FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE HOUSE #4 INVERNESS GARDENS MILLER HOMES DECEMBER 2011 Submitted to: NYSERDA 17 Columbia Circle Albany, NY 12203 Submitted by: HOMEPIC Team CDH Energy Corp. PO Box 641 Cazenovia, NY 13035 315-655.1063 and Syracuse Center of Excellence in Energy and Environmental Systems Northeast Green Building Consulting Camroden Associates Building Performance Contractors Association of New York

Transcript of FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report...

Page 1: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

FINAL CONSTRUCTION REPORT

NYSERDA

RESIDENTIAL PERFORMANCE CHALLENGE

HOUSE #4

INVERNESS GARDENS – MILLER HOMES

DECEMBER 2011

Submitted to:

NYSERDA

17 Columbia Circle

Albany, NY 12203

Submitted by:

HOMEPIC Team

CDH Energy Corp.

PO Box 641

Cazenovia, NY 13035

315-655.1063

and

Syracuse Center of Excellence in Energy and Environmental Systems

Northeast Green Building Consulting

Camroden Associates

Building Performance Contractors Association of New York

Page 2: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

HomePIC Team 2 December 2011

Figure 1. Two-Unit Model at Inverness Gardens (Astilbe Path)

This 2-unit model townhome was built by Miller Homes in September 2011. The house was part

of the 2011 Syracuse Parade of Homes. This model has 2-story units with a loft option. The left

side is the finished model unit while the right side was left unfinished to highlight the

construction and insulation details. The unfinished side was also open during Parade of Homes

to educate the public about the energy efficiency improvements available in these units. As part

of the re-design process we worked with the builder’s architect to revise the plans for the 2-story

unit with loft (1984 sq ft) that was built at this site. In addition, the efficiency improvements

were also included into the plans for the 1-story (1582 sq ft) unit and the 2-story without loft

(1841 sq ft).

The major energy efficiency improvements incorporated into these homes included the Superior

Walls precast foundation system with 2.5” of insulation in the basement as well as the exterior

walls with 2” of exterior foam and 2x6” with 24” OC framing. The wall cavities were filled with

BIBS blown fiberglass. The cathedral ceiling used blown fiberglass, closed cell spray foam, and

2” exterior rigid foam under the roof deck. Blown fiberglass was used in the attic.

The key construction details are summarized in the following section. Table 2 compares the

originally proposed improvements to the actual implemented features. Table 3 summarizes the

costs of the implemented improvements. During construction we worked with the contractor and

recommended additional measures that could be implemented to better adjust to constructability.

In many respects the final design was better than we originally proposed.

Page 3: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

HomePIC Team 3 December 2011

Table 1. Energy Performance Ratings for each Window Type

Window Type U-Factor SHGC Visible Transmittance

Double Hung 0.22 0.23 0.37

Slider 0.30 0.20 0.38

Basement 0.28 0.35 0.52

Cathedral Ceiling with 2” Rigid Foam, Spray Foam, and BIBS

Baffles Spray Foamed In Place for Ventilation in Attic

Figure 2. Photos Showing Exterior and Ceiling Insulation Details

The cathedral ceiling with 2x12” with 24” OC framing has 2” exterior rigid foam beneath the

roof deck. In addition, 3” of closed cell spray foam and BIBS blown fiberglass were installed

from below as shown in Figure 2. The design called for the end walls at the gable ends to be

offset by 2” so the exterior foam was not required on the walls for the attic and garage. The

approach eliminated the expense of unnecessary foam board and still allowed the garage and

attic exterior sheathing to be flush with the exterior foam.

EXTERIOR FOAM

CLOSED CELL SPRAY FOAM

BIBS

EXTERIOR FOAM INSTALLED FLUSH WITH OSB IN UNINSULATED

GARAGE AND ATTIC

2” FOAM WITH TAPED SEAMS

Page 4: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

HomePIC Team 4 December 2011

Figure 3. Photos Showing Basement Construction, Insulation, and Sealing Details.

A Superior Wall® pre-cast, insulated, and modular foundation system was chosen over the CMU

foundation (Figure 3) in order meet the tight time-schedule for the Parade of Homes. 2” rigid

foam was installed under the entire basement floor.

XI® SUPERIOR WALL 2” RIGID FOAM

BENEATH BASEMENT FLOOR

SPRAY FOAM ON RIM JOISTS

Page 5: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

HomePIC Team 5 December 2011

Figure 4. Photos Showing Truss Design and Insulation Choices for Second Floor Walls Adjoining Attic Space.

The top two photos in Figure 4 show that the roof trusses were designed to leave space to install

2” rigid foam on the second floor to attic walls. Then the rigid foam was sealed with closed cell

foam shown in the bottom two photos. This completely sealed the second floor from the

unconditioned attic space.

2” FOAM INSTALLED

CLOSED CELL SPRAY FOAM

SPACE LEFT FOR 2” FOAM

INSTALLATION

Page 6: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

HomePIC Team 6 December 2011

Figure 5 shows the details of the tray ceiling in the master bedroom. Closed cell foam seals and

insulates the unconditioned side of the tray ceiling and all of the second floor rim joists to

maintain the conditioned envelope.

Figure 5. Photos Showing Tray Ceiling and 2nd Floor Rim Joist Insulation

The photo in Figure 6 shows a common occurrence in stick framed, residential construction

inaccessible corners are created by the end studs on every corner wall. In this case a jack and

king stud on the left meets a stud on right to form a void that is difficult to insulate. The 2” of

exterior foam and sealing techniques used in the construction of this home reduced the impact of

these empty corners. However, the plans had called for a different stud corner arrangement, as

shown by the drawing on the right side of the Figure that was intended to eliminate this issue.

SIDES OF TRAY CEILING IN MASTER BEDROOM

SECOND FLOOR RIM JOISTS INSULATED ON

BOTH SIDES

Page 7: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

HomePIC Team 7 December 2011

Figure 6. Photo Showing Empty Space Created by Studs in Corners

Mechanical Systems

The mechanical system is a Combi unit that uses a tankless water heater to provide both water

heating and space heating. Potable (domestic) hot water is piped to a hot water coil in the air

handler that also provides cooling to the house. In addition, the system also included a solar

water heating system with a 120 gallon tank. The 94% efficient Rheem RTGH-95DVN

condensing, direct vent, tankless unit is shown in Figure 7. The 2.5 ton Rheem air handler has a

cooling coil installed in the cabinet and a heating coil installed immediately downstream. The

system is shown schematically in Figure 8.

Figure 7. Photos Showing DHW and Space Heating Equipment

HEATING COIL

AIR HANDLER

WHOLE HOUSE VENTILATION CONTROLLER

EMPTY CORNER STUD

CAVITY

STUD ARRANGEMENT CALLED FOR IN PLANS

Page 8: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

HomePIC Team 8 December 2011

Figure 8. Schematic of DHW and Space Heating System (Monitoring Pts Shown as Red)

Ventilation is provided by a fresh air intake on the return side of the air handler. A damper is

installed on the intake duct which is controlled by the Honeywell controller. The controller

operates the AHU fan and damper fan to supply the desired amount of ventilation. The

controller was set to operate the fan and damper for 36 minutes out of every hour (60% of the

time) to provide ventilation to the home. When the AHU operated with damper open, the

measured ventilation flow was 86 cfm; therefore, the average ventilation across each hour was

52 cfm. The controller also closes the damper when heating and cooling operation are required

for more than 36 minutes of each hour to limit over ventilation. Figure 9 shows where damper

control is located in the fresh air intake duct in the basement. The bottom-left photo in Figure 9

also shows the electric ionizing air cleaner that was installed in the air handler return duct.

