Experimental study of CO2 huff-n-puff process for low-pressure reservoirs
Experimental Testing of s-CO2 Regenerator for Use as a ...
Transcript of Experimental Testing of s-CO2 Regenerator for Use as a ...
EXPERIMENTAL TESTING OF S-CO2 REGENERATOR FOR USE AS A REPLACEMENT TO HIGH COST PRINTED CIRCUIT RECUPERATORS FOR USE IN S-CO2 RECOMPRESSION
BRAYTON CYCLE
Jacob F Hinze University of Wisconsin – Madison
Madison, WI, USA
Gregory F Nellis University of Wisconsin – Madison
Madison, WI, USA
Mark H Anderson University of Wisconsin – Madison
Madison, WI, USA
ABSTRACT Supercritical Carbon Dioxide (sCO2) power cycles have
the potential to deliver high efficiency at low cost. However, in
order for s-CO2 cycle to reach high efficiency, highly effective
recuperators are needed. These recuperative heat exchangers
must transfer heat at a rate that is substantially larger than the
heat transfer to the cycle itself and can therefore represent up to
24% of the total power block cost in a recompression Brayton
cycle [1]. Lower cost regenerators are proposed as a cost saving
alternative to high cost printed circuit recuperators. A
regenerator is a heat exchanger that alternately has hot and cold
fluid passing through it. During the first half of its cycle the hot
gas is passed over a storage media bed (stainless steel balls,
screens, or similar fill material) where thermal energy is stored.
During the next half of the cycle, cold fluid is passed through in
the opposite direction, extracting the thermal energy from the
bed. By operating a cycle with two (or more) regenerators,
where one is always in a hot to cold (HTC) blow and the other
in a cold to hot blow (CTH), a quasi-steady state can be
achieved in the cycle to allow continuous operation. A model of
the regenerator was created and used in place of a recuperator
in a model of a 10MW power plant. The thermal effectiveness
of the regenerator cycle was slightly lower than the recuperator
cycle, however the regenerator cycle had a saving of about 9.3
percent in the Levelized Cost of Energy (LCoE). A scale model
of the regenerator is under construction which will verify the
performance of the regenerator model. INTRODUCTION Supercritical carbon dioxide (sCO2) power cycles are very
simply a closed Brayton cycle operating with CO2 as the
working fluid. The main advantage to this cycle is the increase
in thermal efficiency over a typical Rankine cycle as shown in
Figure 1.
FIGURE 1 CYCLE EFFICIENCY VS TURBINE INLET
TEMPERATURE FOR VARIOUS WORKING FLUIDS FROM [1]
It is clear from Figure 1 that the other cycles do not achieve the
same efficiencies as the sCO2 cycle. Supercritical and
superheated steam operate at higher efficiencies than the sCO2
at low temperatures; however, once the turbine inlet
temperature is above 550°C a sCO2 cycle is more efficient. It is
desirable to operate at these high temperatures if the materials
will allow it since the cycle efficiency increases with
temperature. The helium Brayton cycle also allows the cycle to
operate at high temperature, however with a lower efficiency as
Proceedings of the ASME 2016 10th International Conference on Energy Sustainability ES2016
June 26-30, 2016, Charlotte, North Carolina
ES2016-59615
1 Copyright © 2016 by ASME
compared to sCO2. Additionally, helium is much more
expensive than CO2, meaning the seals in the system must be
very good to prevent any loss of helium. The main reason for
the high efficiency associated with the sCO2 cycle is the large
density change that occurs near the critical point. Pumping
power on a per mass basis is roughly equal to the difference in
pressure multiplied by the specific volume of the fluid. For a
Rankine cycle where liquid water is being pumped the energy
needed to pump the water back into the boiler is very small,
usually under 5 percent of the total output from the turbine.
This is in sharp contrast of an air Brayton cycle where the
compressor power can consume almost half of the work output
from the turbine. The high density of CO2 when it is
compressed means that the energy consumed by the compressor
is reduced to about 30 percent of the turbine power, increasing
the efficiency of the cycle. This along with the reduced
corrosion issues of CO2 as compared to steam suggest that
sCO2 cycles may be used for power generation in the future.
sCO2 power cycles have already found a market as a waste
heat recovery engine. In particular Echogen has developed an 8
MW waste heat recovery engine that is the size of
approximately 2 standard shipping containers. It operates with
waste heat at a temperature of 532°C and has a thermal
efficiency of 24 percent [2]. SCO2 offers several advantages
over other heat recovery engines including high efficiency, a
non-toxic/inexpensive working fluid, and compact size.
Alternative heat recovery engines such as organic Rankine
cycles use expensive working fluids and have lower
efficiencies.
