EXISTING SITE PLAN - Prime Construction Grouppressure test newly constructed 30-inch plant effluent...
Transcript of EXISTING SITE PLAN - Prime Construction Grouppressure test newly constructed 30-inch plant effluent...
![Page 1: EXISTING SITE PLAN - Prime Construction Grouppressure test newly constructed 30-inch plant effluent pipe. 8. dewater, shore and excavate pits as required to connect new 30-inch plant](https://reader033.fdocuments.net/reader033/viewer/2022041717/5e4c43e0e54ff74b8d1664fe/html5/thumbnails/1.jpg)
IF THIS BAR DOES NOTMEASURE 1" THEN DRAWINGIS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECTENGINEER: DO NOT USE FOR
CONSTRUCTION
HAZEN AND SAWYER919 LAKE BALDWIN LANE, SUTIE A
ORLANDO, FLORIDA 32814CERTIFICATE OF AUTHORIZATION No. 2771
NORTHWEST WATER RECLAMATION FACILITYREUSE WATER STORAGE IMPROVEMENTS
REV ISSUED FOR DATE BY
ORANGE COUNTYFLORIDA
0 1"1/2"
44014-001
1CONTRACT NO.:
HAZEN NO.:
DATE: APRIL 2017
DRAWINGNUMBER:
R. ANDERSON
ROBERT K. ANDERSON, PE No. 471291 BID SET 04/2017 RKA
RKA
ESM
C01
CIVILEXISTING SITE PLANCIK
EXISTING SITE PLAN1"=30'
EXISTING2.0 MG GROUNDSTORAGE TANK
EXISTINGCLARIFIER
EXISTING SOILCEMENT ROADWAY
EXISTING SOILCEMENT ROADWAY
![Page 2: EXISTING SITE PLAN - Prime Construction Grouppressure test newly constructed 30-inch plant effluent pipe. 8. dewater, shore and excavate pits as required to connect new 30-inch plant](https://reader033.fdocuments.net/reader033/viewer/2022041717/5e4c43e0e54ff74b8d1664fe/html5/thumbnails/2.jpg)
NOTES:1. THE CONTRACTOR SHALL CONTACT THE POWER
COMPANY TO ARRANGE FOR TEMPORARY ELECTRICPOWER FOR FIELD TRAILERS AND OTHER USES.THE CONTRACTOR SHALL PLAN TO GETTEMPORARY ELECTRIC POWER FROM THEFURTHEST POINT AT McCORMICK ROAD.
IF THIS BAR DOES NOTMEASURE 1" THEN DRAWINGIS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECTENGINEER: DO NOT USE FOR
CONSTRUCTION
HAZEN AND SAWYER919 LAKE BALDWIN LANE, SUTIE A
ORLANDO, FLORIDA 32814CERTIFICATE OF AUTHORIZATION No. 2771
NORTHWEST WATER RECLAMATION FACILITYREUSE WATER STORAGE IMPROVEMENTS
REV ISSUED FOR DATE BY
ORANGE COUNTYFLORIDA
0 1"1/2"
44014-001
1CONTRACT NO.:
HAZEN NO.:
DATE: APRIL 2017
DRAWINGNUMBER:
R. ANDERSON
ROBERT K. ANDERSON, PE No. 471291 BID SET 04/2017 RKA
RKA
ESM
C02
CIVILPROPOSED SITE AND
STAGING PLANCIK
PROPOSED SITE PLAN1"=30'
RECIRCULATIONPUMP STATION
EXISTING 2.0 MGGROUND
STORAGE TANK 3.0 MG GROUNDSTORAGE TANK
N=1561238.26E=487732.50
STAGING AREA
N=1561166.02E=487568.27 N=1561188.03
E=487594.27
FIELDOFFICES
![Page 3: EXISTING SITE PLAN - Prime Construction Grouppressure test newly constructed 30-inch plant effluent pipe. 8. dewater, shore and excavate pits as required to connect new 30-inch plant](https://reader033.fdocuments.net/reader033/viewer/2022041717/5e4c43e0e54ff74b8d1664fe/html5/thumbnails/3.jpg)
NOTES:SEQUENCE OF CONSTRUCTION
1. COORDINATE SEQUENCE OF CONSTRUCTION FOR PIPE TIE-INS WITH THE COUNTY AT LEAST7 DAYS IN ADVANCE OF SCHEDULED DATE FOR TIE-INS.
2. FIELD LOCATE UNDERGROUND UTILITIES.
3. RELOCATE SITE ELECTRICAL CABLES AND PULLBOXES IN ADVANCE OF 30-INCH PIPECONSTRUCTION - REFER TO DWG E-03.
4. CONSTRUCT NEW 30-INCH PLANT EFFLUENT PIPE TO WITHIN ONE PIPE LENGTH OF TIE-INLOCATIONS AT EACH END OF NEW 30-INCH PLANT EFFLUENT PIPE.
5. FIELD VERIFY EXISTING 30 INCH PLANT EFFLUENT PIPE ELEVATIONS AT PROPOSED TIE-INLOCATIONS. ESTIMATED CENTERLINE ELEVATIONS ARE:
NORTH TIE-IN 106.67 FT.SOUTH TIE-IN 116.67 FT.
