ETABS Building Structure Analysis and Design Report

34
Page 1 of 34 1. INTRODUCTION 1.1. Problem Statement Analyse and design an economical and stable RCC framed building for the usage in Residential purpose using CSI-ETABS and manual calculations. 1.2. Scope The main scope of this project is to apply standards of Nepal National building codes and IS- 456, IS-13920, IS-1893 in designing a building. These building require great extent consideration of earthquake effects on building. This building is located in seismic zone V therefore the lateral loading of earthquake considered is predominant to the effects of wind loads. Hence wind loads are not considered. Almost materials and their sizes are so chooses that these are easily available in the market. 1.3 General This report summarizes the structural analysis and design of building of “………………..at ………. Municipality/VDC ward no………..It has planned to utilize the building as educational aspect. The aim of design is the achievement of an acceptable probability that structures being designed will perform satisfactorily during their intended life. 1. The building will be used dwellings or hotels so that there are Partition walls inside the building. External walls 230 mm thick and internal walls 115mm thick with 12 mm plaster on both sides are considered. For simplicity in analysis, no sloping shades are used in the building analysis even though balconies and terraces are intentionally included. 2. At ground floor, slabs are not provided and the floor will directly rest on ground. Therefore, only ground beams passing through columns are provided as tie beams. The floor beams are thus absent in the ground floor. 3. The main beams rest centrally on columns to avoid local eccentricity. 4. For all structural elements except slabs, M25 grade concrete will be used. However, higher M30 grade concrete is used for central columns up to plinth, in ground floor and in the first floor. 5. Column size are kept in similar group to ascertain simplicity in construction. 6. The floor diaphragms are assumed to be rigid 7. Preliminary sizes of structural components are assumed by experience. 8. Tie Beams are provided in connecting the footings. This is optional in zones II and III; however, it is mandatory in zones IV and V. 9. Seismic loads will be considered acting in the horizontal direction (along the two principal directions) and not along the vertical direction, since it is not considered to be significant. 10. The analysis and design has been based on the prevailing codes that are in practice in India and Nepal, the Indian Standard code IS 1893(Part 1):2002 and the NBC (105:1994) code at places if required. This report consists of the design procedures adopted, the assumptions made, the inputs made in the design and the design output.

description

Structural engineering

Transcript of ETABS Building Structure Analysis and Design Report

  • Page 1 of 34

    1. INTRODUCTION 1.1. Problem Statement

    Analyse and design an economical and stable RCC framed building for the usage in Residential

    purpose using CSI-ETABS and manual calculations.

    1.2. Scope

    The main scope of this project is to apply standards of Nepal National building codes and IS- 456,

    IS-13920, IS-1893 in designing a building. These building require great extent consideration of

    earthquake effects on building. This building is located in seismic zone V therefore the lateral

    loading of earthquake considered is predominant to the effects of wind loads. Hence wind loads are

    not considered. Almost materials and their sizes are so chooses that these are easily available in the

    market.

    1.3 General

    This report summarizes the structural analysis and design of building of .. at . Municipality/VDC ward no..It has planned to utilize the building as educational aspect. The aim of design is the achievement of an acceptable probability that

    structures being designed will perform satisfactorily during their intended life.

    1. The building will be used dwellings or hotels so that there are Partition walls inside the building.

    External walls 230 mm thick and internal walls 115mm thick with 12 mm plaster on both sides are

    considered. For simplicity in analysis, no sloping shades are used in the building analysis even though

    balconies and terraces are intentionally included.

    2. At ground floor, slabs are not provided and the floor will directly rest on ground. Therefore,

    only ground beams passing through columns are provided as tie beams. The floor beams are

    thus absent in the ground floor.

    3. The main beams rest centrally on columns to avoid local eccentricity.

    4. For all structural elements except slabs, M25 grade concrete will be used. However, higher M30

    grade

    concrete is used for central columns up to plinth, in ground floor and in the first floor.

    5. Column size are kept in similar group to ascertain simplicity in construction.

    6. The floor diaphragms are assumed to be rigid 7. Preliminary sizes of structural components are assumed by experience.

    8. Tie Beams are provided in connecting the footings. This is optional in zones II and III; however, it is

    mandatory in zones IV and V.

    9. Seismic loads will be considered acting in the horizontal direction (along the two principal

    directions) and not along the vertical direction, since it is not considered to be significant.

    10. The analysis and design has been based on the prevailing codes that are in practice in India

    and Nepal, the Indian Standard code IS 1893(Part 1):2002 and the NBC (105:1994) code at places

    if required. This report consists of the design procedures adopted, the assumptions made, the

    inputs made in the design and the design output.

  • Page 2 of 34

    11. As per IS 1893(Part 1):2002, the seismic zoning of Nepal can be taken as ZONE IV and ZONE

    V , most severe zone of India. For our case, we take the site lies on Zone V. Hence the building is

    designed with great consideration towards earthquake resistant practices.

    12. All dimensions are in mm, unless specified otherwise

    1.4 Building Configuration and Features

    The arrangements of Beams, Columns, Balcony slabs, T/B slabs, Room floors are done according as

    the figures shown below. Storey height for all floors is taken as 3200mm. The numbering of beams and

    columns are presented in Annex I

    Building Type : Residential Building of ..

    Located at .

    Structural system : RCC Space frame, ductile moment resisting frame with infill wall

    Plinth area covered : .

    Column : Square size 300x300mm

    Rectangular size (Main beams) :230 x 355 mm

    Slab : 125 mm thick two way slab

    Type of foundation : Isolated footing with STRAP BEAM for footing

    No. of Storey : Three story including stair cover

    Total Height : 9.6 with stair case cover

    Wall : 250 mm & 125mm thick brick masonry (1:5 C/S ratio)

    Probable Partition : (Actual Partition walls are not considered but 1KN/m2 equivalent

    Dead Load is assumed for possible partition)

    Type of Sub-Soil : II (Medium type as per NBC 105)

    Bearing Capacity of soil adopted = 200 KN/m2 as per site condition.

