Evaluator: QW
Date: 04/03/19
Page 1
ASCE 41-17 Tier 1 Seismic Evaluation
Building Name: McCone Hall
CAAN ID: 1762
Auxiliary Building ID: N/A
Address: Core Campus, University of California, Berkeley, CA
Site location coordinates: Latitude 37.8743, Longitudinal -122.2594
Plan Image or Aerial Photo Exterior Elevation Photo
UCOP SEISMIC PERFORMANCE LEVEL (OR “RATING”) BASED ON TIER 1 EVALUATION FINDINGS: V
BUILDING DATA
ASCE 41-17 Model Building Type (Governing Building Type bolded for Seismic Risk Model when multiple
types exist):
a. Longitudinal Direction: C2: Concrete Shear Walls – Stiff Diaphragms
b. Transverse Direction: C2: Concrete Shear Walls – Stiff Diaphragms
Square Footage: 127,850 sf
Building Length: 234 ft
Building Width: 82 ft
Building Height: 78 ft
Story Height: 13 ft (Typical)
Number of stories above grade: 6
Number of basement stories below grade: 0
Year of Original Construction and Code Year: 1961, 1958 UBC (Assumed)
Year of Later Constuction and Code Year: Retrofit 1997 1991 UBC
COST RANGE TO RETROFIT (if applicable): Pending the results of the Tier II evaluation. It is estimated that
the retrofit cost (if required) will be in the medium range. Medium: over $50 per sf and less than $200 per
sf.
BUILDING DESCRIPTION
General
This building is estimated to have been built in 1959-1960 and is situated on a slightly sloping site from
north to south. The building has six stories with and a single-story penhouse at the roof level and is
approximately 78 feet tall. The building is rectangular with a footprint of about 234 feet in the N-S
Building Name: McCone Hall Evaluator: QW
CAAN ID: 1762 Date: 04/03/19
Page 2
direction and 82 feet in the E-W direction. The building area is approximately 127,850 square feet and
houses classrooms, offices, and laboratories. The building had two seismic retrofits in the 1990s. The
first, in 1993 thickened the perimeter concrete walls at the first level. The second retrofit, in 1997 added
concrete walls to the interior face of the north and south elevations, and transverse shear walls at the
west face of the building at a new stair tower.
Structural System
The gravity load structural system consists of concrete flat slabs, which are supported by concrete
columns at the building interior and concrete walls with pilasters at the exterior. The floor slabs are 9
½” thick. The lateral load system consists of punched reinforced concrete shear walls around the entire
perimeter of the building, There are also concrete shear walls at the interior of the building adjacent to
the stair cores and elevator shafts. The concrete floor slabs serve as horizontal diaphragms to transfer
the load to the exterior and interior shear walls. The foundation consists of spread footings at the north
end and caisoons at the south end.
Building Condition
Good.
Date of Site Visit: 03/25/2019, Russell Berkowitz, Forell/Elsesser Engineers
Limitations of walk-through: None
SITE INFORMATION
Site Class (A-F): C Basis: Geologic Hazards and Site Classification, Geomatrix Plate 2
Site Specific Ground Motion Study? Yes, 2015 Update to the Site-Specific Seismic Hazard Analyses and
Development of Seismic Design Ground Motions
BSE-1N Spectral Accelerations: Basis: 2015 Site Specific Report Table 5 for 10-35 ft Soil
SDS: 2.34 SD1: 0.71
BSE-2E Spectral Accelerations: Basis: 2015 Site Specific Report Table 6 for 10-35 ft Soil
SXS: 3.16 SX1: 0.96 (Note: SXS taken as 90% of the maximum spectral acceleration, obtained from the site-
specific spectrum, at any period within 0.2s to 5s, inclusive, in conformance with ASCE41-17 Section
2.4.2.1 and ASCE 7-16, Section 21.4 guidelines)
Level of Seismicity: High
Performance Level: Collapse Prevention Structural Performance
Geologic Hazards:
Fault Rupture No Basis: California Geological Survey Website
https://maps.conservation.ca.gov/cgs/informationwarehouse/regulatorymaps/
Liquefaction No Basis California Geological Survey Website
https://maps.conservation.ca.gov/cgs/informationwarehouse/regulatorymaps/
Landslide No Basis: California Geological Survey Website
https://maps.conservation.ca.gov/cgs/informationwarehouse/regulatorymaps/
PREVIOUS RATINGS SUMMARY
1. Good – 1997 Preliminary Seismic Evaluation (SAFER), Degenkolb Engineers
Building Name: McCone Hall Evaluator: QW
CAAN ID: 1762 Date: 04/03/19
Page 3
DOCUMENTATION
Architectural Drawings: Original Construction; C. & J. Warnecke Architects, January 1959, Sheets
1-25
Structural Drawings: Original Construction; L. H. & B. L. Nishkian , January 1959, Sheets S1 – S16
1993 Seismic Retrofit: Gutierrez Architects A0-A6, Anrold Luft Structural Engineeres, S1-S11
January 1993
1997 Seismic Retrofit: Gordon Chong Architects 97 Sheets, Degenkolb Engineers 18 Sheets,
March 1997.
Seismic Evaluations: 1997 Preliminary Seismic Evaluation, Degenkolb Engineers, June 5, 1997
CONSTRUCTION DATA
LATERAL-FORCE-RESISTING SYSTEM
Longitudinal Transverse
ASCE 41-17 Building Type: C2: Concrete Shear Walls
with Stiff Diaphragms
C2: Concrete Shear Walls
with Stiff Diaphragms
Diaphragms: Concrete Flat Slab Concrete Flat Slab
Vertical Elements: Punched Concrete Shear
Walls
Punched Concrete Shear
Walls
Connections: Slab/Wall Dowels Slab/Wall Dowels
Details: Structural Details: S-8 – S-16 Structural Details: S-8 – S-16
Estimated Fundamental Period, T (sec): 0.525 s 0.525 s
BSE-2E Spectral Acceleration, Sa: 1.829 g 1.829 g
Modification Factor, C: 1.0 (C2 – Table 4-7) 1.0 (C2 – Table 4-7)
Building Weight, W (kips): 36,615 36,615
Gravity Load Structural System: One-way concrete flat slabs supported by interior concrete columns
and interior and exterior concrete walls with pilasters.
Exterior Transverse Walls: Reinforced Concrete Walls Opening(s)? Yes
Exterior Longitudinal Walls: Reinforced Concrete Walls Opening(s)? Yes
Roof Materials/Framing: 9 ½” Concrete Slab with drop panels
Intermediate Floors/Framing: 9 ½” Concrete Slab with drop panels
Ground Floor: Slab on Grade
Columns: 20”x20”, 20”x28”, 24”x24”,
26”x26”, 28”x28” Reinforced
Concrete Columns.
