    s u s t a i n a b I l I t y

    Consultant Defined System Parameters

    PLANT REFRIGERATION CAPACITY 2,700 ton (9,500 kW)

    CHILLED WATER DISTRIBUTION 12.2C Evaporator EWT 6.7C Evaporator LWT 37.2C Condenser LWT

    31.7C Condenser EWT

  • 7/29/2019 EW Luan Nguyen

    3/47

    s u s t a i n a b I l I t y

    The First Step...The First Step...

  • 7/29/2019 EW Luan Nguyen

    4/47

    s u s t a i n a b I l I t y

    If one chiller is fault, remain 50% load ?

    Chiller must be off 2 compressor when it is serviced,

    proper evacuation of a refrigeration

    system is practically impossible with

    active chilled-water flow

  • 7/29/2019 EW Luan Nguyen

    5/47

    s u s t a i n a b I l I t y

    The Next Step...The Next Step...

  • 7/29/2019 EW Luan Nguyen

    6/47

    s u s t a i n a b I l I t y

    Evaluated Pumping Systems

    Primary/Secondary System

    Variable Primary Flow System

    Conclusion: VPF proves best life cycle value

    Fewer pumps

    Reduced plumbing connections

    Reduced electrical connections

    Slight Increase in VFD costs

    Greatly reduced pump operating costs

  • 7/29/2019 EW Luan Nguyen

    7/47

    s u s t a i n a b I l I t y

    Use Low Flow, Low Temperature,High Efficiency Systems

    +/+/--$$

    air handlers

    +/+/--$$

    +/+/--$$controls

    chillers

    +/+/--$$piping

    ~/~/$$

    ductwork

    ~/~/$$

    Earthwise can help the

    owner not only reduce

    first cost, it is also

    saving operating cost

    TheThe 3th3th Step...Step...

  • 7/29/2019 EW Luan Nguyen

    8/47

    s u s t a i n a b I l I t y

    8.0

    ASHRAE Standard 90.1

    C

    hillerefficiency

    ,COP

    6.0

    4.0

    2.0

    0.0best

    available

    Centrifugal>600 tons

    Screw

    150-300 tonsScroll

  • 7/29/2019 EW Luan Nguyen

    9/47

    s u s t a i n a b I l I t y

    Cool More or Pump More?

    Pump efficiency 70%

    COP 0.7

    Chiller COP 7.0

    Chiller COP 10x the pump COP

    Conclusion work your most efficientequipment harder

  • 7/29/2019 EW Luan Nguyen

    10/47

    s u s t a i n a b I l I t y

    How ?

    Leaving condenser watertempature

    Leaving Chilled watertemperature

    Flow rates Towers

    Pumps

    Piping

    Valve

  • 7/29/2019 EW Luan Nguyen

    11/47

    s u s t a i n a b I l I t y

    Do you want your building green

  • 7/29/2019 EW Luan Nguyen

    12/47

    s u s t a i n a b I l I t y

    Ashrae green guide

    Page 169- Ashrae green guide

  • 7/29/2019 EW Luan Nguyen

    13/47

    s u s t a i n a b I l I t y

    Ashrae green guide

    Page 170- Ashrae green guide

  • 7/29/2019 EW Luan Nguyen

    14/47

    s u s t a i n a b I l I t y

    M-Quay newsletter

  • 7/29/2019 EW Luan Nguyen

    15/47

    s u s t a i n a b I l I t y

    Show Me the Impact

    Cooling towers

    Cooling coils

    Chilled pumps Condenser pumps

    Chillers

    Controls

  • 7/29/2019 EW Luan Nguyen

    16/47

    s u s t a i n a b I l I t y

    37.2/31.7/29

    240 LPS

    5.5C range

    2.7C approach

    60 hp

    45 kW

    40/32/29

    113 LPS

    8C range

    3C approach

    30 hp

    22 kW

    Cooling Tower Performance

    2x1800 tons 3x1000 tons

    STD EARTHWISE

  • 7/29/2019 EW Luan Nguyen

    17/47

    s u s t a i n a b I l I t y

    lessons learned

    Cooling Tower Performance

    !Tower watershould be hot!