    1.5 Loads on Buildings

    1.5.1 Dead Load: A constant load in a building structure that is due to the weight of the members, the

    supported structure, and permanent attachments or accessories. This analysis deals with dead loads to

    be assumed in the design of buildings and same is given in the-form of unit weight of

    materials. The unit weight of other materials that are likely to be stored in a building should be

    also included for the purpose of load calculations due to stored materials. These loads are

    calculated as specified in IS875-1987(part I)

    1.5.2 Live Load : The load assumed to be produced by the intended use or occupancy of a building, including the weight of movable partitions, distributed, concentrated loads, load due to impact and

    vibration, and dust load but excluding wind, seismic, snow and other loads due to temperature changes,

    creep, shrinkage, differential settlement, etc. This analysis covers imposed loads*(live loads) to be

    assumed in the design of buildings. The imposed loads, used in this building analysis, are minimum

    loads which should be taken into consideration for the purpose of structural safety of buildings. These

    loads are calculated as specified in IS875-1987 (part II)

  • Page 3 of 34

    1.5.3 Seismic Load: The force on a structure caused by acceleration induced on its mass by an

    earthquake. This load is included in design to determine the extent of seismic reinforcing. The

    seismic loads on the structure during an earthquake result from inertia forces which were created by

    ground accelerations. The magnitude of these loads is a function of the following factors: mass of

    the building, the dynamic properties of the building, the intensity, duration, and frequency content

    of the ground motion, and soil-structure interaction. The analysis method and earthquake loads

    are calculated as specified in IS1893-2002.

    1.5.4 Wind Load: Wind is air in motion relative to the surface of the earth. The primary cause of wind is traced to earths rotation and differences in terrestrial radiation. The radiation effects are primarily responsible for convection either upwards or downwards. The wind generally blows horizontal to the

    ground at high wind speeds. Since vertical components of atmospheric motion are relatively small, the

    term wind denotes almost exclusively the horizontal wind, vertical winds are always identified as such. Wind load on the building would be usually uplift force perpendicular to the roof due to suction

    effect of the wind blowing over the roof. The positive or negative force of the wind acting on the

    structure; wind applies a positive pressure on the windward side of the building and a negative suction

    to the leeward side.. This analysis ignored the wind loads as the building is located in seismic zone V

    and hence the earthquake loads predominant it and the height of the building is less.

    2. METHODOLOGY

    The project provided to us is completed performing each section works mentioned in the contents

    before The following stages are involved in the analysis and design of three and half storey

    building.

    2.1 Load Calculation

    Load calculation is done using the IS 1893:2002 and NBC105: 1994 as code of standards. The

    exact value of unit weights of the materials from the code is used in the calculation. The thickness

    of materials is taken as per design requirements.

    2.2 Preliminary Design

    The tentative size of structural elements are determined through the preliminary design so

    that after analysis the pre assumed dimensions might not deviated considerably , thus

    making the final design both safe and economical . Tentative sizes of various elements

    have been determined as follows:

    2.2.1 Slab

    For slab, preliminary design is done according to deflection criteria span /effective depth =

    26*modification factor.( IS456-2000 Art 23.2.1)

    2.2.2 Beam

    Thumb rule of d=L/12 to L/15 basis is adopted to consider the preliminary design of the

    beam section .

    b/D=1/2

    2.2.3 Column

    Preliminary design of column is done consideration and interior column. For the load acting in the

    column, live load is decreased according to IS456-2000 & SP 16. Cross-sections of the columns

  • Page 4 of 34

    are adopted considering the economy. Square column section is adopted in this building project as

    per the internal aesthetic requirements.

    2.2.4 Staircase

    Stairs is designed as per drawing. Coolum for stairs boxes is not included in the grid

    system but they are assumed to be simply tied with main frame with beam.

    2.3 Loading Patterns

    Loading pattern from slab to beam is obtained by drawing 450 offset lines from each corners then

    obtained trapezoidal as well as the triangular loading and is converted into the equivalent UDL as

    described in the respective sections .The loading from cantilever slab part is converted to UDL

    acting in beam by dividing the total load by beam. Load from all cantilever part is converted to

    UDL acting in beam by dividing total load (wall UDL*total wall length) by length of the beam.

    Self-weight of the projected beam

    2.4. Gravity Load Calculation

    There are three types of loads for which the provided proposed project is designed:

    Dead load

    Live load

    Seismic load

    Dead load consists of the load from each element of building i.e. weight of column, beam, slab and

    wall. Dimensions of column, beam, and slab are taken from preliminary design and Corresponding

    density from code. For wall load thickness of wall is taken from plan. Live load is taken from

    relevant code. In case of different live loads in one panel of slab, highest value of load is taken for

    the panel. For seismic load whole mass lump of building is calculated from which base shear is

    obtained according to code.

    2.5 Tools for Analysis

    For analysis, different softwares are available during these days. Concerning to the project CSI-ETABS V-15 integrated building software is used for analysis of frames. Manual analysis and design using IS456:2000 carried out for the slabs and foundations with the help of me created

    excel-templates made accordingly.

    2.6 Design Method

    Limit State Method

    It uses the concept of probability and based on the application of method of statistics to the

    variation that occurs in practice in the loads acting on the structures or in the strength of material.

    The structures may reach a condition at which it becomes unfit for use for one of many reasons e.g.

    collapse, excessive deflection, cracking, etc. and each of this condition is referred to a limit state

    condition. The aim of limit state design is to achieve an acceptable probability that a structure will

    not become unserviceable in its lifetime for the use for which it has been intended i. e it will not

    reach a limit state. It means structures should be able to withstand safely all loads that are liable to

    act on it throughout its life and it would satisfy the limitations of deflection and cracking. We

    adopt limit state method for design.

  • Page 5 of 34

    3. FRAME DESIGN

    3.1 ETABS Analysis

    3.1.1 Assignments Materials

    Table 1 - Material Properties Concrete

    Concrete

    Grade

    E

    G Unit

    Weight Fc

    Lightweight?

