Examples Examples

download Examples Examples

of 14

Transcript of Examples Examples

  • 7/30/2019 Examples Examples

    1/14

    Example 1 . A three-phase, Y-connected generator is rated at 100 kVa, 60

    cycles, 2300 volts. The effective resistance of the armature is 1.5 ohms per

    leg. The test data are given below:

    Field

    Current

    (A)

    10 20 30 40

    Terminal 1200 2100 2830 3460

    Calculate the synchronous impedance and the synchronous reactance per

    phase for this machine, using the highest point given on the saturation or

    open circuit voltage curve to obtain the values.

    Volts (OC)SC

    Current

    13.2 26.0

    A-PDFOFFICE

    TOPDFDEMO:Purchasefromwww.A

    -PDF.comtoremovethewatermark

    http://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demohttp://www.a-pdf.com/?op-demo
  • 7/30/2019 Examples Examples

    2/14

    Example 2 . A three-phase, slow speed, Y-connected alternator is rated at

    5000 kVA and 13,200 volts. The resistance of the armature between terminals

    is 0.192 ohm at 75 C. The effective resistance is 1.6 times the dc-value at 75

    C.. The test data on this machine is given below.

    Field

    Current (A)

    90 135 180 225

    a) Calculate the regulation at a pf of 0.8 lagging.

    b) Calculate the regulation for a load of unity pf.

    TerminalVolts (OC)

    9800 13000 14900 15800

    SC Current 195 291

  • 7/30/2019 Examples Examples

    3/14

    Example 3: A 3-phase, 800 kVA, 3000 V, 50 Hz alternator gave thefollowing results:

    ExcitingCurrent (A)

    30 35 40 50 60 65 70 75 77.5 80 85 90 100 110

    O.C. volt(line)

    _ _ _ 2560 3000

    3250 3300 3450 3500 3600 3700 3800 3960 4050

    S.C. current 140 150 170 190 _ _ _ _ _ _ _ _ _ _

    a) A field current of 110 A is found necessary to circulate a full loadcurrent on short circuit of the alternator. The armature resistance perphase is 0.27225 . Calculate the voltage regulation at 0.8 p.f.

    lagging and 0.9 p.f leading, using synchronous impedance method.Show also the vector diagram.

  • 7/30/2019 Examples Examples

    4/14

    Example 4 . A 30-kVA, Y-connected alternator rated at 555 volts at 50 Hz has

    the open circuit characteristics given by the following data:

    A field current of 25 A is found necessary to circulate a full load current on

    short circuit of the alternator. Calculate the voltage regulation at 0.8 p.f.

    Field

    Current

    (A)

    2 4 7 9 12 15 20 22 24 25

    Terminal

    Volts

    155 287 395 440 475 530 555 560 610 650

    . . . , .

    also the vector diagram. Solution:IL = 30 kVA /(3) (650) = 26.6469355 AZS = [ 650 / (3) ] / 26.6469355 = 14.08333333 A

    Ra=0; XS = ZSIXS = 375.2776749 V

    Eph = Vph + IL ( Ra + j XL ) ; Vph + IXS < 53.13010235Eph = 622.7425899 < 28.8224976 VVR% = 622.7425899 (555/ 3)

    (555/ 3)= 94.34627131 %

  • 7/30/2019 Examples Examples

    5/14

    Solution:IL = 30 kVA /(3) (550) = 31.49183286 AVph = 550 / 3 = 317.5426481 V

    IRa= 4.72377493 V/phase

    Eph = Vph + IL ( Ra + j XL ) ; Vph + IRa < 36.86989765Eph = 321.3341678 < 0.50537273 VELL = 556.5671049 V

    If = 20

  • 7/30/2019 Examples Examples

    6/14

    :Solution

    ( )191188

    144toslots

    P

    S ==

    =

    2

    10x3cospk

    == 1018

    180

    1. The following information is given in

    connection with an alternator: slots = 144;

    poles = 8; rpm = 900; conductors/slot = 6; fluxper pole = 1.8 x 106 maxwells; coil span = slots

    1 to 16; winding connection = star. Calculate:

    (a) the voltage per phase; (b) the voltage

    between terminals. 20 PTS

    ( ) conductorsZT 8641446 ==

    864==

    965925826.0=pk

    6

    3

    8

    144

    ==

    phase

    poles

    slots

    m

    =

    2

    10sin6

    2

    10x6sin

    dk 95614277.0=dk

    3p

    phaseturnsT /1442

    288==

    ( )( )( )( )( )( )86 10x16014410x8.144.4 = pdg kkE VEg 7283753.637=

    ( )

    V

    E LLg

    577947.1104

    7283753.6373

    =

    =

    1 pt

    1 pt

    1 pt

    1 pt

    8 pts

    8 pts

  • 7/30/2019 Examples Examples

    7/14

    2. In a 3 phase, start connected alternator, there

    are 2 coil per slot and 16 turns per coil.

