    Q.8.4 Pipes laid or fixed inducts, trenches andchases

    Shall be described.

    SUMMARY OF MEASUREMENT RULES

    SUMMARY OF MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    84/125

    Q.8.5 Flow and return

    header pipe

    All measurement stating the length, type and

    nominal size of the main pipe and branch pipeand also method of construction and jointingthe ends.

    Nos.

    Q.8.6 Pipe fittings andpurpose made pipefittings

    All details, cutting and jointing shall bedescribed.

    Nos.

    Q.8.7 Expansion loops All measurement stating the limiting dimensionsand the amount of expansions to beaccommodated.

    Nos.

    Q.8.8 Expansioncompensators

    All measurement stating the type of joint andthe amount of expansions to beaccommodated.

    Nos.

    Q.8.9 Flanges and unions Necessary solely for erection purposes shallincluded.

    Q.8.10 Jointing All jointing shall be deemed included with theitems.

    Q.8.11 Fittings and jointing All measurements stating he size and kind ofpipe flanged concerned perforating

    Nos.

    SUMMARY OF MEASUREMENT RULES

    SUMMARY OF MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    85/125

    Q.9.1 Special connections

    Special joints in pipesMeasured separately stating nominal size,

    kind of pipe, method of jointing and must

    be classifya) Connections between pipes of different

    materials and difference grades and of thesame material.

    b) Connections between pipes andappliances or equipment.

    c) Connections to existing pipes.

    Q.9.2 Isolated joints As extra over stating the type of jointing

    Q.10 Made bends, madesprings, made offsets,beaded ends,ornamental ends, etc.

    Shall included with the pipes on which theyoccur.

    Q.12.1 Standard pipesupports

    Shall described on the description of the pipesstating the type and spacing.

    Q. 12.2 Non-standard pipesupports

    Shall be described. Nos.

    Q.12.3 Supports that arelined to insulate pipes

    Shall described stating the type of liningmaterial.

    SUMMARY OF MEASUREMENT RULES

    SUMMARY OF MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    86/125

    Q.12.4 Clips, saddles, pipe-

    hooks, holderbats,brackets, rollers,chairs, hangers/blackplates,Gender-laps

    Enumerated separately stating the type and size Nos.

    Q.12.5 Pipe anchor Enumerated separately stating nominal size of

    pipe, type and size of components, method offixing of the pipe and nature of work.

    Nos.

    Q.13 Connection Work which may only carried out by PublicUndertaking or Local Authority.

    P.S

    SUMMARY OF MEASUREMENT RULES

    SUMMARY OF MEASUREMENT RULES

  • 8/2/2019 Fire Fighting Note

    87/125

    Q.15.1 Special connections,special joints

    Enumerated separately stating the size, kindof ducting and also method of jointing ,

    classify ;a) Connections between ducting of differing

    materials.b) Connections between ducting and

    equipment stating the nature of theequipment.

    c) Isolated joints which differ from those

    given in the description of the ducting.d) Flexible connections between ducting and

    plant.

    Nos.

    Q.15.2 Ducting turn andsplitters

    Enumerated separately stating type andmaterial size of ducting

    Nos.

    Q.15.3 Nozzle outlets, testholes and coresaccess doors

    Shall described stating size, method of jointingand material and thickness or gauge

    Nos.

    Q.15.4 Cowls, terminals,intake louvers

    Stating size and type, size of ducting andmethod of jointing.

    Nos.

    SUMMARY OF MEASUREMENT RULES

    Taking off list

  • 8/2/2019 Fire Fighting Note

    88/125

    g_______________________________________________________________________________________________________________________

    1.Hose Reel System

    Swing hose reelWater tank

    Electrical duty pump

    Diesel standby pump

    Alarm bell

    3.Brass Work

    Ball float valveStrainer valve

    Stop valve

    Flexible connection

    Check valve

    Gate valvePressure gauge

    2.Pipe Work

    Incoming pipe

    Distribution pipe

    Rising pipe

    Painting to pipe

    4.Connection To Public Main

    5.Builders work

    6.Testing

    Taking off List

  • 8/2/2019 Fire Fighting Note

    89/125

    Taking off List_______________________________________________________________________________________________________________________

    No. ITEM CLAUSE UNIT

    1. Hose Reel System

    Swing hose reel

    Water tank

    Electrical duty pumpDiesel standby pump

    Alarm bell

    Q.19.1 Nos.