    MPa 1/C MPa kN/m MPa

    M20 20 0.2 5.50E-06 9316.95 25 20 No

    Table 2 - Material Properties - Rebar

    Name E

    Unit

    Weight Unit Mass Fy Fu

    MPa 1/C kN/m kN-s/m MPa MPa

    HYSD415 200000 1.17E-05 76.9729 7.849 415 485

    Table 3 - Reinforcing Bar Sizes

    Name Diameter Area

    mm mm

    8 8 50

    12 12 113

    16 16 201

    Loads

    The following considerations are made for the assignment of loads on the structural model:

    The loads distributed over the area are imposed on area element and that distributed over length are

    imposed on line element whenever possible.

    Where such loading is not applicable, equivalent conversion to different loading distribution is carried

    to load the model near the real case as far as possible.

    The imposed loading of infill walls are considered(as per architectural drwg.) as equivalent UDL with

    25% to 30% deductions for openings, but the actual modelling of infill walls as equivalent Struts are

    not performed. Hence the stiffness of infill walls are not considered.

  • Page 6 of 34

    The Plinth Tie Beams are designed as purely tie members for lateral loads only, not designed as

    flexural members as floor beams.

    For simplicity of Structural analysis, Modelling of stair case is not performed & no landing beam is

    considered. The DL & LL load of stair case is transferred to the floor beam as equivalent UDL.

    Load Patterns

    Table 4 - Load Patterns

    Name Type Self-Weight Multiplier Auto Load

    Dead Load Dead 1

    Live Load Live 0

    Seismic Load(X) Seismic 0 IS1893 2002

    Seismic Load(Y) Seismic 0 IS1893 2002

    Load cases

    Name Stiffness From Mass Source Load Type Load Name Scale Factor Design Load Type

    Dead Preset P-delta MsSrc1 Load Pattern Dead 1 Program Determined

    Live Preset P-delta MsSrc1 Load Pattern Live 1 Program Determined

    EQX Preset P-delta MsSrc1 Load Pattern EQX 1 Program Determined

    EQY Preset P-delta MsSrc1 Load Pattern EQY 1 Program Determined

    Dead loads (DL)

    Assessment of unit Dead loads

    Table 7 Assessment of unit Live Loads

    Unit Weight of Concrete = 25 KN/m3 Unit Weight of Brickwork with

    Plaster = 20 KN/m3 Unit Weight of Floor Finish 20 KN/m3 Probable Partition Equivqlent Dead

    Load = 1 KN/m2 Beam-1 Width = 230 mm, Beam-2 Width = 230 mm,

    Beam-1 Depth = 355 mm, Beam-2 Depth = 355 mm, Height Of wall = 3200 mm

    Width Of External Wall = 250 mm

    Slab Thickness = 150 mm,

    Width Of Internal Wall = 135 mm

    Floor Finish Thickness = 50 mm,

  • Page 7 of 34

    Percentage of Opening on wall = 30 %

    Stair Area = 10.6 m2

    Loads on Beams supporting Two- ways Slabs:

    In case of Beams supporting two-way slabs, the load distribution is trapezoidal on long beams and

    triangular on short beams with base angle of 45 as shown in fig. The ordinates of trapezoidal and

    triangular loads=qLx/2.

    Fig:1 Two-way slab Loading

    Applications of loads on model

    Table 6 Applications of loads on model

    a) Beams subjected to External Wall

    Dead Load = 11 KN/m

    b) Line along the brick masonry partition walls

    Dead Load = 6 KN/m

    c) StairCase Beam ( Beam-2)

  • Page 8 of 34

    Length = 2743 mm

    Self Weight DL = 2 KN/m

    Dead Load from Stair = 9 KN/m (considering one-way spanning of slab)

    Dead Load from Wall = 11 KN/m

    Live Load from Stair = 12 KN/m

    Additional Dead Load= 20 KN/m (other than self-wt. load.i.e.applied on model)

    Additional Live Load= 12 KN/m (due to Live load on stair.i.e.applied on model)

    d) Floor Slab

    Self-Weight DL = 3.75 KN/m2

    Furnishing DL = 1 KN/m2

    Possible Partition DL = 1 KN/m2

    Total Additional Dead Load= 2.00 KN/m2 (other than self-wt. load.i.e.applied on model)

    Imposed Load (LL) The imposed loads on the structural system are taken from IS 875(part2)-1987 for

    Residential/Commercial building

    Assessment of unit Live Loads

    Table 7 Assessment of unit Live Loads

    Type of Building = Residential

    (IS875(II)-1987; Table 1) Clause 3.1

    Corridor = 3 KN/m2

    Stair = 3

    BedRoom = 2

    Toilet/BathRoom = 2

    Balcony = 3

    Roof = 1.5

    Terrace =

    Note-1: While applying the loads on structural model rounding values are used for simplicity

    Note-2: Point load consideration is ignored as the slab has sufficient rigidity to spread the

    concentrated load; IS875 (II) Clause 3.1

  • Page 9 of 34

    Lateral Load Calculation (Earthquake Load)

    According to NBC105:1994 & IS 1823-2002, Chitwan lies on the zone 2, V. Hence, the effect of

    the earthquake is predominant than the wind load. So, the frame is analysed for the EQ as lateral

    load. Among the methods of seismic analysis Seismic Coefficient Method defined in clause 10.1

    NBC 105:1994 and equivalent IS 1893-2002 clauses 6.4.2 is used to calculate seismic

    coefficient. And hence lateral loads are determined

    Assessment of Seismic Loading

    Auto Seismic Loading

    Table - Auto Seismic - IS 1893:2002 (Part 1 of 2)

    Load

    Pattern Type

    Directio

    n

    Eccentri

    city

    %

    Ecc.

