Fault Calculation Steps
-
Upload
rindbergh-develos -
Category
Documents
-
view
247 -
download
10
Transcript of Fault Calculation Steps
-
7/30/2019 Fault Calculation Steps
1/100
Fault CalculationsandSelection ofProtective Equipment
Wednesday, March 22, 2006
8:00AM 3:00PM
Seminole Electric Cooperative, Inc.
16313 North Dale Mabry Hwy.
Tampa, Florida
Ralph Fehr, Ph.D., P.E.University of South Florida TampaSenior Member, [email protected]
-
7/30/2019 Fault Calculation Steps
2/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 2
Symmetrical Components
-
7/30/2019 Fault Calculation Steps
3/100
Most power systems are designed as
balanced systems.
Due to the symmetry of the problem, a
single-phase equivalent approach can be
taken to simplify the calculation process.
When the voltage and current behavior is
calculated for one of the phases, the
behaviors on the other two can be
determined using principles of symmetry.
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 3
-
7/30/2019 Fault Calculation Steps
4/100
But when the system phasors are not balanced,the single-phase equivalent approach cannot
be taken.
This means that either
1. a three-phase solution must be found,
or
2. the unbalanced phasors must be resolved
into balanced components so the single-phase
equivalent method can be used.
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 4
-
7/30/2019 Fault Calculation Steps
5/100
Charles Fortescues Theory of Symmetrical
Components, first published in 1918, proves
that any set of unbalanced voltage or current
phasors belonging to a three-phase system canbe resolved into three sets of components,
each of which is balanced.
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 5
-
7/30/2019 Fault Calculation Steps
6/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 6
A
ICI
BI
-
7/30/2019 Fault Calculation Steps
7/100
Physical Example ofVector Components
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 7
-
7/30/2019 Fault Calculation Steps
8/100
F
d
M = F d
Calculation of Moment
Moment = Force Perpendicular Distance
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 8
-
7/30/2019 Fault Calculation Steps
9/100
Calculation of Moment
d
F
M F d
Moment = Force Perpendicular Distance
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 9
-
7/30/2019 Fault Calculation Steps
10/100
Calculation of Moment
M = FV d
Moment = Force Perpendicular Distance
d
VF F
HF
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 10
-
7/30/2019 Fault Calculation Steps
11/100
Calculation of Moment
d
VF F
HF
FV = F cos
FH = F sin
FH + FV = F
=
V
H1
F
Ftan
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 11
-
7/30/2019 Fault Calculation Steps
12/100
Application of SymmetricalComponents to a Three-PhasePower System
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 12
-
7/30/2019 Fault Calculation Steps
13/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 13
AICI
BI
-
7/30/2019 Fault Calculation Steps
14/100
A-B-C Sequencing
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 14
I B
I CAI
-
7/30/2019 Fault Calculation Steps
15/100
A-C-B Sequencing
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 15
II
B
CI
A
-
7/30/2019 Fault Calculation Steps
16/100
Fortescues theory shows that three sets of
balanced components are required to represent
any unbalanced set of three-phase phasors.
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 16
-
7/30/2019 Fault Calculation Steps
17/100
Positive Sequence Components
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 17
I A1
C1I
B1I
-
7/30/2019 Fault Calculation Steps
18/100
Negative Sequence Components
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 18
A2IB2I
C2I
-
7/30/2019 Fault Calculation Steps
19/100
Zero Sequence Components
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 19
A0IB0I
C0I
-
7/30/2019 Fault Calculation Steps
20/100
The constraint equations for the symmetrical
components require the sum of the three
components for each unbalanced phasor toequal the unbalanced phasor itself.