    Armature has 288 slots on its periphery. Whendriven at 250 rpm it produces 6600 V between

    the lines at 50 Hz. The pitch of the coil is 2

    slots less than the full pitch. Calculate the flux

    per pole, total number of conductors and turns

    per phase. 20 PTS

    :Solution

    VELL 6600=

    VV

    Eg 511777.38103

    6600==

    ( )1311224

    288toslots

    P

    S==

    180 424

    288

    ==poles

    slots

    m( )

    polesN

    fP 24

    120==

    ==12

    =

    2

    15x2cospk

    965925826.0=pk 1 pt

    =

    2

    15sin4

    2

    15x4sin

    dk 957662196.0=dk

    1 pt

    slot

    cond

    slots

    turns

    coil

    turnsx

    slot

    coils .6432162==

    ( ) conductorsZT 1843228864==

    61443

    18432==phZ

    phaseturnsT /30722

    6144

    ==

    6 pts

    6 pts

  • 7/30/2019 Examples Examples

    8/14

    :2. Solutionnoofoncontinuati

    ( ) ( )( )( )50307244.4511777.3810 pd kk=

    mWb040223388.6= 6 pts

  • 7/30/2019 Examples Examples

    9/14

    3. A 3-phase, 10-pole alternator has 90 slots,

    each containing 12 conductors. If the speed is

    600 r.p.m. and the flux per pole is 0.1 Wb,calculate the line e.m.f. and voltage per phase

    when the phases are (i) star connected (ii) delta

    connected. Assume the winding factor to be

    0.96 and the flux sinusoidally distributed.

    20 PTS

    :Solution

    ( ) Hzf 50120

    60010==

    ( ) conductorsZT 10801290 ==

    3603

    1080==phZ 1 pt

    phaseturnsT /1802 ==

    Wye:

    ( )( )( )( )( )180501.0144.4 dg kE =

    VEg 16.3836= 6 pts

    1 pt

    ( )

    V

    E LLg

    424026.6644

    16.38363

    =

    =

    6 pts

    Delta:

    ( )( )( )( )( )180501.0144.4 dg kE =

    LLg EVE == 16.3836

    6 pts

  • 7/30/2019 Examples Examples

    10/14

    1. Three non-inductive resistances, each of100 , are connected in star to 3-phase, 440

    < 0O V supply. Three equal choking coilseach of reactance 100 are also connectedin delta to the same supply.Calculate:

    a) line current of each 3-phase load (in

    polar form)b) the total line current (in polar form)c) power factor of the system

    For Wye load:

    :Solution

    100

    303

    440

    1

    == IIL

    AIIL 30540341184.21 ==

    For Delta load:

    a)

    100

    0440

    jI =

    AI 904.4 =

    AIL 120621023553.72 =

    b) total line current

    AIII LLT 5650512.101033264177.821 =+=

    ( ) ( ) WIP LT 3333331.64510021 ==

    ( ) ( ) VarsIQ LT 19361002

    2 ==

    VAUT 723183.2040=

    )(316227765.0 laggingU

    Ppf

    T

    T ==

  • 7/30/2019 Examples Examples

    11/14

    2. A symmetrical 3-phase, 3-wire supply with aline voltage of 173 < 0OV supplies two balanced

    3-phase loads; one Y-connected with eachbranch impedance equal to (6 + j8) ohm andthe other -connected with each branchimpedance equal to (18 + j24) ohm. Calculate:

    a) line current taken by each 3-phase load

    (in polar form)b) the total line current (in polar form)c) power factor of the entire load circuitd) total real power and apparent power

    For Wye load:

    86

    303

    173

    1j

    IIL+

    ==

    AIIL 309881.91 ==

    a)

    :Solution

    For Delta load:

    2418 jI +=

    AI 13010235.53766666667.5 =

    AIL 13010235.83988159757.92 =

    b) total line current

    AIII LLT 13010235.8397631931.1921 =+=

  • 7/30/2019 Examples Examples

    12/14

    Solution continuation No.2:

    ( ) ( ) WIP LL 58.5986211 ==

    VAUL 6333333.9971 =

    ( ) ( ) WIP LL 5800001.59862

    22 ==

    VAUL 6333334.9972 =

    WPPP LLT 16.119721 =+=

    VAUUU LLT 266667.199521 =+=

    )(6.0 laggingU

    Ppf

    T

    T ==

  • 7/30/2019 Examples Examples

    13/14

    pfIVP LLT 3=

    = 78833062.31

    ( )( )( )85.0554003=TP

    WPT 28511.35628=

    3. A 440-V, 50-Hz induction motor takes a linecurrent of 55 A at a power factor of 0.85

    (lagging). Three -connected capacitors areinstalled to improve the power factor to 0.9(lagging). Calculate the kVA of the capacitorbank and the capacitance of each capacitor.

    power factor of 0.85 (lagging).

    TNEW PQ )tan(=

    = 8419327.25

    VARSQNEW 56604.17255=

    TOLD PQ )tan(=

    VARSQOLD 42799.22080=

    power factor of 0.9 (lagging).

  • 7/30/2019 Examples Examples

    14/14

    NEWOLDCAP QQQ =

    Continuation of No. 3 solution:

    VARSQCAP 861954.4824=

    VARS

    VARS

    QCAP 287318.16083

    861954.4824

    ==

    VARS65519745.3

    287318.1608==

    == 376501.120440

    C

    CI

    VX

    ( )( )FC

    44285915.26

    376501.120502

    1==