    Overridd

    en

    Period

    Method

    Ct

    m

    Top

    Story

    Bottom

    Story Z Type Z

    Soil

    Type I

    EQX Seismic X + Ecc. Y 5 No Program

    Calculated StairCover Base Per Code 0.36 II 1

    EQX Seismic X - Ecc. Y 5 No Program

    Calculated StairCover Base Per Code 0.36 II 1

    EQY Seismic Y + Ecc. X 5 No Program

    Calculated StairCover Base Per Code 0.36 II 1

    EQY Seismic Y - Ecc. X 5 No Program

    Calculated StairCover Base Per Code 0.36 II 1

    Table - Auto Seismic - IS 1893:2002 (Part 2 of 2)

    R

    Period

    Used

    sec

    Coeff

    Used

    Weight

    Used

    kN

    Base

    Shear

    kN

    4 1 0.0612 1145.9946 70.1349

    4 1 0.0612 1145.9946 70.1349

    4 1 0.0612 1145.9946 70.1349

    4 1 0.0612 1145.9946 70.1349

  • 15/04/2015

    Page 10 of 34

    IS1893 2002 Auto Seismic Load Calculation

    This calculation presents the automatically generated lateral seismic loads for load pattern EQX according to

    IS1893 2002, as calculated by ETABS.

    Direction and Eccentricity

    Direction = Multiple

    Eccentricity Ratio = 5% for all diaphragms

    Structural Period

    Period Calculation Method = Program Calculated

    Factors and Coefficients

    Seismic Zone Factor, Z [IS Table 2]

    Response Reduction Factor, R [IS Table 7]

    Importance Factor, I [IS Table 6]

    Site Type [IS Table 1] = II

    Seismic Response

    Spectral Acceleration Coefficient, Sa /g [IS

    6.4.5]

    Equivalent Lateral Forces

    Seismic Coefficient, Ah [IS 6.4.2]

    Calculated Base Shear

    Direction

    Period

    Used

    (sec)

    W

    (kN)

    Vb

    (kN)

    X + Ecc. Y 1 1145.9946 70.1349

    X - Ecc. Y 1 1145.9946 70.1349

    Applied Story Forces

  • 15/04/2015

    Page 11 of 34

    Story Elevation X-Dir Y-Dir

    m kN kN

    StairCover 9.144 14.9102 0

    Second

    Floor 6.096 43.542 0

    First Floor 3.048 11.6826 0

    Base 0 0 0

  • 15/04/2015

    Page 12 of 34

    IS1893 2002 Auto Seismic Load Calculation

    This calculation presents the automatically generated lateral seismic loads for load pattern EQY according to

    IS1893 2002, as calculated by ETABS.

    Direction and Eccentricity

    Direction = Multiple

    Eccentricity Ratio = 5% for all diaphragms

    Structural Period

    Period Calculation Method = Program Calculated

    Factors and Coefficients

    Seismic Zone Factor, Z [IS Table 2]

    Response Reduction Factor, R [IS Table 7]

    Importance Factor, I [IS Table 6]

    Site Type [IS Table 1] = II

    Seismic Response

    Spectral Acceleration Coefficient, Sa /g [IS

    6.4.5]

    Equivalent Lateral Forces

    Seismic Coefficient, Ah [IS 6.4.2]

    Calculated Base Shear

    Direction

    Period

    Used

    (sec)

    W

    (kN)

    Vb

    (kN)

    Y + Ecc. X 1 1145.9946 70.1349

    Y - Ecc. X 1 1145.9946 70.1349

    Applied Story Forces

  • 15/04/2015

    Page 13 of 34

    Story Elevation X-Dir Y-Dir

    m kN kN

    StairCover 9.144 0 14.9102

    Second

    Floor 6.096 0 43.542

    First Floor 3.048 0 11.6826

    Base 0 0 0

  • Page 14 of 34

    Load Combinations

    The load combinations are based on NBC105:1994, clause 4.4 for Limit state design method.

    The following load combinations are used during analysis.

    Table 9- Load Combinations

    S.N

    . Name

    Load

    Case/Combo Scale Factor Type Auto

    1 1.Combo1.5(DL+LL) Dead 1.5 Linear Add No

    Live 1.5 No

    2 5.Combo (DL+1.3 LL-1.25EQY) Dead 1 Linear Add No

    Live 1.3 No

    EQY -1.25 No

    3 6.Combo (0.9DL+1.25EQX) Dead 0.9 Linear Add No

    EQX 1.25 No

    4 7.Combo (0.9DL-1.25EQX) Dead 0.9 Linear Add No

    EQX -1.25 No

    5 8.Combo (0.9DL+1.25EQY) Dead 0.9 Linear Add No

    EQY 1.25 No

    6 9.Combo (0.9DL-1.25EQY) Dead 0.9 Linear Add No

    EQY -1.25 No

    7 4.Combo (DL+1.3 LL+1.25EQY) Dead 1 Linear Add No

    Live 1.3 No

    EQY 1.25 No

    8 3.Combo (DL+1.3 LL+1.25EQX) Dead 1 Linear Add No

    Live 1.3 No

    EQX 1.25 No

    9 2.Combo (DL+1.3 LL-1.25EQX) Dead 1 Linear Add No

    Live 1.3 No

    EQX -1.25 No

  • Page 15 of 34

    Geometry Assignments

    Table 10 Geometry Assignments

    Story Diaphragms Slab thickness

    All Rigid 125 mm

    Story Mesh Option Beams/Lines Wall Edges Further Subdivide Max Element Size

    mm

    All Auto Cookie Cut Yes Yes Yes 300

    Other Assignments

    1) 100mm2 steel sections is overridden to beam section at top for ductile reinforcement

    consideration.

    2) Minimum rebar sizes and numbers are overridden

    for beam 12mm dia and 4 numbers of bars

    for column 16mm dia and 8 number of bars 3) In every floor slabs are interconnected to act as a diaphragm.

    3.1.2 Analysis Preparation

    Selection of Analysis Sections

    Preliminary design is carried out to estimate approximate size of the structural members.

    Grid diagram is the basic guiding parameter for analysis (both approximate and exact)

    and is presented below.

    Slab

    For limit state of serviceability (deflection) criteria,

    Span / depth ratio < Where

    , , ,, are modification factors given by IS 456: 2000 = 26, for continuous slab [IS 456: 2000, CL: 23.2.1(a)] = 1, for span < 10m, [IS 456: 2000, CL: 23.2.1(b)] = 1.24, for pt = 0.5% (assumed) [IS 456: 2000, CL: 23.2.1(c)]

    S.

    N.

