March 2017 EPS F810A Rev 1 Technical data MTL fieldbus networks Eaton Electric Limited, Great Marlings, Butterfield, Luton Beds, LU2 8DL, UK. Tel: + 44 (0)1582 723633 Fax: + 44 (0)1582 422283 E-mail: [email protected] www.mtl-inst.com © 2017 Eaton All Rights Reserved Publication No. EPS F810A Rev 1 March 2017 1 The F810A fieldbus power system is designed to provide redundant FOUNDATION™ fieldbus power for Foxboro EVO™ control systems using FBM228 modules. Eight fieldbus segments are supported. The system comprises a baseplate which accommodates two redundant pairs of Foxboro FBM228 modules and two MTL-Relcom F801 or F802 power modules operating in redundant configuration. Failure alarms, galvanic isolation, power conditioning and segment termination are incorporated into each F80x module. In applications requiring simplex power, a single F80x module may be used. For extreme reliability, the module baseplate has no components and only provides interconnections between FBM228 modules, the power modules and external connections. Each F80x module has indicator LEDs to show both its status and that of the eight segments under power. In normal operation, each green ‘Segment’ LED is lit, showing that the segment is powered. If a segment is shorted, this LED is extinguished, and the red ‘Alarm’ LED is lit. In the alarm condition, a normally closed, galvanically-isolated relay contact goes to an open condition. Connections to the alarm relay are made via screw terminals on the F810A baseplate. If multiple F810A units are used, a common alarm circuit can be achieved by ‘daisy-chaining’ the alarm circuits. The F80x module provides galvanic isolation between the 24V DC input power and the fieldbus segments, as required by the IEC61158-2 fieldbus standard and the Fieldbus FOUNDATIONF810A Integrated Redundant Fieldbus Power for Foxboro EVO TM Control Systems FF-831 validation test for power conditioners. There is also galvanic isolation between the fieldbus segments, thereby preventing multiple segment failures from ground faults on more than one segment. Each segment has its own fieldbus power conditioner and current limitation. Termination of the fieldbus segment is automatically maintained when single or redundant F80x modules are fitted. An F809F-Plus diagnostic module may optionally be installed on the carrier, to automatically collect and distribute diagnostic information on each of the eight fieldbus segments. Measured parameters may be viewed in the Foxboro control system by either assigning the F809F-Plus as a fieldbus device to segment 1 or 8 of the powered segments, or by means of a separate fieldbus segment. Connections for the separate segment are provided on the baseplate. For more information see the F809F-Plus product specification. Redundant 24V DC (nom.) input power can be connected to the F810A baseplate using Foxboro I/A standard AMP connectors. F80x power modules and the F809F-Plus fieldbus diagnostic module can either be powered from the same source or, alternatively, for installations in which standard Foxboro power supplies are unable to provide sufficient current capacity, an external 24V DC supply may be connected. Field wiring connections are available with either pluggable screw terminals (F810A-PS) or pluggable spring clamp terminals (F810A-PC). Accessories are required for T-section and G-section, DIN-rail (DMK01) or surface (SMS01) mounting. FOUNDATIONfieldbus is a trademark of Fieldbus FOUNDATION , Austin, Texas. Integrated redundant fieldbus power for FBM228 FOUNDATION™ fieldbus modules 8-segment redundancy High-density, compact design Fully isolated Low power dissipation No components on carrier Built-in “smart” termination Continuous physical layer diagnostic option

Transcript of F810A - MTL Instruments · 20V Input 24V Input 28V Input Input vs Output Current - Simplex F801...

Page 1: F810A - MTL Instruments · 20V Input 24V Input 28V Input Input vs Output Current - Simplex F801 System 0.50 1.50 2.50 3.50 4.50 0 100 2003 00 400 Average Segment Output Current (mA)

March 2017EPS F810A Rev 1

Technical data MTL fieldbus networks

Eaton Electric Limited, Great Marlings, Butterfield, LutonBeds, LU2 8DL, UK.Tel: + 44 (0)1582 723633 Fax: + 44 (0)1582 422283E-mail: [email protected]

© 2017 Eaton All Rights ReservedPublication No. EPS F810A Rev 1March 2017

1

The F810A fieldbus power system is designed to provide redundant FOUNDATION™ fieldbus power for Foxboro EVO™ control systems using FBM228 modules. Eight fieldbus segments are supported. The system comprises a baseplate which accommodates two redundant pairs of Foxboro FBM228 modules and two MTL-Relcom F801 or F802 power modules operating in redundant configuration. Failure alarms, galvanic isolation, power conditioning and segment termination are incorporated into each F80x module. In applications requiring simplex power, a single F80x module may be used.