    Towers should use

    inverters!

  • 7/29/2019 EW Luan Nguyen

    18/47

    s u s t a i n a b I l I t y

    3unit ( 1standby)

    Flow rate 205 L/S

    Pump head 15 m

    Pump efficiency 78.2%

    Pump power 39 kW

    Primary Chilled Water Pump

    4unit ( 1standby)

    95 L/S

    22 m

    81.5%

    25 kW

    EARTHWISESTANDARD

  • 7/29/2019 EW Luan Nguyen

    19/47

    s u s t a i n a b I l I t y

    5unit ( 1standby)

    Flow rate 102.5 L/S

    Pump head 29 m

    Pump efficiency 84.3%

    Pump power 35 kW

    Less pumps less space

    Secondary Chilled Water Pump

    STD

    Total system flow : 411l/s vs 285l/s

    NONE

    EARTHWISE + VPF

  • 7/29/2019 EW Luan Nguyen

    20/47

    s u s t a i n a b I l I t y

    3unit (1standby)

    Flow rate 240 L/S

    Pump head 32 m

    Pump efficiency 80.6%

    Pump power 94 kW

    4unit (1standby)

    113 L/S

    22 m

    81.2%

    30 kW

    In this installation:a 30% reduction in flow =nearly 50% reduction in condenserwater pumping energy consumption

    Condenser Water Pump

    STD EARTHWISE

  • 7/29/2019 EW Luan Nguyen

    21/47

    s u s t a i n a b I l I t y

    Chiller Energy

    Capacity 2X1350 tons

    LWT 6.7C ( DeltaT 5.5)

    Power 2x785kW (0.58kW/RT)Capacity 2X1350 tons

    LWT 5C ( DeltaT 8)

    Power 3x557 kW (0.619kW/RT)

    No lunch is free

    Earthwise Chiller consume more 29kW

    Standard

    Earthwise

  • 7/29/2019 EW Luan Nguyen

    22/47

    s u s t a i n a b I l I t y

    System Power

    Chil ler 2x785 kW

    P-Chilled water pump 2x39 kW

    S-Chilled water pump 4x35 kW

    Cond water pump 2x94 kW

    Cooling tower 2x45kW

    Total 2066kW

    Standard

    3x557 kW

    3x25 kW

    0

    3x30kW

    3x22kW

    3x634 = 1902 kW

    EARTHWISE

    kW/RT 0.765 0.70

  • 7/29/2019 EW Luan Nguyen

    23/47

    s u s t a i n a b I l I t y

    Chiller plant analyzer

  • 7/29/2019 EW Luan Nguyen

    24/47

    s u s t a i n a b I l I t y

    Monthly energy consumption

    ALT1: Lef tALT2: Right

  • 7/29/2019 EW Luan Nguyen

    25/47

    s u s t a i n a b I l I t y

    Monthly energy cost ($)

