External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall...
Transcript of External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall...
![Page 1: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/1.jpg)
External Wall Insulation Training Guide
For perfect application every time
![Page 2: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/2.jpg)
2.
Introduction...This Guide supplements the training provided by Weber and is a quick reference to the key stages in the installation of webertherm External Wall Insulation systems.
For full technical details on all webertherm systems, please refer to Site Application Guides, and our website www.uk.weber.
Weber can provide technical and application support for all house types including a wide range of non-traditional and system built construction types.
Contents...Introduction and contents 2
Health and safety 3
Preparation... 4-6
Preparation... beads, sills and trims 7
Preparation... base bead fixing 8-9
Preparation... fixings 10-13
Preparation... boarding around windows 14
Preparation... preparation for rendering 15
Preparation... weather working 16-17
webertherm XM... basecoat 18-19
webertherm XM... rendering 20-21
webertherm XM... topcoat finishes 22
webertherm XM... RB brick effect 23
webertherm XP... 24
webertherm XP... scraped finish 25
webertherm XP... light ashlar details 26
webertherm XP... spray rough cast 27
webertherm XP... dry dash finish 28
webertherm XP... 29
Copyright Saint-Gobain Weber – not to be reproduced without permission.
![Page 3: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/3.jpg)
Health and Safety...
Health and safety is the number one priority at Weber.
This applies to our behaviours on construction sites, in our factories and offices, and on the road.
We also want to ensure that our customers are safe – so please follow the use of Personal Protective Equipment shown in this Training Guide at all times.
IF IT’S NOT SAFEIT’S NOT WEBER
![Page 4: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/4.jpg)
Preparation...Before you start make sure you know what standard is required...
...you know the size of the job and that the access is suitable.
Check that the materials on site are correct for specification and are stored correctly.
4.
![Page 5: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/5.jpg)
As soon as access is available drench all areas with
weber CL150. Hammer test suspect wall surface for spalling and
flaking. Hack-off to sound substrate. Brush down with
stiff bristle brush.
Defective areas under 0.1m2 can usually be ignored.
Make good areas to existing surface. Level using Weber Render repair specification.
5.
![Page 6: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/6.jpg)
Where possible remove unnecessary or
damaged features to simplify detailing.
Insert ventilators over existing unless otherwise instructed.
Cut out insulant to profile of specified ventilators and bed into opening
using weberend LAC or weberend LAC rapid.
At this stage builder work needs to be completed. Extend overflows verges etc.
Install new windows where applicable. Remove satellite dishes.
6.
![Page 7: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/7.jpg)
Preparation... beads, sills and trims
Fix verge trim if existing overhang is insufficient and verge is not to
be extended.
Fix new oversills or undersills as designed.
100mmminimum
7.
![Page 8: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/8.jpg)
Preparation... base bead fixing
Full system base beads are normally fixed with heel on
DPC Line.
Fix specified base bead at 700mm centres to line and
level using short drill and drive pins.
A string line will give better alignment.
Don’t over-drive the fixings.
For below DPC, Weber has specific detailing recommendations. Please refer to Site Packages for details.
DPC
8.
![Page 9: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/9.jpg)
Temporary fixing to support flashing.
Where new lead flashings are required, surface fix these behind base bead profile. No need to raggle into wall.
Box bead joining clip.
2mm gap with box beads fully inserted into joining clip.
Fix specified base bead to wall to line and level using
short drill and drive pins.
9.
![Page 10: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/10.jpg)
Preparation... fixingsIf the type of fixing is in doubt or the strength of substrate, carry out a pull-out test, minimum pull-out forge per fixing - 0.75 KN.
OI!Use a flippin
meter.
IDIOT!
10.
![Page 11: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/11.jpg)
Ask our advice on the best machine for the job – some are considerably better than
others.
Always use the depth gauge on the drill.
Remember to ream holes clear of dust
before pinning.
Don’t over-drill.