In this house the builder also provided ventilation in the garage. The continuous duty exhaust

fan operates at low speed but jumps to high speed when the garage door opens. This system was

intended to provide the ventilation of vehicle exhaust and maintains the garage under negative

pressure. In the winter of 2011, the negative pressure (-10 Pa) caused some moisture from under

the slab to condense on the lower portions of the garage wall and discolor the paint. The garage-

slab-to-foundation interface was sealed to eliminate this problem.

TSHS

Electric Air

Cleaner/Ionizer

Heating Coil Tankless Heater

Solar Tank

Outdoor Air

Supply Air

TSHW

TWH

TWC

SRP

TWS

SDHW

TSHR

TSHM Return/ Space

Air

SV

Ventilation Damper

Space Heating Loop

Space Heating Pump

Mixing

Valve Mixing Valve

AHU Fan

WAHU

Page 9: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

HomePIC Team 9 December 2011

Figure 9. Photos Showing Ventilation and Air-Cleaning System

An indirect, flat plate collector solar hot water system was installed with a 120 gallon storage

tank to boost the inlet water temperatures to the DHW system. As shown by Figure 8, the solar

tank can only provide heating when there is a water draw (and not in the space heating mode).

VENT DUCT THOUGH SILL

VENTILATION DAMPER

ELECTRIC IONIZING AIR CLEANER IN RETURN DUCT

EXHAUST FAN IN GARAGE

Page 10: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

HomePIC Team 10 December 2011

Figure 10. Storage Tanks for Solar Thermal System Installed in Basement

Design Summary

Table 2 compares the baseline design to the proposed design and finally to the actual, as-built

details. Table 3 summarizes the incremental costs of the implemented improvements compared

to the baseline design.

120 GALLON SOLAR HOT WATER

STORAGE TANK

Page 11: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

HomePIC Team 11 December 2011

Table 2. Summary of Baseline, Proposed and Actual Design Details

Base Design Proposed Design As Built Details

Walls

Vinyl Siding, 1-1/2”

exterior foam, 2x6”

framing w/ Fiberglass

batts R29

Vinyl Siding, 2”Exterior

Foam, 2x6” framing w/ dense

packed cellulose R30

Vinyl Siding, 2” Exterior Foam,

2x6” framing, BIBS blown in

fiberglass R33

2nd

Floor

Knee Walls 2x4” framing w/

fiberglass batts R13

2” Exterior Foam, 2x6”

framing w/ dense packed

cellulose R30

2” Exterior Foam and Closed Cell

foam 2nd

floor to attic walls

Garage

(Exterior) Vinyl Siding, 2x6”

framing

Vinyl Siding, 2x6” framing Vinyl Siding, 2x6” framing

Attic 2x12 rafters frame with

Fiberglass batts R38

2x12 rafters frame with 16”

cellulose R49

2x12 rafters frame with blown

cellulose R60

Cathedral

Ceiling R38 Fiberglass Batts Blown Fiberglass with 2”

Exterior Foam above roof

deck R58

BIBS, Closed Cell foam, and

Exterior Foam beneath roof deck

R67

Basement

Walls 10” CMU w/ 5’ Hanging

Blown in Fiberglass R10

10” CMU, 2.5” white

Thermax R15

Superior Walls Xi Foundation

System with 2.5” Dow® Extruded

Polystyrene Insulation R15

Basement

Floor Uninsulated poured

concrete floor

2” Rigid Foam under poured

concrete floor R10

2” Rigid Foam under poured

concrete floor R10

Windows U=0.33 Low E Argon

double hung

Super Seal Windows U = 0.20 DH: Triple glazed, Low E, U = 0.22,

SHGC = 0.23

Slider: Double glazed, Low E Argon

filled, U = 0.30, SHGC = 0.20

Basement: Double glazed, Low E

Argon/air filled, U=0.28, SHGC=0.35

Rim/Band

Joists 6” Fiberglass batts w/ 1-

1/2” Ext Foam R 29

3” Closed Cell foam in Band

joists w/ 2” ext Foam R32

3” Closed Cell foam in Band joists

w/ 2” ext Foam R32

Garage-to-

house Wall 2x6 framing w/ Fiberglass

batts R19

2”Exterior Foam, 2x6”

framing w/ dense packed

cellulose R33

2” Exterior Foam, 2x6” framing,

BIBS system blown in fiberglass.

Air Tightness

& Thermal

Bypass

5 ACH50 (with basement)

2 ACH50 (with basement)

Various air sealing and

thermal bypass improvements

1.79 ACH50 with basement

(actual)

Heating/

Cooling 90% Natural Gas Furnace

13 SEER AC Unit

94% Natural Gas Furnace

13 SEER AC Unit

95% Rheem tankless water heater

and heating coil Combi System

13 SEER 2.5 ton AC unit

Ventilation Exhaust Only Ventilation HRV Fantech SH704 run 24

hours, 36 watts, 55 cfm

Fresh Air Ventilation with damper.

Honeywell Whole House

Ventilation Control.

Exhaust fan in garage

Page 12: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

HomePIC Team 12 December 2011

Table 3. Summary of Incremental Cost Differences

Units Quanity Unit Cost Total Cost Notes

Exterior Walls

2" Dow Styrofoam Wallboard ft2 2272 1.22$ 2,780.00$ 71 Sheets (4x8)

Sill Flashing ft 133 1.10$ 146.67$ $80 in material

BIBS ft21138 1.00$ 1,138.39$

Deduct for Tyvek ft21138 0.36$ (409.82)$

Deduct for FG Batts ft21138 0.65$ (739.95)$

2,915.28$

Basement Walls and Floor

Superior Walls with 2.5" Continuous Foam ft2 1427 8.80$ 12,554.50$ Actual Cost From Invoice

Deduct for CMU Foundation ft2 1427 7.50$ (10,702.00)$ From Invoice Estimate

2" Foam Under Slab ft2 1697 1.14$ 1,931.23$

Deduct for 5' Hanging FG batt ft2 1011 0.50$ (505.34)$

3,278.40$

Rim/Band Joists, Framed Floors, Shed roofs

Closed Cell Rim/Band Joist & Shed/Floor ft2 204 3.50$ 713.62$

Other Misc Spray Foam ft2 200 3.50$ 700.00$

Deduct for FG Rim/Band/Dam Joist ft2 204 0.65$ (132.53)$

1,281.09$

Ceiling

R60 Cellulose in Attic Floor ft2 1376 1.80$ 2,476.80$

BIBS in Cathedral Ceiling ft2 460 1.00$ 460.00$

2" Exterior Foam in Cathedral Ceiling ft2 460 1.22$ 562.85$

Closed Cell Spray Foam ft2 460 3.50$ 1,610.00$

Deduct for R38 FG in Ceiling ft2 1836 1.15$ (2,111.40)$

2,998.25$

Windows

Energy Star, Triple Glazed, Low E 1 8,601.00$ 8,601.00$ From Invoice Estimate

Deduct for Estar Double Glazed 1 5,923.00$ (5,923.00)$ From Invoice Estimate

2,678.00$

Heating and Ventilation

Hybrid System w/ 95% Condensing Tankless Unit 1 13,529$ 13,529.00$ From Invoice Estimate

