F13AdditionsI P

download F13AdditionsI P

of 3

Transcript of F13AdditionsI P

  • 7/27/2019 F13AdditionsI P

    1/3A.1

    ASHRAE HANDBOOK

    Additions and Corrections

    This report includes additional information, and technical errorsfound between June 15, 2010, and May 23, 2013, in the inch-

    pound (I-P) editions of the 2010, 2011, and 2012 ASHRAE Hand-book volumes. Occasional typographical errors and nonstandardsymbol labels will be corrected in future volumes. The most cur-rent list of Handbook additions and corrections is on the ASHRAEweb site (www.ashrae.org).

    The authors and editor encourage you to notify them if youfind other technical errors. Please send corrections to: HandbookEditor, ASHRAE, 1791 Tullie Circle NE, Atlanta, GA 30329, ore-mail [email protected].

    2010 Refrigeration

    Ch. 1. All existing references to Table 19 should be to Table 20. All

    existing references to Table 20 should be to Table 19.

    p. 10.4, Table 3. Replace the table with the following.

    p. 11.23, Table 2. Amend the table values as shown above right.

    p. 19.2, Eq. (4). Change two toxwo.

    p. 19.7, Eq. (10). Change to tto (to t)2.

    p. 20.10, Table 6. In the equation forQ3, change Tc to To.

    p. 50.4, Horsepower entry. The value for horsepower should be550 ft lbf/s

    2, not 500.

    2011 HVAC Applications(CD only) Table of Contents, p. 2. Replace the second instance ofBuilding Operations and Management with General Applica-tions.

    Contributors List. For Chapter 4, add Dennis Wessel, KarpinskiEngineering.

    p. 28.8, 1st col. Under U.S. Evolutionary Power Reactor (USEPR),delete (30 Pa).

    p. 35.4, end of 2nd para. It should be = for all conditions.

    p. 35.5, Eq. (17). The equation should beFsg= (1 cos )/2.

    p. 35.10, 2nd col., 3rd para. from bottom. The slope should be0.82 /0.69 = 1.19.

    p. 35.22, Example 7, Solution. The load collector ratio should useEq. (41).

    p. 35.23, 2nd col., last para. The average wind load on a tiltedroof should be 25 lb/ft2.

    p. 35.27, Symbols. Delete the second definition forAap.

    p. 36.9, Table 4. Replace the table with the one on p. A.3.

    p. 48.20, 2nd col. For frequency range #1, consult Table 13 forAf.In definitions for Eq. (10), refer to Table 12 fora .

    p. 48.45, Table 47. Deflection values for cooling towers should be

    Table 3 Cellular Glass Insulation Thickness for

    Indoor Design Conditions(90F Ambient Temperature, 80% Relative Humidity, 0.9 Emittance,

    0 mph Wind Velocity)(2010 Refrigeration, Chapter 10, p. 4)

    NominalPipe Size,

    in.

    Pipe Operating Temperature, F

    40 20 0 20 40 60 80 100

    0.50 1.0 1.0 1.5 1.5 2.0 2.0 2.0 2.50.75 1.0 1.5 1.5 2.0 2.0 2.0 2.5 2.51.00 1.0 1.5 1.5 2.0 2.0 2.0 2.5 2.51.50 1.0 1.5 1.5 2.0 2.5 2.5 3.0 3.0

    2.00 1.0 1.5 1.5 2.0 2.5 2.5 3.0 3.02.50 1.0 1.5 2.0 2.5 2.5 3.0 3.0 3.0

    3.00 1.0 1.5 2.0 2.5 2.5 3.0 3.0 3.04.00 1.0 1.5 2.0 2.5 2.5 3.0 3.0 3.55.00 1.5 1.5 2.0 2.5 2.5 3.0 3.0 3.56.00 1.5 2.0 2.0 2.5 3.0 3.0 3.5 3.58.00 1.5 2.0 2.0 2.5 3.0 3.0 3.5 3.5