All insulation boards should be fixed with five fixings per board. Cut boards should be fully supported with fixings at sides and corners as appropriate.
Fixing types are contract-specific with thermal fixings being the most commonly required.
Non-standard substrates may require special fixings – if in doubt consult Weber for advice.
Don’t overdrive fixings.Don’t distort pin heads.Don’t drive pins squint.
Worn drill bits make pinning difficult.
Rate of wear depends on substrate and depth. Replace bits to maintain hole size.
Before contract starts, try different drill bit sizes with selected pin. Most practical drill bit size depends on substrate. 1-2mm makes a big differenceBut…Pull out requirement still applies.
Not recommended
11.
![Page 12: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/12.jpg)
For full boards, fixings should be 150mm from all board edges.
Starting from the corner, apply boards
broken bond to wall. Form lap bond at arris. Drill and pin according to board type and
Weber package.
Butt boards closely both horizontally and
vertically.
Fill gaps over 6mm between boards
using a fire resistant foam filler.
Maximum acceptable gap 6mm.
Note: Gap fillers are
last resort measures -
emergency only!
12.
![Page 13: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/13.jpg)
Movement or risband joints (existing). Cut insulation on line of joint after boarding.
Supplement fixings as required after
cutting.
Insert Insulation into reveal if specified. This may be
mechanically fixed or stuck and bedded with
adhesive mortar.
Refer to contract details for specified reveal boarding.
13.
Follow the expansion joints
Minimum 250mm cut
![Page 14: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/14.jpg)
Preparation... boarding around windows
Check board around cornerDon’t have board edges aligned with opening either horizontally or vertically.
14.
![Page 15: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/15.jpg)
Preparation... preparing for renderingBefore rendering starts, check boarding pattern and alignment, beads, fixing and trim.
Protect vulnerable surfaces especially sills and glass. Protect at ground level with hessian or polythene.
15.
![Page 16: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/16.jpg)
Preparation... weather workingAll Weber mortars are available factory-batched and dry-bagged. They are pre-mixed in a dry state and only need water, no other additions required.
All essential
ingredients
are in the bag.
Avoid rendering in hot weather or on sunny walls. Do not render in temperatures over 30°C. Too rapid dehydration will result in a weak powdery coat. Wet down undercoat thoroughly. Slowdown curing period by shading.
16.
![Page 17: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/17.jpg)
Don’t render in freezing weather. Temp must be 5°C and rising. Protect new render from frost. Don’t apply to frosted surfaces. Don’t use frozen material.
Don’t render in wet weather or if background is saturated, otherwise wash-off will ruin the coat. Lime bloom or staining will spoil the appearance. Bond will be weakened.
17.
![Page 18: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/18.jpg)
webertherm XM... basecoat
Lap meshcloth 100mm in
each direction.
Apply first pass of weberend LAC or
weberend LAC rapidonto insulation.
First pass should be 3mm thick.
Apply second pass of render when first pass has
taken up. Ensure mesh pattern is completely
obscured. Second pass should be
3mm thick.
Lay meshcloth into first pass
of render whilst still wet.
Allow first coat of weberend LAC to dry
for 36 hours, 24 hours if
weberend LAC rapid is being used, before next stage.18.
![Page 19: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/19.jpg)
Use meshcloth in the longest length practical.
Meshcloth is cut using scissors or a
stanley knife.
Meshcloth Apply supplementary reinforcements at all corners of openings using a 250mm square of Meshcloth applied diagonally.
19.
![Page 20: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/20.jpg)
webertherm XM... rendering
Apply adhesive mortar over meshcloth thick enough to obliterate meshcloth pattern.
If a primer and acrylic coat has been specified, sponge float the weberend LAC base coat.
20.
![Page 21: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/21.jpg)
If a further render coat has been specified (dash receiver, scraped top coat or brick effect finish) weberend LAC or weberend LAC rapid base coat should be comb scratched.