    Design

    Type Story Section Type Analysis Section

    Design

    Procedure Design Section

    1

    Column All*

    Concrete

    Rectangular COL300*300 (4-16,4-12)

    Concrete

    Frame

    Design COL300*300 (4-16,4-12) 2

    Beam All Tie Beams

    Concrete

    Rectangular BM 230*300

    Concrete

    Frame

    Design BM 230*300

    3

    Beam All***

    Concrete

    Rectangular BM 230*355

    Concrete

    Frame

    Design BM 230*400

  • Page 16 of 34

    = 1, for pt = 0% [IS 456: 2000, CL: 23.2.1(d)] = 1, for rectangular section [IS 456: 2000, CL: 23.2.1(e)]

    Take Overall depth (D) = 150 mm Beam

    For main beam

    Depth of beam = (1 / 13) * Longest span [IS 456: 2000 CL 22.2]

    The section of main beam = 230 * 355 mm, 230*400 mm

    Column

    For main column

    d = H/8 to H/10

    D= 3200/ (8 to 10)

    = 400 mm to 320 mm

    Adopt Size of Column

    = 350* 350 mm and 400*400 mm

    3.1.3Analysis Outputs

    Base Reactions

    Table Base Reactions and Foundation Groups

    S.N. Joint

    Label FX FY FZ MX MY

    Foundation

    Group

    kN kN kN kN-m kN-m

    1 1 11 9 359 9 15 F2

    2 2 11 2 240 14 15 F1

    3 3 6 1 420 15 11 F2

    4 4 3 2 210 12 8 F1

    5 5 2 8 337 9 7 F2

    6 6 7 10 610 9 11 F3

    7 7 7 5 559 13 11 F3

    8 8 2 5 305 11 7 F2

    9 9 5 6 665 11 10 F3

    10 10 2 6 343 10 6 F2

    11 11 5 10 391 8 10 F2

    12 12 2 8 196 7 7 F1

    13 13 10 8 221 8 14 F1

    14 14 12 7 385 11 17 F2

    15 15 11 5 326 13 15 F2

    Storey Drifts

    Table: 12 Storey drift

  • Page 17 of 34

    Storey Drift ratio for all storied are checked as defined in clause 7.11.2, IS 1893-2002.It is found that

    storey drift ratio for all stories are within permissible limit 0.004. OK. All the reaction forces, drifts and

    deflections are shown in ANNEX-I

    Base Reactions are used to Design Foundation

    Sections Forces

    Typical analysis forces of beam/column and slab are presented below. All the beam/column

    forces are presented in ANNEX-II

    Fig:5 Direction of forces in Beam Fig:6 Direction of Forces in Column

    Storey Maximum Drift

    Stair Cover 0.000789

    Second Floor 0.000605

    First Floor 0.000521

  • Page 18 of 34

    Fig:7 Axial Force Diagram in Columns of Elevation B

    Fig:8 SFD of First floor Beams in (2-2) of First Floor Beams

  • Page 19 of 34

    Fig:9 Bending Moment Diagram (3-3) of Elevation A and B

  • Page 20 of 34

  • Page 21 of 34

    Fig:10 Resultant Bending Moment (1-1 and 2-2 ) contour in First Floor Slab

    3.2 Design Outputs

    Preliminary designed sections are provided and the structure is checked for different load

    combinations. The detail check and pass of all the message is shown in ANNEX-III

    3.2.1 Typical Output of Critical Sections

    ETABS 2015 Concrete Frame Design

    IS 456:2000 Column Section Design(Envelope)

    Column Element Details

    Level Element Section ID Length (mm) LLRF

    First Floor C7 COL300*300 (4-16,4-12) 3048 0.701

    Section Properties

    b (mm) h (mm) dc (mm) Cover (Torsion) (mm)

  • Page 22 of 34

    b (mm) h (mm) dc (mm) Cover (Torsion) (mm)

    300 300 56 30

    Material Properties

    Ec (MPa) fck (MPa) Lt.Wt Factor (Unitless) fy (MPa) fys (MPa)

    22360.68 20 1 415 415

    Design Code Parameters

    C S

    1.5 1.15

    Longitudinal Check for Pu - Mu2 - Mu3 Interaction

    Column End Rebar Area

    mm

    Rebar

    % D/C Ratio

    Top 1257 1.4 0.603

    Bottom 1257 1.4 0.606

    Design Axial Force & Biaxial Moment for Pu - Mu2 - Mu3 Interaction

    Column End Design Pu

    kN

    Design Mu2

    kN-m

    Design Mu3

    kN-m

    Station Loc

    mm Controlling Combo

    kN kN-m kN-m mm

    Top 600.9743 7.929 -12.0195 2693 1.5 (DL+LL)

    Bottom 610.0605 -4.8085 12.2012 0 1.5 (DL+LL)

    Shear Reinforcement for Major Shear, Vu2

    Column End Rebar Asv /s

    mm/m

    Design Vu2

    kN

    Station Loc

    mm Controlling Combo

    Top 332.53 0.2183 2693 0.9DL-1.25EQY

    Bottom 332.53 0.2183 0 0.9DL-1.25EQY

    Shear Reinforcement for Minor Shear, Vu3

    Column End Rebar Asv /s

    mm/m

    Design Vu3

    kN

    Station Loc

    mm Controlling Combo

    Top 332.53 21.706 2693 0.9DL-1.25EQY

    Bottom 332.53 21.706 0 0.9DL-1.25EQY

    Joint Shear Check/Design

    Joint Shear

    Ratio

    Shear

    Vu,Tot

    kN

    Shear

    Vc

    kN

    Joint

    Area

    mm

    Controlling

    Combo

    Major(Vu2) 0.507 0 0 0 DL+1.3LL+1.25EQX

    Minor(Vu3) 0.507 0 0 0 DL+1.3LL+1.25EQX

    Beam/Column Capacity Ratios

    1.1(B/C)

    Ratio

    Column/Beam

    Ratio

    SumBeamCap

    Moments

    kN-m

    SumColCap

    Moments

    kN-m

    Controlling

    Combo

  • Page 23 of 34

    1.1(B/C)