Foundation: Spread footings
and caissons
General Condition of Structure: Good
Evidence of Settling?: No
Special Features & Comments:
Building Name: McCone Hall Evaluator: QW
CAAN ID: 1762 Date: 04/03/19
Page 4
Seismic Base Shear, V (kips): 66,963 66,963
System Modification Factor, Ms: 4.5 4.5
Significant Structural Deficiencies, Potentially Affecting Seismic Performance Level Designation:
Lateral System Stress Check (wall shear, column shear or flexure, or brace axial as applicable)
☐ Load Path
☐ Adjacent Buildings
☐ Weak Story
☐ Soft Story
☐ Geometry (vertical irregularities)
☐ Torsion
☐ Mass – Vertical Irregularity
☐ Cripple Walls
☐ Wood Sills (bolting)
☐ Diaphragm Continuity
☐ Openings at Shear Walls (concrete or masonry)
☐ Liquefaction
☐ Slope Failure
☐ Surface Fault Rupture
☐ Masonry or Concrete Wall Anchorage at Flexible Diaphragm
☐ URM wall height to thickness ratio
☐ URM Parapets or Cornices
☐ URM Chimney
☐ Heavy Partitions Braced by Ceilings
☐ Appendages
OVERALL SEISMIC DEFICIENCIES & EXPECTED SEISMIC PERFORMANCE
The main deficiency for the structure is general overstress of the shear walls. The shear stress DCRs in
the transverse building direction are approximately 2.5 based on the Tier 1 Quick Check. The columns do
not have adequate shear capacity to develop their flexural strength based on a fixed-fixed assumption. It
is estimate that the columns can withstand approximately one-half inch of drift prior to shear failure.
It is recommended that the deficiencies noted above be further evaluated using a Tier 2 or Tier 3
evaluation to determine if the rating could be improved to a “IV”.
The main non-structural life-safety concerns are unrestrained items on laboratory shelving. These
elements have the potential to create a falling hazard that may pose a threat to life safely. It is
recommended that items be stored properly and shelves with boxes braced to avoid blocking egress in a
seismic event.
Building Name: McCone Hall Evaluator: QW
CAAN ID: 1762 Date: 04/03/19
Page 5
Collapse Prevention Basic Configuration Checklist Non-Complaint Items
• OVERTURNING
Collapse Prevention Structural Checklist for building Type C2-C2A Non-Complaint Items
• SHEAR STRESS CHECK
• DEFLECTION COMPATIBILITY
• OPENINGS AT SHEAR WALLS
Seismic Retrofit Concept Sketches/Description (only if above-listed rating is V or greater):
• Add new shear walls in the transverse direction to provide strength and stiffness.
• Add collectors to deliver force to new shear walls
• Strengthen columns with fiberwrap where the anticipated drifts would lead to shear failure of the
columns.
• Provide new foundations at new shear wall elements. Assume soil anchors required at ends of
foundations to provide additional overturning resistance.
Building Name: McCone Hall Evaluator: QW
CAAN ID: 1762 Date: 04/03/19
Appendices
A. Additional Photos
B. ASCE 41-17 Tier 1 Checklists (Structural)
C. UCOP Seismic Safety Policy Falling Hazards Assessment Summary
D. Quick Check Calculations
Building Name: McCone Hall Evaluator: QW
CAAN ID: 1762 Date: 04/03/19
Appendix A – Additional Photos
Building Name: McCone Hall Evaluator: QW
CAAN ID: 1762 Date: 04/03/19
Building Exterior Elevation
Building Name: McCone Hall Evaluator: QW
CAAN ID: 1762 Date: 04/03/19
Roof – Penthouse Elevation
Rooftop Equipment
Building Name: McCone Hall Evaluator: QW
CAAN ID: 1762 Date: 04/03/19
Laboratory
Unrestrained Laboratory Equipment
Building Name: McCone Hall Evaluator: QW
CAAN ID: 1762 Date: 04/03/19
Appendix B – ASCE 41-17 Tier I Checklists (Structural)
UC Campus: Berkeley Date: April 2, 2019
Building CAAN: 1762 Auxiliary CAAN:
N/A By Firm: Forell/Elsesser Engineers
Building Name: McCone Hall Initials: QW Checked: RB
Building Address: Core Campus, University of California, Berkeley, CA Page: 1 of 3
ASCE 41-17
Collapse Prevention Basic Configuration Checklist
Note: C = Compliant NC = Noncompliant N/A = Not Applicable U = Unknown
LOW SEISMICITY
BUILDING SYSTEMS - GENERAL
Description
C NC N/A U
LOAD PATH: The structure contains a complete, well-defined load path, including structural elements and connections, that
serves to transfer the inertial forces associated with the mass of all elements of the building to the foundation. (Commentary:
Sec. A.2.1.1. Tier 2: Sec. 5.4.1.1)
Comments:
C NC N/A U
ADJACENT BUILDINGS: The clear distance between the building being evaluated and any adjacent building is greater than
0.25% of the height of the shorter building in low seismicity, 0.5% in moderate seismicity, and 1.5% in high seismicity.
(Commentary: Sec. A.2.1.2. Tier 2: Sec. 5.4.1.2)
Comments:
C NC N/A U
MEZZANINES: Interior mezzanine levels are braced independently from the main structure or are anchored to the seismic-
force-resisting elements of the main structure. (Commentary: Sec. A.2.1.3. Tier 2: Sec. 5.4.1.3)
Comments:
BUILDING SYSTEMS - BUILDING CONFIGURATION
Description
C NC N/A U
WEAK STORY: The sum of the shear strengths of the seismic-force-resisting system in any story in each direction is not
less than 80% of the strength in the adjacent story above. (Commentary: Sec. A2.2.2. Tier 2: Sec. 5.4.2.1)
Comments:
C NC N/A U
SOFT STORY: The stiffness of the seismic-force-resisting system in any story is not less than 70% of the seismic-force-
resisting system stiffness in an adjacent story above or less than 80% of the average seismic-force-resisting system stiffness
of the three stories above. (Commentary: Sec. A.2.2.3. Tier 2: Sec. 5.4.2.2)
Comments:
C NC N/A U
VERTICAL IRREGULARITIES: All vertical elements in the seismic-force-resisting system are continuous to the foundation.