As sCO2 technology becomes more mature there will be
many more opportunities for its use. The DOE’s goal for
concentrated solar power is to operate with a turbine inlet
temperature in excess of 700C [3]. Figure 1 shows that steam is
not a viable option at this temperature, and Helium has a
significantly lower efficiency. This leaves sCO2 as the obvious
choice. The size reduction of sCO2 turbo equipment is also
significant, a sCO2 turbine with an equal work output to a
steam turbine will be approximately 1/10th of the size [4],
resulting in lower capital costs, and thus a lower cost of
electricity.
sCO2 Cycle Configurations
The performance and cost of a sCO2 cycle can vary
drastically depending on the configuration of the cycle. A
simple Super Critical Brayton Cycle (SCBC) operates with
only a compressor, turbine, primary heat exchanger, precooling
heat exchanger, and recuperator as shown in Figure 2 (A). This
cycle requires a larger recuperator and the efficiency of the
cycle is limited because of the mismatch in capacitance rates of
the high and low temperature streams in the recuperator. When
CO2 is near the critical point, the specific heat capacity of the
fluid increases greatly which causes a mismatch in the
capacitance rate of the fluids. The Recompression Brayton
cycle (RCBC) seeks to balance the recuperators by adding a
second compressor and recuperator as shown in Figure 2 (B).
(A)
(B)
Figure 2 (A) SIMPLE CLOSED BRAYTON CYCLE (SCBC) AND (B) RECOMPRESSION CLOSED BRAYTON CYCLE
(RCBC) FROM [5]
The recompressor takes warm fluid leaving the low pressure
side of the low temperature recuperator and compresses it to
high pressure and returns it to the cycle after the low
temperature recuperator. Thus the mass flow rate of the low
pressure stream will be higher than the high pressure stream,
balancing the recuperator since the heat capacity of the low
temperature, high pressure CO2 is higher than the high
temperature, low pressure CO2 in the low temperature
recuperator. This allows the cycle to achieve a higher thermal
efficiency. Additionally there is thermodynamic advantage to
using a RCBC, since the fluid exiting the recompressor is at a
higher temperature meaning less heat is needed to reach the
turbine inlet temperature. The combination of balancing the
recuperators and adding the second compressor mean the
RCBC can operate at higher efficiencies than a SCBC for the
same sized recuperator [6].
One of the main barriers to widespread adoption of sCO2
power cycles is that it is untested at large scale and may have a
high cost. The power block is made up of the compressors,
turbine, primary heat exchanger, condenser, and recuperators.
There is substantial uncertainty in the cost of the recuperators
and it is estimated that this heat exchanger will account for
about 24 percent of the total power block costs [5]. In order for
sCO2 cycles to reach high efficiencies, they require highly
effective recuperators, usually greater than 90 percent.
Currently the state of the art recuperators are printed circuit
heat exchangers made by etching a pattern into many thin
layers of stainless steel and then diffusion welding them into a
block. These heat exchangers are very compact, offer high
effectiveness and low pressure drop, but they are very
expensive to build and are characterized by literally miles of
2 Copyright © 2016 by ASME
seals that all must be hermetic. The recuperators are the second
most expensive component behind only the primary heat
exchanger, as a result they are a good candidate for cost
reduction [5].
Regenerator Operation
Instead of a recuperator, a regenerator has been proposed
as a replacement device to accomplish the internal heat transfer
required by the cycle for high efficiency. A regenerator operates
by alternatively flowing a hot and cold fluid over an energy
storage bed. During the hot to cold (HTC) blow, hot fluid is
passed over the cold bed, and the thermal energy is stored in the
bed. Next during the cold to hot (CTH) blow, cold fluid is
passed over the bed and heat transferred to the fluid resulting in
it leaving at an elevated temperature. If this cycle is repeated
many times, the bed eventually reaches a quasi-steady state.
Since each regenerator canister can only have hot or cold fluid
passing through at any instance of time, at least two regenerator
canisters are needed to have the regenerator replace a
recuperator.
Since there is no need to have a hermetic seal between the
high pressure and low pressure streams, the regenerator
construction can be much simpler than for a recuperator. A
regenerator would consist of a tube packed with a filling
material (for example stainless steel balls) with headers welded
on and connected to a manifold of valves. Since there is no
complicated fabrication needed, it is assumed that the majority
of the costs for a regenerator will be the materials. Additionally,
since the sphere size in the bed can be made very small, the
surface area to volume ratio of a regenerator is much higher
than for a recuperator. More surface area means the regenerator
can have a higher effectiveness which results in a higher cycle
efficiency.
In order for regenerators to replace recuperators, they need
to provide an advantage in one or more categories of cost,
maintenance, reliability, or lifetime so that the replacement of
recuperators with regenerators creates a reduction in the LCoE.