Because the insulation effectively prevents drying stresses being taken by the substrate (as in normal brick or block background) the scratch coat must be allowed to dry and shrink fully before subsequent coats are applied. Recommended minimum 36 hours. The low shrinkage characteristics of Weber renders minimise risk of cracking.
Note: 3-7 days curing for synthetic finishes.
21.
![Page 22: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/22.jpg)
webertherm XM... topcoat finishes
Ensure weber PR310 primer is fully dried. If applying a decorative finish, apply only to the depth of the aggregate in the product, e.g. 1.5mm.
Synthetic finish Dash top coat
Apply weberend PTC and once levelled, dashing aggregate can be applied. Ensure all areas are evenly covered.
22.
![Page 23: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/23.jpg)
webertherm XM... RB brick effectBrick effect render. Apply weberend RBB (render brick base coat) 7mm thick over fully cured weberend LAC or weberend LAC rapid. When taken up, apply 3mm of weberend RBF (render brick face coat). Texture of brick face can be achieved with a soft bristle brush whilst wet. When taken up, begin to cut back to mortar coat in pattern specified. Use spirit levels and straight edges for best effect.
Clean tools often with water.
23.
![Page 24: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/24.jpg)
Pump first pass of initial render coat
onto insulation blocks. First pass should be
6-7mm thick.
Lay meshcloth into first pass of render
whilst still wet.
Pump second pass of render when first pass has taken
up. Ensure mesh pattern is completely obscured. Second pass should be 8-9mm thick.
Level second pass with short trowel or straight edge.
24.
webertherm XP...
![Page 25: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/25.jpg)
webertherm XP... scraped finishBetween 5-16 hours after application, (depending on weather) scrape back to 12mm (remove 2-3mm) with scraper tool.
Use an ‘I’ section scrapper to identify and remove any high points in render.
Always keep scraper tool flat to render surface.
Use a regular, circular scraping motion with even pressure to ensure a consistent finish.
25.
![Page 26: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/26.jpg)
webertherm XP... light ashlar detailsScrape render back to 15mm. Cut ashlar 2-3mm deep.
Scrape back to leave a minimum of 15mm
Use a straight edge to guide ashlar tool on long straight cuts.
26.
![Page 27: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/27.jpg)
webertherm XP... spray rough castPump render to 6mm, lay in mesh, pump second application of render to 6mm, render pump rough cast.
Pump first pass 6mm thick.
Lay in meshcloth then pump second pass 6mm thick.
Adjust pump pressure and nozzle size to achieve desired rough cast effect.
27.
![Page 28: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/28.jpg)
webertherm XP... dry dash finishPump render to 6mm, lay in mesh, pump second application of render to 6mm, roughly level then dash at once.
Pump first pass 6mm thick.
Lay in meshcloth then pump second pass 6mm thick.
Rough level then dry dash at once.
28.
![Page 29: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/29.jpg)
For below DPC level. Weber produce an RBF
render for use with webertherm M1.
29.
webertherm XP...
![Page 30: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/30.jpg)
Following this guide can help you achieve the perfect finish. More information is
available from our website.www.uk.weber
30.
![Page 31: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/31.jpg)
Our other activities...
Technical Mortar Products Tile Fixing Products
Renders & Decorative Finishes Flooring Systems
![Page 32: External Wall Insulation Training Guide - Weber UK Cartoon Training Guide 2018_0.pdfExternal Wall Insulation systems. For full technical details on all webertherm systems, please refer](https://reader035.fdocuments.net/reader035/viewer/2022070100/60136625dddff569e90e8672/html5/thumbnails/32.jpg)
@SGWeberUK
Weber app
Use the QR code to download the Weber app
Rev 11/18
Saint-Gobain Weber Dickens House, Enterprise Way,
Maulden Road, Flitwick, Bedford, MK45 5BY
+44 (0) 8703 330070
www.uk.weber