DRAWN BYLAST DATEREVISED DRAWING NO.
SS-ESSR / RT-7JMP3/26/20SS-11
ESR ISOLATION CURB
ESR ISOLATION CURB
ROOFOPENING
RT-7 PANELS
RT-7 PANELS
NOTE: UNLESS OTHERWISE NOTED,FLOOR PANELS ARE TO BE FIELDINSTALLED, AFTER ESR CURB ASSEMBLY.
Transmission Loss dB
Frequency Hz
Calculated TL
63
16*
125
24
250
26
500
32
1000
42
2000
56
4000
62
8000
59*
STC
37
*ASHRAE HANDBOOK 2017, CHAPTER 8, EQUATION 39
RT-7 FLOOR
-
DRAWN BYLAST DATEREVISED DRAWING NO.
SS-FCBO / RT-7JMP3/26/20SS-11
FACTORY CURB
FACTORY CURB(BY OTHERS)
(CURB DESIGN MAY VARY)
ROOFOPENING
RT-7 PANELS
RT-7 PANELS
Transmission Loss dB
Frequency Hz
Calculated TL
63
16*
125
24
250
26
500
32
1000
42
2000
56
4000
62
8000
59*
STC
37
*ASHRAE HANDBOOK 2017, CHAPTER 8, EQUATION 39
NOTE: UNLESS OTHERWISE NOTED,FLOOR PANELS ARE TO BE FIELDINSTALLED, AFTER ESR CURB ASSEMBLY.
RT-7 FLOOR
-
DRAWN BYLAST DATEREVISED DRAWING NO.
SS-KSR / RT-7JMP3/26/20SS-11
KSR ISOLATION RAIL
FACTORY CURB(BY OTHERS)(CURB DESIGN MAY VARY)
ROOFOPENING
RT-7 PANELS
RT-7 PANELS
Transmission Loss dB
Frequency Hz
Calculated TL
63
16*
125
24
250
26
500
32
1000
42
2000
56
4000
62
8000
59*
STC
37
*ASHRAE HANDBOOK 2017, CHAPTER 8, EQUATION 39
NOTE: UNLESS OTHERWISE NOTED,FLOOR PANELS ARE TO BE FIELDINSTALLED, AFTER ESR CURB ASSEMBLY.
RT-7 FLOOR
KSR ISOLATION RAIL
-
DRAWN BYLAST DATEREVISED DRAWING NO.
SS-KIP / RT-7JMP3/26/20SS-11
KIP-RT ISOLATION STRIPS
FACTORY CURB(BY OTHERS)(CURB DESIGN MAY VARY)
ROOFOPENING
RT-7 PANELS
RT-7 PANELS
Transmission Loss dB
Frequency Hz
Calculated TL
63
16*
125
24
250
26
500
32
1000
42
2000
56
4000
62
8000
59*
STC
37
*ASHRAE HANDBOOK 2017, CHAPTER 8, EQUATION 39
NOTE: UNLESS OTHERWISE NOTED,FLOOR PANELS ARE TO BE FIELDINSTALLED, AFTER ESR CURB ASSEMBLY.
RT-7 FLOOR
KIP-RT ISOLATION STRIP
-
DRAWN BYLAST DATEREVISED DRAWING NO.
SS-KSCR / RT-7JMP3/26/20SS-11
KSCR ISOLATION CURB
ROOFOPENING
RT-7 PANELS
RT-7 PANELS
Transmission Loss dB
Frequency Hz
Calculated TL
63
16*
125
24
250
26
500
32
1000
42
2000
56
4000
62
8000
59*
STC
37
*ASHRAE HANDBOOK 2017, CHAPTER 8, EQUATION 39
NOTE: UNLESS OTHERWISE NOTED,FLOOR PANELS ARE TO BE FIELDINSTALLED, AFTER ESR CURB ASSEMBLY.
RT-7 FLOOR
KSCR ISOLATION CURB