    Ratio

    Column/Beam

    Ratio

    SumBeamCap

    Moments

    kN-m

    SumColCap

    Moments

    kN-m

    Controlling

    Combo

    Major33 0.653 1.685 0 0 0.9DL-1.25EQY

    Minor22 0.432 2.547 0 0 0.9DL-1.25EQY

    ETABS 2015 Concrete Frame Design

    IS 456:2000 Beam Section Design (Envelope)

    Beam Element Details

    Level Element Section ID Length (mm) LLRF

    First Floor B10 BM230*355 2743.2 1

    Section Properties

    b (mm) h (mm) bf (mm) ds (mm) dct (mm) dcb (mm)

    230 355 230 0 60 60

    Material Properties

    Ec (MPa) fck (MPa) Lt.Wt Factor (Unitless) fy (MPa) fys (MPa)

    22360.68 20 1 413.69 413.69

    Design Code Parameters

    C S

    1.5 1.15

    Flexural Reinforcement for Major Axis Moment, Mu3

    End-I

    Rebar Area

    mm

    End-I

    Rebar

    %

    Middle

    Rebar Area

    mm

    Middle

    Rebar

    %

    End-J

    Rebar Area

    mm

    End-J

    Rebar

    %

    Top (+2 Axis) 227 0.28 212 0.26 262 0.32

    Bot (-2 Axis) 212 0.26 212 0.26 212 0.26

    Flexural Design Moment, Mu3

    End-I

    Design Mu

    kN-m

    End-I

    Station Loc

    mm

    Middle

    Design Mu

    kN-m

    Middle

    Station Loc

    mm

    End-J

    Design Mu

    kN-m

    End-J

    Station Loc

    mm

    Top (+2 Axis) -5.1633 150 -0.8944 1828.8 -25.512 2593.2

    Combo 1.5 (DL+LL) 0.9DL-1.25EQY 1.5 (DL+LL)

  • Page 24 of 34

    End-I

    Design Mu

    kN-m

    End-I

    Station Loc

    mm

    Middle

    Design Mu

    kN-m

    Middle

    Station Loc

    mm

    End-J

    Design Mu

    kN-m

    End-J

    Station Loc

    mm

    Bot (-2 Axis) 4.3834 532.2 5.4108 1828.8 3.2232 2211

    Combo 0.9DL-1.25EQY 0.9DL-1.25EQY 0.9DL-1.25EQY

    Shear Reinforcement for Major Shear, Vu2

    End-I

    Rebar Asv /s

    mm/m

    Middle

    Rebar Asv /s

    mm/m

    End-J

    Rebar Asv /s

    mm/m

    442.08 378.52 446.36

    Design Shear Force for Major Shear, Vu2

    End-I

    Design Vu

    kN

    End-I

    Station Loc

    mm

    Middle

    Design Vu

    kN

    Middle

    Station Loc

    mm

    End-J

    Design Vu

    kN

    End-J

    Station Loc

    mm

    47.2187 150 0.0394 1828.8 48.9573 2593.2

    DL+1.3LL-1.25EQX DL+1.3LL-1.25EQX DL+1.3LL-1.25EQX

    Torsion Reinforcement

    Shear

    Rebar Asvt /s

    mm/m

    505.54

    Design Torsion Force

    Design Tu

    kN-m

    Station Loc

    mm

    Design Tu

    kN-m

    Station Loc

    mm

    4.386 2593.2 4.386 2593.2

    1.5 (DL+LL) 1.5 (DL+LL)

    3.1.2 Summary of Design Sections

    Column The brief description of column sections is tabulated below. The detailed column section

    reinforcements are presented in Column Schedule attached in structural drawing section

    of this report

    Structural drawings are explained in ANNEX-IV

    Table: 12 Column Sizes and Brief Rebar Schedule

    Column Sizes Rebar Area Rebar numbers Ties Remarks

    mm*mm mm2

    1 300*300 8mm ,6-legged ties @

    100mm at joint

    and @150mm

    at middle of

    column

    Ties spacing explained

    here is a general idea

    proper spacing is

    presented in column

    schedule 1257 4-16,4-12

    *Spacing is illustrated in structural drawing attached with this report

  • Page 25 of 34

    **Column Framing Plan and Column Schedule are attached in structural drawing sheets.

    Beam All the sizes of beams and their labels and corresponding rebar are tabulated in Beam Rebar

    Table attached with this report in structural drawing section (ANNEX-IV). Mainly the adopted

    structurally passed sections are tabulated below

    Table:13 Types of Adopted Beams and Their Sizes

    Beams Width (mm) Depth(mm)

    Main Beams 230 355

    Staircase stair landing Beams 230 355

    Tie Beams 230 230

    Cantilever Overhanging Beams 230 230

  • Page 26 of 34

    4. SLAB DESIGN 4.1 General

    Slabs are plate elements forming floors and roofs of buildings and carrying distributed

    loads primarily by flexure. A staircase can be considered to be an inclined slab. They

    may be supported on walls or beams or in the columns. The beam supporting the slabs

    are considered stiff and do have deflections relative small as that compared to the slabs.

    The slabs supported on the wall or beams are called edge supported slab. 4.1.1 Types of Slab

    Slabs are classified according to the manner of the support

    a) One-way Slab spanning in one direction b) Two-way slab spanning in two direction c) Circular slab d) Flat slab e) Ribbed slab

    Two-way slabs are analysed and designed for this building

    4.1.2 Methodology of slab design

    Important information regarding the design of slab according to IS456:2000

    1. Slab is designed for 1m wide strip

    2. Temperature reinforcement (Ast min) = 0.12% bD for deformed bars along the

    transverse direction to the main bars (Cl.26.5.2.1)

    3. Cover minimum = 25mm

    4. If Ly/Lx < 2, two way slab is designed

    Design Steps for two way restrained slab

    1. Effective depth (d) is taken from the preliminary design

    2. Find out the loading

    3. Find out the effective span

    Leff = lo+ t

    = lo + d whichever is less

    4. Bending moment is calculated according to Annex D IS 456:2000

    Mux = x * wu * (lx)2 Muy = y * wu * (lx)2 x and y are the bending moment coefficient from table 26 (IS 456: 2000) Mux and Muy are the moments on the strips of unit width spanning lx and ly

    respectively.