(Commentary: Sec. A.2.2.4. Tier 2: Sec. 5.4.2.3)
Comments:
UC Campus: Berkeley Date: April 2, 2019
Building CAAN: 1762 Auxiliary CAAN:
N/A By Firm: Forell/Elsesser Engineers
Building Name: McCone Hall Initials: QW Checked: RB
Building Address: Core Campus, University of California, Berkeley, CA Page: 2 of 3
ASCE 41-17
Collapse Prevention Basic Configuration Checklist
Note: C = Compliant NC = Noncompliant N/A = Not Applicable U = Unknown
C NC N/A U
GEOMETRY: There are no changes in the net horizontal dimension of the seismic-force-resisting system of more than 30%
in a story relative to adjacent stories, excluding one-story penthouses and mezzanines. (Commentary: Sec. A.2.2.5. Tier 2:
Sec. 5.4.2.4)
Comments:
C NC N/A U
MASS: There is no change in effective mass of more than 50% from one story to the next. Light roofs, penthouses, and
mezzanines need not be considered. (Commentary: Sec. A.2.2.6. Tier 2: Sec. 5.4.2.5)
Comments:
C NC N/A U
TORSION: The estimated distance between the story center of mass and the story center of rigidity is less than 20% of
the building width in either plan dimension. (Commentary: Sec. A.2.2.7. Tier 2: Sec. 5.4.2.6)
Comments:
MODERATE SEISMICITY (COMPLETE THE FOLLOWING ITEMS IN ADDITION TO THE ITEMS FOR LOW SEISMICITY)
GEOLOGIC SITE HAZARD
Description
C NC N/A U
LIQUEFACTION: Liquefaction-susceptible, saturated, loose granular soils that could jeopardize the building’s seismic
performance do not exist in the foundation soils at depths within 50 ft (15.2m) under the building. (Commentary: Sec. A.6.1.1.
Tier 2: 5.4.3.1)
Comments:
C NC N/A U
SLOPE FAILURE: The building site is located away from potential earthquake-induced slope failures or rockfalls so that it is unaffected by such failures or is capable of accommodating any predicted movements without failure. (Commentary: Sec. A.6.1.2. Tier 2: 5.4.3.1)
Comments:
C NC N/A U
SURFACE FAULT RUPTURE: Surface fault rupture and surface displacement at the building site are not anticipated.
(Commentary: Sec. A.6.1.3. Tier 2: 5.4.3.1)
Comments:
UC Campus: Berkeley Date: April 2, 2019
Building CAAN: 1762 Auxiliary CAAN:
N/A By Firm: Forell/Elsesser Engineers
Building Name: McCone Hall Initials: QW Checked: RB
Building Address: Core Campus, University of California, Berkeley, CA Page: 3 of 3
ASCE 41-17
Collapse Prevention Basic Configuration Checklist
Note: C = Compliant NC = Noncompliant N/A = Not Applicable U = Unknown
HIGH SEISMICITY (COMPLETE THE FOLLOWING ITEMS IN ADDITION TO THE ITEMS FOR MODERATE SEISMICITY)
FOUNDATION CONFIGURATION
Description
C NC N/A U
OVERTURNING: The ratio of the least horizontal dimension of the seismic-force-resisting system at the foundation level to the building height (base/height) is greater than 0.6Sa. (Commentary: Sec. A.6.2.1. Tier 2: Sec. 5.4.3.3)
Comments: D/H = 1.05 vs. 0.6Sa = 1.10. However, this condition is not expected to present a significant threat to life
safety.
C NC N/A U
TIES BETWEEN FOUNDATION ELEMENTS: The foundation has ties adequate to resist seismic forces where footings, piles, and piers are not restrained by beams, slabs, or soils classified as Site Class A, B, or C. (Commentary: Sec. A.6.2.2. Tier 2: Sec. 5.4.3.4)
Comments:
UC Campus: UC Berkeley Date: April 2, 2019
Building CAAN: 1762 Auxiliary CAAN:
By Firm: Forell/Elsesser Engineers
Building Name: McCone Hall Initials: QW Checked: RB
Building Address: Core Campus, University of California, Berkeley, CA Page: 1 of 3
ASCE 41-17
Collapse Prevention Structural Checklist For Building Type C2-C2A
Note: C = Compliant NC = Noncompliant N/A = Not Applicable U = Unknown
Low And Moderate Seismicity
Seismic-Force-Resisting System
Description
C NC N/A U
COMPLETE FRAMES: Steel or concrete frames classified as secondary components form a complete vertical-load-carrying system. (Commentary: Sec. A.3.1.6.1. Tier 2: Sec. 5.5.2.5.1)
Comments:
C NC N/A U
REDUNDANCY: The number of lines of shear walls in each principal direction is greater than or equal to 2. (Commentary: Sec. A.3.2.1.1. Tier 2: Sec. 5.5.1.1)
Comments:
C NC N/A U
SHEAR STRESS CHECK: The shear stress in the concrete shear walls, calculated using the Quick Check procedure of Section 4.4.3.3, is less than the greater of 100 lb/in.2 (0.69 MPa) or 2√f’c. (Commentary: Sec. A.3.2.2.1. Tier 2: Sec. 5.5.3.1.1)
Comments: Shear stress check is not satisfied N-S direction: Level 1: Shear Stress = 140 psi E-W Direction: Level 1: Shear Stress = 250 psi
C NC N/A U
REINFORCING STEEL: The ratio of reinforcing steel area to gross concrete area is not less than 0.0012 in the vertical direction and 0.0020 in the horizontal direction. (Commentary: Sec. A.3.2.2.2. Tier 2: Sec. 5.5.3.1.3)
Comments:
Connections
Description
C NC N/A U
WALL ANCHORAGE AT FLEXIBLE DIAPHRAGMS: Exterior concrete or masonry walls that are dependent on flexible diaphragms for lateral support are anchored for out-of-plane forces at each diaphragm level with steel anchors, reinforcing dowels, or straps that are developed into the diaphragm. Connections have strength to resist the connection force calculated in the Quick Check procedure of Section 4.4.3.7. (Commentary: Sec. A.5.1.1. Tier 2: Sec. 5.7.1.1)
Comments:
UC Campus: UC Berkeley Date: April 2, 2019
Building CAAN: 1762 Auxiliary CAAN:
By Firm: Forell/Elsesser Engineers
Building Name: McCone Hall Initials: QW Checked: RB
Building Address: Core Campus, University of California, Berkeley, CA Page: 2 of 3
ASCE 41-17
Collapse Prevention Structural Checklist For Building Type C2-C2A
Note: C = Compliant NC = Noncompliant N/A = Not Applicable U = Unknown
C NC N/A U
TRANSFER TO SHEAR WALLS: Diaphragms are connected for transfer of seismic forces to the shear walls. (Commentary: Sec. A.5.2.1. Tier 2: Sec. 5.7.2)
Comments:
C NC N/A U
FOUNDATION DOWELS: Wall reinforcement is doweled into the foundation with vertical bars equal in size and spacing to the vertical wall reinforcing directly above the foundation. (Commentary: Sec. A.5.3.5. Tier 2: Sec. 5.7.3.4)
Comments:
High Seismicity (Complete The Following Items In Addition To The Items For Low And Moderate Seismicity)
Seismic-Force-Resisting System
Description
C NC N/A U
DEFLECTION COMPATIBILITY: Secondary components have the shear capacity to develop the flexural strength of the components. (Commentary: Sec. A.3.1.6.2. Tier 2: Sec. 5.5.2.5.2)
Comments: Column deflection compatibility checks are not satisfied. Type C: DCR = 1.61
C NC N/A U
FLAT SLABS: Flat slabs or plates not part of the seismic-force-resisting system have continuous bottom steel through the column joints. (Commentary: Sec. A.3.1.6.3. Tier 2: Sec. 5.5.2.5.3)
Comments:
C NC N/A U
COUPLING BEAMS: The ends of both walls to which the coupling beam is attached are supported at each end to resist vertical loads caused by overturning. (Commentary: Sec. A.3.2.2.3. Tier 2: Sec. 5.5.3.2.1)
Comments:
Diaphragms (Stiff Or Flexible)
Description
C NC N/A U
DIAPHRAGM CONTINUITY: The diaphragms are not composed of split-level floors and do not have expansion joints. (Commentary: Sec. A.4.1.1. Tier 2: Sec. 5.6.1.1)
Comments:
UC Campus: UC Berkeley Date: April 2, 2019
Building CAAN: 1762 Auxiliary CAAN:
By Firm: Forell/Elsesser Engineers
Building Name: McCone Hall Initials: QW Checked: RB
Building Address: Core Campus, University of California, Berkeley, CA Page: 3 of 3
ASCE 41-17
Collapse Prevention Structural Checklist For Building Type C2-C2A
Note: C = Compliant NC = Noncompliant N/A = Not Applicable U = Unknown
C NC N/A U
OPENINGS AT SHEAR WALLS: Diaphragm openings immediately adjacent to the shear walls are less than 25% of the wall length. (Commentary: Sec. A.4.1.4. Tier 2: Sec. 5.6.1.3)
Comments: The walls adjacent to stairs and elevators have diaphragm openings for the entire length of the wall at all
levels. However, there is slab on the adjacent side of the opening.