6. MAINTAIN CENTERLINE ELEVATION AT 106.67' FOR ALL SEGMENTS OF 30 INCH PLANTEFFLUENT PIPELINE WITHIN 25 FEET OF THE PROPOSED 3.0 MG GROUND STORAGE TANK TOFACILITATE TANK CONSTRUCTION.
7. PRESSURE TEST NEWLY CONSTRUCTED 30-INCH PLANT EFFLUENT PIPE.
8. DEWATER, SHORE AND EXCAVATE PITS AS REQUIRED TO CONNECT NEW 30-INCH PLANTEFFLUENT PIPE TO EXISTING 30-INCH PLANT EFFLUENT PIPE (TYPICAL EACH END OF NEW30-INCH PLANT EFFLUENT PIPE).
9. INSTALL TEMPORARY PUMPS AND PIPING TO CONVEY PLANT EFFLUENT FROM EXISTINGPIPING AFTER THE PIPE HAS BEEN CUT. TEMPORARY PIPING SHALL CONVEY PIPE DRAINWATER TO LOCATIONS DESIGNATED ON THE DRAWINGS. INSTALL EROSION ANDSEDIMENT CONTROLS AT TEMPORARY PIPE DISCHARGE LOCATIONS.
10. CUT EXISTING 30-INCH PLANT EFFLUENT PIPE AND ALLOW WATER TO DRAIN FROM THEPIPE. PUMP DRAIN WATER TO LOCATION(S) DESIGNATED ON THE DRAWINGS.
11. TIE-IN NEW 30-INCH PLANT EFFLUENT PIPE TO EXISTING 30-INCH PLANT EFFLUENT PIPEUSING RESTRAINED PIPE COUPLINGS AND FITTINGS AS SHOWN ON THE DRAWINGS. LEAVETIE-INS EXPOSED UNTIL NEW 30-INCH PLANT EFFLUENT PIPE HAS BEEN PLACED BACK INTOSERVICE AND THERE ARE NO VISIBLE LEAKS FOR AT LEAST 2 FULL DAYS OF PLANTEFFLUENT PIPE SERVICE. DO NOT REMOVE TEMPORARY PUMPS OR PIPING UNTIL THE NEW30-INCH PLANT EFFLUENT PIPE HAS BEEN DEEMED TO BE LEAK-FREE BY THE COUNTY'SON-SITE REPRESENTATIVE.
IF THIS BAR DOES NOTMEASURE 1" THEN DRAWINGIS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECTENGINEER: DO NOT USE FOR
CONSTRUCTION
HAZEN AND SAWYER919 LAKE BALDWIN LANE, SUTIE A
ORLANDO, FLORIDA 32814CERTIFICATE OF AUTHORIZATION No. 2771
NORTHWEST WATER RECLAMATION FACILITYREUSE WATER STORAGE IMPROVEMENTS
REV ISSUED FOR DATE BY
ORANGE COUNTYFLORIDA
0 1"1/2"
44014-001
1CONTRACT NO.:
HAZEN NO.:
DATE: APRIL 2017
DRAWINGNUMBER:
R. ANDERSON
ROBERT K. ANDERSON, PE No. 471291 BID SET 04/2017 RKA
RKA
ESM
C03
CIVILPROPOSED 30 INCH RW RELOCATION,
AND SOIL BORING LOCATIONSCIK
PLAN1"=30'
2.0 MG GROUNDSTORAGE TANK
DEMOLISH PORTIONOF EXISTING 30"RECLAIMED WATER MAIN
ENLARGED PLAN1"=10'
SEE ENLARGED PLAN,TYP BOTH ENDS OF TIE IN
30" DIP RW
30" 45° BENDCL EL = 110.67'
30" 45° BEND
30" 22.5° BENDCL EL = 106.67'
30" 22.5° BENDCL EL = 106.67'
30" 22.5° BEND
HARNESSED FLEXIBLE COUPLING
4M09
HARNESSED FLEXIBLE COUPLING
4M09
HARNESSEDFLEXIBLE COUPLING
4M09
SEE NOTE 5
SEE NOTE 6
PUMP DRAIN WATER FROM PIPELINE RELOCATION ACTIVITIES TOEXISTING STORMWATER INLET STRUCTURE. OUTLET PIPE FROM THESTRUCTURE IS A 30-INCH STORM SEWER PIPE.
![Page 4: EXISTING SITE PLAN - Prime Construction Grouppressure test newly constructed 30-inch plant effluent pipe. 8. dewater, shore and excavate pits as required to connect new 30-inch plant](https://reader033.fdocuments.net/reader033/viewer/2022041717/5e4c43e0e54ff74b8d1664fe/html5/thumbnails/4.jpg)
113
114
133
132
130
128
126
131
129
127
125
123121
119
117
115
112.50
111.50
121
120
119118
117112 115
126
126
124123
122
125
127
111
111
111
111
112
113
111
110
112 11
5
110
119
121
123
115
125
NOTES:1. ALL DISTURBED AREAS SHALL BE SODDED IN
ACCORDANCE WITH SPECIFICATION SECTION02120 SODDING.