IA = IA0 + IA1 + IA2
IB = IB0 + IB1 + IB2
IC = IC0 + IC1 + IC2
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 20
-
7/30/2019 Fault Calculation Steps
21/100
The a operator
a 23
21 j+ = 1 /120
a2 = 1 /240 a3 = 1 /360
j2 = 1 /180 = 1 j3 = 1 /270 = j j4 = 1 /360 = 1
Recall the j operator
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 21
-
7/30/2019 Fault Calculation Steps
22/100
Using the a operator and the symmetry of the
sequence components, we can develop asingle-phase equivalent circuit to greatly
simplify the analysis of the unbalanced system.
We will start by expressing the sequencecomponents in terms of a single phases
components. We will use Phase A as the phase
for developing the single-phase equivalent.
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 22
-
7/30/2019 Fault Calculation Steps
23/100
Positive Sequence Components
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 23
B1I
A1I
I C1
1= I
= a I1
= a I 12
-
7/30/2019 Fault Calculation Steps
24/100
Negative Sequence Components
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 24
I A2 = I 2I B2 = a I2
2C2 = a II 2
-
7/30/2019 Fault Calculation Steps
25/100
Zero Sequence Components
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 25
A0I = I 0= IB0I 0
= II C0 0
-
7/30/2019 Fault Calculation Steps
26/100
Recall the original constraint equations:
IA = IA0 + IA1 + IA2
IB = IB0 + IB1 + IB2
IC = IC0 + IC1 + IC2
Rewrite them using the a operator
to take advantage of the symmetry:
IA = I0 + I1 + I2
IB = I0 + a2 I1 + a I2
IC = I0 + a I1 + a2 I2
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 26
-
7/30/2019 Fault Calculation Steps
27/100
Unbalanced Phasors and their Symmetrical Components
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 27
I A
I 1
I 2
0I
CI
a I1
2a I 2
I 0
BI0I
2a I1a I
2
-
7/30/2019 Fault Calculation Steps
28/100
=
2
1
0
2
2
C
B
A
I
II
aa1
aa1111
I
II
=
2
1
0
2
2
1
2
2
C
B
A
1
2
2
I
I
I
aa1
aa1
111
aa1
aa1
111
I
I
I
aa1
aa1
111
=
C
B
A
1
2
2
2
1
0
I
I
I
aa1
aa1
111
I
I
I
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 28
-
7/30/2019 Fault Calculation Steps
29/100
=
C
B
A
1
2
2
2
1
0
I
I
I
aa1
aa1
111
I
I
I
=
C
B
A
2
2
2
1
0
I
I
I
aa1
aa1
111
3
1
I
I
I
( )CBA0 III3
1I ++=
( )C2BA1 IaIaI31I ++=
( )CB2A2 IaIaI3
1I ++=
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 29
-
7/30/2019 Fault Calculation Steps
30/100
( )CBA0 III3
1I ++=
( )C2
BA1 IaIaI3
1
I ++=
( )CB2A2 IaIaI3
1I ++=
Summary of Symmetrical Components
Transformation Equations
IA = I0 + I1 + I2
IB = I0 + a2 I1 + a I2
IC = I0 + a I1 + a2 I2
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 30
-
7/30/2019 Fault Calculation Steps
31/100
Workshop #1Symmetrical Components
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 31
Ia = 0.95 /328
Ib = 1.03 /236
Ic = 0.98 /92
Find I0, I1, and I2
I0 = 0.7 /300
I1 = 1.2 /10
I2 = 0.3 /167
Find Ia, Ib, and Ic
-
7/30/2019 Fault Calculation Steps
32/100
Workshop #1Symmetrical Components
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 32
Ia = 0.95 /328
Ib = 1.03 /236
Ic = 0.98 /92
Find I0, I1, and I2
I0 = 0.1418 /297
I1 = 0.9634 /339
I2 = 0.1622 /191
Ia
cI
bI
I1I2
I0
a I1
a I22 I0
1a I2
2a II0
-
7/30/2019 Fault Calculation Steps
33/100
Workshop #1Symmetrical Components
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 33
I0 = 0.7 /300I1 = 1.2 /10