    Taking off List

  • 8/2/2019 Fire Fighting Note

    90/125

    Taking off List_______________________________________________________________________________________________________________________

    No. ITEM CLAUSE UNIT

    2. Pipe Work

    Incoming pipe

    Distribution pipe

    Rising pipePainting to pipes

    Pipe fittings

    Q.7, Q.8.1

    Q.8.6

    M

    Item

    Nos.

    Taking off List

  • 8/2/2019 Fire Fighting Note

    91/125

    g_______________________________________________________________________________________________________________________

    No. ITEM CLAUSE UNIT

    3. Brass Work

    Ball float valve

    Strainer valve

    Stop valve

    Flexible connectionCheck valve

    Gate valve

    Pressure gauge

    Q.19.1 Nos.

    ki ff i

  • 8/2/2019 Fire Fighting Note

    92/125

    Taking off List_______________________________________________________________________________________________________________________

    No. ITEM CLAUSE UNIT

    4.

    5.

    6.

    Connection to public

    main

    Builders work

    Testing

    Q.13

    Q.31, Q.32.1

    Q.30.4

    Provisional

    Sum

    Item

  • 8/2/2019 Fire Fighting Note

    93/125

    TAKING OFF

    LIST

    1 Hose reel No

  • 8/2/2019 Fire Fighting Note

    94/125

    1. Hose reel. -No2. Water storage tank. -No3. Electrical duty pump. -No4. Diesel standby pump -No5. Incoming pipe. -M6. Main distribution pipe .-M7. Rising main pipe. -M8. Distribution pipe. -M9. Suction pipe. -M

    10.Drain pipe.- M11.Ball float valve. -No12.Strainer valve. -No13.Stop valve. -No14.Flexible connection. -No15.Check valve. -No

    16.Pressure gauge. -No17.Pressure switch. -No18.Automatic air release valve. -No19.Cables. -M20.Testing -item

  • 8/2/2019 Fire Fighting Note

    95/125

    1. Main fire alarm console panel. -No2. Manual break glass. -No3. Fire Alarm Bell. -No4. Heat detector. -No

    5. Smoke detector. -No6. Cables. -No7. Testing -item.

    TAKING-OFF LIST1 P bl

  • 8/2/2019 Fire Fighting Note

    96/125

    1. Preambles

    2. Builders work

    i.Exc.trench to receive hydrant pipe M

    ii.Exc.trench to receive incoming pipe M

    3. Pipework

    i.For pillar hydrant

    - 150mm dia. MSCL pipe laid in trench M

    ii.For incoming pipe

    - 150mm dia. MSCL pipe laid in trench M

    - 150mm dia. MSCL pipe laid on slab M

    - 150mm dia. MSCL pipe fixed to wall M

    iii.For pump house

    - 200mm dia. MSCL pipe laid on slab M- 50mm dia. MSCL pipe laid on slab M

    - 200mm dia. MSCL pipe fixed to wall M

    - 50mm dia. MSCL pipe fixed to wall M

    - 150mm dia. MSCL pipe fixed to wall M

    TAKING-OFF LIST (Contd)

  • 8/2/2019 Fire Fighting Note

    97/125

    3. Pipework (contd)

    iv.For hosereel

    - 50mm dia. G.I pipe fixed to wall M

    - 25mm dia. G.I pipe fixed to wall M

    v.For sprinkler

    - 150mm dia. G.I pipe fixed to ceiling M

    - 100mm dia. G.I pipe fixed to ceiling M

    - 80mm dia. G.I pipe fixed to ceiling M- 65mm dia. G.I pipe fixed to ceiling M

    - 50mm dia. G.I pipe fixed to ceiling M

    - 45mm dia. G.I pipe fixed to ceiling M

    - 32mm dia. G.I pipe fixed to ceiling M

    - 25mm dia. G.I pipe fixed to ceiling M- 150mm dia. G.I pipe fixed to wall M

    - 25mm dia G.I drain pipe fixed to wall M

    vi.Brasswork

    - Gate valve NO

    - Alarm valve NO

    TAKING-OFF LIST (Contd)

    Pipework (contd)