The LCoE takes into account all of the capital costs associated
with the power block and spreads them out evenly to the
electricity produced by the cycle using the method outlined in
[7]. The LCoE calculations for this analysis were done for a
power plant with a 20MW thermal heat input and a turbine inlet
temperature of 700°C. The constant heat input takes into
account the difference in thermal efficiencies associated with
using regenerators compared to recuperators. A high efficiency
results in more power generation and thus more energy to
spread the capital costs over. The costs for the power block and
recuperators were obtained from [5] and the regenerator cost
was estimated using the mass of material needed and the cost of
this material inflated for manufacturing. A model was created
based on a RCBC operating with a 700°C turbine inlet
temperature and at pressures of 25 and 8 MPa. The recuperators
were specified to have a effectiveness of 90 percent which is
the maximum due to the manufacturing process where some of
the headers have to be in a cross flow configuration which
reduces the effectiveness [8]. The effectiveness of the
regenerators is therefore set to 95 percent since they can be
operated in a true counter flow configuration. To take into
account the losses in converting the shaft energy to electrical
energy it was assumed that the motors and generator had an
efficiency of 92.2 percent.. The thermal efficiency of the cycle,
the cost of the recuperator or regenerator, and the resulting
LCoE are summarized in Table 1.
TABLE 1 EFFICIENCY, RECUPERATOR COSTS, AND LCoE FOR A RECUPERATOR AND REGENERATOR OPERATING
AT IDENTICAL CONDITIONS Thermal
Efficiency (%)
LCOE
($/kWh)
Recuperator/
regenerator
cost (k$)
Recuperators 40.1 0.02087 2250
Regenerators 38.1 0.01893 971
The cycle operating with a regenerator has a similar thermal
efficiency (slightly smaller due to the carryover effect) and a
9.3 percent reduction in LCoE due to the much lower cost of
the regenerator. This simple calculation of costs savings shows
that regenerators have the potential to reduce the costs of the
sCO2 power cycle.
REGENERATOR DESIGN While regenerators do not see widespread use in the power
industry currently, regenerators have been used successfully for
many years for HVAC and cryogenic applications. The design
of a regenerator for use in power cycle will modify models
already used in these industries. In [9] an effectiveness-NTU-
Cm method is defined for regenerators. This method is very
similar to the effectiveness-NTU method for heat exchangers,
but this model adds an additional parameter, the matrix capacity
ratio defined by equation (1).
0 min
b bm
m cC
P C (1)
where mb is the mass of the packed bed, cb is the specific heat
capacity of the bed, P0 is the switching period, and minC is the
minimum capacitance rate of the fluids passing through the
bed. The capacitance rate of each stream is defined by equation
(2).
,p avgC c m (2)
where cp,avg is the average specific heat capacity through the
regenerator of the stream and m is the mass flow of the fluid. It
is important to understand the effect that changing the matrix
capacity ratio has on the effectiveness of the regenerator. A high
matrix capacity ratio means that the bed can hold much more
energy than the fluid can impart, and temperature of the packed
bed will change very little during the cycle. In the extreme case
where the matric capacity ratio approaches infinite, the
regenerator will behave in exactly the same way as a
recuperator because, as in a recuperator, the bed temperature
will not change with time. As the matrix heat capacity is
reduced, the effectiveness of the regenerator also decreases.
This is because the temperature of the bed changes more
3 Copyright © 2016 by ASME
dramatically during each cycle as it absorbs and releases
energy. After the HTC blow, the temperature at the hot end of
the regenerator will be approximately equal to the temperature
of the hot fluid coming in. During the CTH blow, cold fluid
will start flowing through the bed in the opposite direction and
at the beginning the exit temperature will be very close to the
temperature of the hot fluid, however as the cycle continues the
temperature will decrease since the temperature of the bed on
the hot side is being reduced by the cold fluid passing over it.
The temperature of the cold fluid leaving the regenerator during
the HTC blow is shown in Figure 3.
FIGURE 3 TEMPERATURE OF FLUID LEACING HOT SIDE OF REGENERAOTR DURING THE HOT TO COLD BLOW
The temperature that really matters is the average fluid exit
temperature, and as the matrix capacity ratio gets lower, the exit
temperature will fall further. When averaged over the mass flow
out of the regenerator the average exit temperature will be
lower and as a result the effectiveness of the regenerator will be
lower.
The number of transfer units, NTU, also factors
heavily into the effectiveness of the regenerator. Much like a
recuperator, a higher NTU will result in higher effectiveness.
The NTU is function of the minimum capacitance rate and the
conductance defined by equation (3).
1
1 1
H s C s
UA
hc A hc A
(3)
where hcH is the average heat transfer coefficient for the HTC
blow, hcC is for the CTH blow, and As is the surface area that is
exposed to the fluid. NTU is defined according to equation (4).
min
UANTU
C (4)
It is much easier to have a large NTU in a regenerator as
compared to a recuperator because the specific surface area of a
bed of spheres is much higher than a printed circuit heat
exchanger and the passages are quite small leading to high heat
transfer coefficients. A correction needs to be added to the
matrix capacity ratio and NTU since the capacitance rate on
each side of the regenerator are not the same. The matrix
capacity ratio is adjusted according to equation (5).
,
2
1
R mm e
R
C CC
C
(5)
The NTU is corrected according to equation (6).