I2 = 0.3 /167
Find Ia, Ib, and Ic
I1
2
0
I
I
Ia
Ic
a I1
2a I2
I0
I0
1a I2
2a I
Ia = 1.2827 /345
Ib = 2.0209 /271
Ic = 0.5749 /112
-
7/30/2019 Fault Calculation Steps
34/100
Electrical Characteristics ofthe Sequence Currents
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 34
-
7/30/2019 Fault Calculation Steps
35/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 35
O
y DA
x
I
L
-
7/30/2019 Fault Calculation Steps
36/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 36
I
t
-
7/30/2019 Fault Calculation Steps
37/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 37
Bottom Wire
Top WireMiddle Wire
t = T
I
t
-
7/30/2019 Fault Calculation Steps
38/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 38
O
I0
D
A
LI0
0I
-
7/30/2019 Fault Calculation Steps
39/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 39
3 I
0I
0
0I
I0
O
DA
L
-
7/30/2019 Fault Calculation Steps
40/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 40
O3 I
0I D
0 A
LI0
0I
VN = (3 I0) ZN
VN = I0 (3 Z(3 ZNN))
-
7/30/2019 Fault Calculation Steps
41/100
The Delta-Wye Transformer
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 41
-
7/30/2019 Fault Calculation Steps
42/100
Ic
Ia
Ib
IA
IC
IB
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 42
Assume Ia = 1 /0o, Ib = 1 /240
o, and Ic = 1/120o.
Ic
Ia
Ib
Ic
Ia
Ib
IB = Ib Ic = 1 /240o 1 /120o = /270o3
IC = Ic Ia = 1 /120o 1 /0o = /150o3
The Delta-Wye Transformer
IA
IB
IC
Ia
Ib
IcIA = Ia Ib = 1 /0
o 1 /240o = /30o3
-
7/30/2019 Fault Calculation Steps
43/100
Workshop #2Non-Standard Delta-Wye Transformer
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 43
Given that Ia = 1/0o, Ib = 1/240
o, and Ic = 1/120o, find IA, IB, and IC.
Ib
aI
cI
BI
AI
CI
-
7/30/2019 Fault Calculation Steps
44/100
IC aI
IA
IB
cI
bI
Ib
cII acI
bII a
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 44
Workshop #2Non-Standard Delta-Wye Transformer
Ia = 1/0o
Ib = 1/240o
Ic = 1/120o
IA = Ia Ic = 1/0o 1/120o
= /330o3
IB = Ib Ia = 1/240o 1/0o
= /210o3
IC = Ic Ib = 1/120o 1/240o
= /90o3Ia
Ib
Ic
IA
IC
IB
-
7/30/2019 Fault Calculation Steps
45/100
Sequence Networks
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 45
-
7/30/2019 Fault Calculation Steps
46/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 46
T1 T2
T3
M1 M2
M3
GUtilityXn
1
2
One-Line Diagram
Positive Sequence Reactance Diagram
-
7/30/2019 Fault Calculation Steps
47/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 47
T1 T2
T3
M1 M2
M3
GUtility Xn
1
2
Utility M1 M2 M3G
Positive-Sequence Reference Bus
Positive-Sequence Reactance Diagram
Positive-Sequence Reactance Diagram
-
7/30/2019 Fault Calculation Steps
48/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 48
T1 T2
T3
M1 M2
M3
GUtility Xn
1
2
Positive-Sequence Reactance Diagram
M3M1
1
T1 M2 T2
Utility G
Positive-Sequence Reference Bus
Positive-Sequence Reactance Diagram
-
7/30/2019 Fault Calculation Steps
49/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 49
T1 T2
T3
M1 M2
M3
GUtility Xn
1
2
Positive-Sequence Reactance Diagram
2
T3 M3
Positive-Sequence Reference Bus
1
T1 M2M1 T2
Utility G
Negative-Sequence Reactance Diagram
-
7/30/2019 Fault Calculation Steps
50/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 50
T1 T2
T3
M1 M2
M3
GUtility Xn
1
2
Negative Sequence Reactance Diagram
2
T3 M3
Positive-Sequence Reference Bus
