Final Control Elements - Arun K....
Transcript of Final Control Elements - Arun K....
1
Final Control Elements
Introduction:• Final control element receives the signal from
the controller and implements the manipulation required to control the process.
• In industry, the final control element takes many forms. It can be a heating coil in the case of temperature control of a furnace etc.
• In chemical engineering applications, the manipulation is usually flow (liquids, gases or vapors) through control valves.
3
Principle of I / P (Current to Pressure) Converter
Signal to thecontrol valve
Signal fromthe controller
4
What are the Components of a Control Valve?
Top portion is called as actuator
Bottom portionis valve body
Diaphragm
Calibrated spring
Stem
5
Types of Control Valves based on Valve Action
• The valve is direct acting because the air pressure signal is directly applied on the top of the diaphragm.• The valve is air - to- close type because when the air pressure signal increases from 3 to 15 psi (20 to100kPa) the valve closes.
6
Direct acting Air-to-Open Type Valve
• The valve is direct acting because the air pressure signal is directly applied on the top of the diaphragm.• The valve is air - to- open type because when the air pressure signal increases from 3 to 15 psi (20 to100kPa) the valve opens.
7
Reverse acting Air-to-Close Type Valve
• The valve is reverse acting because the air pressure signal is applied at the bottom of the diaphragm.• The valve is air - to- close type because when the air pressure signal increases from 3 to 15 psi (20 to100kPa) the valve closes.
8
Reverse acting Air-to-Open Type Valve• The valve is reverse acting because the air pressure signal is applied at the bottom of the diaphragm.• The valve is air - to- open type because when the air pressure signal increases from 3 to 15 psi (20 to100kPa) the valve opens.
10
Quick Opening Control Valve
• This valve provides a large change in flow rate for a small change in valve position.
• This valve is used for ON / OFF applications (also called as two position control system).
• The valve moves quickly from open to close position or vice versa and hence makes the corrective action immediately.
11
The Linear Control Valve
• The linear characteristic can be described by
S Smax
Q
Qmax
0 0
• The valve is used where the flow has to be linear with the controller signal
Flow
rate
Stem position
12
Hysteresis in Linear Control Valves is eliminated by Valve Positioner
• The valve provides two different flow rates while the stem position is increasing and decreasing
• Hysteresis is caused by the friction in the stem movement
Valvepositioner
14
Correct Estimation of ‘R’ from Plant Data
Semilog Plot:
Log
(Q/Q
max
)
(S-Smax) / Smax
Slope is Log R
15
Control Valve Sizing
• Control valve sizing means determining the correct size of the control valve for specific installation.
• First we find the Valve Coefficient CV.• CV is defined as the number of US gallons of
water per minute that will flow through a fully open valve with a pressure drop of 1 psi.
• For example, a control valve with CV of 5 will pass 5 gal / min of water when the valve is fully open and the pressure drop is 1 psi.
16
To find the Valve Size:
QLP1 P2
QL= Maximum liquid flow rate in m3 / min.
P1 = Valve inlet pressure, kPa
P2 = Valve outlet pressure, kPa
17
Step1: Find CV from the Formula
CV = Valve coefficientSG = Specific gravity of the liquid flowing (density
of liquid divided by the density of water)K = 1.4 * 10-3ΔP = P1-P2 = Pressure drop across the valve
Note: Different formulae are given in the literature for gases, vapors and steam
18
Step 2: Use the following Table to find the Valve Size in mm
CV Valve Size
CV Valve Size
0.3 7 108 76
3 13 174 102
14 25 400 152
35 38 725 203
55 50 1100 254
19
Dynamic Characteristics of Control Valves (Speed of Response)
3 psi
15 psi
Time, secFl
ow
ΔX
ΔY
ΔX=Step change in input air pressure signal
ΔY=Transient response in the flow
Time, sec
X
Y
20
Control Valves usually show First-order Response
X Y
X = Input air pressure signal, kPaY = Response in the flow, m3 / secGV = Transfer function of the control valveKV = Gain of the control Valve,
( m3 / sec) / kPaτ = Time constant of the control valve,
sec