    Lx and ly are the length of shorter span and longer span respectively.

    5. Find out the area of the steel

    Mu = 0.87 *fy *Ast*(d- (fy*Ast/fck * b))

    6. Find out the spacing for the arrangement of steel.

    Sv = 1000 * ( / 4 * 2) / Ast 7. Check for development length according to cl. 25.2.1 IS 456:2000

    8. Check for deflection according to cl.23.2.1 IS 456:2000

  • Page 27 of 34

    4.2 Analysis and Design of Two-way slab

    Table: 14 Two-way Slab Sizes and Bottom Main Reinforcement

    Calculations of sample slab are presented in ANNEX-V

    DL

    (KN/m2)

    LL

    (KN/m2)

    Lx (Short

    Span)_mm

    Ly (Long

    Span)_mm

    fy

    (N/mm2) fck Mpa

    Overal thickness of

    slab (mm)

    clear cover

    (mm)

    S1 5.750 2.000 4000 4700 415 20 125 20 535 10 125 209 8 300 126 8 300

    S2 5.750 2.000 3700 4700 415 20 125 20 512 10 125 179 8 300 126 8 300

    S3 5.750 2.000 3700 4000 415 20 125 20 416 10 125 142 8 300 126 8 300

    S4 5.750 2.000 3000 4000 415 20 125 20 386 10 125 93 8 300 126 8 300

    Atx mm2 (mm)

    c/c

    spa.(mm)

    Reinforcements along Long

    span (Middle Strip)

    Reinforcements along ANY

    Span (Column Strip)

    Slab

    group

    Er. Buddhi Sagar Bastola, NEC 7059 'CIVIL' A

    Atx mm2 (mm)

    c/c

    spa(mm) Aty mm2

    (mm) c/c spa.

    Table : Slab Dimensions and Rebars Positive Moment Side

    Client

    Reinforcements along short

    span (Middle Strip)

    Table :

    DL

    (KN/m2)

    LL

    (KN/m2)

    Lx (Short

    Span)_m

    m

    Ly (Long

    Span)_m

    m

    fy

    (N/mm2) fck Mpa

    Overal

    thickness

    of slab

    (mm)

    clear

    cover

    (mm)

    S1 5.750 2.000 4000 4700 415 20 125 20 614 10 125 286 8 300 126 8 300

    S2 5.750 2.000 3700 4700 415 20 125 20 593 10 125 244 8 300 126 8 300

    S3 5.750 2.000 3700 4000 415 20 125 20 484 10 125 189 8 300 126 8 300

    S4 5.750 2.000 3000 4000 415 20 125 20 440 10 125 124 8 300 126 8 300

    Reinforcements along Long

    span (Middle Strip)

    Reinforcements along ANY

    Span (Column Strip)

    Slab group

    Er. Buddhi Sagar Bastola, NEC 7059 'CIVIL' A

    Atx mm2 (mm)

    c/c

    spa(mm) Aty mm2 (mm) c/c spa. Atx mm2 (mm)

    c/c

    spa.(m

    m)

    Slab Dimensions and Rebars

    Client

    Reinforcements along short

    span (Middle Strip)

    Negative Moment Side

  • Page 28 of 34

    5. FOUNDATION DESIGN 5.1 General

    Foundation are the structural element that transfer the loads from the building or

    individual columns to the earth. The scope of foundation design is to consider the

    excessive settlement, rotation, differential settlement and safety against sliding

    /overturning of foundation.

    5.1.1 Types of Footings

    a) Isolated Footing: used for single column and may have square rectangular or circular shapes

    b) Strip Footing: Wall footing

    c) Combined footing: supports two or more columns

    d) Raft/Mat foundation: Support all columns. Used when soil bearing capacity is low

    and sum of individual footing area is more than 50% of plinth area.

    e) Pile/Well foundations: minimum three piles are capped to support the structures.

    Well foundations are used in bridge foundations.

    Selection of footings is made from experience but for economical foundations following

    factors governs the major.

    - Bearing capacity of soil and N-values of SPT - Permissible differential settlement - Soil strata - Type of structures and loadings on them

    Here the type of footing adopted is an isolated footing of size .

    5.1.2 Bearing Capacity of soil The total load per unit area under the footing must be less than permissible bearing capacity of

    the soil. Foundations must be designed to resist vertical loads, horizontal loads and moments.

    Typical net bearing capacity of different soil types are described below.

    Rock: 3300KN/m2 to 450 KN/m2

    Non-cohesive soil: 450 KN/m2 to 100 KN/m2

    Cohesive soil: 450 KN/m2 to 50 KN/m2.

    Here the safe bearing capacity adopted is a minimum 200KN/m2 for the proposed site.

    5.1.3 Depth of Foundation Factors

    -Seasonal weather change e.g. erosion and movement of upper soil

    -Lateral earth pressure required to resist horizontal loads.

    -safe bearing capacity

    Minimum depth of foundation = p/ [(1-sin)/ (1+sin)] =angle of repose of soil, p= gross bearing capacity, = density of soil However minimum depth of 500mm is mandatory.

    Here the depth of foundation adopted is a minimum of 1 m from the existing ground level.

    5.2 Analysis and Design of Foundation

    The reaction forces are obtained from ETABS analysis and the corresponding designs are

    made manually with the help of EXCEL template following the criterion of IS: 456-2000.

  • Page 29 of 34

    Here the safe bearing capacity is taken on the basis of categorization of site soil and

    peripheral geographical/hydrological features. Experiences with similar soil type and location

    as the determination of proper value is out of the scope of this report. The design parameters

    are shown in below and corresponding drawing are also attached in structural drawing section

    of the architectural report.

    Table: 15 Foundation design assignment of forces and output results.

    Calculations of major footings are presented in ANNEX-VI

    20

    200

    415

    S.N. F-Group # Joint

    Labels

    FZ MX MY Bar Spacing c/c

    kN kN-m kN-m Lx (mm) Ly (mm) Depth

    (mm)

    (mm) (mm) Bar No

    ..