Deduct for 90% Efficient Gas Furnace 1 5,300$ (5,300.00)$ From Invoice Estimate

Deduct for 0.63 EF Water Heater 1 1,200$ (1,200.00)$

Garage Ventilation 1 464$ 464.00$ Actual Cost From Invoice

7,493.00$

NET Total 20,644.02$

Inverness Gardens 2 Story with Loft Costs

Page 13: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

HomePIC Team 13 December 2011

Energy Performance

The energy use and savings predicted by REM/Rate for this house is shown in Table 4. The

heating load for the house with the proposed improvements is 37% of the baseline design and the

final, as-built design is 50% that of the baseline design.

Table 4. Summary of Energy Use and Savings

Space

Heating

(MMBtu/yr)

Peak Space

Heating

(MMBtu/h)

Fuel for Space

Heating

(MMBtu/yr)

Fuel for Water

Heating

(MMBtu/yr)

Relative

Fuel

Annual

Cost

Cost

Savings

Baseline 66.1 38.3 75.1 18.8 100% 1,409$ -$

Proposed Improvements 31.3 21.8 34.2 0.6 37% 522$ 887$

As-built Improvements 43.8 27.8 46.6 0.4 50% 705$ 704$

Inverness Gardens 2 Floor With Loft Design

The house was rated according to the Energy Star requirements. The HERS Index for the house

was 52 and the NY HERS Score was 89.6. Savings are primarily due to air tightness and added

insulation.

Thermal images, using a Fluke TiR3FT, were taken of the duplex on December 2, 2011, in the

morning before sunrise. The stud bays built into the Superior Wall panels are clearly visible

through the variation of heat transfer. Slightly more heat loss is evident at the inside corner of

the foundation wall (surface 14-15°F warmer).

Figure 11. Thermal Images Showing Foundation Wall and Slider Doors Near Deck

DOWNSPOUT

DECK JOIST

FOUNDATION INSIDE CORNER

Page 14: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

HomePIC Team 14 December 2011

Figure 12. Thermal Image of End of Unit

The foam-to-sheathing (or OSB) transition is slightly visible from the infrared image shown

above. In Figure 13 it is apparent the model unit on the left side heated while the unfinished

unit on right side is unheated.

Figure 13. Thermal Image of Building from Front (Only Left-Side Unit is Heated)

FOAM-TO-OSB TRANSITION

Page 15: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

HomePIC Team 15 December 2011

Figure 14. Thermal Image of Unheated Side (Foundation is slightly warmer)

Figure 15. Thermal Image of Building showing Front Door Area

Page 16: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

HomePIC Team 16 December 2011

Figure 16. Thermal Image of Front Windows

Figure 17. Thermal Image of Both Front Door Areas

Page 17: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

HomePIC Team 17 December 2011

Figure 18. Thermal Image of Superior Wall at Rear of Building (at center of building)

Figure 19. Thermal Image of Superior Wall (AC Unit Shown)

Page 18: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

AIR LEAKAGE REPORT

Date: November 30, 2011 Rating No.: 0061-0206c.blg

Building Name: Duplex Model Home Rating Org.: James E. Hammel, Inc.

Owner's Name: M&A Homes, Inc. Phone No.: 315 638 1757

Property: 4964 Astilbe Path Rater's Name: James E. Hammel

Address: Liverpool, NY 13088 Rater's No.: R 0061

Builder's Name: Troy Adams

Weather Site: Syracuse, NY Rating Type: Confirmed Rating

File Name: 4964 Astilbe Path Liverpool M&A Homes Model H Rating Date: 11/11/11

REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.

© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Whole House InfiltrationBlower door test

Heating CoolingNatural ACH: 0.13 0.11ACH @ 50 Pascals: 1.79 1.79CFM @ 25 Pascals: 714 714CFM @ 50 Pascals: 1120 1120Eff. Leakage Area: [sq.in] 61.5 61.5Specific Leakage Area: 0.00018 0.00018ELA/100 sf shell: [sq.in] 0.90 0.90

Duct Leakage Leakage to Outside Units Supply/ReturnCFM @ 25 Pascals: 25CFM25 / CFMfan: 0.0115CFM25 / CFA: 0.0104CFM per Std 152: N/ACFM per Std 152 / CFA: N/ACFM @ 50 Pascals: 39Eff. Leakage Area: [sq.in] 2.15Thermal Efficiency: N/ATotal Duct Leakage Units CFM25Total Duct Leakage: 50.00

Ventilation Mechanical: Balanced Sensible Recovery Eff. (%): 0.0 Total Recovery Eff. (%): 0.0 Rate (cfm): 115 Hours/Day: 11.0 Fan Watts: 25.0Cooling Ventilation: Natural Ventilation

ASHRAE 62.2 - 2010 Ventilation Requirements

For this home to comply with ASHRAE Standard 62.2 - 2010 Ventilation and Acceptable Indoor Air Quality in Low-RiseResidential Buildings, a minimum of 54 cfm of mechanical ventilation must be provided continuously, 24 hours per day. Alternatively, an intermittently operating mechanical ventilation system may be used if the ventilation rate is adjustedaccordingly. For example, a 108 cfm mechanical ventilation system would need to operate 12 hours per day, as long as thesystem operates to provide required average ventilation once each hour.

Page 19: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

BUILDING FILE REPORT

File Name: 4964 Astilbe Path Liverpool M&A Homes Model Date: November 30, 2011

REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Property/Builder: Rating Building Name: Duplex Model Home Org. Name: James E. Hammel, Inc.