    10.00 1.5 2.0 2.0 2.5 3.0 3.5 3.5 4.0

    12.00 1.5 2.0 2.0 2.5 3.0 3.5 3.5 4.014.00 1.5 2.0 2.5 3.0 3.0 3.5 4.0 4.016.00 1.5 2.0 2.5 3.0 3.5 3.5 4.0 4.518.00 1.5 2.0 2.5 3.0 3.5 3.5 4.0 4.520.00 1.5 2.0 2.5 3.0 3.5 3.5 4.0 4.524.00 1.5 2.0 2.5 3.0 3.5 4.0 4.0 4.5

    28.00 1.5 2.0 2.5 3.0 3.5 4.0 4.0 4.530.00 1.5 2.0 2.5 3.0 3.5 4.0 4.0 4.536.00 1.5 2.0 2.5 3.0 3.5 4.0 4.5 4.5

    Notes:1. Insulation thickness is chosen either to prevent or minimize condensation on outside

    jacket surface or to limit heat gain to 8 Btu/h ft2, whichever thickness is greater.2. All thicknesses are in inches.3. Values do not include safety or aging factor. Actual operating conditions may vary.

    Consult a design engineer for appropriate recommendation for your specific system.4. Data calculated using NAIMA 3E Plus program.

    Table 2 Values(2010 Refrigeration, Chapter 11, p. 23)

    Refrigerant f

    On the low side of a limited-charge cascade system:

    R-13, R-13B1, R-503 2.0 (0.163)

    R-14 2.5 (0.203)

    R-23, R-170, R-508A, R-508B, R-744, R-1150 1.0 (0.082)

    Other applications:

    R-11, R-32, R-113, R-123, R-142b, R-152a, R-290, R-600, R-600a, R-764

    1.0 (0.082)

    R-12, R-22, R-114, R-124, R-134a, R-401A, R-401B,R-401C, R-405A, R-406A, R-407C, R-407D, R-407E,R-409A, R-409B, R-411A, R-411B, R-411C, R-412A,R-414A, R-414B, R-500, R-1270

    (0.131)

    R-115, R-402A, R-403B, R-404A, R-407B, R-410A,R-410B, R-502, R-507A, R-509A 2.5 (0.203)

    R-143a, R-402B, R-403A, R-407A, R-408A, R-413A 2.0 (0.163)

    R-717 0.5 (0.041)

    R-718 0.2 (0.016)

    Equipment TypeSlab onGrade

    Floor Span

    Up to 20 ft 20 to 30 ft 30 to 40 ft

    Cooling Towers 0.25 3.5 3.5 3.5

    0.25 2.5 2.5 2.5

    0.25 0.75 0.75 1.5

    http://www.ashrae.org/mailto:[email protected]:[email protected]://www.ashrae.org/
  • 7/27/2019 F13AdditionsI P

    2/3

    A.2 20102012 ASHRAE Handbook Additions and Corrections

    p. 51.2, Eq. (10). Change Ta to Ta.

    p. 55.8, Eq. (16). The equation should be as follows:

    pp. 55.12-13, Eqs. (27), (28), (30), and (31). For all four equations,the denominators of the last two terms should be b anda, not 2b and2a. Also, for Eq. (31), change the first + sign to a sign.

    p. 60.9, Fig. 9. Replace the figure with the one above left.

    2012 HVAC Systems and Equipment

    p. 26.12, Example 2. Flow rate for ethylene glycol should be ingpm.

    p. 41.3, Fig. 3. Replace parts B and C of the graphic with the hori-zontal polymer tube shown above right.

    p. 44.8, Table 1. In both equations for flow and head, change theminuses to equals signs.

    Fig. 9 Typical Layout of UVGI Fixtures for Patient IsolationRoom

    (First et al. 1999)(2011 HVAC Applications, Ch. 60, p. 9)

    Fw ef f Tef f 2 Vef f

    2+=

    Fig. 3 Indirect Evaporative Cooling (IEC) Heat Exchanger(Courtesy Munters/Des Champs)

    (2012 HVAC Systems and Equipment, Ch. 41, p. 3.Replaces only parts B and C of Fig. 3.)