2. PREPARE EXISTING SOIL CEMENT ROAD ANDOVERLAY WITH ASPHALT CEMENT PAVEMENT INACCORDANCE WITH SPECIFICATION SECTION02513.
IF THIS BAR DOES NOTMEASURE 1" THEN DRAWINGIS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECTENGINEER: DO NOT USE FOR
CONSTRUCTION
HAZEN AND SAWYER919 LAKE BALDWIN LANE, SUTIE A
ORLANDO, FLORIDA 32814CERTIFICATE OF AUTHORIZATION No. 2771
NORTHWEST WATER RECLAMATION FACILITYREUSE WATER STORAGE IMPROVEMENTS
REV ISSUED FOR DATE BY
ORANGE COUNTYFLORIDA
0 1"1/2"
44014-001
1CONTRACT NO.:
HAZEN NO.:
DATE: APRIL 2017
DRAWINGNUMBER:
R. ANDERSON
ROBERT K. ANDERSON, PE No. 471291 BID SET 04/2017 RKA
RKA
ESM
C04
CIVILPAVING, GRADING AND
DRAINAGE PLANCIK
PLAN1"=20'
EXISTING2.0 MG GROUNDSTORAGE TANK
3.0 MG GROUNDSTORAGE TANK
SOIL-CEMENT BASE WITH ASPHALTCEMENT PAVEMENT OVERLAY
DRIVEWAYN=1561166.02E=487568.27
DRIVEWAYN=1561166.02E=487594.27
12'
MAX 4:1 SLOPE
MAX 4:1 SLOPE
MAX 4:1 SLOPE
MAX 4:1 SLOPE
TERMINATE NEW ASPHALT CEMENTPAVEMENT INTO EXISTINGSOIL-CEMENT ROADWAY.N=1561122.03E=487463.26
DRIVEWAYN=1561142.02E=487594.27
CONTINUED ON PLAN - ROADWAY NORTH ON THIS SHEET
PLAN - ROADWAY NORTH1"=20'
SEE NOTE 2
8C07
TERMINATE NEW ASPHALT CEMENTPAVEMENT INTO EXISTINGSOIL-CEMENT ROADWAY.N=1561122.03E=487463.26
8C07
![Page 5: EXISTING SITE PLAN - Prime Construction Grouppressure test newly constructed 30-inch plant effluent pipe. 8. dewater, shore and excavate pits as required to connect new 30-inch plant](https://reader033.fdocuments.net/reader033/viewer/2022041717/5e4c43e0e54ff74b8d1664fe/html5/thumbnails/5.jpg)
NOTES:1. SEE SPECIFICATION SECTION 15390 FOR PIPE
SCHEDULE.
2. SOD ALL DISTURBED AREAS IN ACCORDANCEWITH SPECIFICATION SECTION 02120 SODDING.
3. FILED LOCATE EXISTING UTILITIES INCLUDINGELECTRICAL DUCTBANKS IN VICINITY WHERE 2CLS CROSSES THE PLANT ROADWAY.
IF THIS BAR DOES NOTMEASURE 1" THEN DRAWINGIS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECTENGINEER: DO NOT USE FOR
CONSTRUCTION
HAZEN AND SAWYER919 LAKE BALDWIN LANE, SUTIE A
ORLANDO, FLORIDA 32814CERTIFICATE OF AUTHORIZATION No. 2771
NORTHWEST WATER RECLAMATION FACILITYREUSE WATER STORAGE IMPROVEMENTS
REV ISSUED FOR DATE BY
ORANGE COUNTYFLORIDA
0 1"1/2"
44014-001
1CONTRACT NO.:
HAZEN NO.:
DATE: APRIL 2017
DRAWINGNUMBER:
R. ANDERSON
ROBERT K. ANDERSON, PE No. 471291 BID SET 04/2017 RKA
RKA
ESM
C05
CIVILYARD PIPING PLANCIK
YARD PIPING PLAN1"=40'
3.0 MG GROUNDSTORAGE TANK
RELOCATED 30" DIP RWMSEE CIVIL DRAWING
SEE ENLARGED PLAN ON C06
2.0 MG GROUNDSTORAGE TANK
TO PARDISTRIBUTION PS
8" DRAIN
16" TANK OUTLET
RECIRCULATION PUMPSAND EQUIPMENT, SEEMECHANICAL DRAWINGS
12" TANK INLET
2" CLS FROMCHLORINEBUILDING
2" CLS SCH 80 PVC
SEE SHEET M08 FOR TIE ININFORMATION AT CHLORINE BUILDING
6" DRAIN
RAISE TOP OF EXISTING 4'MANHOLE TO ELEVATION113.00± (APPROX. 2.5')
EXISTING 4' MANHOLE (TANK DRAIN)TOP EL 110.50'±, INV 108.8' ±
2" 90° BEND
2" 60° BEND
2" CLS SCH 80 PVC
ROAD OPEN CUT
5C07
FIELDOFFICES
SEE NOTE 3
1-1/2" RWSCH 80 PVC
![Page 6: EXISTING SITE PLAN - Prime Construction Grouppressure test newly constructed 30-inch plant effluent pipe. 8. dewater, shore and excavate pits as required to connect new 30-inch plant](https://reader033.fdocuments.net/reader033/viewer/2022041717/5e4c43e0e54ff74b8d1664fe/html5/thumbnails/6.jpg)
NOTES:1. REMOVE EXISTING 8" CAP AND TIE-IN NEW 8"
DRAIN PIPING.