For extreme reliability, the module baseplate has no components and only provides interconnections between FBM228 modules, the power modules and external connections.

Each F80x module has indicator LEDs to show both its status and that of the eight segments under power. In normal operation, each green ‘Segment’ LED is lit, showing that the segment is powered. If a segment is shorted, this LED is extinguished, and the red ‘Alarm’ LED is lit. In the alarm condition, a normally closed, galvanically-isolated relay contact goes to an open condition. Connections to the alarm relay are made via screw terminals on the F810A baseplate. If multiple F810A units are used, a common alarm circuit can be achieved by ‘daisy-chaining’ the alarm circuits.

The F80x module provides galvanic isolation between the 24V DC input power and the fieldbus segments, as required by the IEC61158-2 fieldbus standard and the Fieldbus FOUNDATION™

F810AIntegrated Redundant Fieldbus Power for Foxboro EVOTM

Control Systems

FF-831 validation test for power conditioners. There is also galvanic isolation between the fieldbus segments, thereby preventing multiple segment failures from ground faults on more than one segment. Each segment has its own fieldbus power conditioner and current limitation. Termination of the fieldbus segment is automatically maintained when single or redundant F80x modules are fitted.

An F809F-Plus diagnostic module may optionally be installed on the carrier, to automatically collect and distribute diagnostic information on each of the eight fieldbus segments. Measured parameters may be viewed in the Foxboro control system by either assigning the F809F-Plus as a fieldbus device to segment 1 or 8 of the powered segments, or by means of a separate fieldbus segment. Connections for the separate segment are provided on the baseplate. For more information see the F809F-Plus product specification.

Redundant 24V DC (nom.) input power can be connected to the F810A baseplate using Foxboro I/A standard AMP connectors. F80x power modules and the F809F-Plus fieldbus diagnostic module can either be powered from the same source or, alternatively, for installations in which standard Foxboro power supplies are unable to provide sufficient current capacity, an external 24V DC supply may be connected.

Field wiring connections are available with either pluggable screw terminals (F810A-PS) or pluggable spring clamp terminals (F810A-PC). Accessories are required for T-section and G-section, DIN-rail (DMK01) or surface (SMS01) mounting.

Foundation™ fieldbus is a trademark of Fieldbus FOUNDATION™, Austin, Texas.

• Integrated redundant fieldbus power for FBM228 Foundation™ fieldbus modules

• 8-segment redundancy

• High-density, compact design

• Fully isolated

• Low power dissipation

• No components on carrier

• Built-in “smart” termination

• Continuous physical layer diagnostic option

Page 2: F810A - MTL Instruments · 20V Input 24V Input 28V Input Input vs Output Current - Simplex F801 System 0.50 1.50 2.50 3.50 4.50 0 100 2003 00 400 Average Segment Output Current (mA)

F810AMarch 2017

2

ELECTRICALEMC Compliance

To EN61326:2013 Electrical equipment for measurement, control and laboratory use - EMC requirements

F810A - BLOCK DIAGRAM

ENVIRONMENTAL

Ambient temperature F801 F802Operating (full load) - 40°C to +65°C - 40°C to +50°COperating (60% load) - 40°C to +65°C - 40°C to +65°CStorage - 40°C to +85°C - 40°C to +85°C

Note: Temperature range applies only when mounted on a horizontal DIN rail attached to a vertical surface.

Ingress protectionIP20 to BS EN60529 (For additional protection mount the equipment in an enclosure)

PHYSICAL NETWORKSIEC61158-2ISA-S50.02 Part 2-1992FOUNDATION™ fieldbus H1

ORDERING INFORMATION

DESCRIPTION PART NO.Carrier, unpopulated F810A-CA

8-segment power module: 21.5V, 350mA F8018-segment power module: 28V, 500mA F802

F810A system with pluggable screw terminal connectors and two F801 modules

F810A-PS

F810A system with pluggable screw terminal connectors and two F802 modules

F810A-2-PS

F810A system with pluggable spring clamp connectors and two F801 modules

F810A-PC

F810A system with pluggable spring clamp connectors and two F802 modules

F810A-2-PC

Blanking module * F800-BLK

Fieldbus diagnostic module F809F-Plus

DIN-rail mounting kit, T or G section (pack of 40 clips)

DMK01

Surface mounting kit (pack of 40 clips) SMS01

* Used in place of an F80x power module for non-redundant operation in order to defeat the failure alarm caused by the absence of the F80x.