1
T1 M2M1 T2
Utility G
Negative
Negative-Sequence Reactance Diagram
-
7/30/2019 Fault Calculation Steps
51/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 51
T1 T2
T3
M1 M2
M3
GUtility Xn
1
2
Negative Sequence Reactance Diagram
2
T3 M3
1
T1 M2M1 T2
Utility G
Negative-Sequence Reference Bus
Zero-Sequence Reactance Diagram
-
7/30/2019 Fault Calculation Steps
52/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 52
T1 T2
T3
M1 M2
M3
GUtility Xn
1
2
Zero Sequence Reactance Diagram
2
T3 M3
1
T1 M2M1 T2
Utility G
Negative-Sequence Reference BusZero
+3Xn
Adjust Topology
Zero-Sequence Reactance Diagram
-
7/30/2019 Fault Calculation Steps
53/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 53
T1 T2
T3
M1 M2
M3
GUtility Xn
1
2
q g
M3
2
1
T3
Zero-Sequence Reference Bus
M1T1
Utility
M2 T2
GXn
+ 3 Xn
Zero-Sequence Reactance Diagram
-
7/30/2019 Fault Calculation Steps
54/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 54
T1 T2
T3
M1 M2
M3
GUtility Xn
1
2
q g
M3
2
1
T3
Zero-Sequence Reference Bus
M1T1
Utility
M2 T2
GXn
+ 3 Xn
Connection AlterationConnection Alteration
Gr.Gr. WyeWye NoneNone
WyeWye OpenOpen CktCkt..
Delta OpenDelta Open CktCkt. AND. AND
Short to Ref. BusShort to Ref. Bus
Zero-Sequence Reactance Diagram
-
7/30/2019 Fault Calculation Steps
55/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 55
T1 T2
T3
M1 M2
M3
GUtility Xn
1
2
q g
+ 3 Xn
2
T3
1
T1 M1 M2 T2
M3
Zero-Sequence Reference Bus
UtilityG
Xn
-
7/30/2019 Fault Calculation Steps
56/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 56
Workshop #3Sequence Networks
Draw the positive-,
negative-, and
zero-sequence
networks for the
one-line diagram
on the left.
T2
G
Xn
M2
Xn
1
M1
2
T3
Utility
T1
-
7/30/2019 Fault Calculation Steps
57/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 57
Workshop #3Sequence Networks
Positive-Sequence Reference Bus
2
T1
1
T3
M1 T2
Utility G
M2
-
7/30/2019 Fault Calculation Steps
58/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 58
Workshop #3Sequence Networks
T3 M2
2
Utility
T1
1
M1 T2
Negative-Sequence Reference Bus
G
-
7/30/2019 Fault Calculation Steps
59/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 59
Workshop #3Sequence Networks
Zero-Sequence Reference Bus
1
T1
Utility
2
T3
M1 T2
M2
G
+3Xn
Xn+3Xn
-
7/30/2019 Fault Calculation Steps
60/100
Thevenin Reduction ofSequence Networks
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 60
P iti S R t Di
-
7/30/2019 Fault Calculation Steps
61/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 61
Positive-Sequence Reactance Diagram
Bus 1 Thevenin
Equivalent
Bus 2 Thevenin
Equivalent
[(T1+Utility) M1 M2 (T2+G)] (T3+M3)
M3 {T3+ [(T1+Utility) M1 M2 (T2+G)]}2
T3 M3
Positive-Sequence Reference Bus
1
T1 M2M1 T2
Utility G
-
7/30/2019 Fault Calculation Steps
62/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 62
Positive-Sequence Reactance Diagram
Thevenin
Equivalent
X1
+
Pre-faultVoltage
FaultLocation
N ti S R t Di
-
7/30/2019 Fault Calculation Steps
63/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 63
Negative-Sequence Reactance Diagram
Bus 1 Thevenin
Equivalent
Bus 2 Thevenin
Equivalent
[(T1+Utility) M1 M2 (T2+G)] (T3+M3)
M3 {T3+ [(T1+Utility) M1 M2 (T2+G)]}2
T3 M3
1
T1 M2M1 T2
Utility G
Negative-Sequence Reference Bus
-
7/30/2019 Fault Calculation Steps