2
1
Re
R
C NTUNTU
C
(6)
In both equations CR is the capacitance ratio defined by
equation (7).
min
max
R
CC
C (7)
The model takes the corrected NTU and matrix capacity ratio
and determines the effectiveness [9].
The carryover mass is an unavoidable loss associated with
the operation of a regenerator that is not present with a
recuperator. The carryover mass is the high pressure fluid that
is stuck in the regenerator when it is switched from the CTH
blow to the HTC blow. Since the pressure difference is large
between the CTH and HTC blow, the specific volume of the
fluid differs greatly. This means the amount of mass that enters
the regenerator at high pressure and then returns to the
compressor without going through the turbine during the
switching process can be significant, up 25 percent of the total
mass that passes through the regenerator during the flow
processes depending on the conditions. This carryover mass is a
direct reduction to the cycle efficiency since the energy used to
compress it is not recovered in the turbine. Having a large
carryover mass will result in a lower thermal efficiency which
in turn reduces the LCoE; therefore, it is important to minimize
the carryover as much as possible. The carryover mass is
calculated by equation (8).
2
0(1 )( ( , ) ( , ))
4
L
c v H L
πm D e rho T P rho T P dL
(8)
where D is the inner diameter of the regenerator, ev is the void
volume fraction of the packed bed (0.37 for a bed of spheres),
and rho(T,PH) and rho(T,PL) is the density of the fluid at
location L in the canister at the point that the flow process is
complete for the high pressure and low pressure cases. As a
rough estimation it assumed that the temperature of the fluid in
the canister varies linearly from the hot inlet temperature to the
cold inlet temperature. Since there are two regenerator beds,
this mass of fluid is returned to the compressor twice every
period. This carryover mass is quantified as a mass flow rate
according to equation (9) and treated as a leakage in the system.
4 Copyright © 2016 by ASME
0
2 cc
mm
P (9)
The model also calculates a pressure drop based on the size
of the packed bed of spheres, and the average properties of the
fluid using a correlation for flow in a packed bed [10]. The
effectiveness-NTU-Cm model expects an input for the size of
the regenerator, however it is desirable to specify the
effectiveness of the regenerator and have the model determine
the size. To accomplish this the iterative equation solving in
EES is used [10]. The user specifies the effectiveness, sphere
size, switching period, and pressure drop, and the model
iteratively solves for the diameter, length, and carryover mass
for a regenerator meeting the desired operating parameters.
Design Goals
The goal for designing the regenerator is to have the largest
possible reduction in LCoE due to the use of regenerators rather
than recuperators. The main reduction in LCoE comes from the
reduced capital costs of the regenerators as compared to the
recuperators. To meet this goal the regenerator should be kept
as small as possible. There are two ways of having a high
effectiveness regenerator, the first is having a large matrix
capacity ratio, and the second is having a high NTU. Equation
(1) shows that to keep the same Cm for a given minimum
capacitance rate the mass of the bed must be increased if the
switching time is increased. Therefore, the switching time
needs to be kept as short as possible. For a set switching time
the only way to increase matrix capacity ratio is to increase the
mass of bed which will increase the cost. So instead of having a
large matrix capacity ratio the more economical method is to
have a large NTU. The NTU is based on the UA of the cycle
which can be increased by simply making the size of the
spheres smaller. This increases the UA two ways, first by
increasing the surface area for heat transfer, and second by
increasing the heat transfer coefficients by decreasing the
hydraulic diameter. The disadvantage of this is that the pressure
drop also increases with a smaller hydraulic diameter.
Limitations for Design Parameters
Several limits need to be placed on what is possible for
these parameters. The first is to constrain the pressure drop, since
increasing the pressure drop directly decreases the cycle
efficiency. Therefore, the maximum pressure drop was set to 1
percent of the absolute pressure of the cycle or 250 kPa. The
pressure drop is controlled by changing the aspect ratio
(length/diameter) of the regenerator, a small aspect ratio will
result in a smaller pressure drop. The switching time cannot be
too small since the valves need time to respond. The valve
response time was estimated to be 3 seconds to fully open and
close and therefore so the smallest allowable flow period is set
to 30 seconds. The spheres in the packed bed can only be made
so small, it was assumed that the smallest possible size sphere is
1mm. Stress analysis was conducted on standard pipe sizes to
determine what size pipe can be used to construct the
regenerator. The largest pipe size that would be able to tolerate
the temperature and pressure in the regenerator is a 24 inch
schedule 160 pipe. This is smaller than the diameter needed for
the regenerator so it is assumed that many tubes will be plumbed
in parallel to obtain the proper mass and pressure drop. A larger
diameter pipe allows for fewer pipes to be used, lowering the
total manufacturing costs of the regenerator. The material for the
outer tube is 316 and the packed bed is 304. For the optimized
designed conditions the dimensions of the high and low
temperature regenerators are listed in Table 2.