Note: Foxboro FBM228 modules are not included and must be obtained separately.

SPECIFICATIONLocation of equipment

Safe area

INPUT F801 F802

Input voltage (DC) 19.2 - 30.0V 19.2 - 30.0V

Current consumption(24V input, all outputs fully loaded) 4.4A* 6.9A*

Total Power dissipation(24V input, all outputs fully loaded)

42W* 46W*

* Redundant operation(Figures based upon fully populated F810A baseplate, including all F80x, FBM228 and F809F -Plus modules - see also next page)

OUTPUT F801 F802

Number of channels Eight (8) Eight (8)Voltage (DC) 21.5V - 24.0V 28.0V - 30.0VDesign current (per segment) 0 to 350mA 0 to 500mACurrent limit > 370mA > 520mAMinimum load 0mA 0mAIsolationFieldbus to input power: 250V AC rms withstandSegment to segment: 200V DC withstand

ALARMSAlarm contact rating

1A maximum @ 30V DC maximumAlarm contact status

Normally closed

Alarm threshold F801 F802Segment output <19V DC <24V DC

SYSTEM CONNECTIONSFoxboro ‘Fieldbus’ LAN

9-way subminiature D, femaleAddress switchesFieldbus wiring

Segment 1–8 and diagnostic segment – each has 3-way pluggable connector in screw terminal or spring clamp version, 0.14 to 2.5mm2

(See ordering information)Foxboro primary and secondary power inputs

2 x 3-way socket headers type AMP Universal MATE-N-LOKAlternative power inputs

2 x 4-way pluggable connector, 0.14 to 2.5mm2(Note these connectors are spring clamp type for -PC and -PS product variants. (See ordering information)

Chassis ground and screen/shield ground Separate M4 terminal studsAlarm contacts

2-way fixed screw terminal connector, 0.14 to 2.5mm2

MECHANICALMounting method DIN-rail or vertical flat panel. DIN-rail mounting requires mounting clips (quantity 9 per F810A), available as part number DMK01 for pack of 40 clips.Weights

F801: 1.45kgF802: 1.50kg F810A-CA: 0.55kg

�����

���

��������

�� ��

�������

�������

������ ������������������ ����

�����������

���� �

���

���

������

�����

���

���������������

���� �

���

���

������

�����

���

��������������

����������� ��

������������ ��

������������­��

� ����

� ����

� ����

� ����

�� �

�����

����

���

�� ������������

�� ������������

�­ ��������������­��������

������ ����������������� 

������������� 

Baseplate I.D.Sw.1 Sw.2

0 ON ON1 ON OFF2 OFF ON3 OFF OFF

Posn. Sw.31 - 4 ON5 - 8 OFF

Page 3: F810A - MTL Instruments · 20V Input 24V Input 28V Input Input vs Output Current - Simplex F801 System 0.50 1.50 2.50 3.50 4.50 0 100 2003 00 400 Average Segment Output Current (mA)

F810AMarch 2017

3

F801 PARAMETERS

Power Dissipation - Simplex F801 System

8.00

10.00

12.00

14.00

16.00

18.00

20.00

0 100 200 300 400

Average Segment Output Current (mA)

Pow

er D

issi

patio

n (W

)

20V Input24V Input28V Input

Input vs Output Current - Simplex F801 System

0.50

1.50

2.50

3.50

4.50

0 100 200 300 400

Average Segment Output Current (mA)

Mod

ule

Inpu

t Cur

rent

(A)

20V Input24V Input28V Input

Input vs Output Current - Redundant F801 System

0.50

1.50

2.50

3.50

4.50

150 200 250 300 350 400

Average Segment Output Current (mA)

Mod

ules

Inpu

t Cur

rent

(A)

20V Input24V Input28V Input

Power Dissipation - Redundant F801 System

12.00

14.00

16.00

18.00

20.00

22.00

150 200 250 300 350 400

Average Segment Output Current (mA)Po

wer

Dis

sipa

tion

(W)

20V Input24V Input28V Input

a) b)

c) d)

F802 PARAMETERS

Input vs Output Current - Simplex F802 System

0

1

2

3

4

5

6

7

8

0 100 200 300 400 500 600

Average Segment Output Current (mA)

Mod

ule

Inpu

t Cur

rent

(A)

