EXHAUSTO Inc in North America - Wesmech · PDF fileSub Title EXHAUSTO Inc in North America...
Transcript of EXHAUSTO Inc in North America - Wesmech · PDF fileSub Title EXHAUSTO Inc in North America...
Sub Title
EXHAUSTO Inc in North America
In Atlanta since 1990 25,000 sq.ft. office and
warehouse 86 authorized sales
and service offices in USA and Canada.
Sub Title
The First Fan - 1957
The first chimney fan - a first worldwide and the foundation of EXHAUSTOs existence
Sub Title
A 50-year Old Company
Founded in 1957 300,000+ sq.ft. of
manufacturing and administration
High-tech ISO 9001 certified manufacturing facilities
Sub Title
Certifications
Sub Title
Mechanical Draft Systems
Sub Title
Products RSV Fan
3/16 Cast aluminum housingHinged for easy service and cleaningDirect driveClass H insulated motorMaintenance free482 F Continuous Duty575 F Intermittent DutyUL 378 Draft Equipment
Capacity:
6,000 MBH on CAT I Appliances
10,000 MBH on CAT IV Appliances
Sub Title
Products RSV Fan
The RSV fan can vent all appliance categories with or without barometric dampers
Up to 6,000 - 10,000 MBH High temperature motor
eliminates the need for secondary fan cooling
Simple design with few components reduces the risk of failure and simplifies service
Sub Title
CASI Chimney Automation System
Sub Title
RSIB Power Venter
SS316 constructionRemovable access doorDirect driveClass A insulated motor - eliminates the need for secondary fan coolingMaintenance freeUp to 575 F DutyThe RSIB fan can vent category I, II, III & IV appliancesSimple design with few components reduces the risk of failure and simplifies serviceRSIB is of Type B, Spark Resistant ConstructionUL 378 Draft Equipment
Capacity:
8,000 MBH on CAT I Appliances
15,000 MBH on CAT IV Appliances
Sub Title
RSIF Power Venter
Rated to 400F non-condensing applicationsForward inclined impeller. Statically and dynamicallybalanced.Insulated housing in galvanized steelHinged fan housing easily opens to provide easy access to duct and impellerDirect drive, variable speed, TEFC motor located outside housing for easy access.
Capacity:
1,800 MBH on CAT I Appliances
Sub Title
Modulating Overdraft Damper System
Sub Title
Controls
EBC30 Modulating Pressure Control
Sub Title
Controls EBC30
Features
100% microprocessor based controlPlug-and-Play initialization processIntegrated PDS function with adjustable time delay Intermittent or continuous operation for all fansField-adjustable PID loopPriority Operation functionBearing Cycle functionRotation Check for three-phase fans
Sub Title
Controls
Differential pressure transducerEnsures proper draft before and during appliance operationProbe includedRange: 0.04 to 0.60 W.C.
PDS Proven Draft Switch
Sub Title
Controls
VFD Variable Frequency Drive
Pre-programmed from the factory1 5 HP in 200 Volt Class input1 7.All wiring is done externally conduits and wires are pre-installedQuick-menu for field adjustable ParametersNEMA 1 rating
Sub Title
Products Accessories
SCA Steel Chimney Adapter
Steel chimney adapterUsed as transition between a round stack and the fanMade of 304 stainless steel
Sub Title
Products Accessories
BBF Balancing Baffle
Balancing baffle with flange connectionsFor positive pressure stacksFor balancing pressure drops on systems with multiple appliances
Sub Title
CASV Applications Stack Downsizing
Hazen High School Renton, WA
Soldier Field - Chicago, IL
Sub Title
CASV Applications - Aesthetics
Getty Center Los AngelesRigel San Francisco
MCASMechanical Combustion Air Supply Systems
Sub Title
MCAS Modulating Combustion Air Supply System
Sub Title
MCAS Components SFTA Fan
Fan can be mounted indoors Impeller cast aluminum.Housing in steelDirect drive, variable speed, TEFC motor located outside housing for easy access.Variable Frequency Drive is used on three phase models (VFD should be located inside the building).
Seven Models1,500 30,000 cfm
Sub Title
MCAS Components BESF/BESB Fan
Fan can be mounted indoors or outdoors.Impeller - statically and dynamically balanced.Insulated housing in galvanized steelHinged fan housing easily opens to provide easy access to duct and impellerDirect drive, variable speed, TEFC motor located outside housing for easy access.Variable Frequency Drive is used on three phase models In-door or out-door installations(VFD should be located inside the building).
