7/22/2019 Fire and Gas Detection Specification
1/4
PTMARKINAHSPBG CNG untuk Angkutan
Umum di Palembang
Basic Design and General
Specification
B.6102.FireandGasDetectionSpecification
0 18102011 Issued for review
Rev. Date Description By Checked Appr.
-
7/22/2019 Fire and Gas Detection Specification
2/4
PTMARKINAHDOCUMENTCODE:
MANUAL
REV:
0
TITLE:
FireandGasDetectionSpecification
PAGE:
2OF4
GROUP:
ENGINEERING
DISCIPLINE:
INSTRUMENT&CONTROL
PROJECT::
DEDCPROYEKPEMBANGUNANSPBGCNG
ANGKUTANUMUMDIPALEMBANGDATE:
10
Oktober
2011
DOC.NUMBER:
CNG
OOO
IC
D02
1. Code,StandardsandSpecificationsThe fireandgassystem shallbedesigned
andfabricated
in
accordance
with
this
specification and the applicable provision
ofthe latesteditionofbelow listedcodes,
standards,andspecifications.
APIRP500 RecommendedPractice
forClassificationof
LocationsforElectrical
InstallationsatPetroleum
Facilities.
ISA12.13.01 Performance
requirementsfor
Combustiblegas
Detector
FM Factorymutual,Various
2. FireandGasDetectionThe fire and gas system shall include:
smoke,
heat,
flame
and
gas
detectors;
2.1SmokeDetectorsSmoke detectors commonly installed
insidebuildingareas,incertainindoors
areas. In areas where ionization and
thermaldetectorsarenotappropriate,
photoelectric smoke detectors or
flame sensors may utilize ionization
smokedetectorscommonlybeusedin
nohydrocarbonsarea.
Smoke sensing detectors shall be
located in enclosed areas where an
ordinary combustible or an electrical
typefiremayoccur.
1. Kode,StandardanSpesifikasiFire andGas System harus dirancang dan
dibuatsesuai
dengan
spesifikasi
dan
ketentuan yang berlaku dari kode edisi
terbaru, di bawah inidaftar, standar,dan
spesifikasi.
APIRP500 RecommendedPractice
forClassificationof
LocationsforElectrical
InstallationsatPetroleum
Facilities.
ISA12.13.01 Performance
requirementsfor
Combustiblegas
Detector
FM Factorymutual,Various
2. FireandGasDetectionFire and gas system meliputi: detector
asap,
panas,
api
dan
detektor
gas;
2.1DetektorasapDetektor asap biasanya dipasang di
dalamareabangunan,didalam daerah
ruangan tertentu. Di daerah dimana
detektor ionisasi dan termal yang
sesuai, detektor asap atau sensor
fotoelektrik api dapat memanfaatkan
ionisasidetektorasapbiasadigunakan
didaerahtidakadahidrokarbon.
Sensordetector asap harus berada di
area tertutup dimana daerah yang
mudah terbakar atau api listrik
mungkinterjadi.
-
7/22/2019 Fire and Gas Detection Specification
3/4
PTMARKINAHDOCUMENTCODE:
MANUAL
REV:
0
TITLE:
FireandGasDetectionSpecification
PAGE:
3OF4
GROUP:
ENGINEERING
DISCIPLINE:
INSTRUMENT&CONTROL
PROJECT::
DEDCPROYEKPEMBANGUNANSPBGCNG
ANGKUTANUMUMDIPALEMBANGDATE:
10
Oktober
2011
DOC.NUMBER:
CNG
OOO
IC
D02
Control rooms and electrical
equipment room shall have a
minimumoftwodetectorarrangedto
provideco
incident
detection,
or
crosszone.
2.2GasDetectorsGasdetectors shallbeof the infrared
type.
Visual and audible alarms shall be
provided for two levels of detection.
Theminimumlevelshallbe20percent
ofLEL,themaximumlevelshallbe60
percent of LEL. Alarm levels shall be
adjustable.
2.3HeatdetectorCombination rateofrise/fixed
temperature heat detectors shall be
usedinopenandconfinedareas.
Sensors shallbe locateddirectlyover,
andincloseproximityto,theprobable
heatssource(S)
ventilation
and
air
movement shall be considered when
locatingthesensors.
Detector may be addressable and
producesand increasesignal incircuit
when it detects heat. Otherwise,
system shallbecapable to indicateat
least for internal circuit conditions,
that is: shortcircuit fault, falsealarm,
andopencircuitfault.
Ruang kontrol dan ruang peralatan
listrik memiliki minimal dua detektor
diatur untuk memberikan coinsiden
deteksi,atau
lintas
zona.
2.2GasDetectors.
Detektorgasdarijenisinframerah.
Visualdanaudiblealarmterdapatdua
tingkat deteksi. Tingkatminimum 20
persendariLEL,tingkatmaksimum 60
persen dari LEL. Tingkat alarmbisadi
adjust/disesuaikan.
2.3DetektorsuhuKombinasi detektor suhu rateof
rise/fixed panas harus digunakan di
areaterbukadanterbatas.
Sensorharusditempatkan langsungdi
atas, dan se dekat mungkin dengan
sumberyang
dapt
memanas,
ventilasi
dan pergerakan udara harus
dipertimbangkanketikamenempatkan
sensor
Detektordapatdialamatkandandapat
meningkatakan sinyal pada rangkian
ketikamendeteksi sebuah panas. Jika
tidak, sistem harus mampu untuk
menunjukkansetidaknyauntukkondisi
sirkuit internal, yaitu: kesalahan short
sirkuit, alarm palsu, dan kesalahan
opensirkuit.
-