    Alternative Standard Earthwise Saving

    Month $ $ %

    Jan 44,250.60 37,004.50 16%

    Feb 40,877.00 35,192.10 14%

    Mar 51,121.40 44,361.90 13%

    Apr 46,792.00 40,090.90 14%

    May 51,351.20 44,232.60 14%

    Jun 48,920.50 41,896.30 14%

    Jul 43,512.10 37,673.90 13%

    Aug 49,276.30 42,603.60 14%

    Sep 42,338.30 36,906.30 13%

    Oct 48,493.40 41,996.40 13%

    Nov 46,157.40 39,835.90 14%

    Dec 43,512.20 37,129.90 15%

  • 7/29/2019 EW Luan Nguyen

    26/47

    s u s t a i n a b I l I t y

    Annual cost

    Saving

    14%/yr

    -

    50,000.00

    100,000.00150,000.00

    200,000.00

    250,000.00

    300,000.00

    350,000.00

    400,000.00

    450,000.00

    500,000.00

    $ $ $ $

    Electric Water Electric Water

    Standard Earthwise

    Standard Earthwise

    Electric Water Electric Water

    $ $ $ $

    556,602.38 11,141.40 478,924.31 9,407.40

  • 7/29/2019 EW Luan Nguyen

    27/47

    s u s t a i n a b I l I t y

    Chilled Water Plant Costs Estimated

    Chiller's price is based on TraneVSDs price is based on Trane

    Pump's price is based on Drunfos,

    Cooling Tower is based on Ocean

    the prices are not include piping, valves

  • 7/29/2019 EW Luan Nguyen

    28/47

    s u s t a i n a b I l I t y

    Compare prices with 2 alternative

    Items STANDARD EARTHWISE STD ($) EWS ($)

    Chiller 2x1350RT(0.58kw/RT) 3x900RT(0.619kw/RT) 1,200,000 1,250,000

    P-Chilled water

    pump3x205 l/s-15m(39kw) 4x95 l/s-22m(25kw) 47,000 40,000

    S-Chilled water

    pump5x102.5 l/s-29m(35kw) 0 70,000 0

    Condenser water

    pump3x240 l/s-32m(94kw) 4x113 l/s-22m(30kw) 115,000 48,000

    VSD for chilled

    pumps5x45kw 4x30kw 30,000 15,000

    Cooling tower 2x1800RT (45kw) 3x1000RT (22kw) 120,000 100,000

    VSD for Cooling

    tower 0 3x22kw 0 10,000

    Chiller plant control OtherTrane chiller plant

    control0 40,000

    Total chiller plant 2066kw 1902kw 1,580,000 1,500,000

    System Kw/RT 0.765 0.7 - 80,000

  • 7/29/2019 EW Luan Nguyen

    29/47

    s u s t a i n a b I l I t y

    EARTHWISE SYSTEM

    FIRST

    COST

    5%

    OPARATING

    COST

    14%

    1,580,000 $

    1,500,000 &

    567,743.00/yr

    488,330.00/yr

    This saving is not account for the reduction of piping, valves..

  • 7/29/2019 EW Luan Nguyen

    30/47

    s u s t a i n a b I l I t y

    Tranes chiller plant control

    Your chiller system is

    not optimal like our

    analyzer without

    chiller plant

    control

  • 7/29/2019 EW Luan Nguyen

    31/47

    s u s t a i n a b I l I t y

    EarthWise Chiller Plant Control SystemFeatures and Benefits

    Software Features

    3-D animated system and equipment graphics

    Energy monitoring & reports

    System and equipment performance analysis

    Web access

    Energy Optimization

    Advanced chiller sequencing

    Cooling tower optimization

    Variable primary chilled water flow control

    Reliable & Flexible Operation

    Matrix pump & cooling tower control

    Auto equipment failure recovery

    Auto equipment rotation

    Alarm Management

    Chiller diagnostic messages

    SMS alarm notification

    Factory Panel

    Pre-wired and tested

  • 7/29/2019 EW Luan Nguyen

    32/47

    s u s t a i n a b I l I t y

    Energy OptimizationEnergy Optimization

    Factory-engineered Optimization Algorithms Advanced Chiller Sequencing

    Cooling Tower Optimization

    Variable Primary Chilled Water Flow Control

    Optimized based on Best System efficiency;