  • 8/2/2019 Fire Fighting Note

    98/125

    Pipework (cont d)

    vii.Breeching inlet NO

    4. Pillar Hydrant NO5. Hose Reel System

    i.Swing hose reel NO

    ii.Electrical duty pump NO

    iii.Diesel standby pump NO

    6. Sprinkler System

    i.Sprinkler head NOii.Sprinkler tank NO

    iii.Electrical duty pump NO

    iv.Electrical jockey pump NO

    v.Diesel standby pump NO

    7. Conduitsi. 2 x 2.5mm2 PVC cable in metal conduit M

    ii. 2 x 1.5mm2 PVC cable in metal conduit M

    8. Cable

    i. 2 x 2.5mm2 PVC cable in metal conduit M

    ii. 2 x 1.5mm2 PVC cable in metal conduit M

    TAKING-OFF LIST (Contd)

  • 8/2/2019 Fire Fighting Note

    99/125

    9. Fire Alarm System

    i.Control gear NOii.Junction box NO

    iii.Manual break glass NO

    iv.Fire alarm bell NO

    v.Heat detector NO

    vi.Smoke detector NO

    10. Portable Fire Extinguisher

    i.Dry powder extinguisher NO

    ii.CO2 extinguisher NO

    11. Testing ITEM

    FIRE FIGHTING SYSTEMTAKING OFF LIST UNTUK HOSE REEL SYSTEM.

  • 8/2/2019 Fire Fighting Note

    100/125

    1. Builders Work

    a) Excavation M

    2. Hose Reel System

    a) Swing hose- reel No

    b) Water storage tank No

    c) Electrical duty pump No

    d) Diesel duty pump No e) Piping: incoming pipe M

    rising pipe M

    distribution pipe M

    3. Fire Alarm Panel

    Manual Break Glass NO Fire Alarm Bell NO

    Batteries NO

    Batery Charger NO

    FIRE FIGHTING SYSTEMTAKING OFF LIST UNTUK HOSE REEL SYSTEM.

  • 8/2/2019 Fire Fighting Note

    101/125

    4. Brasswork Air release valve No Gate valve No Check valve No Strainer valve No Flexible joint No5. Equipment and Ancillaries Concrete plinth M26. Pipe Support Pipe hanger NO7. Sundries Testing Item

  • 8/2/2019 Fire Fighting Note

    102/125

    Fire fightingInstallation system

    Bill of Quantities

    ITEM DESCRIPTION UNIT QTY RATE RM CENT

    FIRE FIGHTING INSTALLATION, TESTING,

  • 8/2/2019 Fire Fighting Note

    103/125

    COMMISSIONING AND MAINTENANCE OF

    FIRE FIGHTING SYSTEM.

    HOSE REEL SYSTEM

    Swing hose-reel complete with 25mm diameter x

    30mm long hose,12.5mm diameter nozzles, fixing,

    bracket, reducer, gate valve and other accessories as

    described.

    Hot-dipped galvanized pressed steel water storage

    tank of approved type, manufactured to BS 1564,

    3.66m x 2.44m x 1.22m height with 2400 gallons

    capacity, complete with float valve, level indicator,

    ladder, overflow pipe and drain pipe, at approximately

    1000mm high above ground level.

    Electrical duty pump, 30 igpm, 150 ft. head.

    Diesel standby pump, 32 igpm, 160 ft. head.

    TESTINGAllow for testing the foregoing fire fighting system,

    make good any defects and leave the whole of the

    installation in perfect working order to the

    satisfaction of the S.O and Local Authority.

    No.

    No.

    No.

    No.

    Item

    20

    1

    1

    1

    Preambles

  • 8/2/2019 Fire Fighting Note

    104/125

    The drawing where the drawing no.

    FNP/BL/0205/F01-04 shows the layout of the fire

    fighting system.All quantities are all provisional

    subject to remeasurement upon combination

    construction of the said item.

    The fire fighting system to be excuted by the

    contractor in accordance to Jabatan Bomba

    Malaysia requirement and approval.

    All wiring to brickwall and soffit of ceiling shall

    be concealed unless otherwise stated and all

    wiring above ceiling space of roof level shall be in

    galvanised iron conduit and coloured by red.

    The item of this bill not fully described and the

    rates shall be held to include for all short running,

    bend,tees,joints,valve,reducer,backnuts and the

    like.The contractor must allow for testing fire

    fighting system and handling over the test

    certificate to the architect.

    The contractor shall be provide for obtaining all

    necessary plan.

  • 8/2/2019 Fire Fighting Note

    105/125

    ITEM DESCRIPTION UNI

    T

    QTY RATE RM CENT

    FIRE FIGHTING INSTALLATION, TESTING,

    COMMISSIONING AND MAINTENANCE OF

    FIRE FIGHTING SYSTEM.