2. REFER TO DRAWING M01 FOR YARD VALVESREQUIRING ELECTRIC ACTUATORS.
3. FIELD VERIFY ELEVATIONS OF EXISTING YARDPIPING AT ALL TIE-IN LOCATIONS PRIOR TOSUBMITTING YARD PIPING AND GROUND STORAGETANK SHOP DRAWINGS.
IF THIS BAR DOES NOTMEASURE 1" THEN DRAWINGIS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECTENGINEER: DO NOT USE FOR
CONSTRUCTION
HAZEN AND SAWYER919 LAKE BALDWIN LANE, SUTIE A
ORLANDO, FLORIDA 32814CERTIFICATE OF AUTHORIZATION No. 2771
NORTHWEST WATER RECLAMATION FACILITYREUSE WATER STORAGE IMPROVEMENTS
REV ISSUED FOR DATE BY
ORANGE COUNTYFLORIDA
0 1"1/2"
44014-001
1CONTRACT NO.:
HAZEN NO.:
DATE: APRIL 2017
DRAWINGNUMBER:
R. ANDERSON
ROBERT K. ANDERSON, PE No. 471291 BID SET 04/2017 RKA
RKA
ESM
C06
CIVILYARD PIPING ENLARGED PLANSCIK
ENLARGED PIPING PLAN AT TANK1"=20'
EXISTING 2 MG GROUND STORAGE TANK(PAR)
3 MG GROUND STORAGE TANK(PAR/ REJECT)
12" TEE
12" GV
16" 90° BEND (TYP)
CONNECT TO EXISTING 16" VALVESEE NOTE 3
CONNECT TOEXISTING 12" VALVESEE NOTE 3
16" TEE
TO PAR DISTRIBUTION PS
RECIRCULATION PUMPSAND EQUIPMENT, SEEMECHANICAL DRAWINGS
16" GV
12" TANK INLET
16" TANK OUTLET
12" GV
8" DRAIN
8" GV
RELOCATED 30" DIP PLANTEFFLUENT SEE CIVIL DRAWING
MOV-211
EXIST VALVE WITHMOTORIZED ACTUATOR
TK-220
TK-210
12" RW
16" RW
30" PLANT EFFLUENT
CONNECT TO EXISTING PVC DRAIN(REDUCE/TRANSITION ASREQUIRED; APPROX. INV. 104.7)
3'
4" BOLLARD (TYP 4)
3" PUMP OUTCONC SLAB(MATCH EXISTING ASPHALT)
PVC
DIP
NOTE:
3” TYPE 316 SST KAMLOCK MODEL 633B-SS30 MALE ENDNPT WITH MODEL 634B-SS30 DUST CAP, OR EQUAL.
2" CLS
2" CLS FROMCHLORINEBUILDING
NOTES 1AND 3
8" 45° BEND
12" 90° BEND (TYP 3)
2" 90° BEND, TYP
3" QUICK DISCONNECT(SEE NOTE)
4" BOLLARD
6" CONC SLAB
18"
6" PVC
3" PUMP OUT ELEVATIONNTS
TIE-IN TO EXIST 4" RECLAIMEDMAIN AND EXTEND A 1-1/2" SCH 80PVC LINE TO RECIRCULATION PUMPSTATION FOR HOSE BIBB. INSTALL1-1/2" CORPORATION STOP ANDVALVE BOX ADJACENT TO TIE-INLOCATION
1-1/2" RW SCH 80 PVC
16" GV
![Page 7: EXISTING SITE PLAN - Prime Construction Grouppressure test newly constructed 30-inch plant effluent pipe. 8. dewater, shore and excavate pits as required to connect new 30-inch plant](https://reader033.fdocuments.net/reader033/viewer/2022041717/5e4c43e0e54ff74b8d1664fe/html5/thumbnails/7.jpg)
NOTES:
1. INITIAL BACKFILL: SELECT COMMON FILL COMPACTED TO 95% (98% UNDER PAVEMENT) OF THEMAXIMUM DENSITY AS PER AASHTO T-180.
2. TRENCH BACKFILL: COMMON FILL COMPACTED TO 95% (98% UNDER PAVEMENT) OF THE MAXIMUMDENSITY AS PER AASHTO T-180.
3. TYPE A BEDDING MATERIAL SHALL CONFORM TO FDOT NO. 57 AGGREGATE.
4. 15" MAX. (12" MIN.) FOR PIPE DIAMETER LESS THAN 24" AND 24" MAX (12" MIN) FOR PIPE DIAMETER24" AND LARGER.
