FIL/VAM/01-0516 Ammonia - Water Vapor Absorption ...
Transcript of FIL/VAM/01-0516 Ammonia - Water Vapor Absorption ...
Ammonia - Water Vapor Absorption
Refrigeration System
Applications
Chemical IndustryPharmaceutical Industry
Dairy Industry Ice Production Cold Storage
FRICK INDIA LIMITED
nnnnn
n
nnnn
FRICK VAM Advantages:
Quite in operation, because no moving parts except pump motor.
Low Maintenance cost / Running CostIt will work only with Thermal energy as a input.Capacity of 50 to 400TR( Even for above 1000TR.)Operate at designed C.O.P's as well as in part
loads by generator temperature
Features
nnnnnn
Highest possible COPBoiler tubes for generatorAdvance series flow technologyVFD for solution pumpPLC based control panelColour Touch screen
50 TRto
400 TR
FIL/VAM/01-0516
Introduction
Frick Ammonia vapour absorption machine can utilise various heat sources like steam, hot water, fuel and exhaust. These machines are used for serving the negative chilling demand (below 0ºC) and can achieve chilled brine temperature as low as -55ºC. The capacity of these machines ranges from 50 to 400 TR for standard packaged units and up to 1000 TR for custom built design units.
The working of ammonia-water absorption refrigeration
system is based on the simple vapor absorption
refrigeration system. In this system ammonia is used as the
refrigerant and water is used as the absorbent.
The ammonia-water absorption system is used in the
domestic as well the commercial applications where the
requirement of the temperature is below 0 Deg C for better
COP.
The major advantage of the ammonia-water solution is that
water has strong affinity for ammonia and they are soluble
with each other in wide operating conditions that occur in
different refrigeration applications.
Ahmedabad : Bangalore : [email protected] Chennai : [email protected]
Cochin : [email protected] New Delhi : [email protected] Jalandhar : [email protected]
Kolkata : [email protected] Mumbai : Patna : [email protected] Secunderabad : [email protected]
Vizag : [email protected]
FRICK INDIA LIMITED809, “Surya Kiran”, 19 K. G. Marg, New Delhi - 110 001. Ph : 23322381/84/91. Fax : 23322396 Email : [email protected]
Factory : 21.5 km, Main Mathura Road,
Faridabad - 121 003.
Ph : 2275691-94, 2270546-47 Fax : 0129-2275695
email : [email protected]
www.frickweb.com
Components of Vapour Absorption System
n Generatorn Absorber & Absorber Tankn Solution Heat Exchangern Stripping Columnn Rectification Columnn Partial Condenser & Condensern Ammonia Receivern Sub-Coolern Evaporatorn Pump
Specifications PLC Display of the Plant
FREEZING APPLICATIONS ( EVAPORATING AT MINUS 30 DEG C)
SL MODEL NOMINAL STEAM CONDENSER BRINENO. CAPACITY FLOW COOLING WATER FLOW
(TR) (KL./HR) KL./HR) KL./HR)
1. VAM 50 50 625 52995 35855
2. VAM 75 75 940 76470 53785
3. VAM 100 100 1240 102210 71710
4. VAM 150 150 1851 168830 107565
5. VAM 200 200 2460 204415 143420
6, VAM 250 250 3050 255895 179275
7. VAM 300 300 3600 306620 215130
8. VAM 350 350 4185 358100 250985
9. VAM 400 400 4760 408825 286840
Speci
ficatio
ns
are
subje
cted to c
hange w
ithout prior
Notic
e