Flexible Diaphragms
Description
C NC N/A U
CROSS TIES: There are continuous cross ties between diaphragm chords. (Commentary: Sec. A.4.1.2. Tier 2: Sec. 5.6.1.2)
Comments:
C NC N/A U
STRAIGHT SHEATHING: All straight-sheathed diaphragms have aspect ratios less than 2-to-1 in the direction being considered. (Commentary: Sec. A.4.2.1. Tier 2: Sec. 5.6.2)
Comments:
C NC N/A U
SPANS: All wood diaphragms with spans greater than 24 ft (7.3 m) consist of wood structural panels or diagonal sheathing. (Commentary: Sec. A.4.2.2. Tier 2: Sec. 5.6.2)
Comments:
C NC N/A U
DIAGONALLY SHEATHED AND UNBLOCKED DIAPHRAGMS: All diagonally sheathed or unblocked wood structural panel diaphragms have horizontal spans less than 40 ft (12.2 m) and aspect ratios less than or equal to 4-to-1. (Commentary: Sec. A.4.2.3. Tier 2: Sec. 5.6.2)
Comments:
C NC N/A U
OTHER DIAPHRAGMS: Diaphragms do not consist of a system other than wood, metal deck, concrete, or horizontal bracing. (Commentary: Sec. A.4.7.1. Tier 2: Sec. 5.6.5)
Comments:
Connections
Description
C NC N/A U
UPLIFT AT PILE CAPS: Pile caps have top reinforcement, and piles are anchored to the pile caps. (Commentary: Sec. A.5.3.8. Tier 2: Sec. 5.7.3.5)
Comments:
Building Name: McCone Hall Evaluator: QW
CAAN ID: 1762 Date: 04/03/19
Appendix C – UCOP Seismic Safety Policy Falling Hazards
Assessment Summary
UC Campus: UC Berkeley Date: April 2, 2019
Building CAAN: 1762 Auxiliary CAAN:
N/A By Firm: Forell/Elsesser Engineers
Building Name: McCone Hall Initials: QW Checked: RB
Building Address: Core Campus, University of California, Berkeley, CA Page: 1 of 1
UCOP SEISMIC SAFETY POLICY
Falling Hazard Assessment Summary
Note: P= Present, N/A = Not Applicable
Description
P N/A
Heavy ceilings, features or ornamentation above large lecture halls, auditoriums, lobbies, or other areas where large numbers of people congregate (50 ppl or more)
Comments:
P N/A
Heavy masonry or stone veneer above exit ways or public access areas
Comments:
P N/A
Unbraced masonry parapets, cornices, or other ornamentation above exit ways or public access areas
Comments:
P N/A
Unrestrained hazardous material storage
Comments:
P N/A
Masonry chimneys
Comments:
P N/A
Unrestrained natural gas-fueled equipment such as water heaters, boilers, emergency generators, etc.
Comments:
P N/A
Other: Unrestrained items
Comments: Unrestrained items were found on laboratory shelves. These elements have the potential to create
a falling hazard that may pose a threat to life safely. It is recommended that items be stored properly and shelves with boxes braced to avoid blocking egress in a seismic event.