5. WATER SHALL NOT BE PERMITTED IN THE TRENCH DURING CONSTRUCTION.
6. ALL PIPE TO BE INSTALLED WITH BELL FACING UPSTREAM TO THE DIRECTION OF THE FLOW.
7. BEDDING DEPTH SHALL BE 4" MINIMUM FOR PIPE DIAMETER UP TO 12" AND 6" MINIMUM FOR PIPEDIAMETER 16" AND LARGER.
8. DEPTH FOR REMOVAL OF UNSUITABLE MATERIAL SHALL GOVERN DEPTH OF BEDDING ROCKBELOW THE PIPE. UTILITIES SHALL DETERMINE IN THE FIELD REQUIRED REMOVAL OF UNSUITABLEMATERIAL TO REACH SUITABLE FOUNDATION.
9. FINAL RESTORATION IN IMPROVED AREAS SHALL BE IN COMPLIANCE WITH ALL APPLICABLEREGULATIONS OF GOVERNING AGENCIES. SURFACE RESTORATION WITHIN ORANGE COUNTYRIGHT-OF-WAY SHALL COMPLY WITH REQUIREMENTS OF R/W UTILIZATION REGULATIONS ANDROAD CONSTRUCTION SPECIFICATIONS.
NOTES:
1. INITIAL BACKFILL AND HAUNCHING: SELECT COMMON FILL COMPACTED TO 95% (98% UNDERPAVEMENT) OF THE MAXIMUM DENSITY AS PER AASHTO T-180.
2. TRENCH BACKFILL: COMMON FILL COMPACTED TO 95% (98% UNDER PAVEMENT) OF THEMAXIMUM DENSITY AS PER AASHTO T-180.
3. PIPE BEDDING UTILIZING SELECT COMMON FILL OR BEDDING ROCK IN ACCORDANCE WITHTYPE A BEDDING AND TRENCHING DETAIL MAY BE REQUIRED AS DIRECTED BY UTILITIES.
4. 15" MAX. (12" MIN.) FOR PIPE DIAMETER LESS THAN 24" AND 24" MAX (12" MIN) FOR PIPEDIAMETER 24" AND LARGER.
5. WATER SHALL NOT BE PERMITTED IN THE TRENCH DURING CONSTRUCTION.
6. ALL PIPE TO BE INSTALLED WITH BELL FACING UPSTREAM TO THE DIRECTION OF THE FLOW.
7. FINAL RESTORATION IN IMPROVED AREAS SHALL BE IN COMPLIANCE WITH ALL APPLICABLEREGULATIONS OF GOVERNING AGENCIES. SURFACE RESTORATION WITHIN ORANGE COUNTYRIGHT-OF-WAY SHALL COMPLY WITH REQUIREMENTS OF RIGHT-OF-WAY UTILIZATIONREGULATIONS AND ROAD CONSTRUCTION SPECIFICATIONS.
90° ELBOWPVC TO BRASSADAPTER
1" SCH 80 PVC PIPE 1" BRASSPIPE
SECURE TOPOST WITH316 SSSTRAPS
ANTI-SIPHON DEVICE
3/4" BRASS HOSE BIB 1" X 3/4" 90° ELBOW
1- #4 REBAR
4"X4" PRECASTCONCRETE POST
1" LOCKABLE CURBSTOP
ALUMINUM OR 316SS HOSE HANGER
18" MIN
2'-0
" MINC
OV
ER
HOSE BIBB FIGURE A408
24" (
TYP)
DATE: February 11, 2011
FINISHED GRADE
18"
(MIN)
(MAX)(TYP) (TYP)
7/16"1/2"
5/8"1/2"
1/2"1/2"
1/2" RAD.(TYP)
(MIN)
12"
12"
1-1/8"
4-3/8"
1-1/4"
18"
5/8"
3/4"
36"
FIGURE A501
:1. SIGN TO BE PROVIDED BY OCU.2. HEIGHT OF SIGN WILL DEPEND ON LOCATION AND SURROUNDING LANDSCAPE PLANT
TYPES. IN ALL CASES, THE SIGN SHALL BE VISIBLE TO THE PUBLIC.3. BACKGROUND SHALL BE WHITE, LETTERS SHALL BE BLACK (HELVETICA, SWISS 721
COREL OR ACCEPTABLE EQUAL) AND BORDER SHALL BE PANTONE PURPLE 522C.4. ENGINEERING GRADE REFLECTIVE MATERIALS SHALL BE USED.5. SIGN MATERIAL SHALL BE OF 0.040 GAUGE METAL.6. POST SHALL BE 2-3/8" OD ALUMINUM PIPE, HOT DIP GALVANIZED PER ASTM A-123.
POST TO BE PROVIDED BY CUSTOMER.7. MOUNTING HARDWARE SHALL BE STAINLESS STEEL.8. SIGNS SHALL BE PLACED BY THE CONTRACTOR IN ACCORDANCE WITH CHAPTER
62-610 "ACCESS CONTROL AND ADVISORY SIGNS", FAC, THE COUNTY APPROVEDENGINEERING PLANS AND/OR AS APPROVED BY THE UTILITIES.