    HOSE REEL SYSTEM

    Swing hose-reel complete with 25mm diameter x

    30mm long hose,12.5mm diameter nozzles, fixing,

    bracket, reducer, gate valve and other accessories as

    described.

    Hot-dipped galvanized pressed steel water storagetank of approved type, manufactured to BS 1564,

    3.66m x 2.44m x 1.22m height with 2400 gallons

    capacity, complete with float valve, level indicator,

    ladder, overflow pipe and drain pipe, at

    approximately 1000mm high above ground level.

    Electrical duty pump, 30 igpm, 150 ft. head.

    Diesel standby pump, 32 igpm, 160 ft. head.

    TESTING

    Allow for testing the foregoing fire fighting system,

    make good any defects and leave the whole of the

    installation in perfect working order to the

    satisfaction of the S.O and Local Authority.

    No.

    No.

    No.

    No.

    Item

    20

    1

    1

    1

    APARTMENT J.B

    Description QTY Unit Rate RM SENELEMENT FIRE FIGHTING INSTALLATION

    Fire-Fighting in connecting (internally)

    Fire Alarm system

    A Manual Break glass fire alarm with 24 volts 6 NO

    D C supply mounted at wall as described

  • 8/2/2019 Fire Fighting Note

    106/125

    D.C supply, mounted at wall as described

    B 150 mm Diameter fire alarm bell with 24 6 NO

    volts D.C supply, mounted as described

    Fire Fighting Equipment

    Lighting Installation (internally)

    C KELUAR' Sign complete with nickel 8 NO

    Cadmium batteries, tuber, etc and

    accessories with approved 13 W

    non-contained fluorescent

    D Self contained Emergency Light fitting 8 NO

    complete with nickel cadmium battery and

    outomatic charger unit similar econ lite

    Hose Reel system

    E Hot Dipped Galvanised Pessed Steel Water 1 NO

    Storage Tank of approved type,

    manufactured to BS 1564, 3m x 2m x 2m

    height with 2640 Gallons capacity,

    complete with 50 diameter overflow

    pipe,suction pipe, drain pipe incoming pipe

    at approximately 100 mm above ground

    level

    F 1" Diameter Swing Type Hydraulic hose reel 6 NO

    drums each c/w diameter x 100 ft. non.

    Kink double braided tubing and 1" diameter

    3 jet spray nozzle

    G Electrical Duty Pump, 30 IGPM, 120 ft head 1 NO

    H Diesel Standby Pump, ditto 1 NO

    Galvanised Iron class 'B' Tubing to comply

    with BS 1387, screw socket together

    K 50 mm Diameter incoming pipe, at High 2.00 M

    level free standing

    L 50 mm Diameter overflow pipe,ditto 4 M

    APARTMENT J.B

    Description QTY Unit Rate RM SEN

    Galvanised Iron class 'B' Tubing to comply

    with BS 1387, screw socket together

    A 50 mm Diameter suction pipe at low level 1 M

  • 8/2/2019 Fire Fighting Note

    107/125

    A 50 mm Diameter suction pipe at low level, 1 M

    free standing

    B 25 mm Diameter riser pipe fixed to brickwall 3 M

    C 50 mm Diameter drain pipe at low level and 2 M

    jointing to Galvanised iron pipe

    Brasswork To Comply With BS 1010 as described :-

    D 50 mm Diameter flexible connection and 2 NO

    jointing to galvanised iron pipe

    E 50 mm Diameter Check valve, ditto 2 NO

    F 50 mm Diameter stop valve, ditto 2 NO

    G 50mm Diameter Ball float valve, ditto 2 NO

    H 50mm Diameter gate valve, ditto 2 NO

    J 50mm Diameter outomatic air release valve, 2 NO

    ditto

    K 50mm Diameter pressure gauge, ditto 1 NO

    L 50mm Diameter stairer valve, ditto 2 NO

    BUILDER'S WORK

    M Wire brush and painting primer, undercoat Item

    and two coat gloss oil to surface of

    galvanised iron pipe

    N Installation inclusive of hacking, punching of Item

    holes in wall and floors, coring of holes

    through reinforce concrete slab and making

    good

    Testing

    O Allow for testing foregoing fire fighting Item

    system, make good and any defects and

    leave the whole of the installation in perfect

    working order to the satisfaction of the S.O

    and Local Authority

  • 8/2/2019 Fire Fighting Note

    108/125

    PROJEK

    Cadangan Merekabentuk, Membina &

    Menyiapkan SMK Kenangan, Segamat, Johor,Di atas Lot 5848, 2259 Sebahagian Lot 5848

    dan Sebahagian Lot 2258.