P N/A
Other:
Comments:
P N/A
Other:
Comments:
Falling Hazard Risk: Low
Building Name: McCone Hall Evaluator: QW
CAAN ID: 1762 Date: 04/03/19
Appendix D – Quick Check Calculations
FORELL/ELSESSER ENGINEERS, INC.STRUCTURAL ENGINEERS
160 PINE ST., 6TH FLOOR (415) 837-0700
SAN FRANCISCO, CA 94111 FAX (415) 837-0800
McCone Hall
CAAN ID: 1762
Evaluator: QW
Date: 5/8/2019
McCone Hall
UC Berkeley
Berkeley, California
37.8743 (Source: Google Earth)
-122.2594 (Source: Google Earth)
ASCE 41-17
2.340 g Table 5, 10 - 35 ft Soil
0.710 g Table 5, 10 - 35 ft Soil
Level of Seismicity = HIGH
SX1,BSE-1N =
2015 Site-Specific Seismic Hazard Analyses
Building Code Reference
2015 Site-Specific Seismic Hazard Analyses
Site Parameters
Site Latitude
Site Longitude
SXS,BSE-1N =
Site & Seismicity Information
FORELL/ELSESSER ENGINEERS, INC.STRUCTURAL ENGINEERS
160 PINE ST., 6TH FLOOR (415) 837-0700
SAN FRANCISCO, CA 94111 FAX (415) 837-0800
McCone Hall
CAAN ID: 1762
Evaluator: QW
Date: 5/8/2019
Determine BSE-2E Spectral Response Acceleration Parameters
McCone Hall
UC Berkeley
Berkeley, California
37.8743 (Source: Google Earth)
-122.2594 (Source: Google Earth)
C Geologic Hazards & Site Classification,
Liquefaction Potential Low Geomatrix Plate 2
ASCE 41-17
BSE-2E
3.510 g Table 6, 10 - 35 ft Soil
90% Per ASCE41-17, Sect. 2.4.2.1 &
ASCE7-16, Sect. 21.4
3.159 g
0.960 g Table 6, 10 - 35 ft Soil
SXS,BSE-2E, Max 0.2s to 5s =
SX1,BSE-2E =
2015 Site-Specific Seismic Hazard Analyses
Building Code Reference
EQ Hazard Level
2015 Site-Specific Seismic Hazard Analyses
% Multiplier
SXS,BSE-2E =
Site Parameters
Site Latitude
Site Longitude
Site Data
Site Soil Classification
FORELL/ELSESSER ENGINEERS, INC.STRUCTURAL ENGINEERS
160 PINE ST., 6TH FLOOR (415) 837-0700
SAN FRANCISCO, CA 94111 FAX (415) 837-0800
McCone Hall
CAAN ID: 1762
Evaluator: QW
Date: 5/8/2019
Determine Building Period per ASCE 41-17 Section 4.4.2.4
Ct β
Steel moment-resisting frames (S1, S1a) 0.035 0.80
Concrete moment-resisting frames (C1) 0.018 0.90
Steel eccentrically braced frames (S2, S2a) 0.030 0.75
0.020 0.75
Structure
Type
Height of Roof Level Above Base = 78.0 ft
Ct
β
hn
T = Cthnβ
Transverse
78.0 ft
Longitudinal
0.020
0.750
Period, T , ASCE 41-17 Equation 4-4
0.525 s
Values of Period Parameters C t and β
Structure Type
All other framing systems
0.525 s
Longitudinal Transverse
C2 C2
Concrete Shear Walls - Stiff DiaphragmsConcrete Shear Walls - Stiff
Diaphragms
78.0 ft
0.020
0.750
FORELL/ELSESSER ENGINEERS, INC.STRUCTURAL ENGINEERS
160 PINE ST., 6TH FLOOR (415) 837-0700
SAN FRANCISCO, CA 94111 FAX (415) 837-0800
McCone Hall
CAAN ID: 1762
Evaluator: QW
Date: 5/8/2019
Weight of Materials
Concrete 150 pcf
Floor Length 234.0 ft
Floor Width 82.00 ft
Floor Area 19188 sq.ft
1st - 2nd Floor Area Ratio
9 1/2" NWC Slab 118.75 psf 19188 sq.ft 1.00 118.75 psf
7 1/2" Drop Panel 93.75 psf 4760 sq.ft 0.25 23.26 psf
25% of LL 50.00 psf 9500 sq.ft 0.50 24.76 psf
Flooring 3.00 psf 19188 sq.ft 1.00 3.00 psf
Concrete Overpour 3.00 psf 19188 sq.ft 1.00 3.00 psf
Ceiling 3.00 psf 19188 sq.ft 1.00 3.00 psf
Distributed M/E/P 5.00 psf 19188 sq.ft 1.00 5.00 psf
Partitions 10.0 psf 19188 sq.ft 1.00 10.00 psf
Misc 5.00 psf 19188 sq.ft 1.00 5.00 psf
Total = 196 psf
3rd - 5th Floor Area Ratio
9 1/2" NWC Slab 118.75 psf 19188 sq.ft 1.00 118.75 psf
7 1/2" Drop Panel 93.75 psf 4760 sq.ft 0.25 23.26 psf
25% of LL 50.00 psf 4800 sq.ft 0.25 12.51 psf
Flooring 3.00 psf 19188 sq.ft 1.00 3.00 psf
Concrete Overpour 3.00 psf 19188 sq.ft 1.00 3.00 psf
Ceiling 3.00 psf 19188 sq.ft 1.00 3.00 psf
Distributed M/E/P 5.00 psf 19188 sq.ft 1.00 5.00 psf
Partitions 10.0 psf 19188 sq.ft 1.00 10.00 psf
Misc 5.00 psf 19188 sq.ft 1.00 5.00 psf
Total = 184 psf
Penthouse Floor & Main Roof Area Ratio
9 1/2" NWC Slab 118.75 psf 19188 sq.ft 1.00 118.75 psf
7 1/2" Drop Panel 93.75 psf 4760 sq.ft 0.25 23.26 psf
4" Machine Room Slab 50.00 psf 2000 sq.ft 0.10 5.21 psf
25% of LL 37.50 psf 6300 sq.ft 0.33 12.31 psf
Roofing 5.00 psf 19188 sq.ft 1.00 5.00 psf
Concrete Overpour 3.00 psf 19188 sq.ft 1.00 3.00 psf
Topping Slab 25.0 psf 19188 sq.ft 1.00 25.00 psf
Distributed M/E/P 5.00 psf 19188 sq.ft 1.00 5.00 psf
Equipment 10.0 psf 19188 sq.ft 1.00 10.00 psf
Partitions 5.00 psf 19188 sq.ft 1.00 5.00 psf
Misc 5.00 psf 19188 sq.ft 1.00 5.00 psf
Total = 218 psf
Penthouse Roof Area Ratio
6" NWC Slab 75.00 psf 6857 sq.ft 1.00 75.00 psf
Concrete Beams 3.00 psf 6857 sq.ft 1.00 3.00 psf
Roofing 5.00 psf 6857 sq.ft 1.00 5.00 psf
Concrete Overpour 3.00 psf 6857 sq.ft 1.00 3.00 psf
Flooring 3.00 psf 6857 sq.ft 1.00 3.00 psf
Distributed M/E/P 5.00 psf 6857 sq.ft 1.00 5.00 psf
Partitions 10.0 psf 6857 sq.ft 1.00 10.00 psf
Misc 5.00 psf 6857 sq.ft 1.00 5.00 psf
Total = 109 psf
FORELL/ELSESSER ENGINEERS, INC.
STRUCTURAL ENGINEERS
160 PINE ST., 6TH FLOOR (415) 837-0700
SAN FRANCISCO, CA 94111 FAX (415) 837-0800
McCone Hall
CAAN ID: 1762
Evaluator: QW
Date: 5/8/2019
WALLS
2 2 19 6 20 6 16 10
2 10 8 5 10 6 16 10
2 6 8 5 10 6 7 0
26 0 19 6 10 6 17 0
26 0 19 6 10 6 17 0
26 0 10 8 10 6 19 9
26 0 136 6 10 6 19 9
9 6 52 10 10 6 16 2
10 10 271 52 13 6 16 11.5
10 10 Length 275 ft 13 6 16 11.5
10 10 Thickness 8 in 116 60 159 63
10 10 Wall Area 184 sf Length 121 ft Length 164 ft
4 4 Thickness 18 in Thickness 8 in
3 3 Wall Area 182 sf Wall Area 110 sf
117 0
283 71
Length 289 ft 29 20
Thickness 10 in 29 20
Wall Area 241 sf 58 40
Length 61 ft
Thickness 24 in
9 6 26 0 Wall Area 123 sf
9 6 26 0
9 6 Length 26 ft
19 6 Thickness 23 in
19 6 Wall Area 50 sf
19 6
19 6 20 0
9 6 20 0
9 6 Length 20 ft
9 6 Thickness 10 in
9 6 Wall Area 17 sf
9 6
9 6
157 78
Length 164 ft
Thickness 18 in
Wall Area 245 sf
X-DIRECTION
Exterior Walls Interior Walls
19
97
Y-DIRECTION
Exterior Walls Interior Walls
19
97
19
59
19
93
, 1
99
7
19
93
, 1
99
7
19
59
19
59
FORELL/ELSESSER ENGINEERS, INC.