RECLAIMED WATER SIGNAGE"DO NOT DRINK WATER"
DATE: February 11, 2011
(SE
E N
OTE
2)
TRE
NC
H B
AC
KFI
LL
12" L
IFTS
MAX
IMU
M
w/ SIZE OF PIPEVARIES
SEE NOTE 4
PIPE O.D.COMMON FILL
BEDDING MATERIAL
12" (TYP)
UNDISTURBED EARTH
FINISHED GRADETRENCH WIDTH
SELECT COMMONFILL
INITIALBACKFILL (S
EEN
OTE
1)
(SEE
NO
TE 3
)HAUNCHING
BEDDING(SEE NOTES 7 & 8)
BEDDING AND TRENCHING - TYPE A FIGURE A101DATE: May 16, 2014
(SE
E N
OTE
2)
TRE
NC
H B
AC
KFI
LL
W/ SIZE OF PIPEVARIES
SEE NOTE 4
PIPE O.D.COMMON FILL
12" (TYP)
FINISHED GRADETRENCH WIDTH
SELECT COMMONFILL
INITIALBACKFILL
(SE
E N
OTE
1)
HAUNCHING
12" L
IFTS
MAX
IMU
M
UNDISTURBED EARTH(SEE NOTE 3)
BEDDING AND TRENCHING - TYPE B FIGURE A102DATE: May 16, 2014
IF THIS BAR DOES NOTMEASURE 1" THEN DRAWINGIS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECTENGINEER: DO NOT USE FOR
CONSTRUCTION
HAZEN AND SAWYER919 LAKE BALDWIN LANE, SUTIE A
ORLANDO, FLORIDA 32814CERTIFICATE OF AUTHORIZATION No. 2771
NORTHWEST WATER RECLAMATION FACILITYREUSE WATER STORAGE IMPROVEMENTS
REV ISSUED FOR DATE BY
ORANGE COUNTYFLORIDA
0 1"1/2"
44014-001
1CONTRACT NO.:
HAZEN NO.:
DATE: APRIL 2017
DRAWINGNUMBER:
R. ANDERSON
ROBERT K. ANDERSON, PE No. 471291 BID SET 04/2017 RKA
RKA
ESM
C07
CIVILDETAILS SHEET 1CIK
DETAIL 1C07NTS
BEDDING AND TRENCHING - TYPE A DETAIL 2C07NTS
BEDDING AND TRENCHING - TYPE B
DETAIL 3C07NTS
HOSE BIBB DETAIL 4C07NTS
BOLLARD36
" (M
IN.)
5' (TYP.) 5' (TYP.)
8" HIGH EARLY CONCRETE
SAW CUT
1. LONGITUDINAL CUTS MAY REQUIRE MILLINGAND OVERLAY/RESURFACING OF THECOMPLETE WIDTH OF THE TRAVELLED WAY.
EXISTING BASE EXISTING BASE
PERMANENT HOT ASPHALT REPLACEMENTAPPLIED IN 2 INCH MAXIMUM LAYERS
UTILITY PIPE
SUBGRADE(COMPACTED TO 98%
MAX. DENSISTY)EXISTINGSUBGRADE
HOT PATCH
CONCRETEREPLACEMENT
1. BASE REPLACEMENT SHALL BE 3000 PSI HIGH EARLYSTRENGTH CONCRETE.
2. ASPHALTIC CONCRETE SURFACE MATERIAL SHALL BEREPLACED WITH THE SAME TYPE OF MATERIAL THATEXISTED AT THE TIME OF REMOVAL.
3. MINIMUM ASPHALTIC CONCRETE SURFACE OVERLAYTHICKNESS SHALL BE (1"- 5") INCH/ES, OR ASAPPROVED BY THE COUNTY ENGINEER.
4. ALL JOINT CUTS SHALL BE MECHANICALLY SAW-CUT.
5. SUB-GRADE TO BE COMPACTED TO 98% MAX.DENSITY AS DETERMINED BY AASHTO T-180. CUT TOBE REPLACED WITH 3000 PSI HIGH EARLY CONCRETETO TOP OF EXISTING BASE. CUT AREA TO BE PLATEDOR PROTECTED ON DAY OF POUR. EXISTINGSURFACE TO BE SAW CUT TO AN AREA 5 FEETBEYOND BASE CUT.1'
(TYP.)