19V Input24V Input30V Input

Power Dissipation - Simplex F802 System

4.0

9.0

14.0

19.0

24.0

29.0

0 100 200 300 400 500 600

Average Segment Output Current (mA)

Pow

er D

issi

patio

n (W

)

19V Input24V Input30V Input

Power Dissipation - Redundant F802 System

4.0

9.0

14.0

19.0

24.0

29.0

0 100 200 300 400 500 600

Average Segment Output Current (mA)

Pow

er D

issi

patio

n (W

)

19V Input24V Input30V Input

Input vs Output Current - Redundant F802 System

0

1

2

3

4

5

6

7

8

0 100 200 300 400 500 600

Average Segment Output Current (mA)

Mod

ule

Inpu

t Cur

rent

(A)

19V Input24V Input30V Input

a) b)

c) d)

Calculating current requirements

There are two separate methods of powering the F80x power modules on the baseplate - Option 1 - from the Foxboro Power system or - Option 2 - from External Power supplies. Both methods can provide redundant power to the F810A.

Note: Power for the FBM228 modules is always taken from the Foxboro power supplies.

Option 2 current requirement from either external supply:1. Use the 801/802 a) graph for simplex operation or

the b) graph for redundancy.2. Add 0.08A for the F809F-Plus - if fitted.Option 1 current requirement from Foxboro supply:Add a total of 0.8A for four FBM228 module to Option 2 current.

�����

���������

�����

���������

��

Linking alarm circuits

Page 4: F810A - MTL Instruments · 20V Input 24V Input 28V Input Input vs Output Current - Simplex F801 System 0.50 1.50 2.50 3.50 4.50 0 100 2003 00 400 Average Segment Output Current (mA)

F810AMarch 2017

The given data is only intended as a product description and should not be regarded as a legal warranty of properties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.

Eaton Electric Limited, Great Marlings, Butterfield, LutonBeds, LU2 8DL, UK.Tel: + 44 (0)1582 723633 Fax: + 44 (0)1582 422283E-mail: [email protected]

© 2017 Eaton All Rights ReservedPublication No. EPS F810A Rev 1 010317March 2017

EUROPE (EMEA):

+44 (0)1582 723633 [email protected]

THE AMERICAS:

+1 800 835 7075 [email protected]

ASIA-PACIFIC:

+65 6645 9864 / 9865 [email protected]

4

DIMENSIONS (mm)

1

1c1a

16c

16a

1c 1a

16c

16a

LABEL

PID

CO

N11

1C

ON

141

CO

N12

4

CO

N12

1

CO

N50

9

CO

N13

1C

ON

21

CON505

SW1

CO

N11

9

CO

N24

CO

N20

CO

N11

7

CO

N41

CO

N12

0

CON506

CO

N51

0

CO

N11

CO

N11

8C

ON

18

CO

N17

CO

N19

CO

N31

CO

N50

7

1

13

ON

1c 1a

16c

16a

1

1c1a

16c

16a

1c 1a

16c

16a

1c1a

16c

16a

31

1c1a

16c

16a

1c 1a

16c

16a

1

SEGM

ENT8 -S+

SEGM

ENT7 -S+

SEGM

ENT6 -S+

SEGM

ENT5 -S+

+S

-

SEGM

ENT4

+S

-

SEGM

ENT3

-S+

SEGM

ENT2

-S+

SEGM

ENT1

FOXBORO POWER B

POW

ER M

ODULE A

POW

ER M

ODULE B

FIELDBUS

FIELDBUS

FOX 24V

EXT 24VB-

+-

++

-+

-FO

X 24VEXT 24VA

ALARM

H1- H1S H1+

-1H+1H S1H

A2

A1

MODULEDIAGNOSTIC

DIAGNOSTIC SEGMENT

DIAGNOSTIC SEGMENT

FOXBORO POWER A

A

1 2 3

OFF

FBM SEG

1-4 1

FBM SEG

5-8 2FBM

SEG 1-4 2

FBM SEG

5-8 1

B

SCREEN/SHIELD

GROUND

CHASSISGROUND

1

1 CON26

CON27REDUNDANT FOUNDATION FIELDBUS POWER SYSTEM

F810A - CA

F809

F-PL

US

260

300

148

135 1155

145

145

5

F80x module top panels showing indicators

2

2

Country Authority Standard Certificate Approved for Ratings

– Fieldbus FOUNDATION™ FF-831PS001700 (F801) PS001900 (F802)

H1 Profile - 132 –

APPROVALS - for the latest certification information visit www.mtl-inst.com/support/certificates/