STRUCTURAL ENGINEERS
160 PINE ST., 6TH FLOOR (415) 837-0700
SAN FRANCISCO, CA 94111 FAX (415) 837-0800
McCone Hall
CAAN ID: 1762
Evaluator: QW
Date: 5/8/2019
WINDOWS
12 0 5 0
5 0 5 0
5 0 5 0
5 0 5 0
5 0 5 0
5 0 5 0
5 0 5 0
5 0 5 0
5 0 5 0
5 0 5 0
5 0 5 0
5 0 5 0
5 0 5 0
5 0 5 0
5 0 70 0
5 0 70
5 0
5 0
5 0
5 0
5 0
5 0
5 0
5 0
5 0
5 0
5 0
5 0
5 0
5 0
5 0
5 0
167 0
167
Exterior Windows Exterior Windows
X-DIRECTION Y-DIRECTION
FORELL/ELSESSER ENGINEERS, INC.STRUCTURAL ENGINEERS
160 PINE ST., 6TH FLOOR (415) 837-0700
SAN FRANCISCO, CA 94111 FAX (415) 837-0800
McCone Hall
CAAN ID: 1762
Evaluator: QW
Date: 5/8/2019
Summary of Column Seismic Weight
Column Weights
Story
Penthouse Roof 0 0 24 24 0 0 0 0
Roof 20 20 24 24 24 24 20 20
Level 5 20 20 24 24 24 24 20 20
Level 4 20 20 24 24 24 24 20 20
Level 3 20 20 24 24 24 24 20 20
Level 2 20 20 26 26 26 26 20 20
Level 1 20 20 28 28 28 28 20 28
Column Area
Story 17 14 2 15
Penthouse Roof 0 576 0 0
Roof 400 576 576 400
Level 5 400 576 576 400
Level 4 400 576 576 400
Level 3 400 576 576 400
Level 2 400 676 676 400
Level 1 400 784 784 560
Story H (ft) A (sq.ft) W (K)
Penthouse Roof 13 56 55
Roof 13 153 204
Level 5 13 153 298
Level 4 13 153 298
Level 3 13 153 298
Level 2 13 164 309
Level 1 13 193 348
Total Column Seismic Weight = 1809 K
153
153
153
164
193
150 pcfConcrete
153
Column Sizes (in x in)
Total Area (sf)
56
FORELL/ELSESSER ENGINEERS, INC.STRUCTURAL ENGINEERS
160 PINE ST., 6TH FLOOR (415) 837-0700
SAN FRANCISCO, CA 94111 FAX (415) 837-0800
McCone Hall
CAAN ID: 1762
Evaluator: QW
Date: 5/8/2019
Summary of Wall Seismic WeightConcrete 150 pcf
Exterior Cement Plaster 10.00 psf
Interior Insulation 5.00 psf
Interior Plaster 10.00 psf
Glass window 20.00 psf
Wall Geometry
Length Width Perimeter
Exterior Wall 534 182 716
Interior Wall 184 232 416
Glass Window 167 70 474
Wall Weights
Wall
Thickness (in)
Wall Unit
Weight
(psf)
Wall Trib
Height
(ft)
Wall
Length
(ft)
Overall
Wall Area
(sq. ft.)
Wall Weight
(kips)
Roof Level Walls
Exterior Concrete Wall (Below) 10 150 6.50 716 4652 698
Interior Concrete Wall (Below) 8 125 6.50 416 2702 338
Glazing (Below) - 20 4.00 474 1896 38 1073
Level 1-5 Walls
Exterior Concrete Wall (Above) 10 150 6.50 716 4652 698
Interior Concrete Wall (Above) 8 125 6.50 416 2702 338
Glazing (Above) - 20 4.00 474 1896 38
Exterior Concrete Wall (Below) 10 150 6.50 716 4652 698
Interior Concrete Wall (Below) 8 125 6.50 416 2702 338
Glazing (Below) - 20 4.00 474 1896 38 2147
Story
Penthouse Roof 0
Roof 1073
Level 5 2147
Level 4 2147
Level 3 2147
Level 2 2147
Level 1 2147
Total Wall Seismic Weight = 11808 K
FORELL/ELSESSER ENGINEERS, INC.STRUCTURAL ENGINEERS
160 PINE ST., 6TH FLOOR (415) 837-0700
SAN FRANCISCO, CA 94111 FAX (415) 837-0800
McCone Hall
CAAN ID: 1762
Evaluator: QW
Date: 5/8/2019
Summary of Seismic Weight
Original Building
Flat Weights
LevelFlat Unit Weight
(psf)
Flat Area
(sf)
Flat Weight
(K)
Column
Weight (K)
Wall Weight
(K)
Penthouse Roof 109 6857 747 55 0
Roof 218 19188 4174 204 1073
Level 5 184 19188 3521 298 2147
Level 4 184 19188 3521 298 2147
Level 3 184 19188 3521 298 2147
Level 2 196 19188 3756 309 2147
Level 1 196 19188 3756 348 2147
Total Seismic Weight = 22998 K 1809 K 11808 K
Building Weight Summary:
Penthouse Roof 802 kips
Roof 5451 kips
Level 5 5966 kips
Level 4 5966 kips
Level 3 5966 kips
Level 2 6212 kips
Level 1 6251 kips
Total Building Seismic Weight = 36615 kips
FORELL/ELSESSER ENGINEERS, INC.STRUCTURAL ENGINEERS
160 PINE ST., 6TH FLOOR (415) 837-0700
SAN FRANCISCO, CA 94111 FAX (415) 837-0800
McCone Hall
CAAN ID: 1762
Evaluator: QW
Date: 5/8/2019
Determine Psuedo Seismic Force per ASCE 41-17 Section 4.4.2.1
Number of Stories = 6
Building Type C2
Period 0.525
SXS 3.159
SX1 0.960
SX1 / T 1.829 ASCE 41-17, Section 4.4.2.3, Eq. 4-3
Sa 1.829
C 1
W 36615 kips
V 66963 kips
0.6Sa 1.10
D 82
H 78
D/H 1.05
D/H > 0.6Sa No
FORELL/ELSESSER ENGINEERS, INC.STRUCTURAL ENGINEERS
160 PINE ST., 6TH FLOOR (415) 837-0700
SAN FRANCISCO, CA 94111 FAX (415) 837-0800
McCone Hall