TABLE 2 REGENERATOR DIMENSIONS FOR 10MW POWER PLANT
Low Temp Regenerator
High Temp Regenerator
Length (m) 1.34 (52.8 in) 0.86 (33.9 in)
Reqd. Total Frontal Area (m2)
1.27 (13.7 ft2) 1.37 (14.7 ft2)
Regenerator Volume (m3)
1.70 (60.0 ft3) 1.17 (41.3 ft3)
Number of 24 inch Pipes Needed
14 16
Numerical Validation
In order to verify that the relatively simple effectiveness-
NTU-Cm model with empirical correction factors was providing
correct results, a MATLAB [11] numerical model was created
to check the solution based on the numerical one-dimensional
regenerator model outlined in [12]. This model is provided with
the dimensions of the regenerator, the temperature and mass
flow rate of the fluid entering the regenerator at each side, and
average heat transfer coefficient for each blow of the
regenerator. The model uses matrix decomposition to calculate
the temperature of the fluid throughout the cycle using the
average capacitance rate of the fluid. Then using successive
substitution it calculates the heat transfer rate based on the heat
transfer rate based on the actual properties at each node of the
regenerator. The numerical model predicts a heat transfer rate
that is approximately 5 percent larger for the low temperature
regenerator, and 2.5 percent larger for the high temperature
regenerator. The numerical model shows good agreement with
the effectiveness-NTU-Cm model and therefore provides
confidence in the results it predicts.
REGENERATOR IMPROVEMENTS The main area for improvement of the regenerator system
is decreasing the carryover mass. One of the simplest ways of
doing this is decreasing the void volume fraction of the
regenerators. The void volume fraction is the fraction of
volume in the regenerator that is occupied by the working fluid.
For a packed bed of spheres the normal void volume fraction is
0.37, if this reduced to 0.26 the theoretical limit for packed
spheres [13], the thermal efficiency is increased to 39.6 percent.
This could be accomplished by using a mix of large and small
diameter balls, where the small balls nest inside of the voids
between the large diameter balls.
Another way to decrease the carryover mass is by using the
high pressure gas in one regenerator to partially fill the low
pressure regenerator rather than allowing this mass to drain
directly back to the compressor. If a valve is introduced that
5 Copyright © 2016 by ASME
allowed the two regenerators to exchange mass with each other
before opening the valves to the system lines, the high pressure
fluid that would have returned directly to the compressor
instead comes to equilibrium with the low pressure fluid in the
other regenerator. Then, once the pressure has equalized, the
valves are opened, and normal operation is resumed. Operating
the valves in this fashion would reduce the carryover mass by a
factor of 2 and increase the thermal efficiency from 38.1
percent to 40.0 percent. This valve operation is illustrated in
Figure 4.
Regenerator
Regenerator
High Pressure
Inlet
Low Pressure
Exit
High Pressure
Exit
Low Pressure
Inlet
Bypass Valve
Regenerator
Regenerator
High Pressure
Inlet
Low Pressure
Exit
High Pressure
Exit
Low Pressure
Inlet
Bypass Valve
Regenerator
Regenerator
High Pressure
Inlet
Low Pressure
Exit
High Pressure
Exit
Low Pressure
Inlet
Bypass Valve
HP
HP
LP
LP
EP
EP
FIGURE 4 BYPASS VALVE OPERATION, HP = HIGH
PRESSURE, LP = LOW PRESSURE, EP = EQUILIBRIUM PRESSURE
As Figure 4 shows the bypass valves requires that all
valves to each regenerator be closed except for the bypass
valve. This means that there will be nowhere for the high
pressure fluid exiting the compressor to go. To eliminate this
problem, the regenerator is broken into multiple beds so that
continuous flow can be maintained. This means that while one
pair of beds are pressurizing/depressurizing the other beds are
still operating normally. This also serves a secondary purpose
of being able to operate more effectively at part load
conditions. If all of the beds were used under part load
conditions the regenerators would be much larger than needed
to obtain high effectiveness. That extra mass would result in
larger carryover relative to the mass flow through the system
reducing the thermal efficiency. Instead unneeded regenerators
can be removed and the cycle can always be operating with
essentially an optimally sized regenerator.
VALVE CHOICE AND TESTING
Almost as important as the regenerators themselves are the
valves the will direct the flow of the high temperature and
pressure CO2 into the proper regenerator. Not only is the
temperature in the valves very high (560ºC for a 700ºC
turbine), it is also not constant during each cycle. Figure 3
shows the temperature variation that the valve will experience
every 15 seconds as the cycle is running. Rapid temperature
changes cause thermal stresses in the valve body which can
result in leakage or premature breakage of the valves. Ideally a
valve would last for the lifecycle of the power plant (20 years)
but that may not be feasible in such a hostile environment. The
very shortest limit for the valve is one year which is how often
most plants shutdown for maintenance. The valves also need to
be able to open and close quickly so that regenerators can
operate correctly. The valve opening/closing time as well as
lifespan while determine what switching period can be used in
the cycle.