TEMPORARY COLD PATCH OVER CONCRETE BASE - TYPICAL OF MAJOR OPEN CUTS
DETAIL 5C07NTS
STANDARD ROADWAY OPENCUT DETAIL
DETAIL 6C07NTS
RECLAIMED WATER SIGNAGE "DO NOT DRINK WATER" DETAIL 7C07NTS
ASHPALT PAVEMENT
DETAIL 8C07NTS
TIE IN TO EXISTING
1-1/2" ASPHALTIC CONCRETE
PRIME ANDTACKCOATS 8" SOIL
CEMENT BASE
STABILIZEDSUBBASE
NEW PAVEMENTSOIL CEMENT
REMOVE EXISTPAVEMENT, NEWPAVEMENT TO MATCHSAWCUT EDGE
TACK COAT VERTICALSURFACE BEFORENEW CONSTRUCTION
EXISTING PAVEMENT
EXISTING BASE
EXIS
T EO
P
SAW
CU
T
1-1/2" ASHPALT
8" SOIL CEMENT BASE(350 PSI, 7 DAY)
10" STABILIZEDSUBGRADE TO 75 PSI, FBV
DETAIL 9C07NTS
ACCESS ROAD
![Page 8: EXISTING SITE PLAN - Prime Construction Grouppressure test newly constructed 30-inch plant effluent pipe. 8. dewater, shore and excavate pits as required to connect new 30-inch plant](https://reader033.fdocuments.net/reader033/viewer/2022041717/5e4c43e0e54ff74b8d1664fe/html5/thumbnails/8.jpg)
RECLAIMED WATER
RECLAIMED
NOTE:1. LOCKING LIDS ARE REQUIRED ON ALL VALVE BOXES.
TYPICAL LOCKINGBOLT
VERTVERT HORIZVERTHORIZVERTHORIZ HORIZ
HORIZONTAL & VERTICAL SEPARATION REQUIREMENTS
NOTES:
1. THIS SEPARATION REQUIREMENT IS TO PROVIDE ACCESSIBILITY FOR CONSTRUCTION ANDMAINTENANCE. THREE FEET OF HORIZONTAL SEPARATION IS THE MINIMUM FOR PIPES WITH THREEFEET OF COVER. FOR PIPES INSTALLED AT GREATER DEPTHS, PROVIDE AN ADDITIONAL FOOT OFSEPARATION FOR EACH ADDITIONAL FOOT OF DEPTH.
2. THE 18-INCH SEPARATION REQUIREMENT APPLIES WHEN THE STORM PIPE CROSSES ABOVE THEOCU MAIN, AND WHEN THE STORM PIPE HAS A DIAMETER EQUAL TO OR GREATER THAN 24 INCHES.OTHERWISE, THE REQUIRED SEPARATION IS 12 INCHES.
3. THIS SEPARATION REQUIREMENT COMPLIES WITH MINIMUM FDEP SEPARATION REQUIREMENTSOUTLINED IN 62-555.314, FAC. VARIANCES FROM THE FDEP REQUIREMENTS MUST COMPLY WITH62-555.314(5), FAC AND MUST BE APPROVED INDIVIDUALLY BY BOTH FDEP AND OCU.
4. DISTANCES GIVEN ARE FROM OUTSIDE OF PIPE TO OUTSIDE OF PIPE.5. NO WATER PIPE SHALL PASS THROUGH OR COME IN CONTACT WITH ANY PART OF SANITARY OR
STORM WATER MANHOLE OR STRUCTURE.
PROPOSEDUTILITY
POTABLE WATER
RECLAIMEDWATER
WASTEWATER(GRAVITY AND FM)
POTABLEWATER
RECLAIMEDWATER
WASTEWATER(GRAVITY & FM) STORM SEWER
3'NOTE 1
6'NOTE 3
12"
12"NOTE 3
3'NOTE 1
3'NOTE 1
3'NOTE 1
3'NOTE 1
3'NOTE 1
3'NOTE 1
12"NOTE 3
12"NOTE 3
12"
6'NOTE 3
12"NOTE 3
12"
12"12"
12"/18"NOTE 2 & 3
12"/18"NOTE 2
12"/18"NOTE 2
RIGHT OF WAY 3'NOTE 1
3'NOTE 1
3'NOTE 1
N/A N/A N/A N/A N/A
3'NOTE 1 & 3
3'NOTE 1 & 3
3'NOTE 1 & 3
LOCKINGBOLT
STANDARD VALVEBOX
ALIGNMENTRING
SLIDINGADJUSTER
VALVEBOX LID
NOTES:1. FOR ALL MAINS 6' DEEP OR GREATER.2. FOR MAINS 16" IN DIAMETER OR GREATER REGARDLESS OF DEPTH.
WATER
OUTSIDE PAVEMENTINSIDE PAVEMENT
24" X 24" SQUARE (ROUND OPTIONAL)CONCRETE OR POLYMER PADTYP EACH VALVE BOX
VALVE BOX AND LOCKING COVER
6" THICK 2500 PSI(MIN) CONCRETE WITH#4 REBAR CONTINUOUS (SEENOTE 2) OR 4" THICKPOLYMER MIX MATERIAL
24"
24"
NOTES:1. BRONZE (OR STAINLESS STEEL) IDENTIFICATION DISC SHALL BE REQUIRED FOR ALL VALVES,
EXCEPT HYDRANT VALVES.2. IN LIEU OF PRECAST CONCRETE PAD, A 6" THICK X 24" (ROUND OR SQUARE) POURED
CONCRETE PAD WITH TWO #4 REBAR AROUND PERIMETER MAY BE USED.