    and NOT best equipment efficiency

  • 7/29/2019 EW Luan Nguyen

    33/47

    s u s t a i n a b I l I t y

    Advanced Chiller Sequencing

    Results

    Good chiller sequencing and chiller loading

    CHILLER LOADING

    30

    40

    50

    60

    70

    80

    90

    100

    TIME

    %R

    LA

    CH-1

    CH-2

    CH-3

    CH-4

    CH-5

    CH-6

    5 10%chiller plant energy saving

  • 7/29/2019 EW Luan Nguyen

    34/47

    s u s t a i n a b I l I t y

    Energy Optimisation

    Cooling Tower Optimization

    But, Im tired Water is so cool, Im ok

  • 7/29/2019 EW Luan Nguyen

    35/47

    s u s t a i n a b I l I t y

    Energy Optimisation

    Cooling Tower Optimization

    Minimum chiller + cooling tower kW input

    condenser water temperature, F

    400

    74

    en

    ergyconsumption,

    kW

    76 78 80 8272

    300

    200

    100

    084

    tower

    chiller

    total

    optimalcontrol point

    3 5%chiller plant energy saving

  • 7/29/2019 EW Luan Nguyen

    36/47

    s u s t a i n a b I l I t y

    Scan and evaluate all AHU valves position every minute Reset pump speed according to satisfy most critical Fan coil

    Fan coils should equip with modulating control valves

    EarthWise Chiller Plant ControlSystem

    P

    Variable

    speedpump

    Fan coil with modulating valve

    VFD

    Energy Optimisation

    Variable Primary Chilled Water Flow ControlEnergy Optimisation

    Variable Primary Chilled Water Flow Control

    3 5%chiller plant energy saving

  • 7/29/2019 EW Luan Nguyen

    37/47

    s u s t a i n a b I l I t y

    Connected with the other system

    If you want to have a saving energy chiller system ,

    you must have Tranes chiller plant control

  • 7/29/2019 EW Luan Nguyen

    38/47

    s u s t a i n a b I l I t y

    Conclusion

    Use Earthwise concept help the owner savingboth first and operating cost

    Remember that the meter is on the building,not on the chiller

    The first cost saving is not account thereduction of piping, valve.

    Use the innovative chiller plant control for

    optimal HVAC system Tranes solution can help your building

    greener

  • 7/29/2019 EW Luan Nguyen

    39/47

    s u s t a i n a b I l I t y

    Yeah!

    Show me the references

  • 7/29/2019 EW Luan Nguyen

    40/47

    s u s t a i n a b I l I t y

    BITEXCO FINANCIAL TOWER

    THE HIGHEST BUILDING IN HCM CITY

    68 STOREYS

    4 x 900 TONS R123

    CENTRIFUGAL CHILLER

    5-13oC; 37-45oC

    YEAR: 2008-2009-2010

  • 7/29/2019 EW Luan Nguyen

    41/47

    s u s t a i n a b I l I t y

    Vincom Eden

    Complex in HCMC

    8x 1000RT

    CenTraVac R123

    Chiller

    Year: 2009

    5-13oC/ 32-39oC

  • 7/29/2019 EW Luan Nguyen

    42/47

    s u s t a i n a b I l I t y

    Crowne Plaza

    InterContinential

    5 Stars Hotel,

    in Hanoi

    4x 750RT

    R123 Centrifugal

    ChillerYear 2009

    5-12oC/32-37oC

  • 7/29/2019 EW Luan Nguyen

    43/47

    s u s t a i n a b I l I t y

    Intel Viet Nam Factory- A9T9

    4 x 2350 Tons

    R123 Duplex Chillers +

    AHU

    Installation year: 2008-

    2009

    5-13oC on Chilled Side

  • 7/29/2019 EW Luan Nguyen

    44/47

    s u s t a i n a b I l I t y

    Centre Point Office

    The 1st Green

    Building in HCMC

    R123 Chiller

    3 x 450RT

    Installation year :2008- 2009

    5-12oC/32-37oC

  • 7/29/2019 EW Luan Nguyen

    45/47

    s u s t a i n a b I l I t y

    Sheraton NhaTrangHotel

    3 x 700 Tons

    Centrifugal R123

    Chiller

    5-12oC/32-37oC

    Installation year :

    2008-2009

  • 7/29/2019 EW Luan Nguyen

    46/47

    s u s t a i n a b I l I t y

    2x 250 Tons

    RTHD

    Water-Cooled

    Screw Chiller

    5-12oC/32-40oC

    Year: 2009

    Cuu Long

    Commercial

    Center in

    Camau

  • 7/29/2019 EW Luan Nguyen

    47/47

    s u s t a i n a b I l I t y

    Questions orComments?