There are several types of valves that can withstand the
pressure and temperature experienced in the cycle. The first and
simplest option would be to use an open/closed globe valve.
Each end of the regenerator would have two valves, one that
goes to the high pressure side of the loop, and the other to the
low pressure side, as shown in Figure 4. On the CTH blow, the
valves on each end of the regenerator connected to the high
pressure side of the system would open up, and the high
pressure fluid exiting from the compressor would remove heat
from the bed, in the next half of the cycle the regenerator would
be connected to the low pressure side of the cycle and heat
would instead be stored in the bed. The main disadvantage of
this option is the number of valves needed, even in the simplest
configuration with two bundles of regenerators, 8 valves are
needed, and if the regenerator is broken into smaller bundles
then 4 valves are needed for each bundle.
The next simplest valve would be to use a 3-way valve.
Instead of needing two valves at each end of the regenerator
only one valve is needed since the same valve can connect to
both the high pressure and low pressure connections. The valve
is switched from one connection to the other by rotating the
valve body. This valve would operate in the same way to the
globe valve and would cut the number of valves and actuators
needed in half.
The most complicated valve would be a rotary ball valve.
This valve would have a central mandrel which rotates and
directs flow into ports cut into the body of the valve. Each
regenerator bundle would have its own port and each rotation
would alternatively connect high the and low pressures flows to
the regenerator bundle. Depending on the size of the valve,
many different regenerator bundles could be connected to the
same valve. This means that for a 10MW plant only four valves
6 Copyright © 2016 by ASME
are needed. Of course the issues with sealing, wear, and
maintenance are much greater for rotary valves than for the
other two types because of its complexity.
Choosing the right valve depends on the lifetime costs of
the valve systems. Information is being gathered in
collaboration with a major valve manufacturer in order to
compare the capital and maintenance costs for each type of
valve. The valve system with the lowest overall costs while
maintaining an acceptable level of reliability will be chosen for
use.
SCALE EXPERIMENTAL TESTING To validate the effectiveness-NTU-Cm model and
MATLAB numerical model, a scaled regenerator will be tested
at the same temperature expected in the full scale plant but with
a heat transfer rate of 10kW. However, for the initial test the
pressure will be reduced to 16 MPa due to the limits of the
available compressor. In addition to verifying the model it will
also provide an opportunity to test more practical
considerations of a regenerator system such as the valves,
control scheme, construction, and reliability. The performance
of the small scale system will determine the validity of the
model, the feasibility of using regenerators for power
production, and determine where to focus further research
efforts. The test regenerator will be constructed so that it
operates at the same temperature, pressure, and effectiveness as
the high temperature regenerator in the 10MW plant since this
is the more extreme environment.
To ensure that the results from the 10kW test can be scaled
up to the regenerators for the 10MW power plant, there are two
loss mechanisms that need to be matched from the large
regenerator to the test regenerator. The first is energy storage in
the wall of the regenerator. A simple one dimensional transient
model of the wall of the regenerator was constructed to
determine the amount of energy that would be stored in the wall
every cycle. For the 10MW high temperature regenerator the
amount of energy stored in the wall compared to the energy
stored in the bed was small, under one percent. The energy
stored in the wall doesn’t necessarily hurt the performance of
the regenerator since it just act as an extension of the packed
bed. The second more important inefficiency is axial
conduction along the wall of the regenerator. Axial conduction
takes high temperature heat and transfers it to the low
temperature fluid, this means more energy is leaving the
regenerator on the HTC blow reducing the effectiveness of the
regenerator. As a result it is much more important to match the
axial conduction from the 10MW regenerator to the 10kW
regenerator. The temperature difference between the hot and
cold ends is the same for both the full and subscale cases;
therefore, the amount of conduction will depend on the
resistance to conduction through the wall of the regenerator. As
schedule 160 pipe is scaled down to smaller diameter, the ratio
of internal area to wall area gets smaller. So, per unit length
there is less area for the bed and more area for conduction. The
aspect ratio of the 10MW high temperature regenerator is very
small, if this is scaled down to the 10kW test regenerator the
axial conduction is quite high. Therefore, the aspect ratio itself
is made much higher in the 10kW device. In order to have a fair
comparison of the axial conduction, the percentage of heat
conducted axially is compared to the total ineffectiveness of the
regenerator, as shown in equation (10).
max
100%axialaxial
act
QPer
Q Q
(10)
where Qmax is the maximum amount of heat transfer the
regenerator could have, Qact is the actual heat transfer of the
regenerator, and Qaxial is the heat conducted axially down the
wall of the pipe. The axial conduction was calculated using the
resistance of the pipe wall as shown in equation (11).
,( )
c pipe
axial hot cold
pipe
k AQ T T
L (11)
For the high temperature regenerator of the 10MW power
plant this was calculated to be only one percent of the total
ineffectiveness. However if the same aspect ratio of about 1
was used for the 10kW regenerator, the axial conduction would
be approximately 15 to 20 percent of the ineffectiveness. In
order to minimize the conduction the design for the regenerator
was stretched to have an aspect ratio of about 9. The axial
conduction percentage is about 2 percent of the ineffectiveness
in the regenerator which is very small just like its 10MW
counterpart.