Owner's Name: M&A Homes, Inc. Address: 21 North Street

Property Address: 4964 Astilbe Path City, St, Zip: Baldwinsville, NY 13027

City, St, Zip: Liverpool, NY 13088 Phone No: 315 638 1757

Phone No: Website:

Builder's Name: Troy Adams Rater's Name: James E. Hammel

Phone No: 315 480 9878 Rater's Email: [email protected]

Email Address: pipefish@yahoo Rater's ID: R 0061

Model: Two Story Townhouse

Development: Invernness Gardens Rating Date: 11/11/11

Rating Type: Confirmed Rating

Reason: New Home

Rating No.: 0061-0206c.blg

Registry ID:

General Building Information Area of Cond. Space(sq ft): 2415

Volume of Cond. Space: 37475

Year Built: 2011

Housing Type: Duplex, single unit

Level Type(Apartments Only): None

Floors on or Above-Grade: 2

Number of Bedrooms: 3

Foundation Type: Conditioned basement

Enclosed Crawl Space Type: N/A

Thermal Boundary Location: N/A

Foundation Wall Info: 1 2 3

Name To Garage To Ambient To Ambient

Library Type Superior Wall # 2 Superior Wall # 2 Superior Wall # 2

Length(ft) 20.0 41.5 23.2

Total Height(ft) 9.0 9.0 9.0

Depth Below Grade(ft) 7.0 4.0 7.0

Height Above Grade(ft) 2.0 5.0 2.0

Location Cond->garage/grnd Cond->ambient/grnd Cond->ambient/grnd

Uo Value (wall, airfilm, & soil) 0.070 0.081 0.070

Uo Value (wall assembly only) 0.148 0.148 0.148

Page 20: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

BUILDING FILE REPORT

Duplex Model Home Page 2

REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Foundation Wall Info: 4 5

Name To Ambient To common

Library Type Superior Wall # 2 Superior Wall # 2

Length(ft) 42.0 52.0

Total Height(ft) 9.0 9.0

Depth Below Grade(ft) 6.0 6.0

Height Above Grade(ft) 3.0 3.0

Location Cond->ambient/grnd Cond -> another cond unit

Uo Value (wall, airfilm, & soil) 0.074 0.074

Uo Value (wall assembly only) 0.148 0.148

Foundation Wall: Superior Wall # 2 Type: Solid concrete or stone

Thickness(in): 10.3

Studs: None

Interior Insulation:

Continuous R-Value: 12.5

Frame Cavity R-Value: 0.0

Cavity Insulation Grade: 1

Ins top: 0.3 ft from top of wall

Ins Bottom: 0.3 ft from bottom of wall

Exterior Insulation:

R-Value: 0.0

Ins top: 0.0 ft from top of wall

Ins bottom: 0.0 ft from bottom of wall

Note:

Slab Floor Info: 1

Name Insulated Cellar Fl

Library Type R10P

Area(sq ft) 1731

Depth Below Grade(ft) 6.0

Full Perimeter(ft) 179

Exposed Perimeter(ft) 128

On-Grade Perimeter(ft) 0

Page 21: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

BUILDING FILE REPORT

Duplex Model Home Page 3

REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Slab Floor: R10P Slab Covering Carpet

Perimeter Insulation (R-Value): 10.0

Perimeter Insulation Depth (ft): 0.3

Under-Slab Insulation (R-Value): 0.0

Under-Slab Insulation Width (ft): 0.0

Slab Insulation Grade: 1

Radiant Slab: No

Note:

Frame Floor Info: 1

Name Total

Library Type R34,LDF1,10-16

Area (sq ft) 23

Location Btwn cond & ambient

Uo Value 0.032

Page 22: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

BUILDING FILE REPORT

Duplex Model Home Page 4

REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Frame Floor: R34,LDF1,10-16Information From Quick Fill Screen:

Continous Insulation R-Value 0.0

Cavity Insulation R-Value 33.9

Cavity Insulation Thickness (in.) 9.2

Cavity Insulation Grade 1.0

Joist Size (w x h, in) 1.5 x 9.3

Joist Spacing (in oc) 16.0

Framing Factor - (default) 0.1300

Floor Covering HARDWOOD

Note:

Layers Paths

Cavity Framing GradeInside Air Film 0.920 0.920 0.920

Floor covering 0.680 0.680 0.680

Subfloor 0.820 0.820 0.820

Cavity ins 33.900 0.000 0.000

Continuous ins 0.000 0.000 0.000

Framing 0.000 11.500 0.000

0.000 0.000 0.000

Outside Air Film 0.920 0.920 0.920

Total R-Value 37.240 14.840 3.340

U-Value 0.027 0.067 0.299

Relative Area 0.870 0.130 0.000

UA 0.023 0.009 0.000

Total Component UA: 0.032

Total Component Area: 1.0

Component Uo: 0.032

Page 23: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

BUILDING FILE REPORT

Duplex Model Home Page 5

REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Rim and Band Joist: 1 2 3

Name To Garage 1 st floor Ambient Commen

Area(sq ft) 20.0 106.0 52.0

Continuous Ins 10.0 10.0 10.0

Framed Cavity Ins 24.0 24.0 24.0

Cavity Ins Thk(in) 4.0 4.0 4.0

Joist Spacing 24.0 16.0 16.0

Insulation Grade 1 1 1

Location Cond -> garage Cond -> ambient Cond -> another cond unit

Uo Value 0.031 0.032 0.032

Rim and Band Joist: 4

Name 2 nd floor Ambient

Area(sq ft) 28.0

Continuous Ins 10.0

Framed Cavity Ins 24.0

Cavity Ins Thk(in) 4.0

Joist Spacing 16.0

Insulation Grade 1

Location Cond -> ambient

Uo Value 0.032

Above-Grade Wall: 1 2 3

Name To Garage To Ambient 1st To Ambient 2nd

Library Type BIB FG1,6-24,+10Foam BIB FG1,6-24,+10Foam BIB FG1,6-24,+10Foam

Gross Area(sq ft) 180.00 960.30 290.00

Exterior Color Medium Medium Medium

Location Cond -> garage Cond -> ambient Cond -> ambient

Uo Value 0.034 0.034 0.034

Above-Grade Wall: 4 5

Name Knee Walls common

Library Type BIB.FGG,4-24,+2"Foam BIB.FGG,4-16

Gross Area(sq ft) 560.00 652.00

Exterior Color Medium Medium

Location Cond -> attic Cond -> another cond unit

Uo Value 0.042 0.079

Page 24: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

BUILDING FILE REPORT

Duplex Model Home Page 6

REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Above-Grade Wall: BIB FG1,6-24,+10FoamInformation From Quick Fill Screen:

Standard Wood Frame

Continuous Insulation (R-Value) 10.0

Frame Cavity Insulation (R-Value) 22.0

Frame Cavity Insulation Thickness (in) 5.5

Frame Cavity Insulation Grade 1

Stud Size (w x d, in) 1.5 x 5.5

Stud Spacing (in o.c.) 24.0

Framing Factor - (default) 0.1988

Gypsum Thickness (in) 0.5

Note:

Layers Paths

Cavity Framing GradeInside Air Film 0.680 0.680 0.680

Gyp board 0.450 0.450 0.450

Air Gap/Frm 0.000 0.000 0.000

Cavity ins/Frm 22.000 6.875 1.030

Continuous ins 10.000 10.000 10.000

Ext Finish 0.940 0.940 0.940

0.000 0.000 0.000

Outside Air Film 0.170 0.170 0.170

Total R-Value 34.240 19.115 13.270

U-Value 0.029 0.052 0.075

Relative Area 0.801 0.199 0.000

UA 0.023 0.010 0.000

Total Component UA: 0.034

Total Component Area: 1.0

Component Uo: 0.034

Page 25: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

BUILDING FILE REPORT

Duplex Model Home Page 7

REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Above-Grade Wall: BIB.FGG,4-24,+2"FoamInformation From Quick Fill Screen:

Standard Wood Frame

Continuous Insulation (R-Value) 10.0

Frame Cavity Insulation (R-Value) 14.0

Frame Cavity Insulation Thickness (in) 3.5

Frame Cavity Insulation Grade 1

Stud Size (w x d, in) 1.5 x 3.5

Stud Spacing (in o.c.) 24.0

Framing Factor - (default) 0.1988

Gypsum Thickness (in) 0.5

Note:

Layers Paths

Cavity Framing GradeInside Air Film 0.680 0.680 0.680

Gyp board 0.450 0.450 0.450

Air Gap/Frm 0.000 0.000 0.000

Cavity ins/Frm 14.000 4.375 1.030

Continuous ins 10.000 10.000 10.000

Ext Finish 0.940 0.940 0.940

0.000 0.000 0.000

Outside Air Film 0.170 0.170 0.170

Total R-Value 26.240 16.615 13.270

U-Value 0.038 0.060 0.075

Relative Area 0.801 0.199 0.000

UA 0.031 0.012 0.000

Total Component UA: 0.042

Total Component Area: 1.0

Component Uo: 0.042

Page 26: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

BUILDING FILE REPORT

Duplex Model Home Page 8

REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Above-Grade Wall: BIB.FGG,4-16Information From Quick Fill Screen:

Standard Wood Frame

Continuous Insulation (R-Value) 0.0

Frame Cavity Insulation (R-Value) 15.0

Frame Cavity Insulation Thickness (in) 3.5

Frame Cavity Insulation Grade 3

Stud Size (w x d, in) 1.5 x 3.5

Stud Spacing (in o.c.) 16.0

Framing Factor - (default) 0.2300

Gypsum Thickness (in) 0.5

Note:

Layers Paths

Cavity FramingInside Air Film 0.680 0.680

Gyp board 0.450 0.450

Cavity ins/Frm 15.000 4.375

Continuous ins 0.000 0.000

Ext Finish 0.940 0.940

0.000 0.000

0.000 0.000

Outside Air Film 0.170 0.170

Total R-Value 17.240 6.615

U-Value 0.058 0.151

Relative Area 0.770 0.230

UA 0.045 0.035

Total Component UA: 0.079

Total Component Area: 1.0

Component Uo: 0.079

Page 27: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

BUILDING FILE REPORT

Duplex Model Home Page 9

REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Window Information: 1 2 3

Name 1st Front 1st Rear 1st left

Library Type U:0.22, SHGC:0.25 U:0.22, SHGC:0.25 U:0.22, SHGC:0.25

U-Value 0.220 0.220 0.220

SHGC 0.250 0.250 0.250

Area(sq ft) 33.00 143.20 125.80

Orientation North South East

Overhang Depth 4.0 1.0 1.0

Overhang To Top 1.0 1.0 9.0

Overhang To Bottom 6.5 8.0 15.0

Interior Winter Shading 0.85 0.85 0.85

Interior Summer Shading 0.70 0.70 0.70

Adjacent Winter Shading Complete None Some

Adjacent Summer Shading Complete None Some

Wall Assignment AGWall 2 AGWall 2 AGWall 2

Window Information: 4 5

Name 2nd Front 2nd Left

Library Type U:0.22, SHGC:0.25 U:0.22, SHGC:0.25

U-Value 0.220 0.220

SHGC 0.250 0.250

Area(sq ft) 50.00 30.00

Orientation North East

Overhang Depth 1.0 1.0

Overhang To Top 1.0 4.0

Overhang To Bottom 6.0 9.0

Interior Winter Shading 0.85 0.85

Interior Summer Shading 0.70 0.70

Adjacent Winter Shading Complete Some

Adjacent Summer Shading Complete Some

Wall Assignment AGWall 3 AGWall 3

Window: U:0.22, SHGC:0.25 U-Value: 0.220

Solar Heat Gain Coefficient: 0.250

Note:

Door Information: 1 2

Name Front Garage

Opaque Area(sq ft) 15.0 21.0

Library Type Steel-polyurethane Steel-polyurethane

Wall Assignment AGWall 2 AGWall 1

Uo Value 0.283 0.283

Page 28: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

BUILDING FILE REPORT

Duplex Model Home Page 10

REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Door: Steel-polyurethane R-Value of Opaque Area: 2.6

Storm Door: No

Note:

Roof Information: 1 2

Name Flat ceiling Cathedral

Library Type R60,BFG20" R55, Hybred Adams******

Gross Area(sq ft) 1401.00 372.00

Color Medium Medium

Radiant Barrier No No

Type(Attic) Attic Attic

Uo Value 0.016 0.022

Clay or Cement Tiles: No No

Sub Roof Ventilation: No No

Page 29: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

BUILDING FILE REPORT

Duplex Model Home Page 11

REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Ceiling: R60,BFG20"Information From Quick Fill Screen:

Continous Insulation (R-Value) 48.0

Cavity Insulation (R-Value) 12.0

Cavity Insulation Thickness (in) 3.5

Cavity Insulation Grade 1

Gypsum Thickness (in) 0.500

Bottom Chord/Rafter Size(w x h, in) 1.5 x 3.5

Bottom Chord/Rafter Spacing (in o.c.) 24.0

Framing Factor - (default) 0.1100

Ceiling Type Attic

Note: quick-fill by MP 12/15/05

Layers Paths

Framing Cavity GradeInside Air Film 0.610 0.610 0.610

Gyp board 0.450 0.450 0.450

Cavity Ins/Frm 4.375 12.000 0.000

Continuous ins 48.000 48.000 48.000

0.000 0.000 0.000

0.000 0.000 0.000

0.000 0.000 0.000

Outside Air Film 0.610 0.610 0.610

Total R-Value 54.045 61.670 49.670

U-Value 0.019 0.016 0.020

Relative Area 0.110 0.890 0.000

UA 0.002 0.014 0.000

Total Component UA: 0.016

Total Component Area: 1.0

Component Uo: 0.016

Page 30: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

BUILDING FILE REPORT

Duplex Model Home Page 12

REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Ceiling: R55, Hybred Adams******Information From Quick Fill Screen:

Continous Insulation (R-Value) 10.0

Cavity Insulation (R-Value) 45.5

Cavity Insulation Thickness (in) 11.5

Cavity Insulation Grade 1

Gypsum Thickness (in) 0.500

Bottom Chord/Rafter Size(w x h, in) 1.5 x 7.3

Bottom Chord/Rafter Spacing (in o.c.) 16.0

Framing Factor - (default) 0.1412

Ceiling Type Attic

Note: quick-fill by MP 12/15/05

Layers Paths

Framing Cavity GradeInside Air Film 0.610 0.610 0.610

Gyp board 0.450 0.450 0.450

Cavity Ins/Frm 9.125 45.500 0.000

Continuous ins 10.000 10.000 10.000

0.000 0.000 0.000

0.000 0.000 0.000

0.000 0.000 0.000

Outside Air Film 0.610 0.610 0.610

Total R-Value 20.795 57.170 11.670

U-Value 0.048 0.017 0.086

Relative Area 0.141 0.859 0.000

UA 0.007 0.015 0.000

Total Component UA: 0.022

Total Component Area: 1.0

Component Uo: 0.022

Mechanical Equipment: General Number of Mechanical Systems: 2

Heating SetPoint(F): 68.00

Heating Setback Thermostat: Not Present

Cooling SetPoint(F): 78.00

Cooling Setup Thermostat: Not Present

Page 31: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

BUILDING FILE REPORT

Duplex Model Home Page 13

REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Intg: Int. Heat/DHW SystemType: Combined Appliance

