Excitation Test
-
Upload
georgelapiz -
Category
Documents
-
view
231 -
download
0
Transcript of Excitation Test
-
7/28/2019 Excitation Test
1/16
Generator Reactivity Limit
Testing
Workshop Presentation
WECC Generator Testing Task Force
-
7/28/2019 Excitation Test
2/16
What it is and what it isnt
It is a quick and relatively easy test. It verifies reactive capability for only
one set of conditions at 2 points.
It does not verify generator capabilityfor all conditions.
It does not verify all points in thegenerator capability curve.
-
7/28/2019 Excitation Test
3/16
Letter Defining Requirement
-
7/28/2019 Excitation Test
4/16
-
7/28/2019 Excitation Test
5/16
Testing Requirements
All synchronous machines greater than 10 MVA
Operating conditions should be as close to
normal as practicable, including loading, unittemperatures, and pressures.
Tests should be performed during periods of
operation which maximize the MVAR in/outputof the machine (when system voltage is mostadvantageous to yield these results).
When possible, other synchronous machines orpower system components should be used toobtain the most advantageous terminal voltage
during these tests.
-
7/28/2019 Excitation Test
6/16
Testing Requirements
While operating in a steady state mode at netdependable MW capability (near rated output),
raise excitation in automatic voltage control untilone of the following conditions occurs:
The 100% MVA rating of the machine isreached (reached capability curve)
Rated field current or field voltage is reached
Terminal voltage limit is reached
Generator temperature limits are reached
-
7/28/2019 Excitation Test
7/16
Testing Requirements
Maximum/over excitation limiter is
reached/alarms Maximum reference adjuster travel or limit is
reached
Maximum auxiliary bus voltage is reached
Hold unit at this level for a minimum of 15minutes (30 minutes is a preferable duration),then take measurements
-
7/28/2019 Excitation Test
8/16
Testing Requirements
While operating in a steady state mode at netdependable MW capability lower excitation in
automatic voltage control until one of thefollowing conditions occurs:
UELs are activated
100% MVA rating is reached Generator temperature limits are reached
Minimum reference adjuster travel or limit isreached
Minimum auxiliary bus voltage is reached
Minimum terminal voltage limit is reached
-
7/28/2019 Excitation Test
9/16
Example Hydrogenerator
-
7/28/2019 Excitation Test
10/16
Nom Voltage
Min Voltage
Max Voltage
-
7/28/2019 Excitation Test
11/16
Application to Testing
The rated MVA and 95% PFoverexcited point is at nominalterminal voltage. (blue line)
This machine will not producerated MVA and 95% PF whenterminal voltage is at the
maximum. (turquoise line) This unit passes the reactive
capability test because Tests
should be performed duringperiods of operation whichmaximize the MVAR in/outputof the machine (when system
voltage is most advantageousto yield these results). (red)
Min
Nom
Max
-
7/28/2019 Excitation Test
12/16
Application to Capability
The Generator Capability Curve should stateminimum capability for all rated conditions:
terminal voltage, ambient temperature, etc.
Internal and external events that limit capability
normally considered separately. It may not bepossible to produce all limiting conditionssimultaneously.
The reactive capability test does not validatethe machine capability curve.
-
7/28/2019 Excitation Test
13/16
Machine Capability Maintenance
Owners should be aware of changes and updatemachine capability curves.
Operational events that indicate potentialcompromise of capability should be investigated.
Due to the complicated nature of validatingcapability for all operational conditions andconsidering the potential impact to system
operation, it is not prudent to mandate re-validation of capability.
Operational events and routine maintenancenormally reveal potential problems.
-
7/28/2019 Excitation Test
14/16
Benefits of Reactive Capability Testing
Testing can detect significant degradation.
Tests are simple and cause little risk.
Tests confirm capability under nominal
conditions. If the unit fails to meet the reactive capability
under the most favorable conditions, it isproven to fail to meet the machine capabilitycurve on record.
-
7/28/2019 Excitation Test
15/16
Reactive Capability Testing Limitations
Passing reactive capability testing is a necessarybut not sufficient condition to assure machinecapability curve is accurate.
May not detect outer loop control (SCADA) limits
if tested under local control.
Tests are done steady state with gentle moves
approaching limits. Design for abnominalconditions may require more restrictive SCADAlimits.
-
7/28/2019 Excitation Test
16/16
The End