Seven Models450 5500 cfm
Sub Title
EBC30 Modulating Control
Chimney Automation
System
Modulating Combustion Air Supply
System
Sub Title
SBC Center San Antonio, TX
Two 16 inch ducted combustion air inletsInstead of
Two 10 foot high by 15 foot long Louvers
Sub Title
Lifetime Fitness Savage, MN
Sub Title
Marriott Waterfront Annapolis, MD
One 24 inch ducted combustion air inletInstead of
One 90 ft. louver
MDVSMechanical Dryer Venting Systems
Sub Title
MDVS Mechanical Dryer Venting System
Sub Title
MDVS Components - BESB Fan
ETL Listed to UL705 :"The product (BESB/MDVS)covered by this report is a modulating air exhaust system. The product consists of a box ventilator and a modulating control for permanent installation. Its intended use is exhausting of lint-laden air from single or multiple type I and type II residential and commercial clothes dryers whether electric or gas-fired, exhausting commercial hoods, or for providing make-up air for laundries or mechanical rooms. The box ventilator can be installed indoors or outdoors."
Four Models1200 5500 cfm
Sub Title
MEC 18 Control
Monitor draft in multi-story building exhaust applicationsControls RSV, EFH, BESF and BESBEBC12 functionsUL 508 and CSA C22.2 Standard for Industrial Control Equipment
Sub Title
Kitchen and Dryer Exhaust
Madigral Lofts, MD
Applications
Hotels
Hospitals Fitness Facilities
Sports Arenas
Apartments / Condominiums
Schools
Sub Title
Appliance Categorization
IV
III
II
I
Atmospheric
Fan Assisted(high
efficiency)
Forced Draft
Condensing
Draft Hood
Fan AssistedDraft Diverter
Scotch Marine
NegativePositive
Sub Title
Z223.1-54 (Venting of equipment)
12.1 Minimum Safe Performance
A venting system shall be designed and constructed so as to develop a positive flow adequate to remove flue or vent gases to the outside atmosphere.
12.4.1 Equipment Draft Requirement
A venting system shall satisfy the draft requirement of the equipment in accordance with the manufacturers instructions.
Sub Title
Common Code Violations
(NFPA 54) Z223.1-2006 12.11.9.2 (Venting of Equipment)
(NFPA 54) Z223.1-2006 13.2 (Sizing of Venting Systems)
Sub Title
Common Code Violations
(NFPA 54) Z223 Sizing Tables(NFPA 54) Z223.1-2006 13.2.18 (Sizing of Venting Systems)
3" 4" 5" 6" 7" 8" 9" 10" 12" 14" 16"7" 10" 12" 14" 18" 22" 22" 26" 30" 36" 42"
Sub Title
Mechanical Draft Systems Defined
12.4.3.1 Mechanical draft systems shall be listed and shall be installed in accordance with the terms of their listing and both the appliance and the mechanical draft system manufacturers instructions.
12.4.3.2 Appliances requiring venting shall be permitted to be vented by means of mechanical draft systems of either forced or induced draft design.Exception: Incinerators
12.4.3.5 Where a mechanical draft system is employed, provision shall be made to prevent flow of gas to the main burners when the draft system is not performing so as to satisfy the operating requirements of the equipment for safe performance
Z223.1-2006 Standard for Venting of Equipment
Sub Title
Commercial Laundry Radisson, Orlando, FL
Responsibility
EnvironmentallyfriendlyReduce Emissions
Low Energy
Recyclable Materials
Demand-Controlled
And Still Going Strong...
Reliable2001
2 RSV replaced
Disney Allstar ResortsOrlando, Florida60 RSV installed
1990
The White HouseWashington D.C12 RSV installed
1992
Sample 3
xx RSV installed
2007
Seismological Safe
Eliminates Potential Risks
Eliminates Potential Risks
Seismological Safe
Case:CBS Studio, Hollywood, CABoiler replacement. Must meet air quality requirements and eliminate need for substantial stack work.
Solution:Four condensing boilers installed in a modular system using a single common stack and a CASV system for venting.
Benefits:Simple and Aesthetically pleasingLimited stack work using existing chase
EXHAUSTO Inc in North AmericaThe First Fan - 1957A 50-year Old CompanyCertificationsMechanical Draft SystemsSlide Number 6Slide Number 7CASI Chimney Automation SystemRSIB Power Venter RSIF Power VenterModulating Overdraft Damper SystemControlsControls EBC30ControlsSlide Number 15Slide Number 16Slide Number 17CASV Applications Stack DownsizingCASV Applications - AestheticsMCAS Mechanical Combustion Air Supply SystemsMCAS Modulating Combustion Air Supply SystemMCAS Components SFTA FanMCAS Components BESF/BESB FanE