  • 7/27/2019 F13AdditionsI P

    3/3

    20102012 ASHRAE Handbook Additions and Corrections A.3

    Table 4 Energy Cost Percentiles from 2003 Commercial Survey(2011 HVAC Applications, Chapter 36, p. 9)

    Building Use

    Weighted Energy Cost Values, $/yr per gross square foot

    Percentiles

    Mean10th 25th 50th 75th 90th

    Administrative/professional office 0.50 0.82 1.36 1.92 2.58 1.55Bank/other financial 1.09 1.37 2.00 2.93 4.47 2.41Clinic/other outpatient health 0.61 0.87 1.53 2.03 4.13 1.74

    College/university 0.44 1.20 1.37 2.27 $3.01 1.82Convenience store 2.48 3.75 5.26 8.02 10.12 6.17Convenience store with gas station 1.99 2.75 4.61 6.83 8.74 5.12Distribution/shipping center 0.24 0.33 0.54 0.88 1.37 0.74Dormitory/fraternity/sorority 0.58 0.69 0.87 1.29 2.13 1.07Elementary/middle school 0.54 0.78 1.09 1.57 2.60 1.48Entertainment/culture 0.14 0.42 0.56 2.25 17.82 2.83Fast food 2.93 4.98 8.87 12.29 14.14 8.92Fire station/police station 0.10 0.53 1.15 1.73 2.83 1.31Government office 0.52 0.90 1.40 1.88 2.66 1.52Grocery store/food market 2.60 3.07 4.31 5.27 6.85 4.84High school 0.60 0.87 1.02 1.60 2.19 1.30Hospital/inpatient health 1.37 2.16 2.46 3.17 3.55 2.70Hotel 0.74 1.05 1.33 1.76 2.52 1.58Laboratory 1.34 3.09 4.52 7.64 10.81 5.18Library 0.78 1.06 1.37 2.41 2.92 1.68Medical office (diagnostic) 0.33 0.68 1.02 2.13 2.53 1.33

    Medical office (nondiagnostic) 0.58 0.79 1.06 1.44 1.92 1.15Mixed-use office 0.46 0.85 1.30 1.96 2.90 1.78Motel or inn 0.49 0.83 1.21 1.82 2.67 1.48

    Nonrefrigerated warehouse 0.06 0.17 0.38 0.80 1.43 0.61Nursing home/assisted living 0.73 1.12 1.52 2.47 2.99 1.78Other 0.15 0.51 0.93 1.81 2.41 1.35Other classroom education 0.21 0.50 0.92 1.26 2.14 0.96Other food sales 0.60 0.72 0.95 2.35 6.02 2.20Other food service 0.79 1.60 2.44 6.50 11.56 4.72Other lodging 0.55 0.56 1.13 1.71 2.76 1.30Other office 0.37 0.71 1.19 2.16 2.56 1.47Other public assembly 0.35 0.50 0.81 1.56 2.06 1.15Other public order and safety 1.00 1.13 1.56 3.38 4.74 2.06Other retail 0.97 1.19 1.59 2.98 5.60 2.43Other service 0.76 1.13 1.58 2.92 7.29 2.71Post office/postal center 0.32 0.78 1.09 1.44 1.89 1.07Preschool/daycare 0.46 0.77 1.09 1.57 2.63 1.30

    Recreation 0.30 0.53 0.87 1.38 2.33 1.14Refrigerated warehouse 0.38 0.38 2.21 4.00 5.25 2.45Religious worship 0.25 0.37 0.60 0.84 1.32 0.72Repair shop 0.20 0.35 0.61 1.15 1.47 0.75Restaurant/cafeteria 1.12 1.86 3.33 7.44 10.48 4.80Retail store 0.36 0.53 0.98 1.77 2.90 1.38Self-storage 0.05 0.10 0.20 0.27 0.52 0.23Social/meeting 0.19 0.33 0.66 1.02 2.27 0.89Vacant 0.04 0.08 0.27 0.70 1.19 0.48Vehicle dealership/showroom 0.67 0.89 1.37 2.97 3.98 2.07Vehicle service/repair shop 0.29 0.50 0.77 1.38 2.07 1.10Vehicle storage/maintenance 0.04 0.16 0.48 1.12 1.96 0.83

    SUM or Mean for sector 0.26 0.54 1.06 2.00 3.93 1.80

    Source: Calculated based on DOE/EIA preliminary 2003 CBECS microdata.