    PEJABAT LLM WILAYAH TIMUR BERSERTA KEM DI INTERCHANGE KUANTAN.

    ITEM UNIT QTY RATE RM

    ELEMENT : FIRE FIGHTING INSTALLATION

    (INTERNALLY)

    DESCRIPTION

  • 8/2/2019 Fire Fighting Note

    109/125

    (INTERNALLY)

    PREAMBLE ( All Provisional )

    A The fire fighting installation is to be executed by contrator

    in accordance with Jabatan Bomba requirement and approval.

    Where items in this bill are not fully describes the rates shall

    be held to include for all piping, control gear and etc all as

    described or as required by Jabatan Bomba as being

    appropriate for installation. The rates be held to include for all

    short running lengths, bends, tees and etc. The contractor

    must allow for testing the fire fighting installation and handling

    over the test certifiate to the Architect. (Q.1) Item

    HOSE-REEL SYSTEM

    B Hydraulic hose-reel complete with 36 mm x 25 mm diameter

    long hose, 12.5 mm diameter nozzles, fixing, bracket,

    reducer, gate valve and other accessories as described.

    (Q.19) No 1

    C Electrical duty pump with 30 IGPM at 135 feet head. (Q.19) No 1

    D Diesel standby pump with 130 IGPM at 135 feet head (Q.19) No 1

    Galvanised Iron Class 'B' Tubing to Comply With BS 1387

    Screw Socketed Together Including All Necessary Short

    Length, Fire Bends, Tees, Dimishing Pieces, Plugs and

    The Like as Described.

    E 50 mm Diameter incoming pipe laid in trench. (Q.8) M 13

    F 50 mm Diameter distribution pipe laid in ground slab. (Q.8) M 17

    G 50 mm Diameter distribution pipe fixed in ceiling space

    horizontally with approved brackets. (Q.8) M 23

    H 50 mm Diameter distribution pipe fixed to brickwall vertically

    with approved brackets. (Q.8) M 17

    J 25 mm Diameter distribution pipe fixed to hidraulic hose-reel.

    (Q.8) M 1

    K EXTRA OVER 50 mm Diameter elbow. (Q.8.1) No 11

    FF / 01

    TO COLLECTION

    PEJABAT LLM WILAYAH TIMUR BERSERTA KEM DI INTERCHANGE KUANTAN. (CONT'D)

    ITEM UNIT QTY RATE RM

    ELEMENT : FIRE FIGHTING INSTALLATION

    (INTERNALLY)

    DESCRIPTION

  • 8/2/2019 Fire Fighting Note

    110/125

    (INTERNALLY)

    A EXTRA OVER 50 mm Diameter tee. (Q.8.1) No 1

    B EXTRA OVER 25 mm Diameter elbow. (Q.8.1) No 2

    C 12 mm Diameter mild steel brackets at 600 mm centres

    to centres to support galvanised iron pipe. (Q.12.4) No 68

    Brasswork to Comply with BS 1010 as Described.

    D 50 mm diameter gate valve and jointing to galvanised iron

    pipe. (Q.19) No 6

    E Hot-dipped galvanised pressed steel water storage tank

    opproved type, manufactured to BS 1564, 12' x 4' x 8' height

    with 1000 gallons capacity, complete with float valve, level

    indicator, ladder, overflow pipe and drain pipe at ground level.

    (Q.19) No 1

    Sundries

    F Testing and commissioning the hose-reel system asdescribed in the specification. (Q.30.4) Item

    PORTABLE FIRE EXTINGUISHER

    G 9 kg ABC extinguisher dry powder bomba approved type

    manufactured to BS 5306, complete with brackets and

    accessories. (Q.19) No 7

    Sundries

    H Testing and commissioning the portable fire extinguisher

    as described in the specification. (Q.30.4) Item

    FIRE ALARM SYSTEM

    J 150 mm Diameter fire alarm bell with 24 V (D.C) supply

    mounted at wall as described. (Q.19) No 2

    K Manual break glass fire alarm size 84 mm x 115 mm with

    24 V (D.C) supply mounted at wall as described. (Q.19) No 2

    PVC Insulated Cable Drawn into Concealed Galvanised

    Iron Conduit. (measured separately)