DistributionType: Hydronic w/ air

Fuel Type: Natural gas

Rated Output Capacity (kBtuh): 100.0

Space Heating Efficiency: 0.89 CAafue

DHW Heating Efficiency: 0.89 CAef

Auxiliary Electric: 60 Watts

Note: Location: Conditioned area

Performance Adjustment: 100

% Space Heat Load Served: 100

% DHW Heat Load Served: 100

Number Of Units: 1

Cooling Equipment: ACC, 18K, 13 SEER System Type: Air conditioner

Fuel Type: Electric

Rated Output Capacity (kBtuh): 18.0

Seasonal Equipment Efficiency: 13.0 SEER

Sensible Heat Fraction (SHF): 0.70

Note: Location: Conditioned area

Performance Adjustment: 100

Percent Load Served: 100

Number Of Units: 1

Page 32: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

BUILDING FILE REPORT

Duplex Model Home Page 14

REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Duct System Information: Name Supply/Return

Heating System Int. Heat/DHW

Cooling System ACC, 18K, 13 SEER

Supply Area(sq ft) 489.0

Return Area(sq ft) 452.8

Conditioned Floor Area(sq ft) 2415.0

# of Registers 5 Duct Leakage

Qualitative Assessment - Not Applicable

Duct Leakage to Outside: 25.00 CFM @ 25 Pascals

Supply Duct Leakage - Not Applicable

Return Duct Leakage - Not Applicable

Total Duct Leakage: 50.00 CFM @ 25 Pascals

Duct Tightness Test: Rough-In Test - w/o Air Handler

Duct Information: 1 2

Type Supply Return

Percent Area 100.0 100.0

R-Value 0.0 0.0

Location Conditioned space Conditioned space

Infiltration and Mechanical VentilationWhole House Infiltration

Measurement Type: Blower door test

Heating Season Infiltration Value: 1120 CFM @ 50 Pascals

Cooling Season Infiltration Value: 1120 CFM @ 50 Pascals

Shelter Class 2

2009 IECC Verification: Tested

Mechanical Ventilation for IAQ

Type: Balanced

Rate(cfm): 115

Sensible Recovery Efficiency(%): 0.00

Total Recovery Efficiency(%): 0.00

Hours per Day: 11.00

Fan Power (watts): 25.00

Ventilation Strategy for Cooling

Cooling Season Ventilation: Natural Ventilation

Page 33: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

BUILDING FILE REPORT

Duplex Model Home Page 15

REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Lights and Appliances Simplified Audit

Oven/Range Fuel Type: Electric

Clothes Dryer Fuel Type: Natural gas

Percent Fluorescent - Pin-Based: 0.00

Percent Fluorescent - CFL: 61.00

Refrigerator KWh: 775

Dishwasher EF: 0.46

Ceiling Fan CFM / Watt: 0.00

Page 34: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

BUILDING FILE REPORT

Duplex Model Home Page 16

REM/Rate - Residential Energy Analysis and Rating Software v12.96 © 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Mandatory RequirementsIECC Requirements

Verified IECC 04: false

Verified IECC 06: false

Verified IECC 09: false

Verified IECC 12: false

Verified IECC NY: true

ENERGY STAR Version 2 Checklist

Thermal Bypass Checklist: true

ENERGY STAR Products: true

ENERGY STAR Version 3 Checklists

Thermal Enclosure Checklist: false

HVAC System Quality Installation Contractor Checklist: false

HVAC System Quality Installation Rater Checklist: false

Water Management System Builder Checklist: false

Indoor airPlus Verification Checklist: false

ENERGY STAR Version 3 Appliances

Has Refrigerators: true

Number Of Refrigerators: 1

Has Ceiling Fans: false

Number Of Ceiling Fans: 0

Has Exhaust Fans: true

Number Of Exhaust Fans: 3

Has Dishwashers: true

Number Of Dishwashers: 1

ENERGY STAR Version 3 Basements

Basement Wall Area 50% Below Grade: false

Basement Floor Area: 0

Number of Basement Bedrooms: 0

Active Solar System Type: DHW & space heating

Loop Type: Liquid, indirect

Type: Double glazing, flat black

Orientation: South

Area(sq ft): 64.0

Tilt(degrees): 45.0

Volume(cu ft/gal): 120.0

Page 35: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

FUEL SUMMARY

Date: November 30, 2011 Rating No.: 0061-0206c.blg

Building Name: Duplex Model Home Rating Org.: James E. Hammel, Inc.

Owner's Name: M&A Homes, Inc. Phone No.: 315 638 1757

Property: 4964 Astilbe Path Rater's Name: James E. Hammel

Address: Liverpool, NY 13088 Rater's No.: R 0061

Builder's Name: Troy Adams

Weather Site: Syracuse, NY Rating Type: Confirmed Rating

File Name: 4964 Astilbe Path Liverpool M&A Homes Model H Rating Date: 11/11/11

REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.

© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Duplex Model Home

Annual Energy Cost ($/yr) Natural gas $ 601

Electric $ 1321

Annual End-Use Cost ($/yr) Heating $ 581

Cooling $ 76

Water Heating $ 4

Lights & Appliances $ 1262

Photovoltaics $ -0

Service Charges $ 408

Total $ 2331

Annual End-Use Consumption Heating (Therms) 558

Heating (kWh) 157

Cooling (kWh) 411

Water Heating (Therms) 4

Lights & Appliances (Therms) 45

Lights & Appliances (kWh) 6490

Annual Energy Demands (kW) Heating 0.1

Cooling 1.1

Water Heating (Winter Peak) 0.0

Water Heating (Summer Peak) 0.0

Lights & Appliances (Winter Peak) 0.6

Lights & Appliances (Summer Peak) 1.2

Total Winter Peak 0.6

Total Summer Peak 2.4

Utility Rates: Electricity: NIMO Elect 1/10*************0***0*******

Gas: NIMO Gas 1/10*************0***0*******

Page 36: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

EQUIPMENT SIZING SUMMARY

Date: November 30, 2011 Rating No.: 0061-0206c.blg

Building Name: Duplex Model Home Rating Org.: James E. Hammel, Inc.

Owner's Name: M&A Homes, Inc. Phone No.: 315 638 1757

Property: 4964 Astilbe Path Rater's Name: James E. Hammel

Address: Liverpool, NY 13088 Rater's No.: R 0061

Builder's Name: Troy Adams

Weather Site: Syracuse, NY Rating Type: Confirmed Rating

File Name: 4964 Astilbe Path Liverpool M&A Homes Model H Rating Date: 11/11/11

REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.

© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Duplex Model HomeHEATING Calculated Peak Load (kBtu/hr) 29.3 Sizing Factor (%) 100.0

HEATING EQUIPMENT CAPACITY (kBtu/hr) Required 29.3 Specified 100.0

COOLING Calculated Peak Load (kBtu/hr) 14.1 Sensible 10.6 Latent 3.5 Sizing Factor (%) 100.0

COOLING EQUIPMENT CAPACITY (kBtu/hr) Required Total 14.1 Specified Total 18.0

Required Sensible 10.59 Specified Sensible 12.60

Required Latent 3.48 Specified Latent 5.40

Page 37: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

PERFORMANCE SUMMARY

Date: November 30, 2011 Rating No.: 0061-0206c.blg

Building Name: Duplex Model Home Rating Org.: James E. Hammel, Inc.

Owner's Name: M&A Homes, Inc. Phone No.: 315 638 1757

Property: 4964 Astilbe Path Rater's Name: James E. Hammel

Address: Liverpool, NY 13088 Rater's No.: R 0061

Builder's Name: Troy Adams

Weather Site: Syracuse, NY Rating Type: Confirmed Rating

File Name: 4964 Astilbe Path Liverpool M&A Homes Model H Rating Date: 11/11/11

REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.

© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Duplex Model Home

Annual Load (MMBtu/yr) Heating 49.7 Cooling 5.1 Water Heating 0.3

Annual Consumption (MMBtu/yr) Heating 56.3 Cooling 1.4 Water Heating 0.4 Lights & Appliances 26.6 Photovoltaics -0.0 Total 84.8

Annual Energy Cost ($/yr) Heating $ 581 Cooling $ 76 Water Heating $ 4 Lights & Appliances $ 1262 Photovoltaics $ -0 Service Charges $ 408 Total $ 2331

Design Loads (kBtu/hr) Space Heating 29.3 Space Cooling 14.1

Utility Rates: Electricity: NIMO Elect 1/10*************0***0******* Gas: NIMO Gas 1/10*************0***0*******

Page 38: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

PERFORMANCE SUMMARY

Date: November 30, 2011 Rating No.: 0061-0206c.blg

Building Name: Duplex Model Home Rating Org.: James E. Hammel, Inc.

Owner's Name: M&A Homes, Inc. Phone No.: 315 638 1757

Property: 4964 Astilbe Path Rater's Name: James E. Hammel

Address: Liverpool, NY 13088 Rater's No.: R 0061

Builder's Name: Troy Adams

Weather Site: Syracuse, NY Rating Type: Confirmed Rating

File Name: 4964 Astilbe Path Liverpool M&A Homes Model H Rating Date: 11/11/11

REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.

© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

01020304050

Hea

t

Coo

l

Wat

er H

eatin

g

MMBtu/yr

Annual Load

020406080

100

Hea

ting

Coo

ling

Wat

er H

eatin

g

Ligh

ts &

App

Pho

tovo

ltaic

s

Tota

l

MMBtu/yr

Annual Consumption

0

500

1000

1500

2000

2500

Hea

ting

Coo

ling

Wat

er H

eatin

g

Ligh

ts &

App

Pho

tovo

ltaic

s

Ser

vice

Cha

rge

Tota

l

$/yr

Annual Energy Cost

Duplex Model Home

Page 39: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

PERFORMANCE SUMMARY

Duplex Model Home Page 2

REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.

© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

0

10

20

30

Spa

ce H

eatin

g

Spa

ce C

oolin

g

KBtu/Hr

Design Loads Utility Rates: Electricity: NIMO Elect 1/10*************0***0*******

Gas: NIMO Gas 1/10*************0***0*******

Page 40: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

PERFORMANCE FACTORS

Date: November 30, 2011 Rating No.: 0061-0206c.blg

Building Name: Duplex Model Home Rating Org.: James E. Hammel, Inc.

Owner's Name: M&A Homes, Inc. Phone No.: 315 638 1757

Property: 4964 Astilbe Path Rater's Name: James E. Hammel

Address: Liverpool, NY 13088 Rater's No.: R 0061

Builder's Name: Troy Adams

Weather Site: Syracuse, NY Rating Type: Confirmed Rating

File Name: 4964 Astilbe Path Liverpool M&A Homes Model H Rating Date: 11/11/11

REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.

© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Duplex Model Home

Normalized Loads (Btu/sf shell area/DD) Heating: 1.07 Cooling: 5.14

Normalized Consumption (kBtu/sf floor area/yr) Heating: 23.3 Cooling: 0.6 Water Heating: 0.2 Lighting: 2.3 Appliances: 8.8 Photovoltaics: -0.0 Total w/o PV: 35.1 Total: 35.1

Normalized Consumption (Btu/sf floor area/DD) Heating: 3.4 Cooling: 4.0

Normalized Costs ($/sf floor area/yr) Heating: $ 0.241 Cooling: $ 0.031 Water Heating: $ 0.002 Lighting: $ 0.124 Appliances $ 0.399 Photovoltaics $ -0.000 Total: $ 0.796

Normalized Design Loads (Btuh/sf shell area/DD) Heating: 0.0006 Cooling: 0.0141

Normalization Factors Floor Area: 2415 Shell Area: 6812 Heating Degree Days (B65): 6789 Cooling Degree Days (B74): 147

Page 41: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

EMISSIONS REPORT

Date: November 30, 2011 Rating No.: 0061-0206c.blg

Building Name: Duplex Model Home Rating Org.: James E. Hammel, Inc.

Owner's Name: M&A Homes, Inc. Phone No.: 315 638 1757

Property: 4964 Astilbe Path Rater's Name: James E. Hammel

Address: Liverpool, NY 13088 Rater's No.: R 0061

Builder's Name: Troy Adams

Weather Site: Syracuse, NY Rating Type: Confirmed Rating

File Name: 4964 Astilbe Path Liverpool M&A Homes Model H Rating Date: 11/11/11

REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.

© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Total Emissions

Duplex Model Home

Type of EmissionsCarbon Dioxide (CO2) - tons/year 6.4

Sulfur Dioxide (SO2) - lbs/year 17.3

Nitrogen Oxides (NOx) - lbs/year 15.4

Emissions By End-Use

Duplex Model HomeCarbon Dioxide (CO2) - tons/yearHeating 3.4Cooling 0.2Water Heating 0.0Lights & Appliances 2.8Photovoltaics 0.0

Sulfur Dioxide (SO2) - lbs/yearHeating 0.4Cooling 1.0Water Heating 0.0Lights & Appliances 15.9Photovoltaics 0.0

Nitrogen Oxide (NOx) - lbs/yearHeating 8.5Cooling 0.4Water Heating 0.1Lights & Appliances 6.5Photovoltaics 0.0

Site-to-source energy multipliers and air emission data were taken from the US EPA eGRID2007 database.

Page 42: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

2005 EPACT ENERGY EFFICIENT HOME TAX CREDIT

Date: November 30, 2011 Rating No.: 0061-0206c.blg

Building Name: Duplex Model Home Rating Org.: James E. Hammel, Inc.