Currently the compressor in the experimental test facility is
only rated to 16 MPa, so instead of schedule 160 pipe, schedule
80 pipe can be used which also helps reduce the energy stored
in the wall and axial conduction. The specifications for the test
regenerator are listed in Table 3.
TABLE 3 DIMESIONS OF TEST REGENERATOR
Effectiveness 0.95
Switching Time (s) 60
Length (cm) 45.1 (17.7 in)
Diameter (cm) 4.93 (1.94 in)
Wall thickness (mm) 5.5 (0.216 in)
Sphere size (mm) 3 (0.125 in)
Wall Storage Percent 18
Axial Conduction Percent
2.1
The switching time has also been increased to 60
seconds out of concern for the large temperature change that the
fittings have to endure. By increasing the cycle time the
temperature transients are reduced which should increase the
lifetime of the system components.
Using the design in Table 3 a set of regenerators has
been constructed for testing. One of the most important factors
determining how well the regenerator will operate is the mass
of the packed bed material. It is important therefore to have the
tightest packing possible to closely march the model. Packing
was accomplished by incrementally adding the stainless steel
balls to the tube and vibrating them into place. At three points
in each regenerator a thermocouple was inserted into the
7 Copyright © 2016 by ASME
packed bed through a wall of the pipe. This allows for in-situ
measurement of the packed bed temperature which will help
determine the accuracy of the model. After the regenerator was
filled, the actual mass used to fill was compared to the
theoretical mass calculated from the model, that packing
percentage with very good, about 98 percent for both
regenerators.
The spheres are held in place by stainless steel screens
welded onto the end of the pipe. This was accomplished by
clamping the screen in between the pipe and the end cap, and
welding the endcap into place. When the regenerator was filled
to the top with the balls, the other screen was placed on top of
the pipe and covered with the end cap. The end cap was then
welded into place taking care to not melt the screen. On each
end of the regenerator there will be two thermocouples
measuring the temperature, and one pressure tap, which will
allow measurement of both the absolute pressure at the inlet of
the regenerator and the differential pressure across the
regenerator. The constructed regenerator is shown in Figure 5.
FIGURE 5 CONSTRUCTED REGENERATORS FOR 10kW
TEST FACILITY
EXPERIMENTAL TEST FACILITY In addition to pressure and temperature measurements in
the regenerator, the mass flow rate at the cold end of each
regenerator will be measured using an orifice flow meter. The
pressure drop over the orifice will be calibrated throughout the
expected range of operating temperature and pressures using a
Coriolis flow meter. It is necessary to measure the mass flow
near the regenerator to get an accurate measurement of the
mass flow rate of the fluid entering the regenerator. If mass
flow meter is located far away from the regenerator the peaks
and troughs of flow will be eliminated by the buffer volumes
and it will be difficult to determine the actual mass flow rate
experienced by the regenerator as a function of time. The
Coriolis flow meters are not able to withstand the high pressure
and temperatures that the regenerator will experience, so they
must be located before and after the compressor to measure the
mass flow rate through the compressor. The cycle diagram is
shown in Figure 6.
The compressor available is a hydraulically driven CO2
compressor capable of providing CO2 at 16 MPa. In order to
operate at 25 MPa some modifications will eventually be
needed. The compressor will need to be changed to have a
smaller bore so it can reach a high pressure, or an additional
pump will be needed to boast the pressure. Initial testing will
occur at 16 MPa since the properties of sCO2 do not change
much between 16 MPa and 25 MPa so if the model matches the
experimental results at 16 MPa, it should also work at 25 MPa.
The temperatures at states 2 and 4 are controlled using the
preheater and main heater respectively. The temperature at the
inlet to the compressor is controlled by the water flow rate used
in the compressor. The pressure differential and mass flow rate
through the system will be controlled using the bypass valve
and expansion valves. The system will measure the temperature
at states 3 and 5. Along with flow rate measurements these
temperatures can be used to calculate the effectiveness of the
regenerator. Not shown on the diagram are the pressure
differential across the regenerator which will be used to verify
the analytical model.
CONCLUSIONS The simple effectiveness-NTU-Cm model indicated
that a regenerator optimized to reduce LCoE would
have a Cm near one, a high NTU, and a short switching
time
More sophisticated manufacturing and operating
techinques can increase the effectiveness of
regenerators and provide an even larger savings to
LCoE
FIGURE 6 PROCESS DIAGRAM OF EXPERIMENTAL TEST FACILITY
8 Copyright © 2016 by ASME
The valves needed to control this system pose a
significant challenge, however valves are available
that offer long life at high temperature which will need
to be verified through experimental testing
The 10kW test facility will allow verification of the
regenerator model and provide information about the
practical aspects of operating a high temperature
regenerator
sCO2 power cycles has the potential to provide
electricity at much greater efficiency than current Rankine
cycle technologies due its ability to operate at much high
temperatures. However the high degree of recuperation
necessary means that the printed circuit heat exchangers
necessary are very costly [5]. An initial analysis conducted
compared the costs of a regenerator to a printed circuit heat
exchanger and found that the regenerator would likely cost
half as much as a recuperator. The cost reduction resulted
in a 9.3 percent reduction in LCoE. Regenerators offer the
opportunity to build and operate high temperature sCO2
cycles at a significantly reduced cost compared to a
recuperated RCBC.