64/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 64
Negative-Sequence Reactance Diagram
Thevenin
Equivalent
Location
X2
Fault
_
Zero Sequence Reactance Diagram
-
7/30/2019 Fault Calculation Steps
65/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 65
Zero-Sequence Reactance Diagram
+ 3 Xn
2
T3
1
T1 M1 M2 T2
M3
Zero-Sequence Reference Bus
UtilityG
Xn
Bus 1 Thevenin
Equivalent
Bus 2 Thevenin
Equivalent
T1
T3 + T1
-
7/30/2019 Fault Calculation Steps
66/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 66
Zero-Sequence Reactance Diagram
Thevenin
Equivalent
X0
FaultLocation
0
-
7/30/2019 Fault Calculation Steps
67/100
Types of Fault Calculations
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 67
-
7/30/2019 Fault Calculation Steps
68/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 68
First-Cycle or Momentary
First-cycle fault calculations are done to determine
the withstand strength requirement of the systemcomponents at the location of the fault.
It is the maximum amplitude of the fault current
ever expected (worst case).
It requires use of the subtransient reactances of
rotating machines, and includes induction motors.
-
7/30/2019 Fault Calculation Steps
69/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 69
Contact-Parting or Clearing
Contact-parting fault calculations are done to
determine the interrupting rating of the protectivedevices at the location of the fault.
It is a reduced amplitude of the fault current
anticipated at clearing time (worst case).
It requires use of the transient reactances of
rotating machines, and excludes induction motors.
-
7/30/2019 Fault Calculation Steps
70/100
Short-Circuit FaultCalculations
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 70
-
7/30/2019 Fault Calculation Steps
71/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 71
Three-Phase Fault
-
7/30/2019 Fault Calculation Steps
72/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 72
Line-to-Ground Fault
-
7/30/2019 Fault Calculation Steps
73/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 73
Double Line-to-Ground Fault
-
7/30/2019 Fault Calculation Steps
74/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 74
Line-to-Line Fault
-
7/30/2019 Fault Calculation Steps
75/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 75
Workshop #4Short-Circuit Fault Calculations
The Thevenin-equivalent sequence reactances at agiven bus are:
X1 = 0.032 p.u.
X2 = 0.029 p.u.
X0 = 0.024 p.u.
Find the fault currents at that bus for a (1) three-phase,
(2) line-to-ground, (3) double line-to-ground, and (4) line-
to-line fault.
The base current is 1.5 kA.
-
7/30/2019 Fault Calculation Steps
76/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 76
Workshop #4Short-Circuit Fault Calculations
Three-Phase Fault
IA = 31.25 /-90o p.u. = 46.9 /-90o kA
IB = 31.25 /150o p.u. = 46.9 /150o kA
IC = 31.25 /30o p.u. = 46.9 /30o kA
-
7/30/2019 Fault Calculation Steps
77/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 77
Workshop #4Short-Circuit Fault Calculations
Line-to-Ground Fault
IA = 35.29 /-90o p.u. = 52.9 /-90o kA
IB = 0
IC = 0
-
7/30/2019 Fault Calculation Steps
78/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 78
Workshop #4Short-Circuit Fault Calculations
Double Line-to-Ground Fault
I0 = 12.124 /90o p.u.
I1 = 22.157 /-90o p.u.
I2 = 10.033 /90o p.u.