CAAN ID: 1762
Evaluator: QW
Date: 5/8/2019
Story Shear Forces per ASCE 41-17 Section 4.4.2.2
Original Building
V = 66963 kips
k= 1.01
LevelWeight
(kips)
Height
(ft)w x h
k Cvx
Fx
(kips)
Vj
(kips)
Penthouse Roof 802 91 77204 0.04 2944 2944
Roof 5451 78 448915 0.26 17117 20060
Level 5 5966 65 408526 0.23 15577 35637
Level 4 5966 52 325913 0.19 12427 48063
Level 3 5966 39 243560 0.14 9287 57350
Level 2 6212 26 168211 0.10 6414 63764
Level 1 6251 13 83903 0.05 3199 66963
1756232
� ��ℎ��
����
FORELL/ELSESSER ENGINEERS, INC.STRUCTURAL ENGINEERS
160 PINE ST., 6TH FLOOR (415) 837-0700
SAN FRANCISCO, CA 94111 FAX (415) 837-0800
McCone Hall
CAAN ID: 1762
Evaluator: QW
Date: 5/8/2019
Quick Check - Shear Stress in Shear Walls
N-S Direction E-W Direction
Level 1 Level 1
Aw 736 sf Aw 414 sf
V 66963 K V 66963 K
Ms 4.5 Ms 4.5
vavg 140 psi vavg 250 psi
f'c 3000 psi f'c 3000 psi
Limiting Shear Stress 110 psi Limiting Shear Stress 110 psi
Acceptable? FAILS Acceptable? FAILS
DCR 1.28 DCR 2.28
FORELL/ELSESSER ENGINEERS, INC.STRUCTURAL ENGINEERS
160 PINE ST., 6TH FLOOR (415) 837-0700
SAN FRANCISCO, CA 94111 FAX (415) 837-0800
McCone Hall
CAAN ID: 1762
Evaluator: QW
Date: 5/8/2019
Quick Check - Reinforcing Steel
Wall Thickness 8 in Wall Thickness 10 in
Vertical Reinforcing Vertical Reinforcing
Bar Area 0.20 in2 Bar Area 0.20 in2
Number Curtains 2 --- Number Curtains 2 ---
Bar Spacing 18 in Bar Spacing 16 in
Reinf. Ratio 0.0028 --- Reinf. Ratio 0.0025 ---
Reinf. Limit 0.0012 --- Reinf. Limit 0.0012 ---
Acceptable? OK --- Acceptable? OK ---
Horizontal Reinforcing Horizontal Reinforcing
Bar Area 0.20 in2 Bar Area 0.20 in2
Number Curtains 2 --- Number Curtains 2 ---
Bar Spacing 18 in Bar Spacing 16 in
Reinf. Ratio 0.0028 --- Reinf. Ratio 0.0025 ---
Reinf. Limit 0.0020 --- Reinf. Limit 0.0020 ---
Acceptable? OK --- Acceptable? OK ---
FORELL/ELSESSER ENGINEERS, INC.STRUCTURAL ENGINEERS
160 PINE ST., 6TH FLOOR (415) 837-0700
SAN FRANCISCO, CA 94111 FAX (415) 837-0800
McCone Hall
CAAN ID: 1762
Evaluator: QW
Date: 5/8/2019
Quick Check - Deflection Compatibility of Columns
Freestanding
Column
Freestanding
Column
Location G-16 G-16 Penthouse Roof 20 psf
Column 20"x28" 28"x20" Roof 50 psf
Vertical Reinforcement 12 # 9 12 # 9 Level 5 100 psf
Horizontal Reinforcement # 4 @ 18" # 4 @ 18" Level 4 100 psf
Column w1 = 20 in 28 in Level 3 100 psf
Column w2 = 28 in 20 in Level 2 200 psf
Ag = 560 in2 560 in2 Level 1 200 psf
Trib. Length = 5.00 ft 5.00 ft
Trib. Width = 10.25 ft 10.25 ft Material Property Factor
Trib. Area = 51 sq.ft 51 sq.ft Concrete 1.5
Flat Load (DL) = 59429 lb 59429 lb Reinforcing Steel 1.25
Column Load = 34667 lb 34667 lb
QD = 94 K 94 K f'c 5 ksi
QL = 38 K 38 K f'ce 7.5 ksi
Nu (QD+QL) = 133 K 133 K QG=QD+QL ASCE 41-17 (7-3) fy 40 ksi
fye 50 ksi
Mp = 515 K-ft 753 K-ft Mp obtained from spColumn
L = 13.0 ft 13.0 ft Interpolation
Vp = 2 x Mp / L = 79 K 116 K s/d αCol
0.75 1
knl = 0.7 0.7 1 0
λ = 1.0 1.0
d = 16 in 22 in ASCE 41-17 (10-3)
s = 18 in 18 in
s/d = 1.13 0.80
αCol = 0.00 0.79
MUD / (VUD d) = L / 2d = 4.00 3.48
As = 0.20 in2 0.20 in2
# of tie legs = 4 4
Av = 0.80 in2 0.80 in2
Vcol = 49.1 K 83.8 K
DCR = 1.61 1.38
Story Live Loads
STRUCTUREPOINT - spColumn v6.00 (TM) Page 1
Licensed to: Forell/Elsesser Engineers Inc.. License ID: 69993-1066712-4-20FB8-266FD 04/02/19
j:\~projects 2018\18-068 uc berkeley campus - wide evaluations\eng\calcs\1762 mccone hall\spcolumn\20x28.col12:13 PM
oooooo o
oo oo oo
ooooo oooooo oo ooooo oo oo oo o oooooooooo o ooooo
oo o oo oo oo oo oo oo oo oo oo oo oo oo oo
oo oo oo oo oo oo oo oo oo oo oo oo oo oo
ooooo oo oo oo oo oo oo oo oo oo oo oo oo oo
oo oooooo oo oo oo oo oo oo oo oo oo oo oo
o oo oo oo oo oo oo oo o oo oo oo oo oo oo oo
ooooo oo oooooo ooooo ooo ooooo o oo oo oo oo oo (TM)
==========================================================================================================
spColumn v6.00 (TM)
Computer program for the Strength Design of Reinforced Concrete Sections
Copyright © 1988-2017, STRUCTUREPOINT, LLC.