Owner's Name: M&A Homes, Inc. Phone No.: 315 638 1757

Property: 4964 Astilbe Path Rater's Name: James E. Hammel

Address: Liverpool, NY 13088 Rater's No.: R 0061

Builder's Name: Troy Adams

Weather Site: Syracuse, NY Rating Type: Confirmed Rating

File Name: 4964 Astilbe Path Liverpool M&A Homes Model H Rating Date: 11/11/11

REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.

© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Normalized, Modified End-Use Loads (MMBtu/year)2004 IECC

50% Target As Designed

Heating: 32.9 31.6

Cooling: 6.2 4.3

Total: 39.0 35.9

Envelope Loads (MMBtu/year)2004 IECC

90% Target As Designed

Heating: 59.1 47.2

Cooling: 11.1 5.4

Total: 70.2 52.6

This home MEETS the requirements for the residential energy efficiency tax credits underSection 1332, Credit for Construction of New Energy Efficient Homes, of the Energy Policy Act of 2005.

As demonstrated above, this dwelling unit has a projected level of annual heating and cooling energy consumption that is at least 50% below theannual level of heating cooling energy consumption of a reference dwelling in the same climate zone, and the building envelope componentsimprovements alone account for at least 10% of those savings. The projected heating and cooling energy savings above have been calculated in themanner prescribed in Section 2.02 of Notice 2006-27 of the Internal Revenue Service. Field inspections of the dwelling unit performed by theundersigned eligible certifier during and after the completion of construction have confirmed that all features of the home affecting such heatingand cooling energy consumption comply with the design specifications provided to the undersigned certifier.

Building FeaturesCeiling Flat: R-60, R-56 Slab: R-10.0 Edge, R-0.0 Under

Vaulted Ceiling: NA Duct: Uninsulated

Above Grade Walls: R-32, R-24 Window: U-Value = 0.220, SHGC = 0.250

Foundation Walls: R-12.5 Integrated: Natural gas, Htg eff 0.89 CAafue. DHW eff 0.89 CAef.

Exposed Floor: R-34 Cooling: Air conditioner, Electric, 13.0 SEER.

This report provides information useful in determining whether the home qualifies for Energy Efficiency Tax Credits.It is not valid for tax purposes, as homes must be inspected and approved by a certified HERS rater in order to qualify.

Page 43: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

ENERGY STAR VERSION 2 HOME REPORT

Date: November 30, 2011 Rating No.: 0061-0206c.blg

Building Name: Duplex Model Home Rating Org.: James E. Hammel, Inc.

Owner's Name: M&A Homes, Inc. Phone No.: 315 638 1757

Property: 4964 Astilbe Path Rater's Name: James E. Hammel

Address: Liverpool, NY 13088 Rater's No.: R 0061

Builder's Name: Troy Adams

Weather Site: Syracuse, NY Rating Type: Confirmed Rating

File Name: 4964 Astilbe Path Liverpool M&A Homes Model H Rating Date: 11/11/11

REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.

© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.

Normalized, Modified End-Use Loads (MMBtu/year)ENERGY STAR As Designed

Heating: 52.6 31.6

Cooling: 9.9 4.3

Water heating: 9.9 0.1

Lighting & Appliances: 23.8 26.5

Total: 96.1 62.5

HERS Index: 80 52NY HERS Score: 84.0 89.6

ENERGY STAR Mandatory Requirements

X Thermal Bypass Inspection Checklist X ENERGY STAR Products

X Ductwork Requirements X ENERGY STAR Scoring Exceptions

This home MEETS OR EXCEEDS the energy efficiency requirements for designation as an EPA ENERGY STAR Qualified Home.

Pollution PreventedType of Emissions Reduction

Carbon Dioxide (CO2) - tons/yr 5.0

Sulfur Dioxide (SO2) - lbs/yr 4.7

Nitrogen Oxides (NOx) - lbs/yr 12.3

Energy Cost Savings ($/year)Heating: $428

Cooling: $137

Water Heating: $218

Lights & Appliances: $138

Total: $920

The energy savings and pollution prevented are calculated by comparing the Rated Home to the Reference Home as defined inthe "Mortgage Industry National Home Energy Rating Systems Standards" as promulgated by the Residential Energy ServicesNetwork (RESNET) . In accordance with these guidelines, building inputs affecting setpoints, infiltration rates, window shadingand the existence of mechanical systems may have been changed prior to calculating loads.

Page 44: FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL …cloud.cdhenergy.com/homepic/troy_adams/Final Report - Troy Adam… · FINAL CONSTRUCTION REPORT NYSERDA RESIDENTIAL PERFORMANCE CHALLENGE

4964 Astilbe Path

Liverpool, NY 13088

5 Stars PlusConfirmed Rating

Rating Number: 0061-0206c.blgCertified Energy Rater: James E. Hammel

Rating Date: 11/11/11Rating Ordered For: M&A Homes, Inc.

Estimated Annual Energy CostConfirmed Rating

Use MMBtu Cost Percent Heating 54.2 $563 24%

Cooling 1.5 $79 3%

Hot Water 0.4 $4 0%

Lights/Appliances 26.5 $1253 54%

Photovoltaics -0.0 $-0 -0%

Service Charges $408 18%

Total $2307 100%

This home meets or exceeds the minimumcriteria for all of the following:

TITLECompanyAddressCity, State, ZipPhone #Fax #

Uniform Energy Rating System1 Star 1 Star Plus 2 Stars 2 Stars Plus 3 Stars 3 Stars Plus 4 Stars 4 Stars Plus 5 Stars 5 Stars Plus0-19 20-39 40-49 50-59 60-69 70-79 80-81 81-82 83-85 86-100

Energy Efficient

NY HERS Score: 89.6 / HERS Index: 52General Information

Conditioned Area: 2415 sq. ft. HouseType: Duplex, single unitConditioned Volume: 37475 cubic ft. Foundation: Conditioned basement

Bedrooms: 3Mechanical Systems Features

Integrated Htg/DHW: Natural gas, Htg eff 0.89 CAafue. DHW eff 0.89 CAef.Cooling: Air conditioner, Electric, 13.0 SEER.

Duct Leakage to Outside: 25.00 CFM.Ventilation System: Balanced: 115 cfm, 25.0 watts.

Programmable Thermostat: Heating: No Cooling: No

Building Shell FeaturesCeiling Flat: R-60, R-56 Exposed Floor: R-34

Vaulted Ceiling: NA Window Type: U:0.22, SHGC:0.25Above Grade Walls: R-32, R-24 Infiltration:

Foundation Walls: R-12.5 Rate: Htg: 1120 Clg: 1120 CFM50Slab: R-10.0 Edge, R-0.0 Under Method: Blower door test

Lights and Appliance FeaturesPercent Fluorescent Pin-Based: 0.00 Clothes Dryer Fuel: Natural gas

Percent Fluorescent CFL: 61.00 Range/Oven Fuel: ElectricRefrigerator (kWh/yr): 775.00 Ceiling Fan (cfm/Watt): 0.00

Dishwasher Energy Factor: 0.46

The Home Energy Rating Standard Disclosure for this home is available from the rating provider.

REM/Rate - Residential Energy Analysis and Rating Software v12.96 This information does not constitute any warranty of energy cost or savings.

© 1985-2011 Architectural Energy Corporation, Boulder, Colorado.