IA = 0
IB = 33.29 /147o p.u. = 49.9 /147o kA
IC = 33.29 /33o p.u. = 49.9 /33o kA
-
7/30/2019 Fault Calculation Steps
79/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 79
Workshop #4Short-Circuit Fault Calculations
Line-to-Line Fault
I0 = 0
I1 = 16.39 /-90o p.u.
I2 = 16.39 /90o p.u.
IA = 0
IB = 28.4 /180o p.u. = 42.6 /180o kA
IC = 28.4 /0o p.u. = 42.6 /0o kA
-
7/30/2019 Fault Calculation Steps
80/100
Open-Circuit FaultCalculations
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 80
-
7/30/2019 Fault Calculation Steps
81/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 81
One-Line-Open Fault
-
7/30/2019 Fault Calculation Steps
82/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 82
Two-Lines-Open Fault
-
7/30/2019 Fault Calculation Steps
83/100
X/R Ratio at Fault Location
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 83
The X/R ratio at the point of the fault
-
7/30/2019 Fault Calculation Steps
84/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 84
p
determines the rate of fault current decay.
The larger the X/R ratio, the more slowly the
fault current decays.
Small X/R Large X/R
-
7/30/2019 Fault Calculation Steps
85/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 85
Determination of the X/R ratio requires the
construction of a positive sequence
resistance network.
The X (positive-sequence reactance) and R
must be determined separately at the fault
location. Then the resistance is divided into
the reactance to give the X/R ratio.
A SINGLE IMPEDANCE DIAGRAM
COMBINING R AND X CANNOT BE USED! Itwill undercalculate the actual X/R ratio.
-
7/30/2019 Fault Calculation Steps
86/100
Selection of ProtectiveEquipment
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 86
-
7/30/2019 Fault Calculation Steps
87/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 87
Protective devices are always sized for the
highest possible fault current at the location
where the device will be installed this is NOT
always a three-phase fault!!
RMS symmetrical fault current is used to
determine all protective device ratings.
With the exception of power circuit breakers,
protective devices are sized based on a
multiplying factor to account for X/R ratios that
exceed the manufacturers assumptions.
P Ci it B k
-
7/30/2019 Fault Calculation Steps
88/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 88
Power Circuit Breakers
Power circuit breakers are specified by a Close-and-
Latch rating.
RMS Close-and-Latch rating =
1.6 RMS symmetrical fault current
Crest Close-and-Latch rating =
2.7 RMS symmetrical fault current
Example: If the maximum fault current is 23.5 kA23.5 kA,the required RMS close-and-latch rating
is 1.6 23.5 = 37.637.6 kAkARMSRMS
F d L V lt Ci it B k
-
7/30/2019 Fault Calculation Steps
89/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 89
Fused Low-Voltage Circuit Breakers
94RXfor251
1e2MFRX2
bkrfusedLV ./.
)//(
>+=
Example: Maximum fault current = 27.5 kA27.5 kA
X/R at fault location = 7.87.8
1011
251
1e2MF
872
bkrfusedLV .
.
./
=+
=
So, the fused low-voltage circuit breaker
must be rated at least 27.5 1.101 = 30.3 kA30.3 kA
-
7/30/2019 Fault Calculation Steps
90/100
Medium Voltage Expulsion Fuses
-
7/30/2019 Fault Calculation Steps
91/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 91
Medium-Voltage Expulsion Fuses
15RXfor521
1e2MFRX2
fuseMV >+=
/.
)/(/
Example: Maximum fault current = 45.8 kA45.8 kA
X/R at fault location = 21.421.4
0381
521
1e2MF
4212
fuseMV .
.
./
=+
=
So, the medium-voltage expulsion fuse must
be rated at least 45.8 1.038 = 47.6 kA47.6 kA
Low Voltage Expulsion Fuses
-
7/30/2019 Fault Calculation Steps
92/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 92
Low-Voltage Expulsion Fuses
94RXfor251
1e2MFRX2
fuseLV ./.