All rights reserved
==========================================================================================================
Licensee stated above acknowledges that STRUCTUREPOINT (SP) is not and cannot be responsible for either
the accuracy or adequacy of the material supplied as input for processing by the spColumn computer
program. Furthermore, STRUCTUREPOINT neither makes any warranty expressed nor implied with respect to the
correctness of the output prepared by the spColumn program. Although STRUCTUREPOINT has endeavored to
produce spColumn error free the program is not and cannot be certified infallible. The final and only
responsibility for analysis, design and engineering documents is the licensee's. Accordingly,
STRUCTUREPOINT disclaims all responsibility in contract, negligence or other tort for any analysis, design
or engineering documents prepared in connection with the use of the spColumn program.
STRUCTUREPOINT - spColumn v6.00 (TM) Page 2
Licensed to: Forell/Elsesser Engineers Inc.. License ID: 69993-1066712-4-20FB8-266FD 04/02/19
j:\~projects 2018\18-068 uc berkeley campus - wide evaluations\eng\calcs\1762 mccone hall\spcolumn\28x20.col12:22 PM
General Information:
====================
File Name: j:\~projects 2018\18-068 uc berkeley campus - wide evaluations\eng\calcs\176...\28x20.col
Project: 1762 McCone Hall
Column: 28x20 Engineer: QW
Code: ACI 318-14 Units: English
Run Option: Investigation Slenderness: Not considered
Run Axis: X-axis Column Type: Structural
Material Properties:
====================
Concrete: Standard Steel: Standard
f'c = 7.5 ksi fy = 50 ksi
Ec = 4936.35 ksi Es = 29000 ksi
fc = 6.375 ksi Eps_yt = 0.00172414 in/in
Eps_u = 0.003 in/in
Beta1 = 0.675
Section:
========
Rectangular: Width = 20 in Depth = 28 in
Gross section area, Ag = 560 in^2
Ix = 36586.7 in^4 Iy = 18666.7 in^4
rx = 8.0829 in ry = 5.7735 in
Xo = 0 in Yo = 0 in
Reinforcement:
==============
Bar Set: ASTM A615
Size Diam (in) Area (in^2) Size Diam (in) Area (in^2) Size Diam (in) Area (in^2)
---- --------- ----------- ---- --------- ----------- ---- --------- -----------
# 3 0.38 0.11 # 4 0.50 0.20 # 5 0.63 0.31
# 6 0.75 0.44 # 7 0.88 0.60 # 8 1.00 0.79
# 9 1.13 1.00 # 10 1.27 1.27 # 11 1.41 1.56
# 14 1.69 2.25 # 18 2.26 4.00
Confinement: Other; #3 ties with #11 bars, #4 with larger bars.
phi(a) = 1, phi(b) = 1, phi(c) = 1
Pattern: Irregular
Total steel area: As = 12.00 in^2 at rho = 2.14%
Minimum clear spacing = 2.87 in
Area in^2 X (in) Y (in) Area in^2 X (in) Y (in) Area in^2 X (in) Y (in)
--------- -------- -------- --------- -------- -------- --------- -------- --------
1.00 -8.0 12.0 1.00 -8.0 0.0 1.00 -8.0 -12.0
1.00 -4.0 12.0 1.00 -4.0 -12.0 1.00 0.0 12.0
1.00 0.0 -12.0 1.00 4.0 12.0 1.00 4.0 -12.0
1.00 8.0 12.0 1.00 8.0 0.0 1.00 8.0 -12.0
Factored Loads and Moments with Corresponding Capacities:
=========================================================
Pu Mux PhiMnx PhiMn/Mu NA depth Dt depth eps_t Phi
No. kip k-ft k-ft in in
--- ------------ ------------ ------------ -------- -------- -------- -------- ------
1 133.00 1.00 753.02 753.015 3.68 26.00 0.01821 1.000
*** End of output ***
STRUCTUREPOINT - spColumn v6.00 (TM) Page 2
Licensed to: Forell/Elsesser Engineers Inc.. License ID: 69993-1066712-4-20FB8-266FD 04/02/19
j:\~projects 2018\18-068 uc berkeley campus - wide evaluations\eng\calcs\1762 mccone hall\spcolumn\20x28.col12:13 PM
General Information:
====================
File Name: j:\~projects 2018\18-068 uc berkeley campus - wide evaluations\eng\calcs\176...\20x28.col
Project: 1762 McCone Hall
Column: 20x28 Engineer: QW
Code: ACI 318-14 Units: English
Run Option: Investigation Slenderness: Not considered
Run Axis: X-axis Column Type: Structural
Material Properties:
====================
Concrete: Standard Steel: Standard
f'c = 7.5 ksi fy = 50 ksi
Ec = 4936.35 ksi Es = 29000 ksi
fc = 6.375 ksi Eps_yt = 0.00172414 in/in
Eps_u = 0.003 in/in
Beta1 = 0.675
Section:
========
Rectangular: Width = 28 in Depth = 20 in
Gross section area, Ag = 560 in^2
Ix = 18666.7 in^4 Iy = 36586.7 in^4
rx = 5.7735 in ry = 8.0829 in
Xo = 0 in Yo = 0 in
Reinforcement:
==============
Bar Set: ASTM A615
Size Diam (in) Area (in^2) Size Diam (in) Area (in^2) Size Diam (in) Area (in^2)
---- --------- ----------- ---- --------- ----------- ---- --------- -----------
# 3 0.38 0.11 # 4 0.50 0.20 # 5 0.63 0.31
# 6 0.75 0.44 # 7 0.88 0.60 # 8 1.00 0.79
# 9 1.13 1.00 # 10 1.27 1.27 # 11 1.41 1.56
# 14 1.69 2.25 # 18 2.26 4.00
Confinement: Other; #3 ties with #11 bars, #4 with larger bars.
phi(a) = 1, phi(b) = 1, phi(c) = 1
Pattern: Irregular
Total steel area: As = 12.00 in^2 at rho = 2.14%
Minimum clear spacing = 2.87 in
Area in^2 X (in) Y (in) Area in^2 X (in) Y (in) Area in^2 X (in) Y (in)
--------- -------- -------- --------- -------- -------- --------- -------- --------
1.00 -12.0 8.0 1.00 -12.0 4.0 1.00 -12.0 0.0
1.00 -12.0 -4.0 1.00 -12.0 -8.0 1.00 12.0 8.0
1.00 12.0 4.0 1.00 12.0 0.0 1.00 12.0 -4.0
1.00 12.0 -8.0 1.00 0.0 -8.0 1.00 0.0 8.0
Factored Loads and Moments with Corresponding Capacities:
=========================================================
Pu Mux PhiMnx PhiMn/Mu NA depth Dt depth eps_t Phi
No. kip k-ft k-ft in in
--- ------------ ------------ ------------ -------- -------- -------- -------- ------
1 133.00 1.00 513.50 513.501 3.89 18.00 0.01087 1.000
*** End of output ***