NOMENCLATURE Ac,pipe = Cross sectional area for conduction in pipe
As = Surface area of packed bed
C = Capacity rate
cb = Specific heat capacity of packed bed
Cm = Matrix capacity ratio
cm,e = Equivalent matrix capacity ratio
maxC = Maximum capacity rate
minC = Minimum capacity rate
cp,avg = Averages specific heat capacity
CR = Capacitance ratio
CTH = Cold to Hot
D = Diameter of regenerator
ev = Void volume fraction
hcC = Heat transfer coefficient on cold side of regenerator
hcH = Heat transfer coefficient on hot side of regenerator
HTC = Hot to Cold
LCoE = Levelized Cost of Electricity
Lpipe = Length of regenerator pipe
k = Conductivity of shell material
NTU = Number of Transfer Units
NTUe = Equivalent Number of Transfer Units
m = Mass flow rate
mb = Mass of packed bed
mc = Carryover mass
mc = Carryover mass flow rate
P0 = Switching period
Peraxial = Percentage of axial conduction
PH = High pressure in regenerator
PL = Low pressure in regenerator
RCBC = Recompression Brayton cycle
SCBC = Supercritical carbon dioxide Brayton cycle
Qact = Actual heat transfer in regenerator
Qaxial = Axial conduction in regenerator shell
Qmax = Maximum possible heat transfer in regenerator
Tcold = Low temperature of regenerator
Thot = High temperature of regenerator
UA = Conductance
ACKNOWLEDGMENTS This material is based upon work supported by the U.S.
Department of Energy under Award Number DE-EE0007120.
This report was prepared as an account of work sponsored
by an agency of the United States Government. Neither the
United States Government nor any agency thereof, nor any of
their employees, makes any warranty, express or implied, or
assumes any legal liability or responsibility for the accuracy,
completeness, or usefulness of any information, apparatus,
product, or process disclosed, or represents that its use would
not infringe privately owned rights. Reference herein to any
specific commercial product, process, or service by trade name,
trademark, manufacturer, or otherwise does not necessarily
constitute or imply its endorsement, recommendation, or
favoring by the United States Government or any agency
thereof. The views and opinions of authors expressed herein do
not necessarily state or reflect those of the United States
Government or any agency thereof
REFERENCES [1] M. J. Driscoll, “Supercritical CO 2 Plant Cost
Assessment,” 2004.
[2] Echogen, “EPS100 Heat Recovery Solution,” 2015.
[Online]. Available: http://www.echogen.com/our-
solution/product-series/eps100/.
[3] DOE and EERE, “Concentrating Solar Power:
Advanced Projects Offering Low LCOE Opportunities,”
2014.
[4] M. Persichilli, A. Kacludis, E. Zdankiewicz, and T. Held,
“Supercritical CO 2 Power Cycle Developments and
Commercialization: Why sCO 2 can Displace Steam Ste
am,” Power-Gen India Cent. Asia, pp. 1–15, 2012.
[5] C. K. Ho, M. Carlson, P. Garg, and P. Kumar, “Cost and
Performance Tradeoffs of Alternative Solar-Driven S-
CO2 Brayton Cycle Configurations,” 2015.
[6] J. J. Dyreby, “Modeling the Supercritical Carbon
Dioxide Brayton Cycle with Recompression,” 2014.
[7] W. Short, D. J. Packey, and T. Holt, “A Manual for the
Economic Evaluation of Energy Efficiency and
Renewable Energy Technologies,” 1995.
[8] T. Held, “Performance & cost targets for sCO 2 heat
exchangers,” in NETL-EPRI Workshop on Heat
Exchangers for Supercritical CO2 Power Cycles, 2015.
[9] R. Barron and G. Nellis, Cryogenic Heat Transfer, 2nd
ed. Taylor and Francis, 2016.
[10] F-Chart, “EES Engineering Equation Solver.” 2015.
[11] MathWorks, “Matlab2015a.” 2015.
[12] G. Nellis and S. A. Klein, Heat Transfer. New York:
Cambridge University Press, 2009.
[13] W. Zhang, K. E. Thompson, A. H. Reed, and L. Beenken,
“Relationship between packing structure and porosity in
fixed beds of equilatedal cylidrical particles,” Chem.
Eng. Sci., vol. 61, pp. 8060–8074, 2006.
9 Copyright © 2016 by ASME