    1 F1 2,4,12,13 250 14 15 1250 1200 1000 12 200 10 0

    2 F2

    1,3,5,8,10,

    11,14,15 500 15 15 1700 1600 1000 12 200 12 0

    3 F3 6,7,9 750 13 11 2100 2000 1000 12 200 20 4

    Note: 1.Foundation are grouped so as to make simplicity in construction.

    # F-Group(1) = [Fz=0 to 250 KN] ,F-Group(2) = [Fz=250 to 500 KN] ,F-Group(3) = [Fz=500 to 750 KN],F-Group(4) = [Fz=750 to

    1000 KN], F-Group(5) = [Fz=1000 to 1250 KN],F-Group(6) = [Fz=1250 to 1500 KN],

    2. Minimum dowels of 10 mm bar is provided in each face of column(4 numbers)

    3. All footings have 75mm brick/stone soling and 75mm PCC base from where the depth of footings is so defined in this table.

    Client

    Location

    Date

    .

    .

    Cocrete Strength

    MPA

    Bearing Capacity

    of Soil (KN/m2)

    Rebar Strength

    MPASize of Footings Dowels

  • Page 30 of 34

    Fig: 11 Joint Labels at footing

    6. CONCLUSION

    The purpose of this building is mainly residential as well as small scale of commercial with

    limited resources. Hence due to high cost of soil investigation actual borehole site

    exploration and the determination of bearing capacity of soil is omitted and adopted with

    the experience and visual inspection of site and local possibilities. The frame system

    analysis is made with an well powered software ETABS V17.Attempts are made to

    economise and simplified the construction ensuring earthquake safety and adopting

    common materials, common sections, and schedules. Design process is interactive process

    of selecting frames and checking for loads considered. Final safe checked and passed

    model with possible minimum sizes of frame members and minimum reinforcement is

    adopted. However this design is safe against earthquake no doubly, however more iteration

    are avoided in selection of members which make a little costly but not more than 10%.

  • Page 31 of 34

    Foundations and Slabs are designed manually with the help of excel- design templates

    made on the basis of IS 456:2000.Client is suggested to employ supervisor in the

    construction periods to ensure the quality control of works/materials within a limit. All

    necessary calculations; analysis results and design outputs are presented in annexes as a

    Adarsha.pdf version of soft copy file.

    REFERENCES

    Books and Journals

    1) Jain, A.K- R.C.C Limit State Design, Nem Chand & Bros, Roorkee, 1990

    2) Shah & Kale- R.C.C Design, Macmillan India Limited

    3) Ashok k. Jain- Advanced Structural Analysis, Nem Chand & Bros, Roorkee, 1990

    4) S.S. Bhavikati-Structural Analysis- II, Vikas Publishing House Pvt. Ltd.

    5) V.N. Vazirani- Analysis of Structures-II, Khanna Publishers

    6) S. Ramamrutham-Theory of Structures, Dhanpat Rai Publishing Company

    7) www.csiamerica.com

    8) Bothara,Jitendra Kumar- Protection of educational buildings against earthquake,NSET-Nepal publication

    9) Shrestha, Hima -Retrofitting of common Frame structural houses, NSET-Nepal publication

    Codes

    1) I.S. 456-2000 -Code of Practice for Plain and Reinforced Concrete 2) I S. 456-1978 -Design Aids for Reinforced Concrete ( S.P.-16 ) 3) S.P.34-1987 - Handbook on Concrete Reinforcement and Detailing 4) I S 1893-2003 -Criteria for Earthquake Resistant Design Structure 5) I S 13920-1993 -Ductile Detailing of Reinforced Concrete Structures subjected to

    Seismic forces

    6) I S 875-1987 -Code of practice for Design Loads for Buildings and Structures Part 1- Dead Loads

    Part 2- Imposed Loads

    7) NBC 105 :1994- Seismic Design of Building in Nepal

    8) NBC 108 :1994- Site Consideration for Seismic Hazards

    9) NBC 201 :1994 - Mandatory Rules of Thumb Reinforced Concrete Buildings with Masonry Infill

    Tools

    CSI-ETABS V.17: The frame analysis and design of this building is made with CSI-ETABS software

    choosing the integrated IS codes of standards. The innovative and revolutionary ETABS is the ultimate

    integrated software package for the structural analysis and design of buildings. Incorporating 40 years of

    continuous research and development, this latest ETABS offers unmatched 3D object based modelling and

    visualization tools, blazingly fast linear and nonlinear analytical power, sophisticated and comprehensive

    design capabilities for a wide-range of materials, and insightful graphic displays, reports, and schematic

    drawings that allow users to quickly and easily decipher and understand analysis and design results. The

    entire building structure was analyzed for gravity (including P-Delta analysis), wind, and seismic loadings

    utilizing ETABS version 8.4, from Computers and Structures, Inc (CSI). Major success story of software

    are shortly explained below.

    - ETABS is used in the structural design of the Burj Dubai in the United Arab. The Burj Dubai

    Tower is the worlds tallest structure, passing all previous height records. The entire building structure was

    analyzed for gravity (including P-Delta analysis), wind, and seismic loadings utilizing ETABS version 8.4,

    from Computers and Structures, Inc (CSI).

    - ETABS is used in the design of the new Museum for African Art on Fifth Avenue in New York

    City

  • Page 32 of 34

    Microsoft Office Excel Templates: The Design of Foundations and Slabs are made with Excel-Template

    prepared by myself. The so prepared design templates are based on IS 456:2000 - Code of Practice for Plain

    and Reinforced Concrete

    ANNEXES

    1. ANNEX-I-Base Reactions and Drifts/Deflection Of Structural Elements (Soft Copy)

    2. ANNEX-II-Frame Section Forces (Soft Copy)

    3. ANNEX-III-Design Outputs (Soft Copy)

    4. ANNEX-IV-Structural Drawings (Soft as well as Hard Copy)

    5. ANNEX-V- Calculations of Sample Slabs (Soft Copy)

    6. ANNEX-VI-Calculations of Sample Footings (soft Copy)

  • Er.Buddhi Sagar Bastola NEC CIVIL A 7059

    Page 33 of 34

  • 27/03/2015

    Page 34 of 34