    L 2 x 2.5 mm2 cable. (Q.19.4) M 54

    TO COLLECTION

    FF / 02

    PEJABAT LLM WILAYAH TIMUR BERSERTA KEM DI INTERCHANGE KUANTAN. (CONT'D)

    ITEM UNIT QTY RATE RM

    ELEMENT : FIRE FIGHTING INSTALLATION

    (INTERNALLY)

    DESCRIPTION

  • 8/2/2019 Fire Fighting Note

    111/125

    (INTERNALLY)

    Galvanised Iron Class 'B' Conduit with Screw Joints

    Including All Short Running Length, Bends, Tees, Saddles

    Crampets, Locknuts, Circular Boxes as Described.

    A 50 mm Diameter conduit, chase into brickwall vertically

    with approved bracket. (Q.19.4) M 17

    B 50 mm Diameter conduit, fixed in ceiling space with

    approved bracket. (Q.19.4) M 37

    Sundries

    C Testing and commissioning the fire alarm system as

    described in the specification. (Q.30.4) Item

    BUILDER'S WORK

    D Excavate trench to receive 50 mm diameter incoming pipe,

    maximum depth nearest to 0.25 m including filling in,

    compaction and disposal of surplus soil as desribed. (Q.32.1) M 18

    E 600 mm thick vibrated reinforced conrete grade 20 as

    concrete plinth including all necessary formwork and

    reinforcement. (F.3.19) m2

    F Allow for testing the foregoing fire fighting installation,

    make good any defect and leave the whole of the installation

    in perfect working order to the satisfaction of the S.O and

    Local Authority.

    (Q.30.4) Item

    TO SUMMARY

    FF / 03

    Taking Off list Builders Work

  • 8/2/2019 Fire Fighting Note

    112/125

    u de s o

    Excavate trench to receive pipe - M

    Hose Reel System

    Swing hose reel - NO Water storage tank - NO

    Electrical duty pump - NO

    Diesel standby pump - NO

    Piping

    50 mm Diameter incoming pipe - M

    50 mm Diameter rising pipe M

    50 mm Diameter distribution pipe - M

    Brasswork

    50 mm Diameter air release valve NO

    50 mm Diameter gate valve NO

    50 mm Diameter check valve NO

    50 mm Diameter strainer valve NO

    50 mm Diameter flexible joint NO

    25 mm Diameter gate valve NO

    Cable

    2 x 1.5 mm2 cable

  • 8/2/2019 Fire Fighting Note

    113/125

    2.5 mm2 cable

    Fire Alarm System

    Control gear NO Junction box NO

    Manual break glass NO

    2 x 2.5 mm cable M

    50 mm Diameter conduit M

    Portable Fire Extinguisher 9 kg Fire extinguisher - NO

    Hydrant Hose Cabinet NO

    Lighting Installation

    Keluar sign - NO

    5A Emergency light NO Testing

    Allow for testing the foregoing fire fighting system - ITEM

  • 8/2/2019 Fire Fighting Note

    114/125

    Taking Off List

  • 8/2/2019 Fire Fighting Note

    115/125

    Taking Off List

    1. Pumps. - No

    2. Pipeworks. - M

    3. Tee - No

    4. Bend. - No

    5. Valves and ancillaries. - No

    6. Hydrant box. - No

    7. Pillar. - No

    8. Fire Extinguisher. - No

    9. Electrical Works. - No

    10. Testing. - Item

  • 8/2/2019 Fire Fighting Note

    116/125

    1. Pumps - No

    Equipment - Pumps

    Electric Fire pump, end suction centrifugal

    type with capacity of 750 GPM, 7 bar, 81 Kw/

    108.7 Bhp. No 1

    1 (PU 202)