)/(/
>+=
Example: Maximum fault current = 38.2 kA38.2 kA
X/R at fault location = 11.811.8
1801
251
1e2MF
8112
fuseLV .
.
./
=+
=
So, the low-voltage expulsion fuse must be
rated at least 38.2 1.180 = 45.1 kA45.1 kA
Current Limiting Fuses
-
7/30/2019 Fault Calculation Steps
93/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 93
Current-Limiting Fuses
10RXfor441
1e2MFRX2
fuseitinglimcurrent >+=
/.
)/(/
Example: Maximum fault current = 58.4 kA58.4 kA
X/R at fault location = 16.216.2
0661
441
1e2MF
2162
fuseitinglimcurrent .
.
./
=+
=
So, the current-limiting fuse must be rated at
least 58.4 1.066 = 62.3 kA62.3 kA
Workshop #5P t ti D i S ifi ti
-
7/30/2019 Fault Calculation Steps
94/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 94
Workshop #5Protective Device Specification
1. Find both the RMS Close-and-Latch rating and the
Crest Close-and-Latch rating required for apower circuit breaker to be installed on a bus
where the maximum fault current is 32.9 kA.
2. Find the required interrupting rating for a molded-
case circuit breaker installed on a bus with a
maximum fault current of 46.5 kA and an X/R ratio
of 14.
Workshop #5P t ti D i S ifi ti
-
7/30/2019 Fault Calculation Steps
95/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 95
Workshop #5Protective Device Specification
3. Find the required interrupting rating for a medium-
voltage fuse installed on a bus with a maximumfault current of 46.5 kA and an X/R ratio of 18.
4. Find the required interrupting rating for a low-
voltage fuse installed on a bus with a maximum
fault current of 64.8 kA and an X/R ratio of 12.
5. Find the required interrupting rating for a current-limiting fuse installed on a bus with a maximum
fault current of 27.3 kA and an X/R ratio of 8.
Workshop #5Protective Device Specification
-
7/30/2019 Fault Calculation Steps
96/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 96
Workshop #5Protective Device Specification
2.
46.5 kA 1.111 = 51.7 kA
( )1.111
2.29
1e2MF
/14
bkrcasemolded =+
=
1. Close-and-LatchRMS = 32.9 kA 1.6 = 52.6 kA
Close-and-LatchCrest= 32.9 kA 2.7 = 88.8 kA
Workshop #5Protective Device Specification
-
7/30/2019 Fault Calculation Steps
97/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 97
Workshop #5Protective Device Specification
4.
64.8 kA 1.182 = 76.6 kA
1.1821.25
1e2MF
12/2
fuseLV =+
=
1.0211.52
1e2
MF
18/2
fuseMV=
+=
3.
46.5 kA 1.021 = 47.5 kA
Workshop #5Protective Device Specification
-
7/30/2019 Fault Calculation Steps
98/100
IEEE Fault Calculation Seminara March 2006a Ralph Fehr, Ph.D., P.E.a 98
Workshop #5Protective Device Specification
Since X/R 10, no multiplying factor is used.Required Interrupting Rating = 27.3 kA
10X/Rfor1.44
1e2MF(X/R)/2
fuselimitingcurrent >+=
5.
-
7/30/2019 Fault Calculation Steps
99/100
Fault CalculationsandSelection ofProtective Equipment
http://http://web.tampabay.rr.com/usfpower/fehr.htmweb.tampabay.rr.com/usfpower/fehr.htm
which includes a link toAlex McEacherns Power Quality Teaching Toy
Dont forget the power engineering resources mentioned in this course:
-
7/30/2019 Fault Calculation Steps
100/100
Fault CalculationsandSelection ofProtective Equipment
Thank you!Seminole Electric Cooperative, Inc.
16313 North Dale Mabry Hwy.Tampa, Florida
Ralph Fehr, Ph.D., P.E.University of South Florida TampaSenior Member, [email protected]