VALVE BOX ANDCOVER (SQUARE FORRECLAIMED WATER)
IDENTIFICATION DISC (SEENOTE 1 AND DETAILSBELOW)
O.C.UAFC 6" MANUFACTURER AND SIZE
RWGV TYPE OF VALVE
WATER UTILITY
L-20 DIRECTION AND NUMBER OF TURNS
2009 YEAR
LETTERING TO BE MACHINEENGRAVED WITH 1
4" TO 38" CAP.LETTERS
3" MIN
18" MIN
2" MINTHEFT PROOFANCHOR PIN
DISC TO BE EMBEDDED IN PAD
O.C.UAFC 6"RWGVWATERL-202009
DISC TO BE HANGING IN THE BOXANCHORED TO THE LOCATING WIRE.
3" MIN14"
APPROX. 3"
BASE
TOP FLUSHWITHFINISHED GRADE
VALVE BOXAND COVER(TYP)
ASPHALTSURFACE
LOOP WIRE
LOCATINGWIRE
SEE NOTE 2
FINISHED GRADE
NOTES:1. PVC PIPE OR DUCTILE IRON PIPE EXTENSIONS SHALL NOT BE USED ON VALVE BOX
INSTALLATION.2. THE VALVE ACTUATING NUT SHALL BE EXTENDED TO BE WITHIN 3' OF FINISHED GRADE.3. PROVIDE A PLASTIC DEBRIS SHIELD / ALIGNMENT RING WHICH INSTALLS BELOW THE
VALVE ACTUATING NUT. THIS SHIELD SHALL CENTER THE RISER PIPE BOX OVER THEACTUATING NUT AND MINIMIZE INFILTRATION.
4. LOCATING WIRE SHALL BE CONTINUOUS WITH NO SPLICES AND SHALL EXTEND 12" ABOVETOP OF COLLAR. WIRE SHALL BE COLOR CODED TO MATCH THE UTILITY INSTALLED.
5. FOR NEW CONSTRUCTION, THE VALVE BOX SHALL BE ADJUSTED TO MIDRANGE TOALLOW FOR FUTURE BOX ADJUSTMENTS.
6. REFER TO FIGURE A111 FOR INSTALLATIONS AT A DEPTH OF 6' OR GREATER.
SET TOP OF VALVE BOXTO FINISHED GRADE
RESILIENT SEATM. J. GATE VALVE
WATER MAINOR RECLAIMEDWATER MAIN
ADJUSTABLE SCREWTYPE DUCTILE IRONVALVE BOX
VALVE BOX SHALL REST ONBEDDING ROCK NOT ON VALVEOR PIPE AND SHALL BECENTERED ON OPERATING NUT
ALIGNMENT RING
VALVE BOX PAD(SEE FIGURE A112)
6" FDOT #57STONE
COMPACTED SELECTCOMMON FILL
FIGURE A107GATE VALVE AND BOXWATER AND RECLAIMED WATER MAINS
LOCATING WIRE
LOOP WIRE (SEE NOTE 4)
DRILL HOLE IN BOX3"± 14" FROM TOP
DATE: February 11, 2011
IF THIS BAR DOES NOTMEASURE 1" THEN DRAWINGIS NOT TO FULL SCALE
CHECKED BY:
DRAWN BY:
DESIGNED BY:
PROJECTENGINEER: DO NOT USE FOR
CONSTRUCTION
HAZEN AND SAWYER919 LAKE BALDWIN LANE, SUTIE A
ORLANDO, FLORIDA 32814CERTIFICATE OF AUTHORIZATION No. 2771
NORTHWEST WATER RECLAMATION FACILITYREUSE WATER STORAGE IMPROVEMENTS
REV ISSUED FOR DATE BY
ORANGE COUNTYFLORIDA
0 1"1/2"
44014-001
1CONTRACT NO.:
HAZEN NO.:
DATE: APRIL 2017
DRAWINGNUMBER:
R. ANDERSON
ROBERT K. ANDERSON, PE No. 471291 BID SET 04/2017 RKA
RKA
ESM
C08
CIVILDETAILS SHEET 2CIK
DETAIL 5C08NTS
TYPICAL BOX COVER
DETAIL 6C08NTS
SEPARATION REQUIREMENTS FOR WATER,WASTEWATER AND RECLAIMED WATER MAINS
DETAIL 7C08NTS
GATE VALVE AND BOX AND RECLAIMED WATER MAINS
DETAIL 8C08NTS
SEALED VALVE AND BOX, ADJUSTABLE
DETAIL 9C08NTS
VALVE BOX PAD
RESILIENT SEATM. J. GATE VALVE
WATER MAINOR RECLAIMEDWATER MAIN
VALVE BOX SHALL REST ONBEDDING ROCK NOT ON VALVEOR PIPE AND SHALL BECENTERED ON OPERATING NUT
ALIGNMENT RING
6" FDOT #57STONE
LOCATING WIRE
VALVE NECK EXTENSION
ELECTRICMOTOR ACTUATOR
EXISTING GRADE
DETAIL 10C08NTS
PEDESTAL MOUNTED MOTORIZED GATE VALVE AND BOX
36'X36" CONCRETE PAD, 6-INCHES THICK, 2,500 PSI (MIN)CONCRETE W/#4 REBAR AT 6-INCHES EACH WAY