  • 8/2/2019 Fire Fighting Note

    117/125

    150mm dia. Black steel pipe, ERW. Sch 40,

    embedded in in situ concrete m 130.00

    130.00 (Pump Room) Length

    75,000

    55,000

    130,000

    2.Pipeworks

  • 8/2/2019 Fire Fighting Note

    118/125

    3. Fitting and Accessories

    EXTRA OVER 150x150x65mm Black steel tee. No 5

    5 L.Basement

    EXTRA OVER Bend 90, to 150mm dia Black No 1

    steel pipe

    1 L.Basement

    Tees

    Bend

  • 8/2/2019 Fire Fighting Note

    119/125

    Hydrant

    Indoor hydrant box size 800x1300x300mm,

    complete with house rack, hydrant valve andfire

    house type 40x25m. No 12

    3 L.Basement

    3

    3 L. Dasar

    3

    3 L. 1

    3

    3 L. 2

    3

    12

    4.Hydrant

    5 Fi e E ting i he

  • 8/2/2019 Fire Fighting Note

    120/125

    Fire extinguisher capacity 3 Kg complete with

    box, and all necessary supporting fixing

    accessories as specified. No. 52

    4 13 L.B - L.2

    52

    5. Fire Extinguisher

  • 8/2/2019 Fire Fighting Note

    121/125

    Allow for checking, testing, acceptance testing

    and commisioning the Fire Protection Installation. Item

    Allow for service and maintenance of the complete

    installations during 12 months Defects Liability

    Period, excluding any maintenance resulting from

    defective workmanship or materials requiring repair

    and/or replacement by contractor. Item

    6. Testing

    7. Maintenance

    Item Description Unit Rate Qtty RM

    Element Fire Fighting Installation

    Builder's Work

    A

    17Excavate trench to receive 150mm diameter

  • 8/2/2019 Fire Fighting Note

    122/125

    m 17

    B m 7

    Hose Reel System

    A no 1

    B no 1

    C no 1

    D no 1

    E no 1

    To collection

    Diesel standy pump with the capacity of 30

    igm againts 170 ft static head complete withwiring, pump plinth and other accessories.

    One (1) nos of 2400 gallons of hose reel

    water tank, 6mm thick press steel panel

    complete with ball valve, fittings, level

    indicator, float control, piping, external red

    paint, internal asnd external ladder and other

    accessories.

    ca ate t e c to ece e 50 d a ete

    incoming pipe, maximum depth not

    exceeding 1.0m including filling in,

    compaction and disposal of surplus soil as

    required.

    Swing type hose reel drum with corrugated

    hose 30.5x25mm diameter complete with

    valve, bracket, 12.5mm diameter nozzle and

    other accessories as described.

    Excavate trench to receive 50mm diameter

    Galvanised Iron class 'B' incoming pipe,

    maximum depth not exceeding 1.0m

    including filling in, compaction and disposal

    of surplus soil as described.

    Electrical duty pump with the capacity of 30

    igm againts 170 ft static head complete with

    wiring, pump plinth and other accessories

    Hose reel cabinet type SRI model HRS 045

    or equivalent for all hose reel drum

    Item Description Unit Rate Qtty Rm

    Galvanised Iron Class 'B' Tubing Screw

    S k t d T th I l di All N

  • 8/2/2019 Fire Fighting Note

    123/125

    A m 17

    B m 5

    C m 2

    A no 1

    B no 2

    C no 5

    To collection

    Socketed Together Including All Necessary

    Short Length, Sockets, Connectors,

    Backnuts, Elbows And The Likes As

    Described

    150mm Diameter incoming pipe laid in trench

    (m/s)

    50mm Diameter incoming pipe embedded

    into ground floor slab

    50mm Diameter incoming pipe fixed to

    brickwall

    65mm Diameter gate valve and jointing to

    galvanised iron pipe

    50mm Diameter check valve and jointing togalvanised iron pipe

    50mm Diameter air release valve and jointing

    to galvanised iron pipe

    Brasswork To Comply To BS 1010 As

    Described

    Item Description Unit Rate Qtty Rm

    Fire Alarm System Installation

    A no 1Main fire alarm console panel (6 zones)

  • 8/2/2019 Fire Fighting Note

    124/125

    A no 1

    B no 1

    C no 1

    D no 1

    Testing

    A Item

    To collection

    150mm Diameter fire alarm bell with 24v

    (d.c) suplly mounted at wall as described

    Allow for testing the foregoing fire fightingsystem, make good any defect and leave the

    whole installation in perfect working order to

    the satisfaction of the superitandant officer.

    Main fire alarm console panel (6 zones)

    complete with LED mimic diagram, battery

    compartment complete with 8 AHx24V and

    charger as manufacturer's detail.

    400x400x150mm fixed to wall junction box

    approved type and quality, complete with

    3mm thick galvanised steel covers, gasket

    and all other necessary accessories.

    Manual break glass fire alarm size

    84mmx115mm with 24v(d.c) supply mounted

    at wall as described